Series 1900 Pressure Switch
ON A 4-3/16 [106.36] B.C.
1/8 FEMALE NPT
HIGH PRESSURE CONNECTION
POWER INPUT
TERMINALS
+ –
GROUNDING
SCREW
Specications - Installation and Operating Instructions
Bulletin E-56
Series 1910 pressure switch. All
pressure and electrical connections
and set point adjustments are on one
side for easy installation.
Advanced design and precision construction permit these switches to perform
many of the tasks of larger, costlier units. Designed for air conditioning service, they
also serve many uidics, refrigeration, oven and dryer applications. For use with air
and non-combustible gases. Series 1900 switches are available with set points of
0.07 to 20 inches water column. Set point adjustment can be made easily - before or
after installation. Range screw is inside conduit enclosure to help prevent tampering.
For easy mounting and access, pressure and electrical connections and set point
adjustment are located on one side. This permits installation in corners or spaces too
small for other switches.
SPECIAL MODELS & ACCESSORIES
Special close coupled street elbow for right angle pressure connections. Can be
installed on switch anytime. Zinc plated aluminum.
Weatherproof Housing
16 ga. steel enclosure with
gasketed cover (NEMA 4)
for wet or oily conditions.
Withstands 200 hour salt
spray test. Wt. 5 Ibs. (2.3
kg). Switch must be factory
installed. Change 1910 base
number to 1911 and add -WP
sufx. Example: 1911-1-WP.
Explosion-Proof Housing
NEMA 7, 9 NEMA 3. (7
lbs). Switch must be factory
installed. Change model to
1911 and add -EXPL sufx.
Example: 1911-1-EXPL.
Aluminum base and cover
rated Class I, Groups C & D,
Div. 1. Class II, Groups E, F,
& G, Div. 1.
DWYER INSTRUMENTS, INC.
7/8
[22.23]
3/4
[19.05]
4-3/4
5-1/2
20.65]
[139.7]
4X Ø.281 [7.14]
41/64
Series 1910 switch with conduit
enclosure off. Shows electric switch
and set point adjustment screw.
3 [76.2]
3-1/8 [79.38]
1/2 NPT PROCESS
CONNECTION
3 [76.20]
6-5/8 [168.28]
1-1/8
[28.58]
3/32
[2.38]
[26.99]
4 [101.6] SQ.
(4) 5-16 [7.94] DIA.
MTG. HOLES
HIGH PRESS.
2X 4-1/4
[107.95]
2X 6-1/8
[155.58]
1/8 FEMALE NPT
LOW PRESSURE CONNECTION
CONNECTION HUB
1/29 NPT FEMALE
2 [50.8]
3 [76.2]
3/4 [19.05]
1-1/4 [31.75]
LOW PRESS.
CLEARANCE FOR
COVER REMOVAL
1-19/32
[40.48]
2-11/32
[59.53]
Ø7/8 [22.23]
CONDUIT
CONNECTION
1-3/4 [44.45]
CLEARANCE
FOR COVER
3
[76.20]
Ø3-1/2
[88.90]
HIGH PRESS.
CONNECTION
1-5/16
[33.32]
TYP
51/64
[20.24]
2-7/16 [61.90]
1-7/8
[47.63]
2-9/32
[57.94]
60 TYP
(2) Ø3/16 [4.76]
MOUNTING HOLES
1/8 FEMALE NPT
LOW PRESSURE
CONNECTION
The Dwyer-engineered force-motion amplier increases the leverage of
diaphragm movement and results in a switch with excellent sensitivity and
repeatability.
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Environment: Standard model intended for indoor use.
Wetted Materials: Consult factory.
Temperature Limits: -30 to 180°F (-34 to 82.2°C) (32°F for non dry air).
Pressure Limits: 45˝ w.c. (11.2 kPa) continuous, 10 psig (68.95 kPa) surge.
Humidity Limit: 80% RH (non-condensing).
Altitude Limit: 6560 ft (2000 m) max.
Switch Type: Single-pole double-throw (SPDT).
Repeatability: ±3%.
Electrical Rating: 15 A @ 120-480 VAC (~), 60 Hz. Resistive 1/8 HP @125
VAC(~), 1/4 HP @ 250 VAC(~), 60 Hz. Derate to 10 A for operation at high cycle
rates.
Electrical Connections: 3 screw type, common, normally open and normally
closed.
Installation Category: III (transient over-voltage).
