Dwyer CDTV Carbon Dioxide Operating Instructions

Series CDTV Duct Mount Carbon Dioxide / Volatile
®
Organic Compound Transmitter
Specications - Installation and Operating Instructions
1/8˝
[3.17]
Ø3-5/16˝
[84.14]
4-25/32˝ [121.44]
4-9/32˝
[108.74]
2-13/16˝
[71.44]
Bulletin AQ-CDTV-D-2
11-49/64˝
[298.85]
Ø1-15/64˝
[31.35]
The Series CDTV Carbon Dioxide / Volatile Organic Compound (VOC) Transmitter reduces energy cost in buildings by lowering the amount of conditioned air based on the occupancy of the space. By detecting both CO2 and VOC, the transmitter can also detect fumes that may need to be exhausted during lower occupancy periods. Combining both measurements in one transmitter reduces both labor and material costs by only having to install one CDTV-VOC unit, instead of separate CO2 and VOC transmitters.
Carbon dioxide measurements are taken using our proven Single-Beam Dual­Wavelength Non-Dispersive Infrared (NDIR) sensor. Our sensor allows users to get accurate measurements without waiting for the settling / correction periods of other logic based sensors. Transmitters can be used in buildings and applications that have 24 hour occupancy and can be calibrated on site to match environmental conditions for improved accuracy.
The VOC measurement is a single value derived from the presence of substances including alcohols, aldehydes, aliphatic hydrocarbons, amines, aromatic hydrocarbons, CO, CH4, LPG, ketones, and organic acids. Although a standard unit of measure is
not currently dened, the VOC measurement unit “ppm CO2 equivalent” used by the
device is commonly used in the industry. The VOC measurement does not actually measure CO2, but instead senses and indicates an air quality value that approximately correlates perceived comfort levels to similar concentrations of CO2 in the environment.
Single-beam dual-wavelength sensor advantages:
• Automatically corrects for aging effects in occupied and unoccupied buildings
Perfect for hospitals and manufacturing plants that are occupied 24 hours per
day
• Measures actual unltered light intensity directly
Eliminates error from incorrect assumptions of gas concentration in theoretical
logic assumption methods
SPECIFICATIONS
Range: CO2: 0 to 2000 or 0 to 5000 PPM (depending on model); VOC: 0 to 2000 PPM CO2 equivalent.
Accuracy: CO2: ±40 PPM +3% of reading. Temperature Dependence: ±8 PPM / °C at 1100 PPM.
Non-Linearity: CO2: 16 PPM.
Pressure Dependence: CO2: 0.13% of reading per mm of Hg. Response Time: CO2: 2 min for 99% step change; VOC: 5 min.
Temperature Limits: 32 to 122°F (0 to 50°C).
Power Requirements: 16-35 VDC / 19-28 VAC. Power Consumption: Average: 2 watts; Peak: 3.75 watts. Sensor: CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS (metal oxide
semiconductor). Output: Current: 0-20 mA, 4-20 mA, 0-10 mA, or 2-10 mA (depending on selection
jumper, max 500 Ω); Voltage: 0-10 VDC, 2-10 VDC, 0-5 VDC, or 1-5 VDC (depending on selection jumper, min 500 Ω); Relay: SPST NO 2A @ 30 VDC.
Weight: 5.6 oz (158.8 g). Agency Approvals: CE.
INSTALLATION
WARNING
Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
CAUTION
CAUTION
Disconnect power supply before installation to prevent electrical shock and equipment damage.
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive moisture or corrosive fumes are present.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
CAUTION
NOTICE
transmitter to adjust to the current CO2 concentration.
NOTICE
days.
Phone: 219/879-8000
Fax: 219/872-9057
Do not exceed ratings of this device. Permanent damage not covered by warranty may result.
Upon powering the transmitter, the rmware version will ash on
the display. A warm up period of 30 minutes is required for the
Self calibration feature of the transmitter requires exposure to normal outdoor equivalent carbon dioxide level once every thirty
LEED® is a registered trademark of the U.S. Green Building Council.
www.dwyer-inst.com
e-mail: info@dwyermail.com
MOUNTING
CONFIGURA
AY
ENTER PUSH BUTTON
OUTPUT SELECTION
URRENTVO
0-20 mA
4-20 mA
0-10 mA
2-10 mA
TURE
POWER
1. Cut hole into duct large enough to insert probe.
2. Attach housing ears to duct using the two self-tapping screws provided.
3. Knock out an opening in the housing and attach an electrical tting to route
electrical wiring. PG11 & PG16 knockouts are molded into the housing.
WIRING
Use maximum 18 AWG wire for wiring to terminals. Refer to Figure 4 for wiring information.
UP PUSH BUTTON
REMOTE DISPL
CONNECTOR
DOWN PUSH
BUTTON
TION
SWITCHES
Figure 1: Diagram of circuit board
Selection of Current and Voltage Outputs
Prior to wiring, verify that the current/voltage conguration switches (positions 1 and
2) are set to the desired output type. Refer to Figure 1 to locate the conguration
switches. See Figure 2 for diagram of the current/voltage selection switches. For voltage output selection, the output can be 0-10 VDC, 0-5 VDC, 2-10 VDC or 1-5 VDC. See Figure 3 for the type of voltage output selection switches (positions 3 & 4).
LTAGECURRENT
CO2 CONCENTRATION
Figure 2: Current/Voltage Output
Selection Jumper (PJ1 and PJ2)
0-10 V
2-10 V
Figure 3: Output range selection jumper
TERMINAL
BLOCK
VOLTAGEC
VOC OUTPUT SELECTION
0-5 V
1-5 V
Current / Voltage Outputs
The transmitter may be wired for current or voltage output for both carbon dioxide and VOC. The transmitter can be powered with either 16-35 VDC or 19-28 VAC. Wire the transmitter according to Figure 4.
NOTICE
Thermistor and RTD Outputs
Thermistor and RTD passive outputs are located on terminals 7 and 8 and do not require any power. Passive temperature outputs are not polarity sensitive.
Remote Display
Remote display Model A-449 can be used to display the VOC or carbon dioxide. The mini USB plug of the remote display plugs into the receptor on the side of the housing. After a short warm up time, the display will begin to show the VOC or carbon dioxide measurements.
ACCESSING MENU PARAMETERS
Step 1: To enter the menu structure, press and simultaneously for 5 seconds (display will show RON parameter).
Step 2: Press or to cycle between menu items.
Step 3: Press to edit the value for the displayed menu item (SET will appear on display).
Step 4: Press or to adjust the value of the menu item.
Step 5: Press to save the changes (SET will disappear).
Step 6: Repeat Steps 2 through 5 for each of the parameters.
Step 7: To exit the menu at any time, press and hold and simultaneously for 5 seconds or wait 10 seconds without pushing any buttons.
During the initial 5 minute warm-up phase, the VOC reading will be 0 ppm or an indeterminate value. After warming up, the device is operational and note the VOC output level will be approximately 450 PPM. If the device outputs 0 PPM after the warm-up, there is either an operational error or a disconnected sensor error and customer service should be contacted.
Note: Reference menu descriptions for changing factory settings.
Optional relay can be used as either a dry contact or low voltage switched circuit up to 2 A at 30 VDC.
VOC
SUPPLY
Figure 4: Active output wiring diagram
RECEIVER
CO2
RECEIVER
RELAY CONTACT
PASSIVE TEMPERA SENSOR
Loading...
+ 2 hidden pages