1 = Thermocouple J,K,E,L,N
2 = Thermocouple T,R,S,B,C
3=100 and 120 ohm RTDs
4 = 1000 Ohm RTD
5 = Current, 0 or 4 to 20 mA
6 = Voltage, 0 or 2 to 10 V
Input 2
1 = Thermocouple J,K,E,L,N
2 = Thermocouple T,R,S,B,C
3=100 and 120 ohm RTDs
4 = 1000 Ohm RTD
5 = Current, 0 or 4 to 20 mA
6 = Voltage, 0 or 2 to 10 V
Options:
992RS-485 Serial Communications. Allows remote computer to read
and write all control parameters.
950212 - 24 Vdc/Vac 50-400Hz power supply (control operates on low
voltage equipment).
Output B
1 = SSR
2 = Switched Voltage 5 Vdc
3 = Relay
8 = DC SSR
Output A
1 = SSR
2 = Switched Voltage 5 Vdc
3 = Relay
5 = Proportional current
8 = DC SSR
INSTALLATION
All models are designed for mounting in an enclosed panel. Select
the position desired for the instrument on the panel. If more than one
instrument is required, maintain the minimum of spacing requirements as shown on the drawing opposite. Closer spacing will
structurally weaken the panel, and invalidate the IP66, UL type 4
rating of the panel.
It is not necessary to remove the instrument chassis from the housing for installation. If the instrument chassis is removed from the housing, you
must follow the ANSI/IPC-A-610 standard for handling electronic assemblies to avoid damage from
Electro-Static Discharge (ESD). Failure to properly
handle the instrument may cause damage to the
instrument.
June, 2000Page 3 of 40949-1318
Page 4
Prepare the panel by cutting and deburring the required opening(s).
25.4
(1.00)
45 + 0.6
(1.772 + 0.02)
From the front of the panel, slide the housing through the cutout. The
housing gasket should be flat against the housing flange before
installing.
20.5
(0.807)
22.2 + 0.3
(0.874 + 0.012)
Panel
Collar
Gasket
From the rear of the panel slide the mounting collar over the housing.
Hold the housing with one hand and using the other hand, push the
collar evenly against the panel until the spring loops are slightly
compressed. The ratchets will hold the mounting collar and housing
in place. To remove, gently lift the ratchets and slide a piece of
heavy paper or mylar sheet under each ratchet (a business card
works well). Slide the collar off of the housing.
949-1318Page 4 of 40June, 2000
Page 5
WIRING
WARNING: The inputs of the instrument are not isolated
from each other. The input sources must be isolated
from each other. Thermocouples MUST be of the
isolated junction type. Process inputs may not share a
common external ground.
FAILURE TO OBSERVE THIS WARNING MAY CAUSE
DANGEROUS OR LETHAL VOLTAGES TO BE PRESENT
IN THE INSTRUMENT WHICH MAY CAUSE SERIOUS
INJURY OR DEATH.
DO NOT RUN SIGNAL (CLASS 2) WIRING IN THE
SAME CONDUIT OR CHASE AS THE POWER WIRING. ERRATIC OPERATION OR DAMAGE TO THE
INSTRUMENT CIRCUITRY WILL RESULT.
Use only the type of thermocouple or RTD probe for which
the control has been programmed. Maintain separation
between wiring of sensor, auxiliary in or out, and other wiring.
See the "Secure Menu" for input selection.
For thermocouple input always use extension leads of the same type
designated for your thermocouple.
For supply connections use No. 18 AWG wires rated for at least 75°C. Use
copper conductors only. All line voltage output circuits must have a
common disconnect and be connected to the same pole of the disconnect.
Input wiring for thermocouple, voltage, current, and RTD; and output wiring
for current, DC SSR, and 5 VDC is rated CLASS 2.
June, 2000Page 5 of 40949-1318
Page 6
Control wiring is as shown.
The wiring terminals for the 32DZ are compression type. To open
the wiring terminal, turn the screw for that terminal counterclockwise. Slide the wire into the terminal space. While holding the wire
in place, turn the screw clockwise to tighten. Maximum torque is
0.424 N·m(3.75 in. lb.). Do not overtighten. The wire should be held
snugly in place.
Wiring for Optional Inputs and Outputs
Wire power and outputs as shown. Wiring for options is shown below. All wiring
shown below is Class 2. Shielded twisted pair is required for Option 992.
Option 992:Terminal 5 is line A (-).
Terminal 6 is line B (+).
Last control in chain must have 120 ohm ± 1%
resistor across 5 and 6.
Option 9502: Connect 12 to 24 Volt ac or
dc power to terminals 11 and
12. No polarity.
Note: Industry standard designation for
5
RS-485 lines is A and B. Some equipment manufacturers use a non-standard designation of plus and minus. The
association of A to minus and B to plus is based on a sample of devices marked as
plus and minus and is not intended to represent ALL such labelled devices. Final
responsibility for correct identification of leads and terminals rests with the user/
installer and the manufacturer of the other device(s) installed in the system.
949-1318Page 6 of 40June, 2000
11
6
12
Page 7
Wiring for 4 to 20mA Transmitter inputs
WARNING: The inputs of the instrument are not isolated
from each other. The input sources must be isolated
from each other. Process inputs may not share a
common external ground.
FAILURE TO OBSERVE THIS WARNING MAY CAUSE
DANGEROUS OR LETHAL VOLTAGES TO BE PRESENT
IN THE INSTRUMENT WHICH MAY CAUSE SERIOUS
INJURY OR DEATH.
Wire power and outputs as shown above. Two-wire transmitters wire as
shown below.
External Power Supply
24 Vdc
Transmitter
+ -
+ -
Wiring for Z1 Input
External Power Supply
24 Vdc
+ -
Transmitter
+ -
Wiring for Z2 Input
For three or four wire transmitters follow the wiring instructions provided
with your transmitter.
DO NOT WIRE THE 24 VOLT POWER SUPPLY
ACROSS THE INPUT OF THE CONTROL. DAMAGE
TO THE INSTRUMENT INPUT CIRCUITRY WILL RESULT.
June, 2000Page 7 of 40949-1318
Page 8
FRONT PANEL KEY FUNCTIONS
Set Point 1 LampSP1 Process
Z1
Display
Set Point 2 LampScale Lamp °F
SP2 ProcessScale Lamp °C
Z2
Display
SERIES 32DZ
The decimal point flashes when Self-Tune is operating.
Keys are illuminated when pressed. Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next
menu item. May also be used in conjunction with other keys as noted
below.
UP ARROW: Increments a value, changes a menu item, or selects
the item to ON. The maximum value obtainable is 9999 regardless
of decimal point placement.
DOWN ARROW: Decrements a value, changes a menu item, or
selects the item to OFF. The minimum value obtainable is -1999
regardless of decimal point placement.
ENTER: Pressing ENTER stores the value or the item changed. If
not pressed, the previously stored value or item will be retained. The display
will flash once when ENTER is pressed.
UP ARROW & ENTER: Pressing these keys simultaneously brings
up the secondary menu starting at the alarm, tune, or cycle item (depending
on programming). Pressing these keys for 5 seconds will bring up the secure
menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously
will allow backing up one menu item, or if at the first menu item they will cause
the display to return to the primary menu. If an alarm condition has occurred,
these keys may be used to reset the alarm.
INDEX & ENTER: Pressing these keys simultaneously and
holding them for 5 seconds allows recovery from the various error
messages. The following menu items will be reset:
Correct the problems associated with the above conditions before using
these reset keys. More than one error could be present. Caution is advised
since several items are reset at one time.
While in the Primary or Secondary Menu, if no key is pressed for a period
of 30 seconds, the display will return to the HOME position displaying the
949-1318Page 8 of 40June, 2000
Page 9
temperature value. While in the SecureMenu, if no key is pressed for a
period of 60 seconds, the display will return to the HOME position displaying
the temperature value. Outputs are disabled (turned off) when the Secure
Menu is active.
NOTE: To move to the Primary Menu quickly from any other menu, press
the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN
ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security
level. To change security levels change the password value using the
UPARROW and
key. Refer to the password table (following) for the correct value to enter
for the security level desired. The
may be viewed or changed at any time regardless of the present security
level.
DOWN ARROW keys and pressing the
SEC1SEC1
SEC1 or
SEC1SEC1
SEC2SEC2
SEC2 menu items security level
SEC2SEC2
ENTER
To set the access level to, for example,
UP ARROW key until the upper display shows the password,
Press the
value,
The password values shown in the table cannot be altered, so retain a copy
of these pages for future reference. This is the only reference made to
password values in this instruction book.
22
2, in the upper display.
22
MenuStatus
PrimaryLocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureUnlocked
ENTER key. The display will blink, and return with the level
PASSWORD TABLE
Security Level
Displayed Value
22
2, at the
22
When Viewed
1
2
3
4
SEC1SEC1
SEC1 menu item press the
SEC1SEC1
11011101
1101.
11011101
Password Value
To Enter
1110
1101
1011
111
June, 2000Page 9 of 40949-1318
Page 10
NOTATION CONVENTIONS FOR THE MENUS
Because of the number of features available in this control, information
is included that may not apply to your specific control. All usable
features are included in this book, but may not be used in your process.
To increase clarity the following conventions are used:
1. Certain features, Menu Items, and functions shown in this book may
or may not appear on your control, depending on other Menu Item
selections. At various places in the Menus there are notes identifying
Menu Items that "control" or "direct" other menu items. If you are looking
for a particular menu item and can't find it, check the menu item that is
its "control" for proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of
characters to indicate which set point function (SP1 or SP2) is being
affected. It is also used before a group of characters of a menu item to
indicate that there may be more than one selection or value for that menu
item. This is used for certain repeated items such as in the Ramp/Soak
Program section.
3.
Features that apply only to Options will be printed in Italics.
THE HOME DISPLAY
The home display is the normal display while the control is operating.
If no errors or functions are active, the HOME display will indicate the
Process Variable (the temperature, pressure, flow, RH, etc., that is
being measured) for Set Point 1 on the top display and the Process
Variable for Set Point 2 on the bottom.
THE MENU EDIT FUNCTION
The Menu Edit function (Edit) allows quick access to operational and
set up menu items for either or both of the zones. The Edit menu item
appears at the top of the Secondary Menu and allows selection of the
set point parameters. Setting Edit to 0 allows access to only the Peak
(PEA1 and PEA2), Valley (UAL1 and UAL2), Local/Remote (LOre), and
address (Addr) menu items.
Setting Edit for either 1 or 2 allows access to the Secondary and Secure
Menus for the zone selected.
Setting Edit for 3 allows access to both the Secondary and Secure
Menus for both Zone 1 and Zone 2. Each menu presents the menu items
for Zone 1 first, followed by the menu items for Zone 2, followed by any
common menu items that may be present.
949-1318Page 10 of 40June, 2000
Page 11
Menu items that are dedicated to either Zone 1 or Zone 2 will have either
a 1 or 2 in them for identification.
