Specifications - Installation and Operating Instructions
Rugged and reliable the Flotect®L4 Level switch operates
automatically to indicate tank level. Perfect for starting or stopping
pumps, opening or closing valves, or actuate level alarm signals. A
unique magnetically actuated switching design gives superior
performance. There are no bellows, springs, or seals to fail. Instead, the
free-swinging float attracts a magnet within the solid metal switch body,
actuating a snap switch by means of a simple lever arm. Float arm hinge
design limits the arm angle to prevent vertical hangup.
FEATURES
• Leak proof body machined from bar stock
• Choice of floats dependent on maximum pressure and specific gravity
• Weatherproof, designed to meet NEMA 4
• Explosion-proof (listings included in specifications)
• Installs directly and easily into tank with a thredolet or flange
(see application drawings on page 4)
• Electrical assembly can be easily replaced without removing the unit
from the installation so that the process does not have to be shut down
• Horizontal installation or optional top mount vertical installation
APPLICATIONS
• Direct pump control for maintaining level
• Automatic tank dump operations
• Control levels or provide alarms in sumps, scrubber systems, hydropneumatic tanks, low pressure boilers, and various waste
water/sewage treatment processes
Float Switch
SPECIFICATIONS
Service: Liquids compatible with wetted materials.
Wetted Materials:
Float and Rod: 316 SS;
Body: Brass or 316 SS standard;
Magnet Keeper: 430 SS standard, 316 SS or nickel optional.
Temperature Limits: 4 to 275°F (-20 to 135°C) standard, MT high
temperature option 400°F (205°C) [MT option not UL, CSA, ATEX, or
SAA]. ATEX and IECEx options, ambient temperature -4 to 163°F (-20 to
73°C); Process temperature -4 to 163°F (-20 to 73°F).
Pressure Limit: Brass body 1000 psig (69 bar), 316 SS body 2000 psig
(138 bar). Standard float rated 100 psig (6.9 bar). For other floats see
model chart on next page.
Enclosure Rating: Weatherproof and Explosion-proof. Listed with UL
and CSA for Class I, Groups C and D; Class II, Groups E, F, and G.
ATEX 0344 II 2 G Ex d IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C. Alternate Temperature Class T5 Process
Temp ≤88°C, T4 Process Temp ≤123°C, 145°(T3) Process Temp ≤133°C
consult factory.
EC-Type Certificate No.: KEMA 03 ATEX 2383
ATEX Standards: EN60079-0: 2009;
EN60079-1: 2007.
IECEX Certified: For Ex d IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C. Alternate Temperature Class T5 Process
Temp ≤88°C, T4 Process Temp ≤123°C, 145°(T3) Process Temp ≤133°C
consult factory.
IECEX Certificate of Conformity: IECEX DEK 11.0071
IECEX Standards: IEC 60079-0: 2007; IEC60079-1: 2007
SAA: Exd II C T6 (T amb = 60°C).
Alternate Ratings: T5 (T amb = 75°C) T4 (T amb = 110°C) alternate “T”
ratings may be provided.
IP66 C1 I, Zone I. Also FM approved.
(V~). CSA models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC
(V ). MV option: 1A @ 125 VAC (V~); 1A res., .5A ind. @ 30 VDC (V ).
MT option: 5A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM,
ATEX or SAA].
Electrical Connections: UL and CSA models: 16 AWG, 6˝ (152 mm)
long. ATEX and SAA unit: terminal block.
Process Connection: 1-1/2˝ male NPT standard, 2-1/2˝ male NPT
standard optional floats.
Mounting Orientation: Horizontal installation standard, optional vertical
top mount.
Weight: 4 lb 9 oz (2.07 kg).
Dead Band: 3/4˝ (19 mm) for standard float.
Specific Gravity: 0.7 minimum with standard float. For other floats see
model chart.
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S. A.
