Series DM-1000 DigiMag® Digital Differential Pressure Gage
Specications - Installation and Operating Instructions
The Series DM-1000 DigiMag® Digital Differential Pressure Gage is the ideal digital
instrument to take the place of analog mechanical pressure gages. The DigiMag
Digital Gages are more versatile than analog gages with their ability to be eld-
programmed to display many commonly used engineering units as well as percent of
full scale. The Series DM-1000 can be programmed in 8 commonly used engineering
units plus percent of full scale. This capability allows quick units selection on site,
eliminating the need to calculate various unit conversions. The DigiMag
Differential Pressure Gages have an added feature for lter applications where a set
point can be input where the display will blink when the lter is dirty, alerting the user
that a maintenance action needs to occur.
Programming the Series DM-1000 is easy using the menu key to access 4 simplied
menus which provide access to: Security level; engineering units; lter set point; view
peak and valley process readings; digital damping for smoothing erratic process
applications; display update to conserve battery life; zero and span eld calibration.
®
The Series DM-1000 DigiMag
scale accuracy of 1% on ranges down to 2 in w.c. and 2% accuracy down to the very
low ranges of 1 in to 0.25 in w.c. Models are also available with bi-directional ranges.
®
Digital Differential Pressure Gages offer power versatility by working with 9
DigiMag
to 24 VDC line power or simply 9 V battery power. If using line power and connecting
the 9V battery, the battery will act as a back-up if line power is lost or interrupted.
Digital Differential Pressure Gage possesses a full
®
Digital
SPECIFICATIONS
®
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Housing Materials: Glass lled plastic.
Accuracy: ±1% F.S. including linearity, hysteresis and repeatability; ±2% F.S. for
ranges 1 in w.c. and below.
Temperature Limits: 0 to 140°F (-18 to 60°C).
Compensated Temperature Limits: 32 to 122°F (0 to 50°C).
Long Term Stability: ±1% F.S. per year.
Thermal Effect: ±0.05% F.S./°F typ.; ±0.10% F.S./°F for ranges 1 in w.c. and below.
Display: 4-digit LCD (Digits: 0.60˝H x 0.33˝W).
Display Update: Selectable for 1 second to 10 minutes or update only from button
push.
Pressure Limits: Normal and bi-directional ranges 5 in w.c. and lower = 2 psi (13.7
kPa); Normal and bi-directional ranges 10 in w.c. and higher = 11 psi (75 kPa).
Selectable Engineering Units: in w.c., psi, kPa, Pa, mm w.c., mBar, in Hg, mm Hg,
FS (0-100%).
Power Requirements: 9V battery or external power supply 9-24 VDC. Battery
included but not connected.
Type of Battery: 9V alkaline battery (Duracell
Battery Service Life: Battery life depending on the Display Update setting: 150
hours (typical) if Display Update = 1 second; 9 month (typical) if Display Update =
10 minutes; 1.5 years (typical) if Display Update is disabled. Battery may last up to
four times longer when using lithium-based battery ULTRALIFE U9VL-J.
Current Consumption: 5 mA maximum.
Electrical Connections: Removable terminal block for 16 to 26 AWG.
Electrical Entry: Cable gland for 0.114 to 0.250˝ (2.9 to 6.4 mm) diameter cable.
Process Connections: 1/8˝ (3 mm) ID tubing.
Enclosure Rating: NEMA 4X (IP66).
Weight: 1.18 lb (535 g).
Size: 5˝ (127 mm) O.D. front face.
Agency Approvals: CE, EN 61326-1 [Immunity Test Requirement for Industrial
Environments] with the following SPEC: IEC 61000-3-2, IEC 61000-3-3, IEC610004-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, and IEC610004-11.
®
PC 1604 or equivalent).
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
Duracell® is a registered trademark of The Gillette Company
www.dwyer-inst.com
e-mail: info@dwyermail.com
Page 2
INSTALLATION
3-5/64
[78.27]
3-15/32 [88.12]
THRU HOLE FOR
(3) FLANGE MOUNTING
9 TO 24 VDC
B1
Mounting
A vertical position required. That is the position in which all standard models are
calibrated at the factory. Provide a 4-9/16˝ diameter opening in panel. Insert gage and
secure in place with provided screws and adapters.
Included Accessories:
Mounting lugs – 3
6-20 x 2-1/2 screws – 3
4-20 x 3/8 screws – 3 (mounting hole depth is 3/8˝ [9.53])
Cable gland – 1
CONN6
9V BATTERY
HOLE LOCATIONS
OUTSIDE
DIAMETER
OF A-286
FLANGE
Ø5/8 [15.88]
CONDUIT
CONNECTION
13/32 [10.16]
(3) SURFACE
MOUNTING HOLE
LOCATIONS
Pressure Connections
Two integral tubing connections are provided on the back of the gage. They are sized
to t 3/16˝ (4.8 mm) I.D. x 5/16˝ (7.9 mm) O.D. exible PVC tubing. To measure single
positive pressure, connect tubing to the + port and vent the – port to atmosphere. To
measure single negative pressure (vacuum), connect tubing to the – port and vent the
+ port to atmosphere. To measure differential pressure, connect higher pressure to
the + port and lower pressure to the – port. Be sure the pressure rating of the tubing
exceeds that of the operating ranges.