If Edit is set to any value other than 0, the setting will be retained for
a period of five minutes to allow handy, repeated access to that zone's
menues. After five minutes of keypad inactivity, the Edit setting will
revert to 0, giving an added layer of security to prevent inadvertant
changes to the instrument.
PROGRAMMING SET POINTS FOR ALARM FUNCTIONS
Caution: In any critical application where failure could
cause expensive product loss or endanger personal
safety, a redundant limit controller is required.
The 32DZ Series allows Zone 1 and / or Zone 2 to operate as limit or alarm
type outputs. This function is available on both outputs. To enable a zone
output to act as an alarm or limit,
be set for
OnOfOnOf
OnOf.
OnOfOnOf
Out1Out1
Out1 (for Zone 1) or
Out1Out1
Out2Out2
Out2 (for Zone2) should
Out2Out2
Out1Out1
When
Out1 and / or
Out1Out1
will appear in the Secure Menu for the selected zone(s).
When Set Point Power Interrupt (
SS
Reset (
after a power failure and on subsequent power restoration if no alarm
condition is present.
If Set Point Inhibit (
upon power up until the process value passes through the alarm set point
once. Alarm inhibit can be restored as if a power up took place by pressing
both the
June, 2000Page 11 of 40949-1318
rErE
S#
rE) is programmed for
SS
rErE
Out2Out2
Out2 are set to
Out2Out2
SS
iHiH
S#
iH) is selected
SS
iHiH
INDEX and
Warning: If inhibit is on and a power failure occurs
during a high alarm, on restoration of power inhibit will
suppress the alarm. Do not use the Set Point Inhibit
feature if a hazard may be created by this action. Be sure
to test all combinations of high and low set point inhibit
actions before placing control into operation.
OnOFOnOF
OnOF, then the alarm function menu items
OnOFOnOF
SS
PiPi
S#
Pi) is programmed
SS
PiPi
HoldHold
Hold, the alarm will automatically reset
HoldHold
ONON
ON, an alarm condition is suspended
ONON
ENTER keys for 5 seconds.
ONON
ON and Set Point
ONON
Page 12
Set Point 2 Tracking
Some applications will call for Set Point 2 to follow or 'track' the setting for
Set Point 1. This can be done by changing the S2t setting in the Secure Menu
(edit set for 2 or 3). For a tracking SP2, set S2t to dE.
The Factory Default setting for S2t is ABS, making SP2 completely
independent of SP1.
When setting
dEdE
=
dE), set the difference in value from the Set Point 1 (
dEdE
example if Set Point 2 is required to be 5 degrees below the
SP2SP2
SP2 to
-5. If Set Point 2 is required 20 degrees above the
SP2SP2
2020
to
20. If
2020
relationship as originally set.
When setting SP2 value when Set Point 2 is programmed as absolute (S2t
= AbS), simply set the value at which the alarm is to occur.
Self Tune® allows automatic selection of the necessary parameters to
achieve best control operation from your 32DZ Series control. If you are
using the control output as a simple on-off function (e.g.
none of the following will apply.
Theory of Operation
The Self Tune function calculates the
PID1 tunEPID1 tunE
the
PID1 tunE selection,
PID1 tunEPID1 tunE
selection, the
as shown in the Secondary Menu . These values are determined by measuring
the response of the process connected to the control. When Self Tune is
started, the control temporarily acts as an on-off control. While in this mode
the control measures the overshoot and undershoot of the process, and the
period of the process (the time from peak value to the next peak value). These
measurements are collected over a period that lasts three periods of overshoot
and undershoot. The data collected over this time is then compared and
calculated into final PID and Fuzzy Logic values. The effect of Fuzzy Logic
on the process is still controlled by the
Fi 1Fi 1
If
Fi 1 or Fi 2 is
Fi 1Fi 1
have no effect.
SP2SP2
SP2 value when Set Point 2 is programmed as deviation (
SP2SP2
-5-5
-5-5
SP1SP1
SP1 is changed, the
SP1SP1
OPERATION OF SELF TUNE® FUNCTION
Pb2Pb2
Pb2,
Pb2Pb2
Fbd1Fbd1
Fbd1 and
Fbd1Fbd1
Frt1Frt1
Frt1 parameters, and the
Frt1Frt1
00
Fbd1Fbd1
0, the
Fbd1,
00
Fbd1Fbd1
SP2SP2
SP2 setting will continue to hold the same
SP2SP2
Pb1Pb1
rES2rES2
rES2, and
rES2rES2
Frt1Frt1
Fbd2Fbd2
Frt1,
Fbd2, and
Frt1Frt1
Fbd2Fbd2
rES1rES1
Pb1,
rES1, and
Pb1Pb1
rES1rES1
rtE2rtE2
rtE2 parameters under the
rtE2rtE2
Fi 1Fi 1
Fi 1 and Fi 2 (fuzzy intensity) settings.
Fi 1Fi 1
rtE1rtE1
rtE1 parameters under
rtE1rtE1
Fbd2Fbd2
Fbd2 and
Fbd2Fbd2
Frt2Frt2
Frt2 will be calculated, but will
Frt2Frt2
SP1SP1
SP1) desired. For
SP1SP1
SP1SP1
SP1, then set
SP1SP1
SP1SP1
SP1, then set
SP1SP1
Out1Out1
Out1 set for
Out1Out1
Frt2Frt2
Frt2 parameters,
Frt2Frt2
S2tS2t
S2t
S2tS2t
SP2SP2
SP2
SP2SP2
OnOFOnOF
OnOF),
OnOFOnOF
PID2 tunEPID2 tunE
PID2 tunE
PID2 tunEPID2 tunE
The calculations for Zone 1 and Zone 2 are completely independent. Each zone
has separate Self Tune and Fuzzy Logic parameters.
949-1318Page 12 of 40June, 2000
Page 13
The calculations for the PID values are the same as used in the standard Ziegler
- Nichols equations that have been recognized as standard for decades.
The only modification to the application of the Ziegler - Nichols equations is
controlled by the
amount of rate (derivative) that is applied. A
default) or less allows for less damping. A
for critical damping as set forth in Ziegler - Nichols. A
55
of
5 or more allows over damping of the process.
55
Program Setup and Operation
dFC1dFC1
dFC1 and
dFC1dFC1
dfC2dfC2
dfC2 menu items. These menu items control the
dfC2dfC2
dFC1dFC1
dFC1 or
dFC1dFC1
dFC1dFC1
dFC1 or
dFC1dFC1
dfC2dfC2
dfC2 setting of
dfC2dfC2
dfC2dfC2
dfC2 setting of
dfC2dfC2
dFC1dFC1
dFC1 or
dFC1dFC1
dfC2dfC2
dfC2 setting
dfC2dfC2
33
3 (factory
33
44
4 allows
44
In the secondary menu set
to make sure that
Lrn1Lrn1
Lrn1 /
Lrn1Lrn1
While the Self Tune function is active, the right hand decimal point on the
lower display will blink. When Self Tune is complete, the blinking will stop.
After Self Tune is complete, the
switch(es) to
values calculated. We recommend that you do not change the calculated
values unless you have a firm understanding of the parameters involved and
their function. For more information on PID tuning, please contact your
supplier.
Option 992, Serial Communication.
The serial communications option allows the control to be written to and read
from a remote computer or other similar digital device. Communication is
allowed through a RS-485 (Option 992) port.
See Wiring for Optional Inputs and Outputs for information on wiring the
communication lines. Wiring for the RS-485 is run from control to control in
a daisy chain fashion with a termination resistor (120 ohms) across the
transmit and receive terminals of the last control in the chain.
lrn2lrn2
lrn2 and set to
lrn2lrn2
OPERATION AND PROGRAMMING OF OPTIONS
dFC1dFC1
dFC1 /
dFC1dFC1
PIDPID
PID. This allows examination and / or modification of the
PIDPID
tun1tun1
tun1 or
tun1tun1
dfC2dfC2
dfC2 is (are) set to the desired value. Back up to
dfC2dfC2
YESYES
YES. The control will begin the Self Tune function.
YESYES
tun2tun2
tun2 to
tun2tun2
tun1tun1
tun1 /
tun1tun1
SELFSELF
SELF. Skip
SELFSELF
tun2tun2
tun2 setting(s) automatically
tun2tun2
Lrn1Lrn1
Lrn2Lrn2
Lrn1 /
Lrn2 and check
Lrn1Lrn1
Lrn2Lrn2
Select the control address and communication baud rate with the
bAUdbAUd
bAUd menu items in the Secure Menu. The address for Zone 1 will be the
bAUdbAUd
address selected. The address for Zone 2 will be the address selected for Zone
1 plus one. For example, if
addressed through address 1E and Zone 2 parameters will be addressed
through address 1F.
June, 2000Page 13 of 40949-1318
AddrAddr
Addr is set to 1E, Zone 1 parameters will be
AddrAddr
AddrAddr
Addr and
AddrAddr
Page 14
THE BAUD RATE AND ADDRESS MENU ITEMS WILL TAKE EFFECT ON THE
NEXT POWER UP OF THE CONTROL. BE SURE TO POWER CYCLE THE
CONTROL BEFORE USING THE NEW BAUD RATE AND ADDRESS
In operation, you have the option of preventing a write command from the host
computer. To prevent the host from writing to the control change the
item in the Secondary Menu to
the control set
state, but it is not automatic.)
If your system depends on constant reading or writing to and from the host, you
may wish to set the No Activity Timer (
control. When the
Off, the control will expect to be addressed on a regular basis. If the control
is not addressed in the time set by the value of
the error message
If for any reason you wish to restore the factory settings use the following
procedure.
1. Turn off power to control
2. Turn on power to control
3. While control is performing
and
4. The control will display the ROM ID code. Press
5. The control will display
settings, Press
time. The control will be reset to the original factory settings.
6. Press
option, press the UP ARROW to display the option number. If the
number is flashing, press
flash.
7. Press
8. Press
The control will re-initialize with Factory Default settings.
LOrELOrE
LOrE to
LOrELOrE
ENTER keys.
YESYES
YESChanges are accepted and control re-boots.
YESYES
nono
noChanges are discarded and control re-boots.
nono
rErE
rE. (The host does have the ability to change the
rErE
LOrELOrE
LOrE is set to
LOrELOrE
CHEC LOrECHEC LOrE
CHEC LOrE. To clear the message set
CHEC LOrECHEC LOrE
FACTORY DEFAULT PROCEDURE
INDEX to display
INDEX to display
ENTER.
LOCLOC
LOC. To allow the host to write commands to
LOCLOC
nAtnAt
nAt) to monitor the addressing of the
nAtnAt
rErE
rE and the
rErE
SELFSELF
SELF
SELFSELF
FACtFACt
dFLtdFLt
FACt
dFLt. If you wish to just restore factory
FACtFACt
dFLtdFLt
ENTER and
OPtOPt
OPt. If your control is equipped with an
OPtOPt
ACPtACPt
ACPt. Select
ACPtACPt
nAtnAt
nAt is set to any value other than
nAtnAt
nAtnAt
nAt, then the control will display
nAtnAt
LOrELOrE
LOrE to
LOrELOrE
tESttESt
tESt, press and hold the
tESttESt
INDEX.
