TECHNICAL CHARACTERISTIQUES
INPUT VOLTAGE CURRENT
Range ±200V ±20V ±10V ±100mV ±20mA
Resolution 0.1V 0.01V 1mV 0.1mV 0.01mA
INPUT IMPEDANCE
Volts .................................................................................. 1M
mV ................................................................................ 100M
mA .................................................................................. 12,1
ACCURACY at 23ºC ±5ºC
Max Error. ..................................... ±(0.1% of reading + 3 digits)
Temperature coefficient ........................................... 100 ppm/ºC
Warm up .................................................................... 5 minutes
POWER SUPPLY AND FUSSES (DIN 41661) (Not supplied)
LCI132-00 85–265 VAC 50/60 Hz and 100-300VDC F 0.1A/ 250V
LCI132-01 21-53 VAC 50/60Hz and 10,5-70VDC ... F 0.5A/ 250V
CONVERSIÓN
Technical ................................................................ Sigma-Delta
Resolution .................................................................... ±15 bits
Rate .................................................................................. 25/ s
3
DISPLAY
Range .................................................................. -1999 ÷ 9999
Type .......................................................... 4 dígitos rojos 10mm
Reading rate ........................................................................ 4/s
Overflow indication ..........................................................
ENVIROMENTAL
Operating temperature ....................................... -10ºC ÷ +60ºC
Storage temperature .......................................... -25ºC ÷ +85ºC
Relative humidity (non condensed). ....................... <95% ÷ 40ºC
Maximum altitude .......................................................... 2000m.
Panel sealing ...................................................................... IP65
INSTALATION AND CONECTION
DIMENSIONS
Dimensions ................................................. 48 x 24 x 70mm.
Panel cutout ...................................................... 45 x 22mm.
Weight ........................................................................ 50 g.
Case material .............................. Polycarbonate s/ UL 94 V-0
48 x 24 mm frontal
Panel meter for indication of volts, mA and mV DC, completely
programmable.
Display range –1999 ÷ 9999, programmable decimal point.
Three keys keyboard situated on the bottom of the display.
DESCRIPTION
-INDICATOR for:
-PROCESS (±0-10V, ±20mA)
-VOLTS DC (200.0V and 20.00V)
-AMP DC (shunt ext.)
-mV (±100mV)
PROGRAMATION
Display range: Input (0-10V) (0-20mA) ................ -1999 ÷ 9999
Display range: Input (50/60/100mV) .................................... -1999 ÷ 1999
Display range: Input ......................................... calibrated -199.9 ÷ 199.9
Display range: Input ......................................... calibrated -19.99 ÷ 19.99
WARRANTY
All products are warranted against defective material and workmanship for a period of three years from
date of delivery.
If a product appears to have a defect or fails during the normal use within the warranty period, please
contact the distributor from whom you purchased the product.
This warranty does not apply to defects resulting from action of the buyer such as mishandling or
improper interfacing.
The liability under this warranty shall extend only to the repair of the instrument ; no responsibility is
assumed by the manufacturer for any damage which may result from its use.
1. –IN (COMMON).
2. +(50/ 60/ 100)mV DC.
3. +20mA
4. +(10/ 20)V DC
5. +200V DC
Keyboard detail (bottom view)
WARNING
In order to guarantee electromagnetic compatibility, the following guidelines for
cable wiring must be followed:
Power supply wires must be routed separated from signal wires. Never run
power and signal wires in the same conduit.
Use shielded cable for signal wiring and connect the shield to ground.
The cable section must be 0.25 mm2
INSTALLATION
To meet the requirements of the directive EN61010-1, where the unit is
permanently connected to the mains supply it is obligatory to install a circuit
breaking device easy reachable to the operator and clearly marked as the
disconnect device.
CLEANING: The frontal cover should be cleaned only with a soft cloth soaked in
neutral soap product.
DO NOT USE SOLVENTS
ENTER: Enter programming mode and accepts data.
SHIFT : In programming mode selects mode
or moves the blinking digit
UP : In programming mode increases the value of
the blinking digit
5 seg.
5 seg.
5 seg.
200V and 20V
Calibrated
Ranges.
NOT
Configurable
SCAL: Programming method introducing InP1 and InP2 values by keyboard.
tEAC: Programming method where instrument learns actual values of InP1 and Inp2.
