Dwyer 424 User Manual

2
4
3
2
1
6
5
ulletin D-4
B
Series 424 Stationary Gage
perating Instructions and Parts List
O
Parts list. Contact factory for ordering information.
1) Gage body, 5˝ or 10˝ range
2) Molded Nylon Connector – Rapid shut off type
3) Scale, 5˝ or 10˝ range
4) Mounting
5) Fluid level adjustment assembly
1. Mount Gage securely on a vertical surface, avoiding excessive heat.
(Temperatures over 150ºF (66ºC), will damage gage). Level gage approximately by swinging gage about top center mounting screw and locate bottom bracket screws in center of slot.
2. Turn connectors counter clockwise 1/2 to 3/4 turns, thus venting gage
to atmosphere.
3. Center bubble between guide lines on spirit level by swinging about
4. Turn fluid level adjustment knob to set the meniscus of the fluid
column at zero, as shown below.
Align fluid meniscus and the reflected image to eliminate parallax error.
6) Gage leveling bracket
7) Vinyl tubing 3/16˝ I.D. 3 ft. (not shown)
8) 1/8˝ NPT Tube Adapter (not shown)
9) 1 oz. bottle gage fluid (not shown)
5. Add or remove fluid as necessary.
6. Use left hand gage connection for plus (above atmospheric) pressures. Connect to right side for minus (below atmospheric) pressures. Connect to both sides for differential pressures, as with a Pitot tube.
CAUTION:
Use only Dwyer gage fluid. See gage scale plate for proper specific gravity. Clean only with mild soap and water. Strong liquid soaps and other fluids or cleaning agents may damage the gage. Maximum pressure 100 psi.
AIR VELOCITY
The total pressure of an air stream flowing in a duct is the sum of the static or bursting pressure exerted upon the sidewalls of the duct and the impact or velocity pressure of the moving air. Through the use of a Pitot tube connected differentially to a manometer, the velocity pressure alone is indicated and the corresponding air velocity determined.
DWYER INSTRUMENTS INC.
MICHIGAN CITY, IN 46360 U.S.A.
For accuracy of plus or minus 2%, as in laboratory applications, extreme
35D 60D 8
0D
92D
D
are is required and the following precautions should be observed:
c
1. Duct diameter 4˝ (8.64 mm) or greater.
2. Make an accurate traverse per sketch
at right and average the readings.
3. Provide smooth, straight duct sections
0 diameters in length both upstream
1 and downstream from the Pitot tube.
. Provide an egg crate type straightener
4
upstream from the Pitot tube.
n making an air velocity check, select a location as suggested above,
I connect tubing leads from both Pitot tube connections to the manometer
nd insert in the duct with the tip directed into the air stream. If the
a manometer shows a minus indication reverse the tubes. With a direct reading manometer, air velocities will now be shown in feet per minute. In other types, the manometer will read velocity pressure in inches of water and the corresponding velocity will be found from the curves on the Dwyer website or Dwyer catalog. If circumstances do not permit an accurate traverse, center the Pitot tube in the duct, determine the center velocity and multiply by a factor of .9 for the approximate average velocity. Field tests run in this manner should be accurate within plus or minus 5%. The velocity indicated is for dry air at 70°F (21.3°C), 29.9” Barometric Pressure and a resulting density of .075#/cu. ft. For other variations from these conditions, corrections may be based upon the following data:
Air Velocity = 1096.2 P
V
= velocity pressure in inches of water; D= Air density in #/cu. ft.
where P
Air Density = 1.325 x P
where P
B
Temperature (indicated temperature °F plus 460)
Flow in cu. ft. per min. = Duct area in square feet x air velocity in ft. per minute.
STATIC PRESSURE
In checking inlet and discharge fan and blower pressures, balancing ventilation and dust collection systems, checking exhaust systems and similar installations, air velocities above 700 ft. per min. (12.81 kms/hr) can cause an appreciable error. It is recommended that the static connection of the Pitot tube or a static pressure tip be used. In using the static pressure tip or Pitot tube, the tip should be directed into the air stream. For permanent installation, static pressure tips are recommended. If not available, make connections enter the duct perpendicular to the air stream and finish off flush and smooth on the inside.
FURNACE DRAFT
Connect the terminal tube to the minus pressure gage opening and insert it into the combustion chamber for over fire draft reading. If a drilled port is not available insert through fire door but seal the crack. For last pass or smoke pipe draft, connect into the breeching on the furnace side of any draft control or damper. To determine draft loss through the furnace, make connection as indicated for smoke pipe draft and add a second tube, connecting the manometer differentially to the combustion chamber.
AIR FILTER TEST
To determine the pressure drop across an air filter, connect the manometer differentially with one tubing from the downstream or blower side of the filter to the right hand or minus pressure gage connection. Run the second tubing from the upstream side of the filter to the other gage connection. Use static pressure tips if available, with the tips directed into the air stream, to eliminate possibility of error due to air velocity. Read the pressure drop across the filter in inches of water and follow the filter manufacturer’s recommendations for filter cleaning or replacement.
= Barometric Pressure in inches of mercury; T = Absolute
V
D
B
T
DWYER INSTRUMENTS INC.
MICHIGAN CITY, IN 46360 U.S.A.
©Copyright 2013 Dwyer Instruments Inc. Printed in U.S.A. 5/13 FR# 34-440184-00 Rev. 5
Loading...