DOWN ARROW at the same
ENTER. An enabled option does not
YESYES
YES or
YESYES
nono
no.
nono
.
LOrELOrE
LOrE menu
LOrELOrE
LOrELOrE
LOrE
LOrELOrE
LOCLOC
LOC.
LOCLOC
INDEX
949-1318Page 14 of 40June, 2000
Page 15
MENU SELECTIONS
PRIMARY MENU
Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value.
SP1SP1
SP1Set Point 1 Adjust, Control Point 1.
SP1SP1
SP2SP2
SP2Set Point 2 Adjust, Control Point 2.
SP2SP2
SECONDARY MENU
Hold UP ARROW & ENTER. Press INDEX to advance to the next
menu item. Press UP ARROW or DOWN ARROW to change the
value in the display. Press ENTER to retain the value.
EditEdit
EditEdit Set Point parameters: Select 0, 1, 2, or 3.
EditEdit
00
0Edit function is off.
00
11
1Edit Secondary and Secure Menus for Set Point 1.
11
22
2Edit Secondary and Secure Menus for Set Point 2.
22
33
3Edit Secondary and Secure Menus for both Set
33
Points in sequence (menu items for Set Point 1
followed by menu items for Set Point 2).
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
PEA1PEA1
PEA1The Peak feature stores the highest input the control has
PEA1PEA1
measured for Zone 1 since the last reset or Power On. At
Power On, PEA1 is reset to the present input value. To
manually reset the value
Press the ENTER key to reset.
display the present input value.
UAL1UAL1
UAL1The Valley feature stores the lowest input the Instrument
UAL1UAL1
has measured for Zone 1 since the last reset or Power On.
At Power On,
reset the value
the ENTER key.
input value.
PEA2PEA2
PEA2The Peak feature stores the highest input the control has
PEA2PEA2
measured for Zone 2 since the last reset or Power On. At
June, 2000Page 15 of 40949-1318
00
0, begin.
00
11
33
1 or
3, jump to
11
33
22
2, jump to
22
UAL1UAL1
UAL1 is reset to the present input. To manually
UAL1UAL1
UAL1UAL1
UAL1 must be in the lower display. Press
UAL1UAL1
UAL1UAL1
UAL1 will be reset and display the present
UAL1UAL1
Out1Out1
Out1 on page 17.
Out1Out1
Out2Out2
Out2 on page 21.
Out2Out2
PEA1PEA1
PEA1 must be in the lower display.
PEA1PEA1
PEA1PEA1
PEA1 will be reset and
PEA1PEA1
Page 16
Power On, PEA2 is reset to the present input. To manually
reset the value
the ENTER key to reset.
present input value.
UAL2UAL2
UAL2The Valley feature stores the lowest input the Instrument
UAL2UAL2
has measured for Zone 2 since the last reset or Power On.
At Power On,
reset the value
the ENTER key.
input value.
LOrELOrE
LOrE
LOrELOrE
(Option 992, Serial Communications) Local / Remote Status: Select
LOCLOC
LOC
LOCLOC
The host computer is advised not to send remote
PEA2PEA2
PEA2 must be in the lower display. Press
PEA2PEA2
PEA2PEA2
PEA2 will be reset and display the
PEA2PEA2
UAL2UAL2
UAL2 is reset to the present input. To manually
UAL2UAL2
UAL2UAL2
UAL2 must be in the lower display. Press
UAL2UAL2
UAL2UAL2
UAL2 will be reset and display the present
UAL2UAL2
LOCLOC
LOC
LOCLOC
or
rErE
rE
rErE
.
commands. Any write commands sent to the
controls will be rejected.
rErE
rE
rErE
The host computer is allowed to send write
commands.If the control is not addressed within
the time set in the
Secure Menu) the
nAtnAt
nAt
(No Activity Timer, see
nAtnAt
CHEC LorECHEC LorE
CHEC LorE
CHEC LorECHEC LorE
error message will be
displayed.
AddrAddr
Addr
AddrAddr
(Option 992, Serial Communications) Control Address: Set
from 1 to
3FF
. This number (hexadecimal, base 16) must
match the address number used by the host computer.
Viewed only in this menu. The value displayed is for Zone
1. The address for Zone 2 is the value for Zone 1 plus one.
To change this parameter, see
AddrAddr
Addr
in the Secure Menu.
AddrAddr
End of Secondary Menu when
949-1318Page 16 of 40June, 2000
EditEdit
Edit is set to
EditEdit
00
0.
00
Page 17
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
11
33
1 or
3, begin.
11
33
22
2, jump to
22
Out2Out2
Out2 on page 20.
Out2Out2
Out1Out1
Out1Output selection: Select
Out1Out1
ONOFONOF
ONOFA setting of
ONOFONOF
a simple on/off mode. This setting forces the
control to turn off at set point, and on at the set
point plus the differential (
Out1Out1
the
Out1/
Out1Out1
and the
selections in the Secondary menu and the
S1OHS1OH
and
S1OH selections in the Secure menu are sup-
S1OHS1OH
pressed.
SP1dSP1d
SP1dSet Point On-Off Differential (hysteresis).
SP1dSP1d
ONOFONOF
ONOF allows the control to operate as
ONOFONOF
OnOFOnOF
OnOF menu item is followed by ####/
OnOFOnOF
tun1tun1
tun1,
tun1tun1
Select
-9999-9999
-9999 (reverse acting). This value will be
-9999-9999
negative for reverse acting set points, and
positive for direct acting outputs. Set the
value for the amount of difference between
the turn off point (set point) and the turn on
point. The following drawing shows output
behavior for reverse and direct action.
OnOfOnOf
1tP1tP
OnOf,
1tP, or
OnOfOnOf
1tP1tP
Pb1Pb1
rES1rES1
Pb1,
rES1,
Pb1Pb1
rES1rES1
11
99999999
1 to
9999 (direct acting), or
11
99999999
1PuL1PuL
1PuL.
1PuL1PuL
SP1dSP1d
SP1d). When selected,
SP1dSP1d
OFS1OFS1
OFS1,
OFS1OFS1
rtE1rtE1
rtE1, and
rtE1rtE1
SP1dSP1d
SP1d,
SP1dSP1d
ArS1ArS1
ArS1
ArS1ArS1
S1OLS1OL
S1OL
S1OLS1OL
-1-1
-1 to
-1-1
tPtP
##
tPTime Proportioning Cycle Time. Select
tPtP
80tP80tP
80tP.
80tP80tP
1tP1tP
1tPA setting of
1tP1tP
state outputs (SSR, DC SSR, or 5VDC).
2tP2tP
2tP to
2tP2tP
#
June, 2000Page 17 of 40949-1318
80tP80tP
80tPTime Proportioning Control is ad-
80tP80tP
justable in 1 second steps. Recommended
for mechanical outputs (relays, solenoids,
etc.). For best contact life, a time should
be selected as long as possible without
causing the process to wander.
PuLPuL
PuLPulsed Time Proportioning Output: Select
PuLPuL
1PuL1PuL
1PuL to
1PuL1PuL
most nonlinear. Changes output linearity
for use in cooling applications or for an
extremely fast response processes. At the
center of the proportional band, a pulse
1tP1tP
1tP is recommended for solid
1tP1tP
7PuL7PuL
7PuL.
7PuL7PuL
1PuL1PuL
1PuL = Linear and
1PuL1PuL
1tP1tP
1tP to
1tP1tP
7PuL7PuL
7PuL =
7PuL7PuL
Page 18
value of 1 provides an output of one second on and one second off (50% output). A
pulse value of 2 provides an output of one
second on and two seconds off (33% output). Output at center of band equals one
second on, 2
ProPProP
ProPFor Current (Code 5) outputs only.
ProPProP
(pulse value-1)
seconds off.
tun1tun1
tun1Tuning Choice: Select
tun1tun1
SELFSELF
SELFThe instrument will evaluate the Process and
SELFSELF
select the PID values to maintain good control.
Active for SP1 only.
Lrn1Lrn1
Lrn1Select
Lrn1Lrn1
YESYES
YESStart Learning the Process. After
YESYES
nono
noLearning will stay in present mode.
nono
dFC1dFC1
dFC1Damping factor, Select
dFC1dFC1
the ratio of Rate to Reset for the SELF tunE
mode.
a fast response process the value should
be lowered (less Rate). For a slower process the value should be increased (more
Rate).
PidPid
PidManually adjust the PID values. PID control con-
PidPid
sists of three basic parameters, Proportional Band
(Gain), Reset Time (Integral), and Rate Time
(Derivative).
Pb1Pb1
Pb1Proportional Band (Bandwidth). Select
Pb1Pb1
99999999
9999 °F, °C, or counts.
99999999
rES1rES1
rES1Automatic Reset Time. Select
rES1rES1
99.999.9
99.9 minutes. Select
99.999.9
OFS1OFS1
OFS1 Manual Offset Correction Select
OFS1OFS1
99.999.9
99.9%. Select
99.999.9
rtE1rtE1
rtE1Rate Time. Select
rtE1rtE1
utes, Derivative.
SLOSLO
SLOPID values are preset for a slow response pro-
SLOSLO
cess.
nornor
norPID values are preset for a normal response
nornor
process.
FAStFASt
FAStPID values are preset for a fast response process.
FAStFASt
SELFSELF
SELF,
SELFSELF
YESYES
YES or
YESYES
PidPid
Pid,
PidPid
nono
no
nono
SLOSLO
SLO,
SLOSLO
nornor
nor, or
nornor
FAStFASt
FASt.
FAStFASt
the process has been learned the
menu item will revert to no.
OFFOFF
11
OFF,
OFFOFF
77
7 = most Rate. Factory set to
77
OFFOFF
OFF to switch to
OFFOFF
OFFOFF
OFF to switch to
OFFOFF
OFFOFF
0.010.01
OFF,
0.01 to
OFFOFF
0.010.01
77
1 to
7. Sets
11
77
33
3. For
33
OFFOFF
0.10.1
OFF,
0.1 to
OFFOFF
0.10.1
OFS1OFS1
OFS1.
OFS1OFS1
OFFOFF
0.10.1
OFF,
0.1 to
OFFOFF
0.10.1
rES1rES1
rES1.
rES1rES1
99.9999.99
99.99 min-
99.9999.99
11
1 to
11
ArS1ArS1
ArS1Anti- Reset Windup Feature: Select
ArS1ArS1
OnOn
OnReset Offset value will be cleared to 0% when the
OnOn
OnOn
On or
OnOn
OFFOFF
OFF.
OFFOFF
process input is not within the Proportional Band.
949-1318Page 18 of 40June, 2000
Page 19
OFFOFF
OFFReset Offset Value is retained in memory when the
OFFOFF
process input is not within the Proportional Band.