InP1 , InP2 : Input signal values corresponding to desired display dSP1 and dSP2 .
dSP1: Display value corresponding to InP1.
dSP2: Display value corresponding to InP2.
LC 0: Programming unlocked.
LC 1: Programming totally locked.( Show all parameters like dAtA) .
Valid for panel meters #258 and so on

CARACTERÍSTICAS TÉCNICAS
ENTRADA VOLTAJE CORRIENTE
Rango ±200V ±20V ±10V ±100mV ±20mA
Resolución 0.1V 0.01V 1mV 0.1mV 0.01mA
IMPEDANCIA DE ENTRADA
Voltios ................................................................................ 1M
mV ................................................................................. 100M
mA ................................................................................... 12,1
PRECISIÓN a 23ºC ±5ºC
Error Max. .................................±(0.1% de la lectura + 3 dígitos)
Coeficiente de temperatura ....................................... 100 ppm/ºC
Tiempo de calentamiento ............................................. 5 minutos
ALIMENTACIÓN y FUSIBLES (DIN 41661) (no incorporados)
LCI132-00 85 – 265 VAC 50/60 Hz y 100-300VDC F 0.1A/ 250V
LCI132-01 21-53 VAC 50/60Hz y 10,5-70VDC ....... F 0.5A/ 250V
CONVERSIÓN
Técnica .................................................................... Sigma-Delta
Resolución ................................................................... ±15 bits
Cadencia ............................................................................ 25/ s
DISPLAY
Rango.................................................................. -1999 ÷ 9999
Tipo............................................................ 4 dígitos rojos 10mm
Cadencia presentación ........................................................... 4/s
Indicación de sobreescala .................................................
AMBIENTALES
Temperatura trabajo ........................................... -10ºC ÷ +60ºC
Temp. Almacenamiento ....................................... -25ºC ÷ +85ºC
Humedad Rel. no conden. . ................................... <95% ÷ 40ºC
Altitud máxima ............................................................... 2000m.
Estanqueidad frontal............................................................ IP65
INSTALACIÓN Y CONEXIONADO
DIMENSIONES
Dimensiones .................................................... 48 x 24 x 70mm.
Orificio en panel ...................................................... 45 x 22mm.
Peso ................................................................................. 50 g.
Material de la caja ............................. Policarbonato s/ UL 94 V-0
48 x 24 mm frontal
Instrumento de panel para medición de voltios, mA y mV en contínua,
totalmente programable.
Rango de display –1999 ÷ 9999, punto decimal programable.
Teclado formado por tres teclas situadas en la parte inferior del frontal.
DESCRIPCIÓN
-INDICADOR para :
-PROCESO (±0-10V, ±20mA)
-VOLTIOS DC (200.0V y 20.00V)
-AMPERIOS DC (shunt ext.)
-mV (±100mV)
PROGRAMACIÓN
Rango de display: entradas (0-10V) (0-20mA) ...... -1999 ÷ 9999
Rango de display: entrada (50/60/100mV) ........................... -1999 ÷ 1999
Rango de display: entrada VDC .................. escala calibrada -199.9 ÷ 199.9
Rango de display: entrada VDC .................. escala calibrada -19.99 ÷ 19.99
GARANTIA
Los instrumentos están garantizados contra cualquier defecto de fabricación o fallo de materiales por un
periodo de 3 AÑOS desde la fecha de su adquisición.
En caso de observar algún defecto o avería en la utilización normal del instrumento durante el periodo
de garantía, diríjase al distribuidor donde fue comprado quien le dará instrucciones oportunas.
Esta garantía no podrá ser aplicada en caso de uso indebido, conexionado o manipulación erróneos por
parte del comprador.
El alcance de esta garantía se limita a la reparación del aparato declinando el fabricante cualquier otra
responsabilidad que pudiera reclamársele por incidencias o daños producidos a causa del mal
funcionamiento del instrumento.
Vista posterior
1. –IN (COMÚN).
2. +(50/ 60/ 100) mV DC.
3. +20mA
4. +(10/ 20)V DC
5. +200V DC
Detalle teclado (vista inferior)
ATENCIÓN
Para garantizar la compatibilidad electromagnética deberán tenerse en cuenta las
siguientes recomendaciones:
Los cables de alimentación deberán estar separados de los cables de señal y
nunca se instalarán en la misma conducción.
