Bulletin H-7
Series 400 Air Velocity Meter
Operating Instructions and Parts List
1. Remove gage from case. Set up in vertical position using (a) gage stand
and leveling screw or (b) Magneclips on a vertical steel surface.
2. Turn connectors counterclockwise 1/2 to 3/4 turns, thus venting gage to
atmosphere.
3. Center bubble between cross hairs on spirit level with leveling screw or by
shifting gage position.
4. Turn fluid level adjustment knob to set the meniscus of the fluid column at
zero, as in sketch.
Align fluid meniscus and the reflected image to eliminate parallax error.
5. Add or remove fluid as necessary.
6. Use left hand gage connection for plus (above atmospheric) pressures.
Connect to right side for minus (below atmospheric) pressures. Connect to
both sides for differential pressures, as with a Pitot tube.
CAUTION:
Use only Dwyer
solvents or cleaning agents may damage the gage.
AIR VELOCITY
The total pressure of an air stream flowing in a duct is the sum of the static or
bursting pressure exerted upon the sidewalls of the duct and the impact or
velocity pressure of the moving air. Through the use of a Pitot tube connected
differentially to a manometer, the velocity pressure alone is indicated and the
corresponding air velocity determined.
®
gage fluid. Clean with mild soap and water only. Other fluids,
DWYER INSTRUMENTS INC.
MICHIGAN CITY, IN 46360 U.S.A.
For accuracy of plus or minus 2%, as in laboratory applications, extreme care is
required and the following precautions should be observed:
1. Duct diameter 4˝ (8.64 mm) or greater.
2. Make an accurate traverse per sketch at right
and average the readings.
3. Provide smooth, straight duct sections 10
diameters in length both upstream and
downstream from the Pitot tube.
4. Provide an egg crate type straightener
upstream from the Pitot tube.
In making an air velocity check, select a location as suggested above, connect
tubing leads from both Pitot tube connections to the manometer and insert in the
duct with the tip directed into the air stream. If the manometer shows a minus
indication reverse the tubes. With a direct reading manometer, air velocities will
now be shown in feet per minute. In other types, the manometer will read
velocity pressure in inches of water and the corresponding velocity will be found
from the curves on the Dwyer website or Dwyer catalog. If circumstances do not
permit an accurate traverse, center the Pitot tube in the duct, determine the
center velocity and multiply by a factor of .9 for the approximate average
velocity. Field tests run in this manner should be accurate within plus or minus
5%.
The velocity indicated is for dry air at 70°F (21.3°C), 29.9” Barometric Pressure
and a resulting density of .075=/cu. ft. For other variations from these conditions,
corrections may be based upon the following data:
Air Velocity = 1096.7 P
V
= velocity pressure in inches of water; D= Air density in lbs/cu. ft.
where P
Air Density = 1.325 x P
B
= Barometric Pressure in inches of mercury; T = Absolute Temperature
where P
(indicated temperature plus 460)
V
D
B
T
Flow in cu. ft. per min. = Duct area in square feet x air velocity in ft. per minute.
STATIC PRESSURE
In checking inlet and discharge fan and blower pressures, balancing ventilation
and dust collection systems, checking exhaust systems and similar installations,
air velocities above 700 ft. per min. (12.81 kms/hr) can cause an appreciable
error. It is recommended that the static connection of the Pitot tube or a static
pressure tip be used. In using the static pressure tip or Pitot tube, the tip should
be directed into the air stream. For permanent installation, static pressure tips
are recommended. If not available, make connections, enter the duct
perpendicular to the air stream and finish off flush and smooth on the inside.
FURNACE DRAFT
Connect the terminal tube to the minus pressure gage opening and insert it into
the combustion chamber for over fire draft reading. If a drilled port is not
available insert through fire door but seal the crack. For last pass or smoke pipe
draft, connect into the breeching on the furnace side of any draft control or
damper. To determine draft loss through the furnace, make connection as
indicated for smoke pipe draft and add a second tube, connecting the
manometer differentially to the combustion chamber.
AIR FILTER TEST
To determine the pressure drop across an air filter, connect the manometer
differentially with one tubing from the downstream or blower side of the filter to
the right hand or minus pressure gage connection. Run the second tubing from
the upstream side of the filter to the other gage connection. Use static pressure
tips if available, with the tips directed into the air stream, to eliminate possibility
of error due to air velocity. Read the pressure drop across the filter in inches of
water and follow the filter manufacturer’s recommendations for filter cleaning or
replacement.