Art1Art1
Art1Approach Rate Time: Select
Art1Art1
function defines the amount of Rate applied when the input
is outside of the Proportional Band. The Art1 time and thertE1 time are independent and have no effect on each other.
To increase damping effect and reduce overshoot set the
approach rate time for a value greater than the natural rise
time of the process (natural rise time = process value time
to set point).
Fi 1Fi 1
Fi 1Fuzzy Logic Intensity: Select
Fi 1Fi 1
(disables Fuzzy Logic). The function defines the amount of
impact Fuzzy Logic will have on the output. If
00
Fbd1Fbd1
to
0,
Fbd1 and
00
Fbd1Fbd1
Fbd1Fbd1
Fbd1Fuzzy Logic Error Band: Select
Fbd1Fbd1
Sets the bandwidth of the Fuzzy Logic. Set
PID proportional band (
when used, calculates this value. Will not appear if
00
is
0.
00
Frt1Frt1
Frt1Fuzzy Logic Rate of Change: Select
Frt1Frt1
second. For best initial setting, find the count/second
change of process value near Set Point 1 with output ON
(100% output). Multiply this value by 3. Set
calculated value. Self Tune, when used, calculates this
value. Will not appear if
Frt1Frt1
Frt1 below will not appear.
Frt1Frt1
OFFOFF
0.010.01
OFF,
0.01 to
OFFOFF
0.010.01
00
0 to
00
00
0 to
00
Pb1Pb1
Pb1) for best results. Self Tune,
Pb1Pb1
Fi 1Fi 1
Fi 1 is
Fi 1Fi 1
00
0.
00
99.9999.99
99.99 minutes. The
99.9999.99
100100
100%. 0% is OFF
100100
Fi 1Fi 1
Fi 1 is set
Fi 1Fi 1
40004000
4000 °F, °C, or counts.
40004000
Fbd1Fbd1
Fbd1 equal to
Fbd1Fbd1
Fi 1Fi 1
Fi 1
Fi 1Fi 1
0.000.00
0.00 to
0.000.00
99.9999.99
99.99 counts/
99.9999.99
Frt1Frt1
Frt1 to this
Frt1Frt1
PEA1PEA1
PEA1The Peak feature stores the highest input the control has
PEA1PEA1
measured for Zone 1 since the last reset or Power On. At
Power On, PEA1 is reset to the present input value. To
manually reset the value
Press the ENTER key to reset.
display the present input value.
UAL1UAL1
UAL1The Valley feature stores the lowest input the Instrument
UAL1UAL1
has measured for Zone 1 since the last reset or Power On.
At Power On,
reset the value
the ENTER key.
input value.
June, 2000Page 19 of 40949-1318
UAL1UAL1
UAL1 is reset to the present input. To manually
UAL1UAL1
UAL1UAL1
UAL1 must be in the lower display. Press
UAL1UAL1
UAL1UAL1
UAL1 will be reset and display the present
UAL1UAL1
PEA1PEA1
PEA1 must be in the lower display.
PEA1PEA1
PEA1PEA1
PEA1 will be reset and
PEA1PEA1
Page 20
InC1InC1
InC1Input Correction: Select
InC1InC1
feature allows the input value to be changed to agree with
an external reference or to compensate for sensor error.
Note:InC1 is reset to zero when the input type is changed,
or when decimal position is changed.
-500-500
-500 to
-500-500
500500
500 °F, °C, or counts. This
500500
FiL1FiL1
FiL1Digital Filter: Select
FiL1FiL1
constant of the sensor, or noise could cause the display to
jump enough to be unreadable. A setting of 2 is usually
sufficient to provide enough filtering for most cases, (2
represents approximately a 1 second time constant). When
the 0.1 degree resolution is selected this should be increased to 4. If this value is set too high, controllability will
suffer.
LPb1LPb1
LPb1Loop Break Protection: Select
LPb1LPb1
during operation, the output is minimum (0%) or maximum
(100%), and the input moves less than 5°F (3°C) or 5 counts
over the time set for LPb1, the
appear. The loop break error can be reset by pressing the
ENTER key when at the LPb1 menu item. The INDEX &
ENTER keys may also be used.
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
11
1, jump to
11
33
3, continue.
33
OFFOFF
11
OFF,
1 to
OFFOFF
11
LorELorE
LorE on page 24.
LorELorE
9999
99. In some cases the time
9999
OFFOFF
11
OFF,
OFFOFF
LOOP bAdLOOP bAd
LOOP bAd message will
LOOP bAdLOOP bAd
99999999
1 to
9999 seconds. If,
11
99999999
949-1318Page 20 of 40June, 2000
Page 21
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
11
1, jump to
11
33
3, continue.
33
22
2, begin.
22
LorELorE
LorE on page 24.
LorELorE
Out2Out2
Out2Output selection: Select
Out2Out2
ONOFONOF
ONOFA setting of
ONOFONOF
a simple on/off mode. This setting forces the
control to turn off at set point, and on at the set
point plus the differential (
Out2Out2
the
Out2/
Out2Out2
and the
selections in the Secondary menu and the
S2OHS2OH
and
S2OH selections in the Secure menu are sup-
S2OHS2OH
pressed.
SP2dSP2d
SP2dSet Point On-Off Differential (hysteresis).
SP2dSP2d
ONOFONOF
ONOF allows the control to operate as
ONOFONOF
OnOFOnOF
OnOF menu item is followed by ####/
OnOFOnOF
tun2tun2
tun2,
tun2tun2
Select
-9999-9999
-9999 (reverse acting). This value will be
-9999-9999
negative for reverse acting set points, and
positive for direct acting outputs. Set the
value for the amount of difference between
the turn off point (set point) and the turn on
point. The following drawing shows output
behavior for reverse and direct action.
OnOfOnOf
1tP1tP
OnOf,
1tP, or
OnOfOnOf
1tP1tP
Pb2Pb2
rES2rES2
Pb2,
rES2,
Pb2Pb2
rES2rES2
11
99999999
1 to
9999 (direct acting), or
11
99999999
1PuL1PuL
1PuL.
1PuL1PuL
SP2dSP2d
SP2d). When selected,
SP2dSP2d
OFS2OFS2
OFS2,
OFS2OFS2
rtE2rtE2
rtE2, and
rtE2rtE2
SP2dSP2d
SP2d,
SP2dSP2d
Ars2Ars2
Ars2
Ars2Ars2
S2OLS2OL
S2OL
S2OLS2OL
-1-1
-1 to
-1-1
tPtP
##
tPTime Proportioning Cycle Time. Select
tPtP
80tP80tP
80tP.
80tP80tP
1tP1tP
1tPA setting of
1tP1tP
state outputs (SSR, DC SSR, or 15VDC).
2tP2tP
2tP to
2tP2tP
#
June, 2000Page 21 of 40949-1318
80tP80tP
80tPTime Proportioning Control is ad-
80tP80tP
justable in 1 second steps. Recommended
for mechanical outputs (relays, solenoids,
etc.). For best contact life, a time should
be selected as long as possible without
causing the process to wander.
PuLPuL
PuLPulsed Time Proportioning Output: Select
PuLPuL
1PuL1PuL
1PuL to
1PuL1PuL
most nonlinear. Changes output linearity
for use in cooling applications or for an
extremely fast response processes. At the
1tP1tP
1tP is recommended for solid
1tP1tP
7PuL7PuL
7PuL.
7PuL7PuL
1PuL1PuL
1PuL = Linear and
1PuL1PuL
1tP1tP
1tP to
1tP1tP
7PuL7PuL
7PuL =
7PuL7PuL
Page 22
center of the proportional band, a pulse
value of 1 provides an output of one second on and one second off (50% output). A
pulse value of 2 provides an output of one
second on and two seconds off (33% output). Output at center of band equals one
second on, 2
(pulse value-1)
seconds off.
ProP For Current (Code 5) outputs only.
tun2tun2
tun2Tuning Choice: Select
tun2tun2
SELFSELF
SELFThe Controller will evaluate the Process and se-
SELFSELF
SELFSELF
SELF,
SELFSELF
PidPid
Pid,
PidPid
SLOSLO
SLO,
SLOSLO
nornor
nor, or
nornor
FAStFASt
FASt.
FAStFASt
lect the PID values to maintain good control.
Lrn2Lrn2
Lrn2Select
Lrn2Lrn2
YESYES
YESStart Learning the Process. After
YESYES
YESYES
YES or
YESYES
nono
no
nono
the process has been learned the
11
1 to
11
nono
no.
nono
77
7. Sets
77
menu item will revert to
nono
noLearning will stay in present mode.
nono
dFC2dFC2
dFC2Damping factor, Select
dFC2dFC2
OFFOFF
OFF,
OFFOFF
the ratio of Rate to Reset for the SELF tunE
mode.
77
7 = most Rate. Factory set to
77
33
3. For
33
a fast response process the value should
be lowered (less Rate). For a slower process the value should be increased (more
Rate).
PidPid
PidManually adjust the PID values. PID control con-
PidPid
sists of three basic parameters, Proportional Band
(Gain), Reset Time (Integral), and Rate Time
(Derivative).
Pb2Pb2
Pb2Proportional Band (Bandwidth). Select
Pb2Pb2
99999999
9999 °F, °C, or counts.
99999999
rES2rES2
rES2Automatic Reset Time. Select
rES2rES2
99.999.9
99.9 minutes. Select
99.999.9
OFS2OFS2
OFS2 Manual Offset Correction Select
OFS2OFS2
99.999.9
99.9%. Select
99.999.9
rtE2rtE2
rtE2Rate Time. Select
rtE2rtE2
OFFOFF
OFF to switch to
OFFOFF
OFFOFF
OFF to switch to
OFFOFF
OFFOFF
0.010.01
OFF,
0.01 to
OFFOFF
0.010.01
OFFOFF
OFF,
OFFOFF
OFFOFF
OFF,
OFFOFF
rES2rES2
rES2.
rES2rES2
99.9999.99
99.99 min-
99.9999.99
11
1 to
11
0.10.1
0.1 to
0.10.1
OFS2OFS2
OFS2.
OFS2OFS2
0.10.1
0.1 to
0.10.1
utes, Derivative.
SLOSLO
SLOPID values are preset for a slow response pro-
SLOSLO
cess.
nornor
norPID values are preset for a normal response
nornor
process.
FAStFASt
FAStPID values are preset for a fast response process.
FAStFASt
ArS2ArS2
ArS2Anti- Reset Windup Feature: Select
ArS2ArS2
OnOn
OnReset Offset value will be cleared to 0% when the
OnOn
OnOn
On or
OnOn
OFFOFF
OFF.
OFFOFF
process input is not within the Proportional Band.
949-1318Page 22 of 40June, 2000
Page 23
OFFOFF
OFFReset Offset Value is retained in memory when the
OFFOFF
process input is not within the Proportional Band.
