Dwyer LOFM User Manual

Series LOFM
LOW FLOW ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS
F-LOFM
GENERAL INFORMATION, FEATURES and SPECIFICATIONS
INSTALLATION and CONNECTIONS
The LOFM Electromagnetic Flow Sensor is designed for low-ow chemical injection or difcult-to-meter applications with pulsat­ing metering pumps in 3/4” to 1/4” pipe/tube. The housing is made of sturdy splashproof HDPE plastic.
With no moving parts, the LOFM can handle uids contain­ing particulate matter without clogging or jamming, keeping maintenance at a minimum. With no metallic parts (100% PVDF body and PVDF carbon ber-lled electrodes), the me­ter is corrosion-resistant and compatible with a wide range of chemicals. Accuracy is maintained with conductive uids (>20 microSiemens) of varying viscosities and densities.
FEATURES
8-pin circular bulkhead connector, 20’ (6 m) cable provided
Internals made of chemical and corrosion-resistant PVDF
Sturdy HDPE housing
FlareTek® ttings
are standard
Mounting bracket
The LOFM meter is compact enough to t most pump/injection systems. With zero straight pipe required after an elbow, it can be easily mounted in tight spaces. The mounting bracket adds stability.
The LOFM meter has optocoupled current sinking or current sourcing pulse output that can be connected to the Dwyer’s RTI rate/total display or a 4 to 20 mA loop for powering analog devices. Outputs and power are provided through a cable with 8-pin female circular connector.
Threaded NPT adapters
can be purchased separately
(available in PVC or PVDF)
INSTALLATION
Positioning. The LOFM can be mounted vertically or horizon-
tally. It is important to choose a position that will ensure full pipe. (Under certain conditions of empty or partially-full pipe the meter may give a pulse out when there is no ow.) With a zero straight pipe requirement after an elbow, the LOFM meter can be installed in tight spaces.
Mounting. The LOFM may be supported by its piping connec­tions IF the piping is rigid. The meter and pipe must be per­fectly aligned with no exion at the ttings to prevent damage to the meter and leakage. It is highly recommended to use the mounting bracket provided. The mounting bracket uses two #8 screws on a 1.5” center.
Piping. Metal pipe, metal tube, or plastic tubing can be used with the meter. The standard FlareTek® ttings can be used with or without NPT adapters on 3/4” or 3/8” pipe. If used, NPT adapters should be hand-tightened onto the ttings to avoid damage to internal O-ring seals. Thoroughly clean the pipe threads and nose and apply Teon tape to adapter threads. Hold ttings/adapters with a wrench while tightening the pipe to prevent damage to the meter. If using FlareTek® ttings, fol­low the installation instructions provided with your are tool.
Power Supply. A 12 VDC linear, regulated power supply with an output current of at least 0.25 A is recommended. If a switch­ing power supply must be used, consult Seametrics for ap­proved manufacturer’s model numbers.
CONNECTIONS
Power and signal connections are provided through the 8-pin male bulkhead connector on the meter housing (20’ (6m) cable provided). See the Pin Assignment and Connections diagrams below.
5
4 6
3 7
8
2 1
Cable Plug Contact
Arrangement
In addition, it is necessary for proper operation to ground the unit to a good quality earth ground. Assure negative power supply is grounded to earth and to the entire electrical/me­chanical system. If metal piping is used, jumper inlet and outlet pipes together and connect to ground for best results in metering accuracy.
Pin# Function Color
1 Pulse (-) White 2 Ground Brown 3 Pulse (+) Green 4 4-20 (+) Yellow 5 Not Used Grey 6 Not Used Pink 7 4-20 (-) Blue 8 Power (+) Red
SPECIFICATIONS*
Pipe Size
Fittings
Materials Body
Electrodes
Ground
Housing
Fittings (FlareTek®)
Adapters (NPT)
O-Rings (for NPT)
Temperature Ambient Fluid
Pressure
Flow Range -1
Accuracy -1
Output Signal
-1
Power
Conductivity
Empty Pipe Detection
Environmental
*Specications subject to change **Requires adaptors FlareTek® is a registered trademark of Entegris, Inc.
-2
-2
-2
3/4”, 1/2”, 3/8”, 1/4”**
FlareTek® ttings standard in 3/4” or 3/8” owbody; NPT threaded adapters also available
PVDF
PVDF carbon ber-lled
PVDF carbon ber-lled
HDPE with glass ber
PVDF
PVC or PVDF
EPDM or Fluoroelestomer
0˚ to 130˚ F (-18˚ to 54˚ C) 32˚ to 200˚ F (0˚ to 93˚ C)
150 psi
20 GPM Max. (0.2 GPM cut off)
3 GPM Max. (0.03 GPM cut off)
+/- 1%, +/- 0.005 GPM of reading across rated range
+/- 1%, +/- 0.002 GPM of reading across rated range
Optocoupled current sinking or current sourcing pulse output: 30 Vdc, 5 mA max; 4 to 20 mA current loop: 7 Vdc plus load voltage drop min; 50 Vdc max
PE102-075: 500 pulses/liter (1892 pulses/gallon), PE102-038: 1,000 pulses/liter (3785 pulses/gallon).
10-15 Vdc, 150 mA (linear power supply recommended)
>20 microSiemens
Hardware/software, conductivity-based
NEMA 4X (IP 66)
Dual Power Supply with Loop Isolation
4-20 mA
loop
12-24
Vdc
FlareTek® is a registered trademark of Entegris, Inc.
4 8
LOFM
7
4-20
device
2
Sensor Input
3
1
Power
RTI
12-15
Vdc
4-20 mA Device and RTI with Single Power Supply
12-15
Vdc
4-20 mA
loop
4 8
LOFM
7
4-20
device
2
3
1
Sensor Input
RTI
Power