Bulletin E-20
Model L6
Specifications - Installation and Operating Instructions
xplosion-Proof; UL and CSA Listed -
E
Class I, Groups *A, B, C, & D
Class II, Groups E, F & G
Directive 94/9/EC (ATEX) Compliant for
I 2 G Ex d IIC T6 Gb Process Temp≤75°C
I
ECEx Compliant for Ex d IIC T6 Gb Process Temp≤75°C
I
(Group A, stainless steel body only)
*
Float Switch
PECIFICATIONS
S
ervice: Liquids compatible with
S
wetted materials.
Wetted Materials:
Float: Solid polypropylene or 304
S.
S
ower Body: Brass or 303 SS.
L
agnet: Ceramic.
M
xternal Float Chamber (Tee):
E
Matches lower body choice of brass
or 303 SS.
Other: Lever Arm, Spring, Pin, etc.:
01 SS.
3
emperature Limit: -4 to 220°F (-20 to
T
05°C) Standard, MT high temperature
1
option 400°F (205°C)(MT not UL, CSA,
ATEX, IECEx and KC). ATEX compliant
AT, IECEx IEC and KC option ambient
temperature -4 to 167°F (-20 to 75°C)
rocess temperature: -4 to 220°F (-20
p
o 105°C).
t
ressure Limits: See next page.
P
Enclosure Rating: Weatherproof and
xplosion-proof. Listed with UL and
E
SA for Class I, Groups A, B, C and D;
C
Class II, Groups E, F, and G. (Group A
on stainless steel body models only).
0344 II 2 G Ex d IIC T6 Gb
Process Temp≤75°C.
C-Type Certificate No.: KEMA
E
04ATEX2128.
ATEX Standards: EN 60079-0: 2009;
EN60079-1: 2007.
IECEx Certified: For Ex d IIC T6 Gb
Process Temp≤ 75°C.
ECEx Certificate of Conformity:
I
ECEx DEK II.0039.
I
IECEx Standards: IEC 60079-00:
2007; IEC 60079-1: 2007.
Korean Certified (KC) for Ex d IIC T6
b Process Temp≤75°C.
G
TL Certificate Number: 2012-2454-75.
K
witch Type: SPDT snap switch
S
tandard, DPDT snap switch optional.
s
Electrical Rating: UL models: 5A @
125/250 VAC (V~). CSA, ATEX and
IECEx models: 5A @ 125/250 VAC
V~); 5A res., 3A ind. @ 30 VDC (V ).
(
V option: .1A @ 125 VAC (V~). MT
M
ption: 5A @125/250 VAC (V~). [MT
o
option not UL, CSA, ATEX or IECEx].
Electrical Connections: UL models:
18 AWG, 18˝ (460 mm) long.
ATEX/CSA/IECEx models: terminal
lock.
b
pper Body: Brass or 303 SS.
U
onduit Connection: 3/4˝ male NPT
C
standard, 3/4˝ female NPT on junction
ox models.
b
rocess Connection: 1˝ male NPT on
P
models without external float chamber,
1˝ female NPT on models with external
float chamber.
Mounting Orientation: Horizontal with
ndex arrow pointing down.
i
Weight: Approximately 1 lb (.5 kg)
without external float chamber, 1.75 lb
(.8 kg) with external float chamber.
Specific Gravity: See next page.
MT
Example
Series
Construction
Upper
Body Material
Lower
Body Material
Circuit (Switch)
Type
Line Size
Tee and Float
Options
Switch Options
Options
* Options that do not have ATEX, IECEx or KC.
L6L6EPEPB
B
S
B
B
S
3
B
S
S
D
3
4
5
6
0
A
B
C
H
L
S
MV
MT
AT
CSA
IEC
KC
GL
ID
JCT
JCTLH
TBC
TOP
L6EPB-B-S-3-B-MT level switch; brass upper housing, brass lower housing, brass tee with
Polypropylene spherical float, SPDT snap switch, and high temperature option
Series L6 level switch
Explosion proof and weatherproof
Brass
303 Stainless Steel
Brass
303 Stainless Steel
SPDT
DPDT
1˝ NPT
1-1/4˝ NPT (No tee models only)
1-1/2˝ NPT (No tee models only)
2˝ NPT
No Tee, Solid Polypropylene Spherical Float*
No Tee, 304 SS Cylindrical Float
Brass Tee, Solid Polypropylene Spherical Float*
No Tee, 304 SS Spherical Float
Brass Tee, 304 SS Spherical Float
303 SS Tee, 304 SS Spherical Float
303 SS Tee, Solid Polypropylene Spherical Float*
Gold Contacts on snap switch for dry circuits (see specifications for ratings)
High Temperature switch rated 400°F (205°C) (see specifications for ratings)*
ATEX approved construction (with JCT option standard)
CSA approved construction (with JCT option standard)*
IECEx approved construction (with JCT option standard)
KC approved construction (with JCT option standard)
Ground Lead*
Customer Information on standard nameplate
Weatherproof and explosion-proof junction box*
Weatherproof and explosion-proof junction box, left side
Terminal Block Connector*
Top Mounted (No tee models only)*
Attention: Units without
the “AT” suffix are not
Directive 94/9/EC (ATEX)
compliant. These units are
not intended for use in
potentially hazardous
atmospheres in the EU.
