Series “D” Pressure Controls with Mercury Switches
2-1/4 [57.15]
T
Specications - Installation and Operating Instructions
Bulletin IN-0118
Mercoid Series “D” Pressure Controls Bourdon tube power elements, visible
setpoint, adjustable deadband or xed deadband and pressure ranges from 0 to 30 in
Hg VAC to 800 to 8000 psig (345 bar).
BENEFITS/FEATURES
• Visible calibrated dial
• On/off indication
• Adjustable, xed deadband, or manual reset
• External switch setpoint adjustments
• Minimum deadband is obtainable at any point in the range
• Pressure Ranges of full vacuum to 8000 psig.
• UL listed, CSA approved. Many models FM approved.
• General purpose, weatherproof or explosion-proof enclosures
• Single or two stage operation
Location and Mounting
Select a location that is recommended by equipment manufacter and reasonably
free from vibration caused by reciprocating or rotating machinery. Where excessive
vibration occurs, use a remote connection and mount by means of a mounting bracket
or separable ange (available on order). When in doubt about excessive vibration,
use a remote connection. Where pulsations, pres-sure surges, or water hammer
are present, protect the control with a surge tank or scrubber. Mount all controls
vertically and level.
General Purpose Controls: Install controls prexed by the let-ters DA, DAF, DRF, DL,
DS, DSF, rmly in a level position. Do not mount the control by twisting the case; use
a wrench on the square part of the 1/4˝ bottom pipe connection. To level, sight across
the two cover screws or check the lower end of the glass opening in the cover to see
that the control is lined up horizontal-ly. On general purpose controls provided with a
ange, mount by means of the three holes in the ange.
Ø6-1/64
[152.8]
1/4 NPT
1-1/2 [38.10]
[3] Ø13/64 [5.159]
Ø6-1/2 [165.1]
General purpose with ange for surface mounting
SPECIFICATIONS
Wetted Materials: Brass, 403 SS, or 316 SS.
Temperature Limit: 180°F (82°C).
Pressure Limit: Maximum pressure of the operating range. Enclosure rating:
General purpose, weatherproof or explosion-proof.
Repeatability: ±1% of full operating range.
Switch Type: See circuit chart.
Electrical Rating: See electrical ratings chart.
Electrical Connections: Screw terminal.
Conduit Connection: General purpose: 1/2˝ hole for conduit hub. Weatherproof:
1/2˝ conduit hub. Explosion-proof: 3/4˝ female NPT.
Process Connection: General purpose and weatherproof: 1/4˝ male NPT, 1/2˝
male NPT on ranges 15S and 16S. Explosion-proof: 1/2˝ male NPT and 1/4˝ female
NPT.
Mounting Orientation: Vertical.
Set Point Adjustment: Thumbscrew.
Weight: General Purpose: 4 lb (1.8 kg), weatherproof: 6 lb (2.7 kg), explosion-
proof: 8 lb (3.5 kg).
Deadband: See ranges and differentials chart.
ACCESSORIES
Remote Connection
No. 49-62 (300 psi)
No. 49-62HP (to 2500 psi)
1/4 NPT
7/8
[22.23]
1/4 NPT
Mounting Bracket
1-5/8
[41.28]
ADJUSTMENT
SCREWS
HOLES FOR
FLANGE
SCREWS
1-1/8
[28.58]
General purpose
No. 33-25
1/2˝ CONDUIT HOLE
5/8
[15.88]
Ø6-1/64 [152.8]
Pigtail Siphon
No. 42-52 (300 psi)
No. 42-58 (2,000 psi)
1/2˝ CONDUI
HOLE
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Page 2
General Watertight or Weather-Resistant Types: These controls are prexed by
the letters DAW, DRW, DSW and DLW. They are supplied with anged case, bottom
connection only, for surface mounting. Again, install rmly in a level position. Do not
mount the control by twisting the case; use a wrench on the square part of the 1/4˝
bottom pipe connection. Be sure pipe connection is in a vertical position. After cover is
properly attached, with the name plate on bottom of the cover, sight across the lower
end of the glass opening in the cover to see that the control is lined up vertically. Do
not use holes in case bottom for mounting.
