ulletin D-5
B
Series 421-422 Stationary Gage
perating Instructions
O
1. Mount gage securely on a vertical surface avoiding excessive heat.
(Temperatures over 150°F (65.6°C) will damage gage). Level gage
approximately by swinging gage about top center mounting screw and locate
bottom bracket screws in center of slots.
2. Turn pressure connectors counter clockwise 1/4 to 1/2 turn, thus venting
gage to atmosphere.
3. Center bubble between guide lines on spirit level by swinging about top
center mounting screw and tighten bottom bracket screws.
4. Turn fluid level adjustment knob to set the meniscus of the fluid column at
zero, as in photo.
Align fluid meniscus and the reflected image to eliminate parallax error.
5. Add or remove fluid as necessary.
6. Use left hand pressure gage connection for positive (+) (above atmospheric)
pressures. Connect to right side pressure connection for negative (-) (below
atmospheric) pressures. Connect to both pressure connections for
differential pressures, as with a Pitot tube.
CAUTION:
Use Dwyer gage fluid only. (See Gage Scale for Proper Specific Gravity). Clean
with mild soap and water only. Other fluids or cleaning agents may damage the
gage.
AIR VELOCITY
The total pressure of an air stream flowing in a duct is the sum of the static or
bursting pressure exerted upon the sidewalls of the duct and the impact or velocity
pressure of the moving air. Through the use of a Pitot tube connected differentially
to a manometer, the velocity pressure alone is indicated and the corresponding air
velocity determined.
DWYER INSTRUMENTS INC.
MICHIGAN CITY, IN 46360 U.S.A.
For accuracy of plus or minus 2% as in laboratory applications, extreme care is
equired and the following precautions should be observed:
r
1. Duct diameter 4˝ (101.6 mm) or greater.
. Make an accurate traverse per sketch at right
2
and average the readings.
3. Provide smooth, straight duct sections 10
diameters in length both upstream and
downstream from the Pitot tube.
. Provide an egg crate type straightener
4
upstream from the Pitot tube.
n making an air velocity check select a location as suggest above, connect tubing
I
leads from both Pitot tube connections to the manometer and insert in the duct with
the tip directed into the air stream. If the manometer shows a minus indication
everse the tubes. With a direct reading manometer, air velocities will now be
r
shown in feet per minute. In other types, the manometer will read velocity pressure
in inches of water and corresponding velocity will be found from the curves on the
wyer website or Dwyer catalog If circumstances do not permit an accurate
D
traverse, center the Pitot tube in the duct, determine the center velocity and multiply
by a factor of .9 for the approximate average velocity. Field tests run in this manner
should be accurate within plus or minus 5%.
The velocity indicated is for dry air at 70°F (21.1°C), 29.9” Barometric Pressure and
a resulting density of .075=/cu. ft. For other variations from these conditions,
corrections may be based upon the following data:
Air Velocity = 1096.2 P
V
= velocity pressure in inches of water; D= Air density in =/cu. ft.
where P
Air Density = 1.325 x P
B
= Barometric Pressure in inches of mercury; T = Absolute Temperature
where P
(indicated temperature plus 460)
V
D
B
T
Flow in cu. ft. per min. = Duct area in square feet x air velocity in ft. per minute.
STATIC PRESSURE
In checking inlet and discharge fan and blower pressures, balancing ventilation and
dust collection systems, checking exhaust systems and similar installations, air
velocities above 700 ft. per min. (12.81 kms/hr) can cause an appreciable error. It
is recommended that the static connection of the Pitot tube or a static pressure tip
be used. In using the static pressure tip or Pitot tube, the tip should be directed into
the air stream. For permanent installation, static pressure tips are recommended. If
not available, make connections, enter the duct perpendicular to the air stream and
finish off flush and smooth on the inside.
FURNACE DRAFT
Connect the terminal tube to the minus pressure gage opening and insert it into the
combustion chamber for over fire draft reading. If a drilled port is not available insert
through fire door but seal the crack. For last pass or smoke pipe draft, connect into
the breeching on the furnace side of any draft control or damper. To determine draft
loss through the furnace, make connection as indicated for smoke pipe draft and
add a second tube, connecting the manometer differentially to the combustion
chamber.
AIR FILTER TEST
To determine the pressure drop across an air filter, connect the manometer
differentially with one tubing from the downstream or blower side of the filter to the
right hand or minus pressure gage connection. Run the second tubing from the
upstream side of the filter to the other gage connection. Use static pressure tips if
available, with the tips directed into the air stream, to eliminate possibility of error
due to air velocity. Read the pressure drop across the filter in inches of water and
follow the filter manufacturer’s recommendations for filter cleaning or replacement.
DWYER INSTRUMENTS INC.
MICHIGAN CITY, IN 46360 U.S.A.
©Copyright 2011 Dwyer Instruments Inc. Printed in U.S.A. 4/11 FR# 34-440185-00 Rev. 6