Series DPMP-4 LCD Digital Panel Meters
Specifications - Installation and Operating Instructions
The Series DPMP LCD Digital Panel Meter provides easy viewing on
the 3-1/2 digit LCD display. The display segments are available in a
choice of amber, red or green. The meter features user-selectable
engineering units, adjustable zero and span and field-selectable decimal
point position. The snap-in bezel mount eliminates mounting hardware
for quick installation. A 24 VDC power supply is required for the
operation of the backlight.
INSTALLATION
The Series DPMP is designed for panel mounting in a 2.4˝ (61 mm) W x
1˝ (25.4 mm) H panel cutout.
WIRING
The unit is powered by a 4-20 mA loop and the screw terminals for wiring
are located on the back of the adder board marked with + SIG -. The
backlighting requires a 24 VDC power supply and should be connected
to terminals identified with + B/L -.
SPECIFICATIONS
Inputs: 4 to 20 mA.
Input Impedance: 300Ω nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: Powered by control loop.
Backlight Power Supply: 24 VDC @ 35 mA typical.
Span and Zero: Adjustable. (±1999 counts).
Display: 3-1/2 digits, 7 segments, 0.45˝ (11.4 mm) H.
Decimal Points: 3-position, user selectable.
Engineering Units: DPMP-XXX: °F, °C, %, PSI; DPMP-XXXP: V, A,
KW, PF.
Polarity: Automatic, “-” displayed.
Operating Temperature: 32 to 122°F (0 to 50°C).
Storage Temperature: -4 to 158°F (-20 to 70°C).
Mounting: Snap in bezel mount
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.
Rear View
Note: If backlight supply is not loop supply, ground should be referenced
together.
Phone: 219/879-8000 www.dwyer-inst.com
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
OPERATION
1
*
P Models
V
A
KW
PF
1
13
°F
°C
PSI
%
Selecting Engineering Units
Four sets of jumper pins are located in the back of the meter, between the
meter and the adder board. Move the jumper to fit over the appropriate pins
which correspond to the desired engineering units. See Figure 1.
Setting Min/Max Display Value J1, J2, J3 (See Figure 3 & 4):
If:
Min Display is ≤ 0 or
Min Display is > 0 and Max Display Min Display > 5,
Then:
J1, J2 & J3 should be all set to the top jumper (See Figure 3).
•
•
Figure 3
Figure 1
Selecting Decimal Point Position
Four decimal point positions are available on the digital panel meter. Move
the jumper to correspond to the desired decimal point location. See Figure
2.
Figure 2
If:
Min Display is > 0 and Max Display Min Display < 5,
Then:
J1, J2, J3 should be all set to the jumper (See Figure 4).
MAINTENANCE/REPAIR
Upon final installation of the Series DPMP-4, no routine maintenance is
required. The Series DPMP-4 is not field serviceable and should be
returned if repair is needed. Field repair should not be attempted and may
void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website.
Contact customer service to receive a Return Goods Authorization number
before shipping the product back for repair. Be sure to include a brief
description of the problem plus any additional application notes.
•
•
Figure 4
©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 5/14 FR# R2-443465-00 Rev. 3