Process Connections: 1/8˝ female NPT.
Mounting Orientation: Diaphragm in vertical position. Consult factory for other
position orientations.
Set Point Adjustment: Screw type inside conduit enclosure.
Pollution Degree: 2.
Weight: 1lb. 4.5 oz. (581 g).
Agency Approvals: CE, UL, CSA, FM.
Explanation of Symbols
Symbol Publication Description
IEC 60417 - 5032
~
IEC 60417 - 5019
Alternating current
Protective conductor terminal
Series 1910 Switches - Models Operating Ranges, Deadbands
Model
1910-00
1910-0
1910-1
1910-5
1910-10
1910-20
Operating Range,
in w.c.
0.07 to 0.15
0.15 to 0.5
0.40 to 1.6
1.40 to 5.5
3.0 to 11.75
4.0 to 20.0
Approximate Dead Band
At Min. Set Point At Max. Set Point
0.04
0.10
0.15
0.30
0.40
0.40
0.04
0.10
0.16
0.30
0.40
0.50
99 Washington Street
Melrose, MA 02176
Phone 781-665-1400
Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com

INSTALLATION
1. Select a location that is free from excessive vibration, corrosive atmosphere and
where the ambient temperature is within the limits for these switches.
2. Mount standard switches with the diaphragm in a vertical plane and with switch
lettering and nameplate in an upright position. Some switches are position sensitive
and may not reset properly unless they are mounted with the diaphragm vertical.
(Special units can be furnished for other than vertical mounting arrangements if
required.)
3. Connect switch to source of pressure, vacuum or differential pressure. Metal tubing
with 1/4˝ O.D. is recommended, but any tubing which will not restrict the air ow can be
used. Connect to the two 1/8˝ female NPT pressure ports as noted below:
• Differential pressures - connect pipes or tubes from source of greater pressure to
high pressure port marked HI-PR and from source of lower pressure to low pressure
port marked LO-PR.
• Pressure only (above atmospheric) - connect tube from source of pressure to high
pressure port. The low pressure port is left open to atmosphere.
• Vacuum only (below atmospheric pressure) - connect tube from source of vacuum to
low pressure port. The high pressure port is left open to atmosphere.
OPERATION
Pressure acting on the power diaphragm rotates the amplifying lever, which in turn
extends the range spring and rotates the snap switch input lever. When the set point
is reached, the snap switcch is actuated and the electrical contacts make or break.
ADJUSTMENT
To change the set point, proceed as follows:
A. Remove the snap-on cover from the conduit enclosure by loosening its retaining
screw and pulling rmly at its bottom end. Turn the slotted adjustment screw at the
top of range spring housing clockwise to raise the set point pressure and counterclockwise to lower the set point.
B. The recommended procedure for calibrating or checking
calibration is to use a “T” assembly with three rubber tubing leads, all as short as
possible and the entire assembly offering minimum ow restriction. Run one lead to
the pressure switch, another to the manometer of known accuracy and appropriate
range, and apply pressure through the third tube. Make nal approach to the set point
very slowly. Note that manometer and pressure switch will have different response
times due to different internal volumes, lengths of tubing, uid drainage etc. Be certain
the switch is checked in the position it will assume in use, i.e. with diaphragm in a
vertical plane and switch lettering and nameplate in an upright position.
CAUTION
4. Electrical connections to the standard single pole, double throw snap switch are
provided by means of screw terminals marked “common”, “norm open”, and “norm
closed”. The normally open contacts close and the normally closed contacts open
when pressure increases beyond the set point.
CAUTION
5. Switch loads should not exceed the maximum specied current rating of 15 amps
resistive. Switch capabilities decrease with high load inductance or rapid cycle rates.
Whenever an application involves either of these factors, the user may nd it desirable
to limit the switched current to 10 amps or less in the interest of prolonging switch life.
Power must be off while wiring connections are being made.
Do not exceed the specied voltage rating. Permanent damage
not covered by warranty may result.
C. For highly critical applications it is a good idea to check the set point adjustment
and reset it as necessary once or twice in the rst few months of operation. This
will compensate for any change in initial tension which may occur in the spring and
diaphragm. For most applications this change will not be signicant and no resetting
will be required.
MAINTENANCE
Moving parts of these switches are sealed in and are permanently tamper proof. The
single adjustment is that of the set point. Care should be taken to keep the switch
reasonably dry and free from dust or dirt. No lubrication or unusual precautions are
required for normal use.