Los cables de señal deben de ser blindados y conectar el blindaje a tierra.
La sección de los cables deben de ser 0.25 mm
INSTALACIÓN
Para cumplir los requisitos de la norma EN61010-1, en Equipos
permanentemente conectados a la red, es obligatoria la instalación de un
magnetotérmico o disyuntor en las proximidades del equipo que sea fácilmente
accesible para el operador y que este marcado como dispositivo de protección
LIMPIEZA: La carátula frontal debe ser limpiada solamente con un paño
empapado en agua jabonosa neutra.
NO UTILIZAR DISOLVENTES
ENTER: Entra a programación y acepta datos
SHIFT : En programación selecciona el modo
o desplaza a la derecha el dígito intermitente
5 seg.
5 seg.
5 seg.
200V y 20V
Escalas
calibradas.
NO
configurables
SCAL: Método de programación entrando los valores InP1, InP2 por teclado.
tEAC: Método de programación entrando los valores reales de InP1 y Inp2.
InP1 , InP2 : Valores de señal de entrada para un dSP1 y dSP2 deseados .
dSP1: Valor de display correspondiente a InP1.
dSP2: Valor de display correspondiente a InP2.
LC 0: Instrumento con programación desbloqueada.
LC 1: Instrumento con programación totalmente bloqueada.( Muestra los parámetros
como dAtA) .
Manual válido para aparatos a partir de S/N:258

TECHNISCHE DATEN
EINGANGSSIGNAL SPANNUNG STROM
Bereich ±200V ±20V ±10V ±100mV ±20mA
Auflösung 0.1V 0.01V 1mV 0.1mV 0.01mA
EINGANGSWIDERSTAND
V-Eingang .......................................................................... 1M
mV-Eingang ................................................................... 100M
mA-Eingang ..................................................................... 12,1
GENAUIGKEIT bei 23ºC ±5ºC
Meßfehler . ............................ ±(0.1% beim Ablesen + 3 Stellen)
Temperaturkoeffizient .............................................. 100 ppm/ºC
Anwärmzeit ......................................................................5 min.
VERSORGUNG und SICHERUNGEN (DIN 41661)
LCI132-00 85–265 VAC 50/60 Hz und 100-300VDC F 0.1A/ 250V
LCI132-01 21-53 VAC 50/60Hz und 10,5-70VDC .. F 0.5A/ 250V
UMWANDLUNG
Technik .................................................................. Sigma-Delta
Auflösung .....................................................................±15 bits
Takt ................................................................................. 25/ s
ANZEIGE
Anzeigeumfang .................................................... -1999 ÷ 9999
Typ ............................................................ 4 rote Stellen 10mm
Anzeigetakt .......................................................................... 4/s
Meßbereichsüberschreitung ..............................................
UMGEBUNG
Betriebstemperatur ............................................. -10ºC ÷ +60ºC
Lagertemperatur ................................................ -25ºC ÷ +85ºC
relative nicht kondensierte Feuchtigkeit ............... <95% ÷ 40ºC
Meereshöhe ................................................................... 2000m.
Schutzart der Frontplatte .................................................... IP65
INSTALLATION und ANSCHLÜSSE
ABMESSUNGEN
Maße .......................................................... 48 x 24 x 70mm.
Ausschnitt in der Frontplatte ............................... 45 x 22mm.
Gewicht ....................................................................... 50 g.
Gehäusematerial .............................Policarbonat s/ UL 94 V-0
48 x 24 mm
Einbaumeßgeräte für Messung von Volt, mA und mV
(Gleichspannug + -strom), vollständig programmierbar.
Anzeigeumfang –1999 ÷ 9999, Dezimalpunkt programmierbar.
Tastatur aus drei im unteren Teil der Frontblende befindlichen Tasten.
BESCHREIBUNG
-ANZEIGE für :
-PROZESS (±0-10V, ±20mA)
-SPANNUNG (200.0V und 20.00V)
-STROM (ext. shunt)
-mV (±100mV)
PROGRAMMIERUNG
Meßbereich: Eingänge (0-10V) (0-20mA) -1999 ÷ 9999
Meßbereich: Eingang (50/60/100mV) .................. -1999 ÷ 1999
Meßbereich: Eingang 200VDC ............... kalibriert -199.9 ÷ 199.9
Meßbereich: Eingang 20VDC ................ kalibriert -19.99 ÷ 19.99
Rückansicht
1. –IN (COMMON).