Phone: 219/879-8000www.dwyer-inst.com
Fax: 219/872-9057e-mail: info@dwyer-inst.com
Page 2
Example
FLOAT
316 STNLES. STL.
(STANDARD)
FLOAT ARM & BLOCK
316 STNLS. STL.
OR BRASS
SWITCH BODY
BRASS OR
316 STNLS. STL.
Ø1-5/8
[41.28]
5
[127.00]
6
[152.40]
19-7/32
[488.16]
8-7/32
[208.76]
MAGNET
KEEPER
430 STNLS. STL.
3
[76.20]
5
[127.00]
1-1/2 MALE NPT
MOUNTING
CONNECTION
16 GA. LEADS
6 [152.40] LONG
Ø2-1/2
[63.50]
3-11/32
[84.93]
3/4 FEMALE
NPT CONDUIT
CONNECTION
1-1/2 NPT
6
[152.40]
5
[127.00]
19-7/32
[488.16]
8-7/32
[208.76]
3
[76.20]
5
[127.00]
3/4 NPT
2-1/2
[63.50]
3-11/32
[84.93]
Construction
L4
L4
SS
D
L4-TOP
Wetted Material
Options
SS
316
NI
Switch Options
Float Options
D
50
150
300
Other Options
Flange*
Flange Size
Flange Material
Flange Rating
Bushing*
Bushing Size
Bushing Type
Bushing
Material
* Options that do not have ATEX or IECEx.
C
AT
IEC
SAA
EPOXY
MT
MV
NB
NH
TBC
TRD
TRI
C
1
L4-SS-D-C-F2C1
F
2
Side Mount, Brass Body, SPDT Switch
Top Mount, Brass Body, SPDT Switch (Specify rod length)
316 SS Body with 430 SS Magnet Keeper
316 SS Body and Magnet Keeper (Order with SS option)
Nickel 20 Magnet Keeper
DPDT Switch
2-1/2˝ Spherical, 304 SS rated 50 psi (3.5 bar), > 0.5 s.g.
2-1/2˝ Spherical, 316 SS rated 150 psi (10.3 bar), > 0.7 s.g.
2-1/2˝ Spherical, 304 SS rated 300 psi (20.7 bar), > 0.7 s.g.
ATEX
IECEx
SAA Construction
Epoxy Coated Housing
High Temperature* (See specifications for rating)
Gold Contact Snap Switch* (See specifications for rating)
Neoprene Boot*
No Electrical Housing*
Terminal Block Wire Connections*
Time Delay Relay* (On flow decrease)
Time Delay Relay* (On flow increase)
F
2
3
4
B
1
2
4
Flange Process Connection
2˝
3˝
4˝
Carbon Steel
C
316 SS
S
150 #
1
300 #
3
600 #
6
900 #
9
Bushing Process Connection
2˝
2-1/2˝
4˝
Hex
H
Flush
F
Brass
B
Carbon Steel
C
316 SS
S
304 SS
4
UL/CSA unit
ATEX/SAA unit
PARTS LIST
1. Cover lock. (ATEX/SAA unit only).
2. External ground. (ATEX unit only).
3. Enclosure housing and cover.
4. Terminal block. (ATEX and SAA unit
only, UL/CSA unit has 6˝ leads).
5. Internal ground.
*6. Magnet arm and switch assembly.
7. Switch body.
*8. Float, arm and block assembly.
*Approved replacement parts
Page 3
INSTALLATION
NO
NC
C
NO
NC
C
NO
NC
C
SIDE VIEW DETAIL
F
RONT VIEW DETAIL
C
LAMP
C
LAMP PLATE
SCREW
LOCKWASHER
CONDUCTOR
NOTES:
• Check all ratings given in the instructions and on the product to make
sure that the product is suitable for your application. Do not exceed
electrical ratings, pressure ratings, or temperature ratings of the product.
• Disconnect power supply before beginning installation to prevent
possible equipment damage or electrical shock.
1. Remove packing material from switch body-cap and remove tape from
magnet keeper. Install standard switch in thredolet previously welded to
tank. Install optional switch mountings per application drawings. Make
sure locknuts on float are tight.
2. When mounting switch in the side of a tank, the arrow on the side of
the switch must point up.
3. Wiring: UL and CSA units only: Thread connecting wires through
conduit and connect. ATEX units only: Wire in accordance with local
electrical codes. Cable should enter enclosure housing through an
approved Exx d cable gland (not supplied).
Black - Common
Blue - N.O.
Red - N.C.
NOTE: Double pole, double throw switches have dual black, blue and
red leads. These are connected in the same manner as single pole,
double throw switches, as described above.
ulletin E-73
B
CAUTION: To prevent ignition of hazardous atmosphere, disconnect the
device from the supply circuit before opening. After de-energizing, delay
10 minutes before opening. Keep assembly tightly closed when in
operation.
