Dwyer CDTA User Manual

Series CDTA Communicating Carbon Dioxide Detector
3.65
[92.72]
3.56
[90.42]
1
.08
[
27.33]
4.50
[114.30]
2.80
[71.12]
1
.10
[
27.96]
Specifications - Quick Start Installation and Operating Instructions
European North American
The Series CDTA Communicating Carbon Dioxide Detector combines the
function of three room sensors into a single, compact housing. Parameters include
arbon dioxide, humidity, temperature, and temperature set point with override. By
c
aving field selectable Modbus
h
eeded for power and the communication signal. The communicating detectors
n can be daisy-chained together to further reduce installation cost. In order to reduce the set up time, the RS-485 MAC address is set up using on board dip switches. A second set of dip switches are used to select whether output is Modbus BACnet MS/TP communication protocols and to limit access to the set up menu.
Like our Series CDT Carbon Dioxide Transmitter, the Series CDTA uses a Single Beam Dual Wavelength Non-Dispersive Infrared (NDIR) sensor to measure the carbon dioxide level. This technology can be used in installations that will be occupied 24 hours per day. For improved accuracy, the transmitter can be field calibrated to the environmental conditions of the installation. Also, the barometric pressure can be programmed to correct for altitude. The humidity uses a capacitive polymer sensor and the temperature is measured using a 10KΩ thermistor sensor. The humidity sensor is field replaceable without the need for additional calibration.
Optional local and remote displays are available to display any of the parameters. For applications in which the building occupants aren’t familiar with CO concentrations, the LCD can be programmed to display temperature, humidity, or temperature set point instead.
Installation
CAUTION
Disconnect power supply before installation to prevent electrical shock and equipment damage.
®
nd BACnet Communications, only four wires are
a
®
RTU or
Bulletin AQ-CDTA-QS
PECIFICATIONS
S Sensor (CO
Humidity: Capacitive polymer; Temperature: Solid state band gap.
Range:
C
Accuracy:
CO RH: ±2% (10 to 90% RH); Temperature: ±1°C @ 25°C.
Temperature Dependence (CO Non-Linearity (CO Pressure Dependence (CO Response Time (CO Temperature Limits: 32 to 122°F (0 to 50°C). Humidity Limits: 10 to 95% RH (non-condensing). Power Requirements: 10 to 42 VDC / 10 to 30 VAC. Power Consumption:
2
Average: 0.5 watts;
Peak: 1.2 watts. Output: 2-wire RS-485, Modbus protocol.
Weight: 4.4 oz (125 g). Agency Approvals: BTL, CE, RoHS.
): Single-beam, dual-wavelength NDIR;
2
O
0 to 2000 or 5000 PPM CO2 (depending on model);
:
2
umidity: 0 to 100% RH;
H
emperature: 32 to 122°F (0 to 50°C).
T
2
: ±40 ppm ±3% of reading;
): ±8 ppm / °C at 1100 ppm.
): 16 ppm.
2
): 2 minutes for 99% step change.
2
2
): 0.13% of reading per mm of Hg.
2
®
RTU or BACnet MS/TP communication
Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
NOTICE
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment
damage.
NOTICE
For optimal performance, self calibration feature of the transmitter requires exposure to normal outdoor equivalent
carbon dioxide level once every thirty days.
NOTICE
Avoid locations where severe shock or vibration, excessive moisture or corrosive fumes are present.
NOTICE
Do not exceed ratings of this device, permanent damage not covered by warranty may result.
NOTICE
Upon powering the transmitter, the firmware version will flash on the display. A warm up period of 30 minutes is required for the
transmitter to adjust to the current CO
concentration.
2
Modbus® is a registered trademark of Schneider Automation, Inc.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
igure 1: Removal Of Cover From Back Plate
F
OUNTING
M
. Push tab on top and bottom of cover and lift cover from back plate (See Figure 1).
1
. Select the mounting location, away from diffusers, lights or any external
2
influences.
3. Mount transmitter on a vertical surface to a standard electrical box using the two #6 M2C type screws provided.
4. Pull wires through sub base hole and make necessary connections.
. Reattach cover to base plate.
5
IRING
W
NOTICE
iring should comply with Electrical Characteristics of
W Generators and Receivers for Use in Balanced Digital Multipoint
Systems, TIA/EIA-485-A-1998, Telecommunications Industry Association, 1998.
BACnet installations should comply with ANSI/ASHRAE Standard 135-2010
ACnet A Data Communication Protocol for Building Automation and Control
B
etworks, American Society of Heating, Refrigerating and Air-Conditioning
N Engineers, Inc., 2010.
®
Modbus Serial Line Specification and Implementation Guide V1.02, Modbus
installations should comply with Modbus®Communication Protocol over
®
Organization,
Inc., 2006
igure 3 shows how to connect the CDTA in a network containing individual local
F
upplies. Use a cable containing a twisted pair and a single conductor. The pair is to
s
e used for B(+) and A(-). The single conductor is to be used for common. Both AC
b and DC supplies are suitable for this configuration.
In either configuration you must use shielded cable. Connect the shield to earth
round at one location only to prevent ground loops.
g
ll devices in the network should be daisy chained. Star connections and T
A
onnections are not permitted.
c
The B(+) and A(-) lines must be terminated at both ends with a 120 ohm resistor. If the CDTA is an end device it has an on-board resistor that may be used. See DIP
WITCH SETTINGS to enable it.
S
ip Switch Configuration
D
igure 4: Dip Switch SW2 (Center-Left)
F
Use DIP Switch SW2 (see Figure 4) to configure the RS-485 MAC address of the
evice. A valid address depends on the protocol selected. Valid BACnet addresses
d
ange from 0 to 127. Valid Modbus
r
evice is shipped with BACnet selected and the address set to 127 (as shown in
d
®
ddresses range from 1 to 247. By default, the
a
Figure 4). A valid and unused address should be set before connecting to an existing network. The device will not function properly if an invalid address is set. During the power up sequence, the LCD (if present) will display the RS-485 address as the primary value with “ADR” as the primary text and either “BAC” to indicate BACnet or “MOD” to indicate Modbus
®
as the secondary text. If the RS-485 MAC address is
invalid, the invalid value is shown as the primary value with “ERR” as the primary text.
Communications wiring must be in a daisy-chain fashion. Star connections are not permitted.
Cable shield must be connected to earth ground at one location only.
Figure 2
Figure 2 shows how to connect the CDTA in a network containing a common power supply. Use a cable containing two twisted pairs. One pair is to be used for B(+) and A(-). The other pair is to be used for power and common. This configuration is not suitable for AC supplies. Use a DC supply only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you have many devices, or have long cable runs, the local supply configuration may be a better choice.
Figure 5: Dip Switch SW1 (Bottom-Center)
Use DIP Switch SW1 (see Figure 5) to configure other hardware and software options.
Switch 1 - Menu Enable
2 - Protocol
On
Access to the setup menu is enabled. Modbus
Off
Access to the setup menu is disabled. BACnet
3 - Reserved 4 - Terminating Resister
120Ω Between A (-) and B (+)
Open
Dip Switch
SW2
Dip Switch
SW1
Figure 3
Internal View of Transmitter
Figure 6
Loading...
+ 2 hidden pages