Art2Art2
Art2Approach Rate Time: Select
Art2Art2
function defines the amount of Rate applied when the input
is outside of the Proportional Band. The Art2 time and thertE2 time are independent and have no effect on each other.
To increase damping effect and reduce overshoot set the
approach rate time for a value greater than the natural rise
time of the process (natural rise time = process value time
to set point).
Fi 2Fi 2
Fi 2Fuzzy Logic Intensity: Select
Fi 2Fi 2
(disables Fuzzy Logic). The function defines the amount of
impact Fuzzy Logic will have on the output. If
00
Fbd2Fbd2
to
0,
Fbd2 and
00
Fbd2Fbd2
Fbd2Fbd2
Fbd2Fuzzy Logic Error Band: Select
Fbd2Fbd2
Sets the bandwidth of the Fuzzy Logic. Set
PID proportional band (
when used, calculates this value automatically. Will not
appear if
Frt2Frt2
Frt2Fuzzy Logic Rate of Change: Select
Frt2Frt2
second. For best initial setting, find the count/second
change of process value near set point 1 with output ON
(Output is100%). Multiply this value by 3. Set
calculated value. Self Tune, when used, calculates this
value automatically. Will not appear if
Frt2Frt2
Frt2 below will not appear.
Frt2Frt2
Fi 2Fi 2
Fi 2 is set to
Fi 2Fi 2
OFFOFF
0.010.01
OFF,
0.01 to
OFFOFF
0.010.01
00
0 to
00
00
0 to
00
Pb2Pb2
Pb2) for best results. Self Tune,
Pb2Pb2
00
0.
00
99.9999.99
99.99 minutes. The
99.9999.99
100100
100%. 0% is OFF
100100
Fi 2Fi 2
Fi 2 is set
Fi 2Fi 2
40004000
4000 °F, °C, or counts.
40004000
Fbd2Fbd2
Fbd2 equal to
Fbd2Fbd2
0.000.00
0.00 to
0.000.00
99.9999.99
99.99 counts/
99.9999.99
Frt2Frt2
Frt2 to this
Frt2Frt2
Fi 2Fi 2
Fi 2 is set to
Fi 2Fi 2
00
0.
00
PEA2PEA2
PEA2The Peak feature stores the highest input the control has
PEA2PEA2
measured for Zone 2 since the last reset or Power On. At
Power On, PEA2 is reset to the present input. To manually
reset the value
the ENTER key to reset.
present input value.
UAL2UAL2
UAL2The Valley feature stores the lowest input the Instrument
UAL2UAL2
has measured for Zone 2 since the last reset or Power On.
At Power On,
reset the value
the ENTER key.
input value.
June, 2000Page 23 of 40949-1318
PEA2PEA2
PEA2 must be in the lower display. Press
PEA2PEA2
PEA2PEA2
PEA2 will be reset and display the
PEA2PEA2
UAL2UAL2
UAL2 is reset to the present input. To manually
UAL2UAL2
UAL2UAL2
UAL2 must be in the lower display. Press
UAL2UAL2
UAL2UAL2
UAL2 will be reset and display the present
UAL2UAL2
Page 24
InC2InC2
InC2Input Correction: Select
InC2InC2
feature allows the input value to be changed to agree with
an external reference or to compensate for sensor error.
Note:InC2 is reset to zero when the input type is changed,
or when decimal position is changed.
-500-500
-500 to 500 °F, °C, or counts. This
-500-500
Fil2Fil2
Fil2Digital Filter: Select
Fil2Fil2
constant of the sensor, or noise could cause the display to
jump enough to be unreadable. A setting of 2 is usually
sufficient to provide enough filtering for most cases, (2
represents approximately a 1 second time constant). When
the 0.1 degree resolution is selected this should be increased to 4. If this value is set too high, controllability will
suffer.
LPb2LPb2
LPb2Loop Break Protection: Select
LPb2LPb2
during operation, the output is minimum (0%) or maximum
(100%), and the input moves less than 5°F (3°C) or 5 counts
over the time set for Lpb2, the
appear. The loop break error can be reset by pressing the
ENTER key when at the LPb2 menu item. The INDEX &
ENTER keys may also be used.
The following Menu Items operate on the entire instrument.
There is no Zone or Set Point distinction. They will appear in
the
LOrELOrE
LOrE
LOrELOrE
Edit1Edit1
Edit1,
Edit1Edit1
Edit2Edit2
Edit2, and
Edit2Edit2
(Option 992, Serial Communications) Local / Remote Status: Select
LOCLOC
LOC
LOCLOC
LOCLOC
LOC
LOCLOC
The host computer is advised not to send remote
OFFOFF
11
OFF,
1 to
OFFOFF
11
Edit3 Edit3
Edit3 menus.
Edit3 Edit3
rErE
or
rE
.
rErE
9999
99. In some cases the time
9999
OFFOFF
11
OFF,
OFFOFF
LOOP bAdLOOP bAd
LOOP bAd message will
LOOP bAdLOOP bAd
99999999
1 to
9999 seconds. If,
11
99999999
commands. Any write commands sent to the
controls will be rejected.
rErE
rE
rErE
The host computer is allowed to send write
commands.If the control is not addressed within
the time set in the
Secure Menu) the
nAtnAt
nAt
(No Activity Timer, see
nAtnAt
CHEC LorECHEC LorE
CHEC LorE
CHEC LorECHEC LorE
error message will
be displayed.
AddrAddr
Addr
AddrAddr
(Option 992, Serial Communications) Control Address:
11
Read value from
3FF3FF
1
to
3FF
11
. This number (hexadecimal, base
3FF3FF
16) must match the address number used by the host
computer. Viewed only in this menu. The value displayed
is for Zone 1. The address for Zone 2 is the value for Zone
1 plus one (e.g. if
949-1318Page 24 of 40June, 2000
AddrAddr
Addr
AddrAddr
is set to
1717
17
, Zone 1 is assigned to
1717
Page 25
address
change this parameter, see
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance
to the next menu item. Press UP ARROW or DOWN ARROW to
change the value in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE THE INSTRUMENT IS IN SECURE MENU.
1717
17
and Zone 2 is assigned to address
1717
AddrAddr
Addr
in the Secure Menu.
AddrAddr
1818
18
1818
). To
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
Note: There are no standard menu items for the Secure Menu
when
AddrAddr
Addr
AddrAddr
EditEdit
Edit is set to
EditEdit
(Option 992, Serial Communications) Control Address: Select
from
00
0, begin.
00
11
1 or
11
22
2, jump to
22
11
3FE3FE
1
to
3FE
11
3FE3FE
33
3, jump to
33
00
0.
00
SEC1SEC1
SEC1 on page 26.
SEC1SEC1
SEC2SEC2
SEC2 on page 29.
SEC2SEC2
. This number (hexadecimal, base 16) must match
the address number used by the host computer. The value
displayed is for Zone 1. The address for Zone 2 is the value for
bAUdbAUd
bAUd
bAUdbAUd
Zone 1 plus one (e.g. if
,
1717
17
and Zone 2 is assigned to address
1717
200200
200
200200
, and
300300
300
300300
address
100100
100
100100
AddrAddr
Addr
is set to
AddrAddr
are reserved for Factory use.
(Option 992, Serial Communications) Communication Baud
300300
12001200
Rate: Select
300
300300
,
1200
12001200
24002400
,
2400
24002400
48004800
,
4800
48004800
1717
17
, Zone 1 is assigned to
1717
1818
18
). Addresses
1818
96009600
,
9600
96009600
, or
192192
192
00. This
192192
number must match the baud rate used by the host computer.
nAtnAt
nAt
nAtnAt
(Option 992, Serial Communications) No Activity Timer:
Set from
11
9999
1
-
99
11
9999
OFFOFF
OFF
OFFOFF
OFFOFF
OFF
OFFOFF
Maximum time between host computer accesses.
If timer counts to 0,
No Activity Timer function is disabled.
or
11
1
11
to
9999
99
minutes.
9999
CHECCHEC
CHEC
CHECCHEC
LorELorE
LorE
will be displayed.
LorELorE
End of Secure Menu when
June, 2000Page 25 of 40949-1318
EditEdit
Edit is set to
EditEdit
0 0
0.
0 0
Page 26
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
SEC1SEC1
SEC1Security Code: See the Security Level Selection and the
SEC1SEC1
11
33
1 or
3, begin.
11
33
22
2, jump to
22
SEC2SEC2
SEC2 on page 30.
SEC2SEC2
Password Table in this manual, in order to enter the correct
password.
InP1InP1
InP1Input Type: Select one of the following. Refer to the Input
InP1InP1
wiring section for the proper wiring.
J-ICJ-IC
J-ICType “J” Thermocouple
J-ICJ-IC
CACA
CAType “K” Thermocouple
CACA
Input Group 1
Input Group 2
Input Group 3
Input Group 4
Input Group 5
Input Group 6
E-E-
E-Type “E” Thermocouple
E-EL-L-
L-Type “L” Thermocouple
L-Ln-n-
n-Type “N” Thermocouple
n-nt-t-
t-Type “T” Thermocouple
t-tr-13r-13
r-13Type “R” Thermocouple
r-13r-13
S-10S-10
S-10Type “S” Thermocouple
S-10S-10
b-b-
b-Type “B” Thermocouple
b-bC-C-
C-Type “C” Thermocouple
C-CP392P392
P392100 ohm Platinum (NIST 0.00392 Ω/Ω/°C)
P392P392n120n120
n120120 ohm Nickel
n120n120P385P385
P385100 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
P385P385
1P381P38
1P381000 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
1P381P38
CurrCurr
CurrDC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
CurrCurr
UoLtUoLt
UoLtDC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
UoLtUoLt
diFFdiFF
diFFDC Voltage Input -10 to +10 mV.
diFFdiFF
--------
----Reserved
--------
Caution: Do not change the Input Type outside of the
programming Group on the Model Number. The input
will not function correctly if the Input Type is set to a
selection outside the specified Input Group.
0SP10SP1
0SP1Zero Suppression: Select
0SP10SP1
OnOn
OFFOFF
On or
OFF. Only with Current and
OnOn
OFFOFF
Voltage input types.
OFFOFF
OFFThe input range will start at 0 (zero) Input.
OFFOFF
OnOn
OnThe input range will start at 4.00 mA or 2.00 V.
OnOn
Unt1Unt1
Unt1
Unt1Unt1
FF
CC
C or
CC
NoneNone
None.
NoneNone
F,
FF
FF
F°F lamp is On and temperature inputs will be
FF
displayed in degrees Fahrenheit.
CC
C°C lamp is On and temperature inputs will be
CC
displayed in degrees Celsius.
nonEnonE
nonEBoth the°F and °C lamps will be Off. This selection
nonEnonE
is only available with Current and Voltage Inputs.