Note: ATEX and IECEX units only: The temperature class is determined
by the maximum ambient and or process temperature. Units are
intended to be used in ambient of -20°C≤Tamb≤73°C. Units may be
used in process temperatures up to 133°C providing the enclosure
and switch body temperature do not exceed 73°C. The standard
Temperature Class is T6 Process Temp ≤73°C.
5. For units supplied with both internal ground and external bonding
terminals, the ground screw inside the housing must be used to ground
the control. The external bonding screw is for supplementary bonding
when allowed or required by local code. When external bonding
conductor is required, conductor must be wrapped a minimum of 180°
about the external bonding screw. See below.
ATEX and IECEx Installation Instructions:
Cable Connection
The cable entry device shall be certified in type of explosion
protection flameproof enclosure “d”, suitable for conditions of use
and correctly installed. Cable entry may exceed 70°C. Conductors
and cable gland rated ≥90°C shall be used.
Conduit Connection
An Ex d certified sealing device such as a conduit seal with setting
compound shall be provided immediately to the entrance of the
valve housing. Cable entry may exceed 70°C. Conductors and cable
gland rated ≥90°C shall be used.
NOTE: The switch is deactivated and contacts are in normal condition
when the liquid is below the float.
SPDT
TERMINAL CONNECTIONS
MAINTENANCE
DPDT
Inspect and clean wetted parts at regular intervals. The cover should be
4. Make sure conduit or cable are properly sealed. Electrical
components must be kept free of moisture, including condensation, at all
times.
in place at all times to protect the internal components from dirt, dust, and
weather, and to maintain hazardous location ratings. Disconnect device
from the supply circuit before opening to prevent ignition of hazardous
atmosphere. Repairs to be conducted by Dwyer Instruments, Inc. Units
in need of repair should be returned to the factory prepaid.
Limited Warranty: The Seller warrants all Dwyer instruments and equipment to be free from defects in workmanship or material under normal use and service for a period
of one year from date of shipment. Liability under this warranty is limited to repair or replacement F.O.B. factory of any parts which prove to be defective within that time or
repayment of the purchase price at the Seller’s option provided the instruments have been returned, transportation prepaid, within one year from the date of purchase. All
technical advice, recommendations and services are based on technical data and information which the Seller believes to be reliable and are intended for use by persons
having skill and knowledge of the business, at their own discretion. In no case is Seller liable beyond replacement of equipment F.O.B. factory or the full purchase price. This
warranty does not apply if the maximum ratings label is removed or if the instrument or equipment is abused, altered, used at ratings above the maximum specified, or otherwise
misused in any way.
THIS EXPRESS LIMITED WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER REPRESENTATIONS MADE BY ADVERTISEMENTS OR BY AGENTS AND ALL
OTHER WARRANTIES, BOTH EXPRESS AND IMPLIED. THERE ARE NO IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR
PURPOSE FOR GOODS COVERED HEREUNDER.
Buyers Remedies: THE BUYER’S EXCLUSIVE AND SOLE REMEDY ON ACCOUNT OF OR IN RESPECT TO THE FURNISHING OF NON-CONFORMING OR DEFECTIVE
MATERIAL SHALL BE TO SECURE REPLACEMENT THEREOF AS AFORESAID. THE SELLER SHALL NOT IN ANY EVENT BE LIABLE FOR THE COST OF ANY LABOR
EXPENDED ON ANY SUCH MATERIAL OR FORM ANY SPECIAL, DIRECT, INDIRECT OR CONSEQUENTIAL DAMAGES TO ANYONE BY REASON OF THE FACT THAT
IT SHALL HAVE BEEN NON-CONFORMING OR DEFECTIVE.
Page 4
APPLICATION DRAWINGS FOR FLOTECT
2-1/2
THREDOLET
CUT HOLE
2-7/8 [73] DIA.
2-1/2 X 1-1/2
FACE BUSHING
HORIZONTAL, 2-1/2 THREDOLET INSTALLATION
WITH OPTIONAL 2-1/2 [64] SPHERICAL FLOAT
ANSI RF THREADED
REDUCING FLANGE
HORIZONTAL, FLANGE INSTALLATION
3/4 NPT
11-3/4
[298.5]
STANDARD INSTALLATION
1-1/2 THREDOLET
CUT HOLE 1-15/16 [49] DIA.
3/4 NPT
ANSI RF
THREADED
REDUCING
FLANGE
*FLANGE FACE TO CENTERLINE OF FLOAT
SPECIFIED BY CUSTOMER NORMALLY
SHOULD NOT EXCEED 20' [508 MM].