Explosion-Proof Types: Install controls prexed by the letters DAH, DAHF, DRH,
DSH, DAE, DRE, DSE, rmly in a level position by means of mounting lugs attached
to the control housing. Line up horizontally by sighting across the left and right conduit
hubs.
Semi-Automatic Control with Manual Reset
Prexed by DR, DRF, DRH, DRE, DRW - with sufx -L or -U. Example: Type DR21-2U. A single adjustment sets the operating point for automatic operation. A pushbutton reset must be operated manually to restore the circuit to the original position
after automatic operation. Example: Type DA-21-2L. Circuit will open automatically
on a pressure rise to the pressure indicated by the pointer on the scale. No matter
how much the pressure drops, the circuit will not re-close until the reset button has
been operated. Sufx -L denotes control will operate automatically on an increase
in pressure. Sufx -U denotes control will operate automatically on a decrease in
pressure.
Note: Series D-30, D-230, D-430, D-530 (i.e., DA-31-3, etc.), when used for steam
with operating ranges of 35 psi or higher, must be siphoned to prevent live steam
from entering the Bourdon tube. With high pressure steam in excess of 100 psi, use
a remote connection.
Series D-20, D-220, D-420, D-520 (i.e., DA-21-2, etc.), when incorpo-rate an orice as
standard in the bottom stem to dampen out surges or pul-sations.
WIRING
Wire in accordance with local electrical codes or equipment manufacturer’s instructions.
For general purpose controls, use a short piece of BX between the rigid conduit and
the control so that it will not be subjected to conduit expan-sion and contraction. Where
control is directly connected into load circuit, it should be connected into hot side of
line. For electrical rating, see name-plate attached to control case.
ADJUSTMENTS: How to Set Operating Point Double Adjustment Types - Fully
Automatic
Prexed by DA, DAF, DAW, DAH, DAHF - provided with double adjustments. Adjust
the upper pointer “C” to set the HIGH PRESSURE POINT for switch operation. Adjust
the lower
pointer “U” to set the LOW U PRESSURE POINT. The differ-ence between the HIGH
and LOW pointers is the operating differential between “on-off” switch operation.
C
U
Adjustment
Reset
Semi-automatic control with manual reset
Manual Lock Type Reset Control
Operates automatically on a decrease of pressure with provision for man-ual reset
when pressure is below set point. Prexed by DL, DLW, DLE, DLH. A single adjustment
sets the low pressure operating point of the control at any value on the scale range.
The control will operate automati-cally at the set point only on a drop in pressure. The
lock-type feature per-mits the circuit to be reset and locked in position when pressures
are below control setting. The lock remains in effect until the pressure has risen to a
value above the control setting. Lock then releases and the circuit is held in the reset
position due to the pressure rise. It will remain in the reset position until it is called on
to again operate automatically on a pressure drop to the select-ed setting.
Reset
Adjustment
Double adjustment types - Fully automatic
Single Adjustment Types - Fully Automatic
Prexed by DS, DSE, DSF, DSH -equipped with a single adjustment. The single
pointer on the scale sets the pressure where switch operation occurs. Differential is
xed (not adjustable). Example setting: Type DS-21-2, range 0-60 psi: circuit opens on
pressure rise. If pointer is set at 40 psi, the control will operate to OPEN circuit at 40
psi and RE-CLOSE circuit at the xed differential of 4 psi.
Single
adjustment
Single adjustment types - Fully automatic
Manual lock type reset control
Two-Stage Pressure Controls - Series D-400
Types DA, DAW, DAH, DAE - with sufxes 421, 423, 431, 433, etc., followed by
specication numbers 4122, 4123, 4129, 4132.
This series incorporates two single pole, single throw magnetic mercury switches,
actuated by the same Bourdon tube. The operating point of each switch is adjustable
through an outside adjustment.
The change in pressure which opens and closes each switch at its respective setting
is the switch’s xed differential. The pressure represented by the difference between
the two adjustment pointers is the pressure “spread” between operation of the two
switches. Upper pointer “U” indicates the operating point of the HIGH pressure circuit.