949-1318Page 26 of 40June, 2000
Page 27
Note: If both Set Point 1 and Set Point 2 are set for temperature
inputs, they must both be set for the same scale. While it is possible
to set one input as degrees F and the other degrees C, as there is
only one descriptor, one of the displays is likely to be mis-read. If
one Set Point is set for process input, you may select to display
either the temperature descriptor or neither (nonE).
dPt1dPt1
dPt1Decimal Point Positioning: Select
dPt1dPt1
temperature type inputs this will only effect the Process
Value, SP1, and InC1. For Current and Voltage Inputs all
Menu Items related to the Input will be affected.
00
0No decimal Point is selected. This is available for
00
all Input Types.
0.00.0
0.0One decimal place is available for Type J, K, E, T,
0.00.0
L, RTD’s, Current and Voltage Inputs.
0.000.00
0.00Two decimal places is only available for Current
0.000.00
and Voltage Inputs.
0.0000.000
0.000Three decimal places is only available for Current
0.0000.000
and Voltage inputs.
Int1Int1
Int1Input Fault Timer: Select
Int1Int1
ever an Input is out of range (UFL or OFL displayed), shorted,
or open the timer will start. When the time has elapsed, the
instrument will disable the output(s) and display
If OFF is selected, the Input Fault Timer will not be recog-
nized (time = infinite).
SEn1SEn1
SEn1Sensor Rate of Change: Select
SEn1SEn1
counts per 1 second period. This value is usually set to be
slightly greater than the fastest process response expected
during a 1 second period, but measured for at least 2
seconds. If the process is faster than this setting, the SEn1bAd error message will appear. The outputs will then be
turned off. This function can be used to detect a runaway
condition, or speed up detection of an open thermocouple.
Use the INDEX & ENTER keys to reset.
OFFOFF
OFF,
OFFOFF
0.10.1
0.1 to
0.10.1
00
0.00.0
0,
00
OFFOFF
OFF,
OFFOFF
0.000.00
0.0,
0.00, or
0.00.0
0.000.00
540.0540.0
540.0 minutes. When-
540.0540.0
11
1 to
11
0.0000.000
0.000. On
0.0000.000
bAd InPbAd InP
bAd InP.
bAd InPbAd InP
40004000
4000 °F, °C, or
40004000
SCL1SCL1
SCL1Scale Low: Select 100 to 9999 counts below
SCL1SCL1
span between
Maximum setting range is -1999 to 9999 counts. Minimum
span is 100 counts. For Current and Voltage inputs, this will
set the low range end. Viewable only for Thermocouple and
RTD ranges.
June, 2000Page 27 of 40949-1318
SCL1SCL1
SCL1 and
SCL1SCL1
SCH1SCH1
SCH1 must be within 11998 counts.
SCH1SCH1
SCH1SCH1
SCH1. The total
SCH1SCH1
Page 28
SCH1SCH1
SCH1Scale High: Select 100 to 9999 counts above
SCH1SCH1
span between
Maximum setting range is -1999 to +9999 counts. Minimum
span is 100 counts. For Current and Voltage inputs, this will
set the high range end. Viewable only for Thermocouple and
RTD ranges.
SPL1SPL1
SPL1Set Point Low: Select from the lowest input range value to
SPL1SPL1
SPH1 value. This will set the minimum SP1 value that can
be entered. The value for SP1 will not stop moving when this
value is reached. Attempting to set a value for SP1 lower
than SPL1 will result in a CHEC SP1 error. The value will not
be accepted.
SPH1SPH1
SPH1Set Point High: Select from the highest input range value to
SPH1SPH1
SPL1 value. This will set the maximum SP1 value that can
be entered. The value for SP1 will not stop moving when this
value is reached. Attempting to set a value for SP1 higher
than SPH1 will result in a CHEC SP1 error. The value will not
be accepted.
SCL1SCL1
SCL1 and
SCL1SCL1
SCH1SCH1
SCH1 must be within 11998 counts.
SCH1SCH1
SCL1SCL1
SCL1. The total
SCL1SCL1
S1StS1St
S1StSet Point State: Select
S1StS1St
dirdir
dirDirect Action. As the input increases the output
dirdir
will increase. Most commonly used in cooling
processes.
rErE
rEReverse Action. As the input increases the output
rErE
will decrease. Most commonly used in heating
processes.
Out1Out1
If
Out1 is set for ##
Out1Out1
(following) appear. If
S1OLS1OL
S1OLSet Point Output Low Limit: Select
S1OLS1OL
S1OHS1OH
than
S1OH. This item limits the lowest output value. This is
S1OHS1OH
useful for adding a bias to the process when needed.
Factory set to
2020
to
20 for output code 5 (20% output equals 4 mA output).
2020
S1OHS1OH
S1OHSet Point Output High Limit: Select
S1OHS1OH
S1OLS1OL
than
S1OL for output codes 1, 2, 3, or 8. Select
S1OLS1OL
but not less than S1OL for output code 5. This item allows
setting the maximum output limit. This is useful with processes that are over powered. Adjustment to 102% allows
setting current output to force a full on condition for output
tPtP
tP, #
tPtP
Out1Out1
Out1 is set for
Out1Out1
00
0 for output codes 1,2, 3, and 8. Factory set
00
dirdir
dir or
dirdir
PULPUL
PUL, or ProP, then S1OL and S1OH
PULPUL
rErE
rE.
rErE
ONOFONOF
ONOF, then skip to
ONOFONOF
00
9090
0 to
90% but not greater
00
9090
1010
100100
10 to
100% but not less
1010
100100
1010
10 to
1010
S1rES1rE
S1rE.
S1rES1rE
102102
102%
102102
949-1318Page 28 of 40June, 2000
Page 29
devices which do not have bias adjustments. Factory set
100100
to
100 for all output codes.
100100
Out1Out1
If
Out1 is set for ##
Out1Out1
S1rES1rE
S1rESet Point Reset. Select
S1rES1rE
OnOFOnOF
OnOFControl will automatically reset when process
OnOFOnOF
HoLdHoLd
HoLdManual Reset. Reset (acknowledge) by simulta-
HoLdHoLd
S1PiS1Pi
S1PiSet Point Power Interrupt. Select
S1PiS1Pi
OnOn
OnAlarm Power Interrupt is
OnOn
OFFOFF
OFFAlarm Power Interrupt is
OFFOFF
S1iHS1iH
S1iHSet Point Inhibit: Select
S1iHS1iH
OnOn
OnAlarm Inhibit is
OnOn
OFFOFF
OFFAlarm Inhibit is
OFFOFF
S1LPS1LP
S1LPSet Point Lamp: Select O on or OoFF.
S1LPS1LP
O onO on
O onLamp ON when Output is ON.
O onO on
OoFFOoFF
OoFFLamp OFF when Output is ON.
OoFFOoFF
tPtP
PULPUL
tP, #
PUL, or
tPtP
PULPUL
passes back through
neously pressing the INDEX & DOWN ARROW
keys for 5 seconds.
cally reset on power-up if no alarm condition
exists.
up in alarm condition regardless of condition of
process.
the process value first enters a non-alarm condition.
ProPProP
ProP,then skip to
ProPProP
OnOFOnOF
OnOF or
OnOFOnOF
OnOn
On or
OnOn
OnOn
On. Alarm action is suspended until
OnOn
OFFOFF
OFF.
OFFOFF
HoldHold
Hold.
HoldHold
SP1dSP1d
SP1d.
SP1dSP1d
OnOn
On or
OnOn
OnOn
On. Control will automati-
OnOn
OFFOFF
OFF. Control will power-
OFFOFF
OFFOFF
OFF.
OFFOFF
S1LPS1LP
S1LP.
S1LPS1LP
OFFOFF
OFF.
OFFOFF
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
June, 2000Page 29 of 40949-1318
11
1, jump to
11
33
3, continue.
33
AddrAddr
Addr on page 33.
AddrAddr
Page 30
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
EditEdit
If
Edit is set to
EditEdit
SEC2SEC2
SEC2Security Code: See the Security Level Selection and the Pass-
SEC2SEC2
11
1, jump to
11
33
3, continue.
33
22
2, begin.
22
SPIoSPIo
SPIo on page 33.
SPIoSPIo
word Table in this manual, in order to enter the correct password.
InP2InP2
InP2Input Type: Select one of the following. Refer to the Input
InP2InP2
wiring section for the proper wiring.
J-ICJ-IC
J-ICType “J” Thermocouple
J-ICJ-IC
CACA
CAType “K” Thermocouple
Input Group 1
Input Group 2
Input Group 3
Input Group 4
Input Group 5
Input Group 6
CACA
E-E-
E-Type “E” Thermocouple
E-EL-L-
L-Type “L” Thermocouple
L-Ln-n-
n-Type “N” Thermocouple
n-nt-t-
t-Type “T” Thermocouple
t-tr-13r-13
r-13Type “R” Thermocouple
r-13r-13
S-10S-10
S-10Type “S” Thermocouple
S-10S-10
b-b-
b-Type “B” Thermocouple
b-bC-C-
C-Type “C” Thermocouple
C-CP392P392
P392100 ohm Platinum (NIST 0.00392 Ω/Ω/°C)
P392P392n120n120
n120120 ohm Nickel
n120n120P385P385
P385100 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
P385P385
1P381P38
1P381000 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
1P381P38
CurrCurr
CurrDC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
CurrCurr
UoLtUoLt
UoLtDC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
UoLtUoLt
diFFdiFF
diFFDC Voltage Input -10 to +10 mV.
diFFdiFF
---- Reserved
Caution: Do not change the Input Type outside of the
programming Group on the Model Number. The input
will not function correctly if the Input Type is set to a
selection outside the specified Input Group.
0SP20SP2
0SP2Zero Suppression: Select
0SP20SP2
OnOn
On or
OnOn
OFFOFF
OFF. Only with Current and
OFFOFF
Voltage input types.
OFFOFF
OFFThe input range will start at 0 (zero) Input.
OFFOFF
OnOn
OnThe input range will start at 4.00 mA or 2.00 V.
OnOn
Unt2Unt2
Unt2
Unt2Unt2
FF
CC
C or
CC
NoneNone
None.
NoneNone
F,
FF
FF
F°F lamp is On and temperature inputs will be displayed
FF
in degrees Fahrenheit.
CC
C°C lamp is On and temperature inputs will be displayed
CC
in degrees Celsius.
nonEnonE
nonEBoth the°F and °C lamps will be Off. This selection is
nonEnonE
only available with Current and Voltage Inputs.
949-1318Page 30 of 40June, 2000
Page 31
Note: If both Set Point 1 and Set Point 2 are set for temperature
inputs, they must both be set for the same scale. While it is possible
to set one input as degrees F and the other degrees C, since there
is only one descriptor, one of the displays is likely to be mis-read.
If one Set Point is set for process input, you may select to display
either the temperature descriptor or neither (nonE).
dPt2dPt2
dPt2Decimal Point Positioning: Select
dPt2dPt2
temperature type inputs this will only effect the Process
Value, SP1, SP2, and InC1|InC2. For Current and Voltage
Inputs all Menu Items related to the Input will be affected.