2. +(50/ 60/ 100)mV DC.
3. +20mA
4. +(10/ 20)V DC
5. +200V DC
Tastatur (Ansicht von unten)
ACHTUNG
Um die elektromagnetische Kompatibilität zu garantieren, sind folgende Hinweise zu
beachten:
Die Versorgungskabel müssen von den Signalkabeln getrennt sein und dürfen
nie
in
der gleichen Leitung installiert werden.
Die Signalkabel müssen abgeschirmt sein und die Abschirmung muß an die Erdung
angeschlossen sein.
Der Kabeldurchschnitt muß 0.25 mm betragen.
INSTALLIERUNG
Um die Norm EN61010-1 zu erfüllen, ist bei ständig an den Stromkreis
angeschlossenen Geräten die Installierung eines Unterbrechers oder
Temperaturschutzschalters in der Nähe des Gerätes (leicht zugänglich) obligatorisch.
Er muß als Schutzvorrichtung gekennzeichnet sein.
REINIGUNG: Die Frontplatte sollte nur mit einem leicht mit neutralem
Seifenwasser befeuchteten Tuch gereinigt werden. KEINE LÖSUNGSMITTEL!
ENTER: Zugang zur Programmierung, nimmt Daten an
SHIFT : Bei Programmierung Wahl des Modus
oder Versetzung der blinkenden Stelle nach rechts
5 seg.
5 seg.
5 seg.
GARANTIE
Alle Geräte haben eine Garantiedauer von 3 JAHREN ab dem Kaufdatum auf jegliche
Herstellungs- oder Materialfehler.
Sollte bei normalem Gebrauch des Gerätes während der Garantiedauer ein Defekt oder Fehler
auftreten, wenden Sie sich bitte an Ihren zuständigen Vertragshändler, der Sie über die weitere
Vorgehensweise informiert.
Keine Garantie wird übernommen bei Nichtbeachtung der Installationshinweise oder
unsachgemäßer Benutzung durch den Verbraucher.
Die Garantie beschränkt sich auf Fehler, die in direktem Zusammenhang mit dem Gerät stehen,
und schließt nur die Reparatur ein. Für Fehler oder Fehlfunktionen ohne direkten
Zusammenhang wird keine Haftung übernommen.
SCAL: Eingabe der Werte InP1, InP2 über Tastatur.
tEAC: Übername der gemessenen Werte InP1 und Inp2.
InP1 , InP2 Eingangssignale für dSP1 und dSP2.
dSP1: Displaywert bezogen auf InP1.
dSP2: Displaywert bezogen auf InP2.
LC 0: Programmiersperre aufgehoben.
LC 1: Programmiersperre aktiv. Gesamte. Gesamte Programmierebene gesperrt.( Anzeigen der
Werte mit dAtA) .
200V und 20V
Kalibrierte
Mebereiche.
Nicht
einstellbar.
Gültig für Geräte von nº258

SPECIFICATIONS TECHNIQUES
ENTRÉE TENSION INTENSITE
Plage ±200V ±20V ±10V ±100mV ±20mA
Résolution 0.1V 0.01V 1mV 0.1mV 0.01mA
IMPEDANCE D’ENTRÉE
Tensions en volts .............................................................. 1M
Tensions en mV ............................................................. 100M
Intensités en mA .............................................................. 12,1
PRECISION à 23ºC ±5ºC
Erreur maximale. ........................ ±(0.1% de la lecture + 3 digits)
Coefficient de température ....................................... 100 ppm/ºC
Temps d’échauffement ................................................ 5 minutes
ALIMENTATION et FUSIBLES (DIN 41661) (non inclus)
LCI132-00 85 – 265 VAC 50/60 Hz et 100-300VDC F 0.1A/ 250V
LCI132-01 21-53 VAC 50/60Hz et 10,5-70VDC ..... F 0.5A/ 250V
CONVERSION
Technique ............................................................... Sigma-Delta
Résolution .................................................................... ±15 bits
Rafraîchissement ................................................................ 25/ s
AFFICHAGE
Plage ................................................................... -1999 ÷ 9999
Type ......................................................... 4 digits rouges 10mm
Rafraîchissement affichage ................................................... 4/s
Dépassement d’échelle ....................................................