Lower point “L” indicates the operating point of the low pressure circuit.
Switch B high
Lower
pointer L
Two-stage pressure controls Series 400
Switch A low
Upper
pointer U
Page 3
Example Setting: Type DA-421, Specication No. 4122, range 0 to 60 psi. With lower
pointer “L” set at 25 psi and upper pointer “U” set at 50 psi, both circuits will be closed
when pressure is 25 psi and lower. When pressure rises to 26 psi, mercury switch A will
open its circuit. When pressure rises to 50 psi, mercury switch B will open its circuit.
Both switches remain open above this setting. The xed differential (sensitivity) of
each switch for this particular range is 1 psi. Upon a drop in pressure, mercury switch
“B” will close its circuit at 49 psi; mercury switch “A” will close its circuit at 25 psi.
LOCKING DEVICE
When the control has been adjusted to desired range, the locking bar may be inserted
between the adjustment screws with slot passing over the hole in the lug. By placing
a sealing wire between the locking bar and the hole in the lug protruding from the
adjustment assembly, adjustments cannot be tampered with.
For DAF, DRF, DSF, DAW, DRW, DSW, the adjusting knob cover may be sealed in
place with sealing wire through the cover bolt hole. For DAH, DSH, sealing wire may
pass through locking bar and hole in hub above the adjusting knobs.
CAUTION
CAUTION
CAUTION
CAUTION
Controls with Mercury Switches
APPLICATION
Bourdon tube Material
Brass Bourdon Tubes 0-30 Hg VAC
403 Stainless Steel
Bourdon Tubes
316 Stainless Steel
Bourdon Tubes
Note: Differentials listed are for SP-ST operation only. When controls incorporate two mercury switches for double throw or two pole operation, the
differentials are approximately double those shown for standard single pole, single throw controls.
Do not exceed maximum adjustment/operating range of control.
Remove control if higher pressures are required.
Do not fail to use a siphon on steam where range is 35 lb or more.
Control movement must not be oiled.
Do not overload — note electrical rating on nameplate and be sure
total current passing through switch is within specied rating.
Do not tamper with switch wires. Position of these wires is essential
to proper operation. Tampering with these wires will void warranty.
Adjustable Differential
Double Adjustment for setting both ‘on
and ‘off” operating points Maximum
Differenial - full-scale. Minimum
Adjustable Operating Range
psig
10 in Hg VAC 12
1/8 to 15 psig
1/8 to 20 psig
1 to 35 psig
25 in Hg VAC 50
2 to 60 psig
5 to100 psig
5 to 150 psig
10 to 200 psig
10 to 300 psig
30 in Hg VAC 60
30 in Hg VAC 75
2 to 60 psig
5 to 100 psig
10 to 200 psig
10 to 300 psig
40 to 350 psig
25 to 600 psig
50 to 1000 psig
100 to 1500 psig
300 to 2500 psig
500 to 5000 psig
800 to 8000 psig
30 in Hg VAC 75
5 to 75 psig
10 to 100 psig
10 to 150 psig
10 to 300 psig
30 to 400 psig
75 to 800 psig
100 to 1000 psig
200 to 2500 psig
Two-Stage Pressure Controls, Series D-400 Ranges and Differentials
Range
Number Adj. Working Range
For Steam and Other Applications: DA-431, -DAW-433, DAH-431
1
2
3
3A
4
5
6
7
8
9
27
For General Pressure Applications: DA-421, DAW-423, DAH-421
5S
6S
8S
9S
9AS
10S
11S
12S
13S
15S
25S
26S
316 SS Bourdon Tubes: DA-441, DAW-443, DAH-441
26E
23E
6E
24E
9E
21E
22E
11E
13E
1/8 to 15 psig
0 to 30 in Hg VAC
10 in VAC 12 psig
1/8 to 20 psig
1 to 35 psig
2 to 60 psig
5 to 100 psig
5 to 150 psig
5 to 200 psig
10 to 300 psig
25 in VAC 50 psig
2 to 60 psig
5 to 100 psig
10 to 200 psig
10 to 300 psig
40 to 350 psig
25 to 600 psig
50 to 1000 psig
100 to 1500 psig
300 to 2500 psig
500 to 5000 psig
30 in Hg VAC 60 psig
30 in Hg VAC 75 psig
30 in Hg VAC 75
5 to 75 psig
10 to 100 psig
10 to 150 psig
10 to 300 psig
30 to 400 psig
75 to 800 psig
100 to 1000 psig
200 to 2500 psig
Two Stage, Series D-400 Switch Operating Specications
When ordering, select operation desired, add sufx number to type number of
control. Example: Type DA-431-4122.