00
0No decimal Point is selected. This is available for
00
all Input Types.
0.00.0
0.0One decimal place is available for Type J, K, E, T,
0.00.0
L, RTD’s, Current and Voltage Inputs.
0.000.00
0.00Two decimal places is only available for Current
0.000.00
and Voltage Inputs.
0.0000.000
0.000Three decimal places is only available for Current
0.0000.000
and Voltage inputs.
Int2Int2
Int2Input Fault Timer: Select
Int2Int2
ever an Input is out of range (
or open the timer will start. When the time has elapsed, the
instrument will disable the output(s) and display
If OFF is selected, the Input Fault Timer will not be recognized (time = infinite).
SEn2SEn2
SEn2Sensor Rate of Change: Select
SEn2SEn2
counts per 1 second period. This value is usually set to be
slightly greater than the fastest process response expected
during a 1 second period, but measured for at least 2
seconds. If the process is faster than this setting, the SEn2bAd error message will appear. The outputs will then be
turned off. This function can be used to detect a runaway
condition, or speed up detection of an open thermocouple.
Use the INDEX & ENTER keys to reset.
OFFOFF
OFF,
OFFOFF
UFLUFL
UFL or
UFLUFL
0.10.1
0.1 to
0.10.1
00
0.00.0
0,
00
OFFOFF
OFF,
OFFOFF
0.000.00
0.0,
0.00, or
0.00.0
0.000.00
540.0540.0
540.0 minutes. When-
540.0540.0
OFLOFL
OFL displayed), shorted,
OFLOFL
11
1 to
11
0.0000.000
0.000. On
0.0000.000
bAd InPbAd InP
bAd InP.
bAd InPbAd InP
40004000
4000 °F, °C, or
40004000
SCL2SCL2
SCL2Scale Low: Select 100 to 9999 counts below
SCL2SCL2
span between
Maximum setting range is -1999 to +9999 counts. Minimum
span is 100 counts. For Current and Voltage inputs, this will
set the low range end. Viewable only for Thermocouple and
RTD ranges.
June, 2000Page 31 of 40949-1318
SCL2SCL2
SCL2 and
SCL2SCL2
SCH2SCH2
SCH2 must be within 11998 counts.
SCH2SCH2
SCH2SCH2
SCH2. The total
SCH2SCH2
Page 32
SCH2SCH2
SCH2Scale High: Select 100 to 9999 counts above
SCH2SCH2
span between SCL2 and SCH2 must be within 11998 counts.
Maximum setting range is -1999 to +9999 counts. Minimum
span is 100 counts. For Current and Voltage inputs, this will
set the high range end. Viewable only for Thermocouple and
RTD ranges.
SPL2SPL2
SPL2Set Point Low: Select from the lowest input range value to
SPL2SPL2
SPH1 value. This will set the minimum SP2 value that can
be entered. The value for SP2 will not stop moving when this
value is reached. Attempting to set a value for SP2 lower
than SPL2 will result in a CHEC SP2 error. The value will not
be accepted.
SPH2SPH2
SPH2Set Point High: Select from the highest input range value to
SPH2SPH2
SPL2 value. This will set the maximum SP2 value that can
be entered. The value for SP2 will not stop moving when this
value is reached. Attempting to set a value for SP2 higher
than SPH2 will result in a CHEC SP2 error. The value will not
be accepted.
SCL2SCL2
SCL2. The total
SCL2SCL2
S2StS2St
S2StSet Point State: Select
S2StS2St
dirdir
dirDirect Action. As the input increases the output
dirdir
will increase. Most commonly used in cooling
processes.
rErE
rEReverse Action. As the input increases the output
rErE
will decrease. Most commonly used in heating
processes.
Out2Out2
If
Out2 is set for ##
Out2Out2
appear. If
S2OLS2OL
S2OLSet Point Output Low Limit: Select
S2OLS2OL
S2OHS2OH
S2OHSet Point 1 Output High Limit: Select
S2OHS2OH
Out2Out2
Out2 is set for
Out2Out2
S2OHS2OH
than
S2OH. This item limits the lowest output value. This is
S2OHS2OH
useful for adding a bias to the process when needed.
Factory set to
2020
to
20 for output code 5 (20% output equals 4 mA output).
2020
S2OLS2OL
than
S2OL for output codes 1, 2, 3, or 8. Select
S2OLS2OL
but not less than
setting the maximum output limit. This is useful with processes that are over powered. Adjustment to 102% allows
setting current output to force a full on condition for output
tPtP
tP, or #
tPtP
00
0 for output codes 1,2, 3, and 8. Factory set
00
S2OLS2OL
S2OL for output code 5. This item allows
S2OLS2OL
dirdir
dir or
dirdir
PULPUL
PUL, then
PULPUL
ONOFONOF
ONOF, then skip to
ONOFONOF
rErE
rE.
rErE
S2OHS2OH
S2OH and
S2OHS2OH
S2OHS2OH
S2OH (following)
S2OHS2OH
S2rES2rE
S2rE.
S2rES2rE
00
9090
0 to
90% but not greater
00
9090
1010
100100
10 to
100% but not less
1010
100100
1010
10 to
1010
102102
102%
102102
949-1318Page 32 of 40June, 2000
Page 33
devices which do not have bias adjustments. Factory set
100100
to
100 for all output codes.
100100
Out2Out2
If
Out2 is set for ##
Out2Out2
S2rES2rE
S2rESet Point Reset. Select
S2rES2rE
OnOFOnOF
OnOFControl will automatically reset when process
OnOFOnOF
HoLdHoLd
HoLdManual Reset. Reset (acknowledge) by simulta-
HoLdHoLd
S2PiS2Pi
S2PiSet Point Power Interrupt. Select
S2PiS2Pi
OnOn
OnAlarm Power Interrupt is
OnOn
OFFOFF
OFFAlarm Power Interrupt is
OFFOFF
S2iHS2iH
S2iHSet Point Inhibit: Select
S2iHS2iH
OnOn
OnAlarm Inhibit is
OnOn
OFFOFF
OFFAlarm Inhibit is
OFFOFF
S2LPS2LP
S2LPSet Point Lamp: Select O on or OoFF.
S2LPS2LP
O onLamp ON when Output is ON.
OoFFLamp OFF when Output is ON.
tPtP
PULPUL
tP, #
PUL, or
tPtP
PULPUL
passes back through
neously pressing the INDEX & DOWN ARROW
keys for 5 seconds.
cally reset on power-up if no alarm condition
exists.
up in alarm condition regardless of condition of
process.
the process value first enters a non-alarm condition.
ProPProP
ProP,then skip to
ProPProP
OnOFOnOF
OnOF or
OnOFOnOF
OnOn
On or
OnOn
OnOn
On. Alarm action is suspended until
OnOn
OFFOFF
OFF.
OFFOFF
HoldHold
Hold.
HoldHold
SP2dSP2d
SP2d.
SP2dSP2d
OnOn
On or
OnOn
OnOn
On. Control will automati-
OnOn
OFFOFF
OFF. Control will power-
OFFOFF
OFFOFF
OFF.
OFFOFF
S2LPS2LP
S2LP.
S2LPS2LP
OFFOFF
OFF.
OFFOFF
S2tS2t
S2tSet Point 2 type: Select
S2tS2t
AbSAbS
AbSAbsolute
AbSAbS
be set anywhere between the limits of
SPH2SPH2
SPH2.
SPH2SPH2
dEdE
dEDeviation
dEdE
and allows
when
Note: The
SPL1SPL1
the
SPL1 and
SPL1SPL1
generated by a change of
June, 2000Page 33 of 40949-1318
SPL2SPL2
SPL2 and
SPL2SPL2
SPH1SPH1
SPH1 settings. If not, a
SPH1SPH1
SP2SP2
SP2.
SP2SP2
SP1SP1
SP1 is changed.
SP1SP1
SPH2SPH2
SPH2 settings must be set to correspond with
SPH2SPH2
SP1SP1
SP1.
SP1SP1
AbsAbs
Abs or
AbsAbs
SP2SP2
SP2 is independent of
SP2SP2
SP2SP2
SP2SP2
SP2.
SP2 is set as a deviation from
SP2SP2
SP2SP2
SP2SP2
SP2 to retain its relationship with
SP2SP2
dEdE
dE.
dEdE
SP1SP1
SP1, and may
SP1SP1
SPL2SPL2
SPL2 and
SPL2SPL2
CHEC SP2CHEC SP2
CHEC SP2 error may be
CHEC SP2CHEC SP2
SP1SP1
SP1,
SP1SP1
SP1SP1
SP1
SP1SP1
Page 34
The following Menu Items operate on the entire Instrument.
There is no Set Point distinction. These items will appear in
both the
Edit1Edit1
Edit1,
Edit1Edit1
Edit2Edit2
Edit2, and
Edit2Edit2
Edit3Edit3
Edit3 menus.
Edit3Edit3
SP1oSP1o
SP1oSet Point 1 Output Select: Select
SP1oSP1o
OutAOutA
OutASet Point 1 is routed through Output A, Set Point 2 is
OutAOutA
routed through Output B.
OutbOutb
OutbSet Point 1 is routed through Output B, Set Point 2 is
OutbOutb
routed through Output A.
COPYCOPY
COPY
COPYCOPY
AddrAddr
Addr
AddrAddr
Copy Zone Parameters. Copies program parameters from one
zone to the other.
nonenone
noneNo copy function is performed. Factory default.
nonenone
1to21to2
1to2Copies all parameters from Zone 1 to Zone 2.
1to21to2
2to12to1
2to1Copies all parameters from Zone 2 to Zone 1.
2to12to1
(Option 992, Serial Communications) Control Address: Select
11
1
11
to
3FE3FE
3FE
. This number (hexadecimal, base 16) must match
3FE3FE
from
the address number used by the host computer. The value
displayed is for Zone 1. The address for Zone 2 is the value
for Zone 1 plus one (e.g. if
Addr
assigned to address 17 and Zone 2 is assigned to address
18
). Addresses
100, 200
, and
use.
bAUdbAUd
bAUd
bAUdbAUd
(Option 992, Serial Communications) Communication Baud
300300
12001200
Rate: Select
300
300300
,
1200
12001200
24002400
,
2400
24002400
,
number must match the baud rate used by the host computer.
OutAOutA
OutA or
OutAOutA
OutbOutb
Outb.
OutbOutb
is set to 17, Zone 1 is
300
are reserved for Factory
48004800
4800
48004800
96009600
,
9600
96009600
, or
192192
192
00. This
192192
nAtnAt
nAt
nAtnAt
949-1318Page 34 of 40June, 2000
(Option 992, Serial Communications) No Activity Timer:
Set from
11
9999
1
-
99
11
9999
OFFOFF
OFF
OFFOFF
OFFOFF
OFF
OFFOFF
Maximum time between host computer accesses.
If timer counts to 0,
No Activity Timer function is disabled.
or
11
1
11
to
9999
99
minutes.
9999
CHEC LorE
will be displayed.
