Dwyer LLC User Manual

LLC Series Conductivity Controller
Installation and Operation Bulletin
This bulletin should be used by experienced personnel as a guide to the installation of series LLC controls. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact Dwyer or its representative if further information is required.
Specifications
Control Design: Solid state components enclosed in clear
Lexan plug-in style housing. Housing carries no NEMA rating. Contact Design: SPDT (1 form C): one normally open (N.O.) and one normally closed (N.C.), non-powered contacts. Contact Ratings: 10A @ 120 or 240 VAC resistive, 1/3 H.P. @120 or 240 VAC. Contact Life: Mechanical- 5 million operations. Electrical­100,000 operations minimum at rated load. Supply Voltage: 24, 120, or 240 VAC models- factory set. Plus 10%, minus 15%, 50/60 Hz.
Supply Current: 120, 240, 24 VAC, Relay energized 4.4 VA. Secondary Circuit: 12 VAC RMS voltage on probes, 1.5
milli-amp current. Sensitivity: Models operate from 0-1,000,000 OHM maximum specific resistance- factory set.
Temperature: -40 to 150° F. ambient. Terminals: All connections #6-32 screw type with pressure
clamps. Time Delays: Standard, 0.5 seconds on rising level. Addi­tional time delays on rising and/or falling available as option.
Installation
1. Install octal socket in appropriate enclosure using two (2) #6 or #8 metal screws. 1A. Install rail mount socket on appropriate rail (DIN mount) in appropriate enclosure if applicable.
2. Wire control per wiring diagram, following N.E.C. and local codes
3. Install control module in socket.
Sensitivities vs Maximum
Probe Wire Distance*
Sensitivity
Character
A or K
B or L C or M D or N
E or P
F or R G or S
Sensitivity
(K Ohms)
4.7 10 26 50
100 470
1,000
Distance
(Ft)
10,000
5,700 2,200 1,075
570 270
38
3-1/2”
2-3/4”
5/8”
*
Based on type MTW or THHN wire, #14 or #16 Awg.
Dimensional Diagram
2-3/8”
2-5/16”
1-5/32”
2.0” 1-11/16”
Use copper (60/70° C) wire only. Torque to 20 inch pounds.
11/64”
Dia.
Operation
Wiring Diagram
Direct Mode- Single Level Service: When the
liquid rises to the electrode on terminal 3, the control energizes, changing state of the load contacts. (LED will be lit) The control remains energized until the liquid level recedes below electrode on terminal 3. The control then de­energizes, (LED will not be lit) returning load to original state. Inverse Mode- Single Level Service: Con­trol energizes with power, changing state of the load contacts. (LED will be lit) When the liquid rises to the electrode on terminal 3, the control de-energizes, returning the load con­tacts to shelf state. (LED will not be lit) The control remains de-energized until liquid level recedes below the electrode connected to ter­minal 3. The control then energizes. Direct Mode- Differential Service: When the liquid rises to the electrode on terminal 3, the control energizes, changing state of the load contacts. (LED will be lit) The control remains energized until the liquid level recedes below electrode on terminal 4. The control then de­energizes, (LED will not be lit) returning the load contacts to original state. Inverse Mode- Differential Service: Control energizes with power, (LED will be lit) chang­ing state of the load contacts. When the liquid rises to the electrode on terminal 3, the con­trol de-energizes, returning load contacts to shelf state. (LED will not be lit) The control remains de-energized until the liquid level re­cedes below the electrode on terminal 4. The control then energizes.
AC Supply
L1
1
L2
2
3
4
H
L
- For Differential Service
- For Single Level Service use “H” and “G” Connections
C
8
NC
7
6
5
NO
G
Reference Probe
Low Probe
High Probe
If Metallic, tank may be used Instead of reference probe.
Optional
Time Delays: With time delay on increasing level, the liquid must be
in contact with the short electrode for the full duration of the time delay before control will operate. With delay on decreasing level, the liquid must be below long electrode for the full duration of the time delay before control will operate. In single level service, termi­nals 3 and 4 must be jumpered together to achieve time delays on both increasing and decreasing levels or just decreasing level.
LLC X X X X
Enclosure: Blank = None; 1 = Nema1; 4 = Nema4 Socket: 5 = Din Mount; 8 = 8 Pin Octal Operation: 1 = Direct 10K; 2 = Direct 26K; 3 = Direct 50K; 4 = Direct 100K Supply: 1 = 110 VAC; 2 = 240 VAC; 3 = 24 V AC
DWYER INSTRUMENTS,INC.
P .O.BOX 373 MICHIGAN CITY, INDIANA 46361, U.S.A.
Phone: 219/879-8000 www.dwyer-inst.com Fax: 219/872-9057 e-mail: in fo@dwyer-inst.co m Lit-By Fax: 888/891-4963
Loading...