Contact Position
Specication
Number Pressure Switch Mk.
-4122
-4129
-4132
-4123
Specication No. 4122. One circuit opens on increase of pressure; second circuit
opens on further increase of pressure.
Specication No. 4129. One circuit closes on increase of pressure; second circuit
closes on further increase of pressure.
Specication No. 4132. Both circuits open at intermediate pressure. One circuit
closes on increase of pressure above neutral zone; second circuit closes on
decrease in pressure below neutral zone.
Specication No. 4123. Both circuits close at intermediate pressure. One circuit
opens on increase of pressure above neutral zone; second circuit opens on decrease
in pressure below neutral zone.
Electrical Ratings D-400
See Code C on Page 5 in Electrical Rating Chart.
“A”
“B”
“A”
“B”
“A”
“B”
“A”
“B”
Low
Pressure
Hi-Vac.
ON
ON
OFF
OFF
ON
OFF
OFF
ON
Intermediate
Pressure
OFF
ON
ON
OFF
OFF
OFF
ON
ON
High
Pressure
Lo-Vac.
OFF
OFF
ON
ON
OFF
ON
ON
OFF
Page 5
CIRCUIT CHART
Sufx
Number CircuitCode
-2
-3
-4
-26
-36
-54
-103
SP-STAOpens
SP-STACloses
DP-STBCloses
SP-STA*Closes
SP-STA*Opens
DP-STBOpens
DP-STACloses
Circuit Response to
Pressure Increase
-113
-127
-152
-153SP-DTBOne Closes as Other Opens
-154
-155
-156
-705
-729
-804
-815
-816
*Consult factory.
ELECTRICAL RATING CHART
Circuit
Code
Sufx
A
-2, -3
-153
B
-2, -3
C
-2, -3
*Consult factory.
DP-STA*Closes
DP-STAOpens
SP-DTBOne Closes as Other Opens
2 Circuits
1 Circuit
1 Circuit
2 Circuit
SP-DTAOne Closes as Other Opens
SP-DT
SP-DTBA
SP-ST
SP-DTBA
DP-DTBTwo Close
AC CapacityDC CapacityHorsepower
120 V 240 V 440 V 120 V240 V ACDC
10A
4A
5A
0.3A
BClose
Opens
BCloses
Open
One Closes as Other Opens
Opens
One Closes as Other Opens
Opens
Two Open
B4P-ST Close (2) 9-67
B4P-ST Open (2) 9-67
5A
3A
1*
NA
NA
10A
4A
2-1/2A
0.15A
2A
2A
0.15A
5A
2A
1A
0.07A
3/4
1/8
1/8
NA
1/3
NA
1/10
NA
Page 6
[3] REAR FLANGE
HUB
2-7/8
1/4 NPT
7-3/4 [196.9]
BREATHER
3-1/2 [88.90]
[250.83]
5 [127]
[4] Ø7/16 [11.23] MOUNTING HOLES
10-13/16 [274.7]
3/4 NPT
CONNECTION
TYP
[OPTIONAL]
9-7/8
Explosion-proof prexed by DAH, DAHF DRH, DSH, DSHF
MOUNTING HOLES [OPTIONAL]
[2] STD. Ø13/32
[10.32] MOUNTING
HOLES
1/2 NPT
3/4˝ CONDUIT
CONNECTION
MOUNTING HOLES
Watertight NEMA 2, 3, 4 - Prexed by DAW, DRW, DSW, DLW