AMBIANCE
Température de service ...................................... -10ºC ÷ +60ºC
Température de stockage ................................... -25ºC ÷ +85ºC
Humidité relative non condensée. ........................... <95% à 40ºC
Altitude maxi .................................................................. 2000 m
Etanchéité frontale ............................................................. IP65
RACCORDEMENT
DIMENSIONS
Dimensions .................................................. 48 x 24 x 70mm
Orifice de montage .............................................. 45 x 22mm
Poids ............................................................................ 50 g
Matériau du boîtier ........................ polycarbonate s/UL 94 V-0
Format frontal 48 x 24 mm.
Instrument programmable de tableau pour mesure de tensions (V, mV)
et intensités (mA) continues (avec mise à l’échelle).
Page d’affichage –1999 ÷ 9999 avec point décimal programmable.
Programmation et contrôle par 3 touches situées sous le cadre frontal.
DESCRIPTION
- INDICATEUR pour :
- PROCESS (±0-10V, ±20mA)
- VOLTS DC (200.0V y 20.00V)
- AMPERES DC (shunt extérieur)
- mV (±100mV)
PROGRAMMATION
Plage d’affichage pour entrées (0-10V) (0-20mA)... -1999 ÷ 9999
Plage d’affichage pour entrée (50/60/100)mV......................... -1999 ÷ 1999
Plage d’affichage pour entrées VDC ................ Echelle calibrée -199.9 ÷ 199.9
Plage d’affichage pour entrées VDC ................ Echelle calibrée -19.99 ÷ 19.99
GARANTIE
Les instruments sont garantis contre tout défaut de fabrication ou de composant pour une durée
de 3 ANS à partir de la date de leur acquisition.
En cas de constatation d’un quelconque défaut ou avarie dans l’utilisation normale de l’instrument
pendant la période de garantie, en référer au distributeur auprès duquel il a été acquis et qui donnera les
instructions opportunes.
Cette garantie ne pourra s’appliquer en cas d’usage anormal, mauvais raccordement ou utilisation hors
des critères que nous recommandons.
L’attribution de cette garantie se limite à la réparation ou au strict remplacement de l’appareil. La
responsabilité du fabricant est dégagée de toute autre obligation et en particulier sur les effets du
mauvais fonctionnement le l’instrument.
vue Postérieure
1. –IN (COMMUN).
2. +(50/ 60/ 100)mV DC.
3. +20mA
4. +(10/ 20)V DC
5. +200V DC
Détail clavier (vue inférieure)
ATTENTION
Pour garantir la compatibilité électromagnétique respecter les recommandations
suivantes :
Les câbles d’alimentation devront être séparés des câbles de signaux et ne seront
jamais installés dans la même goulotte.
Les câbles de signal doivent être blindés et raccordés au blindage a terre.
La section des câbles doit être 0.25mm².
INSTALLATION
Pour respecter la recommandation EN61010-1, pour les équipements raccordés
en permanence, il est obligatoire d’installer un magnéto-thermique ou séparer
l’équipement par un dispositif de protection reconnu à sa proximité et facilement
accessible par l’opérateur.
Nettoyage: Le panneau frontal doit seulement être nettoyé avec un tissus
humidifié avec une eau savonneuse neutre.
NE PAS UTILISER DE SOLVANTS
ENTER: Accés à la programmation et acceptation
des données
SHIFT : Mode programme: sélection du mode ou
déplacement vers la droite du digit clignotant
5 s
5 s.
5 s
SCAL : Méthode pour programmer les valeurs InP1, InP2 par le clavier.
TEAC : Méthode pour programmer les valeurs réelles de InP1 et Inp2.
InP1, InP2 : Valeurs du signal d’entrée pour affichages dSP1 et dSP2 désirés.
dSP1 : Valeur de l’affichage correspondant au signal InP1.
dSP2 : Valeur de l’affichage correspondant au signal InP2.
LC 0 : Programmation de l’instrument autorisée.
LC 1 : Programmation de l’instrument interdite mais lecture autorisée (dAtA) .
200V y 20V
Echelles
calibrées. NON
configurables
Valide pour appareils à partir du nº 258