1-1/4
[31.75]
1-51/64
[45.72]
Ø5-17/32 [140.49]
BOLT CIRCLE
2X30°
2xØ13/32 [10.32]
THRU HOLES FOR
PRESSURE PORTS
MOUNTING
HOLE DIMENSION
FOR A-286 FLANGE
Ø5-1/8 [130.18]
STANDARD
MOUNTING HOLE
DIMENSION FOR
DIGIMAG GAUGE
Ø4-9/16 [115.89]
1 [25.44]
POWER SUPPLY
Figure 1
OPERATING INSTRUCTIONS - Key Functions
Menu
Up Arrow
Down Arrow
Enter
Home Position
Function
Allows access to the
menus
Displays pressure
readings instantly
(rAtE KEY MODE only)
Displays full scale
range of unit
Main Menu
Function
Return to
home position
Sequences
through menus
Sequences
through menus
Enter into
SUB MENU
Sub Menu
Function
Return to previous menu
Increments a value
Decrements a value
Changes a value or
setting. Press ENTER and
display will blink. Adjust
with UP or DOWN arrows.
Press ENTER to store.
Display will stop blinking.
ElectricalConnections
A 9V battery or an external power supply 9-24 VDC can be used to power the unit. If
both battery and external power supply are connected, the battery will work as back
up power.
Battery Installation
The unit is shipped with a separate 9V alkaline battery. Remove the unit’s top back
cover, do not remove bottom cover. Connect the 9V battery to the battery holder as
shown in Figure 1. Replace top back cover and tighten screws to 2 ±.25 in. lbs.
External Power Supply Installation
Remove the unit’s back cover then connect the external power supply to the terminal
block as shown in Figure 1.
VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY
WILL RESULT.
CAUTION
POWER MUST BE OFF WHILE WIRING CONNECTIONS
ARE BEING MADE. DO NOT EXCEED SPECIFIED SUPPLY
Page 3
Menu Map
Page 4
Main Menu Programming Instructions
(Upper Right Display Reads MENU)
Security Menu: SECr-MENU
Lock out access to all menus or lock out access to all menus except Auto-Zero function
(Auto-ZERO).
Operation Menu: OPEr-MENU
Select the measurement type – pressure, velocity or ow and corresponding
engineering units (Velocity and ow are not available for Model DM-1100).
Display Menu: diS-MENU
Monitor and adjust display related settings: Filter type, lter point, dampening, display
update, peak and valley.
Advanced Menu: AdU-MENU
Perform auto-zero or full-scale calibration.
Security Menu: SECr-MENU
With the gage reading pressure (home position), press and hold the MENU key until
the Security MENU is displayed. Press the E key to show the security SUB MENU
SECr–0001. When the security SUB MENU is selected, the present security level is
displayed in the upper right hand display. To change the security level, adjust the
number displayed to the number shown in the following table for the desired security
level.
TABLE 1 PRESSURE RANGE VS. AVAILABLE UNITS
in w.c. psikPaPambar mm
0.250
–
0.062
62.20
0.500
–
–
–
0.181
0.361
0.543
0.903
1.806
3.613
0.124
0.249
0.498
1.245
2.491
3.738
6.227
12.45
24.91
1.000
2.000
5.000
10.00
15.00
25.00
50.00
100.0
Note: OFL (over ow) or UFL (under ow) will appear when the low and high range
levels have been exceeded by 10% F.S.
124.5
249.1
498.2
1245
2491
3738
6227
–
–
0.622
1.245
2.492
4.982
12.45
24.91
37.38
62.27
124.5
249.1
in Hg mm Hg% of FSResolution
w.c.
6.35
–
0.467
12.70
25.40
50.80
127.0
254.0
381.0
635.0
1270
2540
–
–
–
0.368
0.736
1.104
1.839
3.678
7.355
0.934
1.868
3.736
9.34
18.68
28.02
46.71
93.42
186.8
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
(in w.c.)
0.001
0.001
0.001
0.001
0.002
0.010
0.010
0.010
0.020
0.100
Security Level
Displayed
1
2
3
The password values shown in the table cannot be altered, so retain a copy of these
pages for future reference.
Operation Menu: OPEr-MENU
With the gage reading a numerical value (home position), press and hold the MENU
key until the Security MENU is displayed. Press the ▼ key to show the OPEr-MENU. Press the E key to show the Operation SUB MENUS.
