MARK II Wind Speed Indicator
Instructions and Operation
OPERATION
The Dwyer Mark II Wind Speed Indicator is
100% pneumatic. It operates on the time
proven principle of aircraft speed indicators.
The complete kit consists of a pick up vane
connected by fifty feet of flexible double
column tubing to the Mark II Indicator, plus
all necessary mounting hardware, fluid and
instructions.
In operation, wind aligns the Mark II weather vane pointing the pick up tube into the
wind. Wind pressure enters and is transmitted through plastic connecting tubing to red
fluid inside the indicator. Fluid level rises
and falls in response to changing wind
speed. Scale calibrations on the indicator
show the wind speed corresponding to various fluid levels. For wind direction, observe
the weather vane position.
INSTALLATION
1. Mount the weather vane assembly outdoors, as high as possible and away from
the diverting effects of trees, roof pitch, and
Bulletin H-89
other structures. A minimum of 5 to 10 feet
of clearance is recommended for mounting
above small or medium sized buildings and
15 to 20 feet for large buildings. Attach the
mounting bracket directly to the pole or television antenna tower with the hardware
provided. It will not interfere with T.V. reception. Assemble the roof top unit as shown in
diagram on page 3. Use the curved slot to
adjust the pick up unit to a vertical position.
Tighten all screws. Make sure weather vane
rotates freely.
2. Thread the dual column tubing through
slots in the mounting bracket and tape
loosely as necessary to relieve strain.
Separate the two tubes for several inches
and slip the red striped tube over the top
pipe on pick up assembly. The plain tube
slips over the lower pipe.
3. Run tubing to the desired indicator location. It can be installed either inside or outside. Use plastic tube clamps (Part No. 285)
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361 U.S. A.
Phone: 219/879-8000 www.dwyer-inst.com
Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Lit-by-Fax: 888/891-4963
to prevent pinching or stretching tubing.
Free passage of air through both tubes is
vital for accurate readings.
4. Mount the Mark II Indicator loosely with
top screw. Center the bubble in spirit level,
then install bottom screw. Tighten the
screws keeping the level bubble centered.
5. Back the zero set knob all the way out,
then turn back in three full turns. Remove
reservoir “fill” plug and carefully fill indicator
until red gage fluid rises to “zero” mark on
scale. Use zero set knob for final adjustment
then replace fill plug. Should you overfill,
fluid may be removed by using a pipe cleaner to absorb excess fluid in the reservoir.
6. Cut off excess connecting tubing, separate the tubes slightly, and slip the red
striped tube over left connector at top of
instrument (above fill plug). Plain tube is
similarly connected to right (or more centered) connector. The Wind Speed Indicator
should now be in operation. If tube connections are reversed, a negative indication will
result.
MAINTENANCE
1. Periodically, disconnect the tubing from
the indicator and adjust fluid level to zero
mark. Add fluid if necessary, but do not use
substitutes. Indicator may be wiped off with
damp cloth as necessary.
4. Check connecting tubing (Part No. 290). It
must not be kinked or flattened at any point.
Cut or worn through spots will cause leaks
and destroy the accuracy of the instrument.
Such leaks must be repaired or the entire
tubing replaced.
5. Rainwater or indicator fluid may occasionally enter the tubing and will cause erroneous readings. The drain system in the roof
top pick up unit has been carefully designed
to expel rainwater in normal quantities.
Presence of water in the connecting tubing
indicates that the drain system is plugged
and should be cleaned or that the pick up
unit is mounted in a location where air flow
is upward (such as too close to a peaked
roof) so that rainwater remains airborne in
excessive quantities.
Gage fluid in the tubing indicates low fluid
level, improper zero adjustment or wind
gusts in excess of 90 MPH (145 KPH). It
may be difficult or impossible to remove this
liquid. Test for presence of obstruction or
water in tubing on a day with no wind.
Remove tubing connections from the gage,
adjust zero set, blow gently into one tube at
a time and attach to gage quickly. If reading
does not stay at zero, there is fluid in the
tubing. To correct, hang tubing vertically
from center with ends down for several
days. Reconnect and retest. If condition
persists, the tubing should be replaced.
2. Occasionally check weather vane (Part
No. 162). It should rotate freely. Pull up to
clean out spider nests, dirt, etc. Openings to
tubing connections in body should be clear
and free of any restriction.
3. Gently, but firmly pull out the static plate
assembly (Part No. 164). Check drain hole
to make certain it is open. If necessary,
clean entire plastic roof top assembly in
soap and water with soft brush or pipe
cleaner. When reassembling static plate and
weather vane, make certain they are pushed
back firmly to prevent their coming apart in
service.
page 2
CAUTION:
Do not blow into gage or weather vane!
Gage fluid may be forced out of the opposite indicator connection into the tubing or
onto your wall or carpet causing difficult to
remove oil spots and stains.
NOTE:
Heavy wind driven snow will sometimes
enter pick up and temporarily affect readings until it thaws or evaporates.