These units may be CE
marked for other
Directives of the EU.
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S. A.
Phone: 219/879-8000 www.dwyer-inst.com
Fax: 219/872-9057 e-mail: info@dwyer-inst.com
AXIMUM PRESSURE CHART
FRONT VIEW DETAIL SIDE VIEW DETAIL
CLAMP
SCREW
LOCKWASHER
CONDUCTOR
M
Model Number
L6EPB-B-S-3-A
L6EPB-B-S-3-B
6EPB-B-S-3-C
L
6EPB-B-S-3-H
L
6EPB-B-S-3-O
L
6EPB-S-S-3-A
L
L6EPB-S-S-3-C
L6EPB-S-S-3-L
L6EPB-S-S-3-O
6EPB-S-S-3-S
L
Float
Cylindrical SS
Polypropylene
ound SS
R
ound SS
R
olypropylene
P
ylindrical SS
C
Round SS
Round SS
Polypropylene
olypropylene
P
ressure Rating
P
psig (kg/cm
200 (13.8)
250 (17.2)
50 (24.1)
3
50 (17.2)
2
000 (69)
1
00 (13.8)
2
350 (24.1)
350 (24.1)
2000 (138)
000 (138)
2
ETTED MATERIALS CHART
W
2
)
Model
B-S-3-A
-S-3-B
B
-S-3-C
B
-S-3-H
B
-S-3-O
B
S-S-3-A
S-S-3-C
S-S-3-L
-S-3-O
S
-S-3-S
S
Brass
X
X
X
X
X
Bronze
X
X
Ceramic
X
X
X
X
X
X
X
X
X
X
Polypropylene
X
X
X
X
X
301SS
X
X
X
X
X
X
X
X
X
X
303SS
X
X
X
X
304SS
X
X
X
X
X
INSTALLATION
Unpack switch and remove any packing material found inside lower housing or float
hamber.
c
witch must be installed with body in a horizontal plane and arrow on side pointing
S
down.
If switch has an external float chamber (tee), connect it to vertical sections of 1˝
NPT pipe installed outside vessel walls at appropriate levels. If unit has no external
loat chamber, it must be mounted in a 1˝ NPT half coupling welded to the vessel
f
all. The coupling must extend through the wall.
w
Inspect and clean wetted parts at regular intervals.
ELECTRICAL CONNECTIONS
onnect wire leads in accordance with local electrical codes and switch action
C
equired. N.O. contacts will close and N.C. contacts will open when liquid level
r
auses float to rise. They will return to “normal” condition on decreasing liquid level.
c
Black = common, Blue = N.O. and Red = N.C.
For units supplied with both internal ground and external bonding terminals, the
ground screw inside the housing must be used to ground the control. The external
bonding screw is for supplementary bonding when allowed or required by local
code. When external bonding conductor is required, conductor must be wrapped a
minimum of 180° about the external bonding screw. See below. Some CSA listed
models are furnished with a separate green ground wire. Such units must be
equipped with a junction box, not supplied but available on special order.
Note: ATEX, IECEx and KC units only: The temperature class is determined by the
maximum ambient and or process temperature. Units are intended to be used in
mbient of -20°C≤ Tamb ≤75°C. Units may be used in process temperatures up to
a
05°C providing the enclosure and switch body temperatures do not exceed 75°C.
1
he standard Temperature Class is T6 Process Temp ≤75°C.
T
Refer to Certificate No: IECEx DEK 11.0039 for conditions of safe use for IECEx
compliant units.
ll wiring, conduit and enclosures must meet applicable codes for hazardous
A
reas. Conduits and enclosures must be properly sealed. For outdoor or other loca-
a
ions where temperatures vary widely, precautions should be taken to prevent con-
t
densation inside switch or enclosure. Electrical components must be kept dry at all
times.
CAUTION: To prevent ignition of hazardous atmospheres, disconnect the device
rom the supply circuit before opening. Keep assembly tightly closed when in use.
f
AINTENANCE
M
Inspect and clean wetted parts at regular intervals. The cover should be in place at
all times to protect, the internal components from dirt, dust and weather and to
maintain hazardous location ratings. Disconnect device from the supply circuit
before opening to prevent ignition of hazardous atmosphere. Repairs to be conducted by Dwyer Instruments, Inc. Units in need of repair should be returned to the
factory prepaid.
EC-Type Certificate IECEX and KC Installation Instructions:
Cable Connection
The cable entry device shall be certified in type of explosion protection flameproof
enclosure “d”, suitable for conditions of use and correctly installed. For Ta ≥ 65°C
cable and cable gland rated ≥ 90°C shall be used.
Conduit Connection
An Ex d certified sealing device such as a conduit seal with setting compound shall
be provided immediately to the entrance of the valve housing. For Ta ≥ 65°C wiring
and setting compound, in the conduit seal, rated ≥ 90°C shall be used.