The Operation SUB MENUS for Series DM-1100 is PrES–INWC (Pressure–Unit)
Pressure Sub Menu: PrES – INWC
PrES – INWC: Pressure – inches of water column
With the LCD reading PrES – INWC, press the E key; the display will blink. Press
the ▼ key to change the pressure unit then press the E key to save the desired unit.
For pressure measurement, the following units are available:
INWC – Inches of water column MBAR – Millibar
PSI – Pounds per square inch INHG – Inches of mercury
KPA – Kilopascals MMHG – Millimeters of mercury
PA – Pascals FS – % of full scale
MMWC – Millimeters of water column
AccessPassword
All menus access
All menus locked except the
auto-zero function
All menus locked
Value to Enter
10
90
111
Page 5
DISPLAY MENU: diS – MENU
With the gage reading a numerical value (home position), press and hold the MENU
key until the Security MENU is displayed. Press the ▼ key until the LCD shows diS
– MENU. Press the E key to show the Display SUB MENUS.
FILTER TYPE SETTING
With the LCD reading FILt – OFF, press the E key; the display will blink. Press the ▼
key to change the lter type then press the E key to save the desired lter type.
FILt – OFF: Filter type = OFF. The lter function is disabled.
FILt – HIGH: Filter type = HIGH. The display blinks when pressure is greater than the
lter point.
FILt – LOW: Filter type - LOW. The display blinks when pressure is less than the lter
point.
FILTER POINT SETTING
With the LCD reading 0.00 – SPPT, press the E key; the display will blink. Press the
▼ key to change the lter point then press the E key to save the desired lter point.
0.00 – SPPT: Filter point = 0.00. The lter point may be set to anywhere within the
range of the instrument.
DAMPING SETTING
With the LCD reading 1 – DAMP, press the E key; the display will blink. Press the ▼
key to change the damping level then press the E key to save the desired damping
level.
1 – DAMP: Damping level = 1. The damping level can be adjusted from 1 to 15.
Damping stabilizes the display from instabilities due to things such as vibration and
excessive pressure uctuations. The damping function adjusts the amount of readings
that are averaged for each display update.
DISPLAY UPDATE SETTING
With the LCD reading rAtE – NORM, press the E key; the display will blink. Press
the q key to change the display update rate then press the E key to save the desired
display update rate.
PEAK AND VALLEY SETTING
100.0 – PEAK: Peak value = 100.0
The peak feature stores the highest pressure reading the instrument has measured
since the last reset or power up. At power up PEAK is reset to the present
pressure reading. To manually reset the PEAK value, press the E key while in the
PEAK SUB MENU.
0.0 – VALY: Valley value = 0.0
The valley feature stores the lowest pressure reading the instrument has measured
since the last reset or power up. At power up VALY is reset to the present
pressure reading. To manually reset the VA LY value, press the E key while in the
VALY SUB MENU.
ADVANCED MENU: AdU – MENU
With the gage reading pressure (home position), press and hold the MENU key until
the Security MENU is displayed. Press the ▼ key until the display shows the AdU
– MENU. Press the E key to show the advanced function SUB MENUS.
Auto ZERO: auto-zero
Note: For accurate calibration, DO NOT apply any pressure when performing this
function.
With the display reading Auto ZERO, release pressure to Zero then press the E key;
the display will blink. Press the E key again to complete the auto-zero.
CAL – SPAN: full-scale calibration
With the display reading CAL – FS, apply full-scale pressure then press the E key; the display will blink. Press the E key again to save the full-scale calibration or press the
MENU key to cancel the calibration.
MAINTENANCE
This model is not eld-serviceable and should be returned if repair is needed (eld
repair should not be attempted and may void warranty). Be sure to include a brief
description of the problem plus any relevant application notes. Contact customer
service to receive a return goods authorization number before shipping.
rAtE – NORM: Display update = Normal (1 second).
The gage reads the process pressure and updates the LCD every second.
rAtE – 10: Display update = 10 minutes.
The gage reads the process pressure and updates the LCD every 10 minutes.
rAtE – KEY (On-Touch mode): Display update is disabled.
The gage reads the process pressure and updates the LCD whenever the ▲ key
is pressed. If the ▲ key is released, the LCD will hold and display the last pressure
reading.
NOTES:
1. Depending on the Display Update setting, the battery life is shown below:
-150 hours (typical) if Display Update is set for “Normal” 1 second update.
rAtE-NORM
-9 months (typical) if Display Update is set for 10 minutes. rAtE-10
-1.5 years (typical) if Display Update is disabled. rAtE-KEY
2. If the Display Update is set for 10 minutes or disabled (On-Touch mode), the
process pressure value can be read instantly by pressing and holding the ▲ key on
the front panel. Also the LCD will automatically show “ALAr” if the lter point has
been exceeded.