Page 35
SPECIFICATIONS
Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current
selectable.
Input Impedance:
Thermocouple = 3 megohms minimum.RTD current = 200 µA.
Current = 10 ohms.Voltage = 5000 ohms.
Sensor Break Protection: De-energizes control output to protect system
after customer set time. (See InP1 and InP2 in Secondary Menu.)
Set Point Range: Selectable (See Range Chart Page 39).
Display: Two 4 digit, 7 segment 6.35 mm (0.25") high LEDs.
Control Action: Reverse (usually heating), Direct (usually cooling) select-
able.
Proportional Band: 1 to 9999 °F, °C, or counts.
Reset Time (Integral): Off or 0.1 to 99.9 minutes.
Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
Cycle Rate: 1 to 80 seconds.
On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,
1° C, or 1 count steps.
Fuzzy Percent: 0 to 100%.
Fuzzy Rate: Off or 0.01 to 99.99 minutes.
Fuzzy Band: Off or 1 to 4000 °F, °C, or counts.
Accuracy: ±0.25% of span, ±1 least significant digit.
Resolution: 1 degree or 0.1 degree, selectable.
Line Voltage Stability: ±0.05% over the supply voltage range.
Temperature Stability: 100 ppm /°C typical, 200 ppm /°C maximum.
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation:
Relay and SSR outputs: 1500 Vac to all other inputs and outputs.
SP1 Current output: Non-isolated, share common groung with input.
SP1 and SP2 Switched Voltage outputs: Non-isolated, shares
common ground with input.
Supply Voltage: 100 to 240 Vac, nominal, +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 Vdc, nominal, +10 -20%.
Supply Voltage (Option 9502): 12 to 24 Vdc, Vac 40-400 Hz, ±20%.
Power Consumption: 5VA maximum.
Operating Temperature: -10 to +55 °C (+14 to 131 °F).
June, 2000Page 35 of 40949-1318
Page 36
Storage Temperature: -40 to +80 °C (-40 to 176 °F).
Humidity Conditions: 0 to 90% up to 40 °C non-condensing, 10 to 50% at
55 °C non-condensing.
Memory Backup: Nonvolatile memory. No batteries required.
Control Output Ratings:
AC SSR (Output A, Output B): 0.75 A @ 240 Vac at 25 °C (77°F).
Derates to 0.5 A @ 55° C (130°F).DC SSR (Output A, Output B): 1.25 A @ 32VDC at 25° C (77°F),
derates to 1.0 A at 55° C (130°F).
Relay (Output A, Output B): SPST, 3 A @ 240 Vac resistive; 1.5A
@240 Vac inductive; 1/10 HP @ 120 Vac.
Current (non-isolated, Output A only): 0 to 20 mA across 600
ohms maximum.
Switched Voltage (non-isolated, Output A, Output B): 5 Vdc @
20 mA.
Panel Cutout: 45.0 mm x 22.2 mm (1.772" x 0.874").
Depth Behind Mounting Surface: 111.6 mm (4.395").
Weight: 114 g (4 oz).
Agency Approvals: UL and C-UL, file #E83725; CE.
Front Panel Rating: IP66, Type 4.
949-1318Page 36 of 40June, 2000
Page 37
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
No
display
lighted
FAILFAIL
FAIL
FAILFAIL
tESttESt
tESt
tESttESt
CHEC SP1CHEC SP1
CHEC SP1
CHEC SP1CHEC SP1
CHEC SP2CHEC SP2
CHEC SP2
CHEC SP2CHEC SP2
CHEC SPL1CHEC SPL1
CHEC SPL1
CHEC SPL1CHEC SPL1
CHEC SPH1CHEC SPH1
CHEC SPH1
CHEC SPH1CHEC SPH1
or
CHEC SPL2CHEC SPL2
CHEC SPL2
CHEC SPL2CHEC SPL2
CHEC SPH2CHEC SPH2
CHEC SPH2
CHEC SPH2CHEC SPH2
Display is blank. Instrument is not getting power, or the supply voltage is too low.
Fail test appears
upon power up if the
internal diagnostics
detect a failure. This
message may occur
during operation if a
failure is detected.
Displays flash.
This message will
appear upon power
up if SP1 is set outside of the SPL1/SPH1 values or SP2
is set outside the
SPL2/SPH2 values.
This message appears at power up if
SPL or SPH values
are programmed outside the input range
ends.
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm inactive
Set point
output(s)
inactive
Alarm active
Set point
output(s)
inactive
Alarm inactive
Check that the power supply is
on, or that the external fuses
are good.
The display alternates between
FAIL tESt and one of the follow-
FACtFACt
ing messages:
ory may be corrupted. Press the
ENTER key and the DOWN
ARROW key to start the factory
default procedure. Recheck controller programming.
Unrecoverable error, return to
factory for service.
Correct the
SPL1SPL1
the
values by programming new
values.
Correct the
or
ming new values.
SPL2SPL2
SPL1,
SPL2,
SPL1SPL1
SPL2SPL2
SPH2SPH2
SPH2 values by program-
SPH2SPH2
FACt
FACtFACt
SP1SP1
SP2SP2
SP1,
SP2. or adjust
SP1SP1
SP2SP2
SPL2SPL2
SPL2, or
SPL2SPL2
SPL1SPL1
SPL1,
SPH1,
SPL1SPL1
dFLtdFLt
dFLt: Mem-
dFLtdFLt
rEtrEt
FACtFACt
rEt
FACt:
rEtrEt
FACtFACt
SPH2SPH2
SPH2
SPH2SPH2
SPH1SPH1
SPL2SPL2
SPL2,
SPH1SPH1
SPL2SPL2
CHECCHEC
CHEC
CHECCHEC
LorELorE
LorE
LorELorE
SEnCSEnC
SEnC
SEnCSEnC
ArEAArEA
ArEA
ArEAArEA
(Alternates
with PV
when near)
This message appears if the Serial
Communications
has timed out.
Sensor Rate of
Change exceeded
the programmed limits set for SEnC. Appears in display of
affected zone.
This message appears
if the ambiient temperature of the control is
near or out of range or
RJC sensor is broken.
Set point
outputs active
Alarm inactive
Set point
output(s)
inactive.
Alarm Active
Set point
outputs active
Alarms active
Restore the communications
LorELorE
line and switch the
Check for the cause of the error. The value setting may be
too slow for the process, or the
sensor is intermittent. Correct
the problem and press INDEX
and ENTER to reset.
Correct the ambient temperature conditions. Ventilate the
area of the cabinet or check for
clogged filters. If RJC broken,
return to factory for service.
LorE to
LorELorE
LOCLOC
LOC.
LOCLOC
June, 2000Page 37 of 40949-1318
Page 38
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
UFLUFL
UFL*
UFLUFL
OFLOFL
OFL*
OFLOFL
bAdbAd
bAd*
bAdbAd
OPEnOPEn
OPEn*
OPEnOPEn
LOOPLOOP
LOOP*
LOOPLOOP
CHECCHEC
CHEC
CHECCHEC
CHECCHEC
CHEC
CHECCHEC
or
CAL1CAL1
CAL1
CAL1CAL1
or
CAL2CAL2
CAL2
CAL2CAL2
Underflow or Overflow: Process value
has exceeded input
range ends.
UFL or OFL will sequence to display
one of these messages if the InPt is
set for a time value.
For RTD inputs RTD
is open or shorted.
For THERMOCOUPLE inputs thermocouple is open.
The sensor may be
defective, heater
fuse open, heater
open, or the final
power output device
is bad.
Message appears
when input group is
selected other than
the one provided from
the Factory
Set point
outputs active
Set point
output(s)
inactive
Set point
output(s)
inactive.
Set point
outputs
inactive
Input signals may normally go
above or below range ends. If
not, check input and correct.
To reset use the INDEX &ENTER keys. When InPt (input fault timer) has been set
for a time, the outputs will be
turned off after the set time.
Setting the time to OFF causes the outputs to remain active, however UFL or OFL will
still be displayed.
Correct or replace sensor. To
reset use the INDEX & EN-TER keys.
Correct or replace sensor, or
any element in the control loop
that may have failed. Correct
the problem, and reset the
control by pressing the INDEX
and ENTER keys, or index to
LPbr and press ENTER.
Calibrate the specified input
before putting Instrument in to
service.
Check calibration appears as an alternating message if the
instrument calibration nears tolerance
edges.
Check calibration appears as a flashing
message if the instrument calibration exceeds specification.
* Message appears in the display of the affected zone. The output for that zone will
be inactive.
Set point
outputs active
Set point
outputs
inactive
Alarm active
Remove the instrument for service and / or recalibration. To
reset use the INDEX & ENTER
keys.
Remove the instrument for
service and / or recalibration.
To reset use the INDEX &ENTER keys.
949-1318Page 38 of 40June, 2000
Page 39
Input Ranges (Field Selectable)
Thermocouple T ypes
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Type J or L*
-100 to +1600
-73 to +871
Type R
0 to 3200
-17 to +1760
Type N*
-100 to +2372
-73 to +1300
Type K*
-200 to +2500
-129 to +1371
Type S
0 to 3200
-17 to +1760
* These Input Types can be set for 0.1° display.
If temperature goes above 999.9° or less than
-199.9° the display will return to whole degree
resolution.
Type T*
-350 to +750
-212 to +398
Type B
+75 to 3308
+24 to 1820
Type E*
-100 to +1800
-73 to +982
Type C
0 to 4208
-17 to 2320
RTD T ypes
Input
Type
Range
1°F
1°C
1000 Ohm
Platinum
0.00385 DIN
Curve*
-328 to +1607
-200 to +875
100 Ohm
Platinum
0.00385 DINCurve*
-328 to +1607
-200 to +875
100 Ohm
Platinum
0.00392 NistCurve*
-328 to +1607
-200 to +875
120 Ohm
Nickel
0.00628 USInd. Curve*
-112 to +608
-80 to +320
Process Input Types
The 0 to 20 mAdc, 4 to 20 mAdc, 0 to 10 Vdc, and 2 to 10 Vdc inputs are
fully scalable from a minimum of 100 counts span placed anywhere within
the within the range of -1999 to +9999. Decimal point position is adjustable
from the zero place (9999), tenths (999.9), hundredths (99.99), or thousandths (9.999).
June, 2000Page 39 of 40949-1318
Page 40
44.86
(1.766)
DIMENSIONS
111.6
(4.395)
22.1
(0.870)
6.35 (0.25)
Maximum Panel Thickness
11
(0.433)
30.1
(1.184)
ALL DIMENSIONS IN MILLIMETERS (INCHES)
PANEL CUT OUT: 45 +0.6 X 22.2 +0.3 (1.772 +0.02 X 0.874 +0.012)
52.8
(2.080)
Z1
Z2
LOVE CONTROLS
LOVE
®
949-1318Page 40 of 40June, 2000
a Division of Dwyer Instruments, Incorporated
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
❍
❍
❍
www.love-controls.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.