Dwyer 3000SGT User Manual

SERIES 3000 SGT PHOTOHELIC
1/8 NPT FEMALE PNEUMATIC TAPS
2-1/16 [52.39]
2
[50.80]
PANEL 5/8 [15.88] MAX
1-1/4
[31.75]
3/16
[4.76]
5/8
[15.88]
2-1/2
[63.50]
3-7/8
[98.43]
5-1/8
[130.18]
4-3/8
[111 .13 ]
HOUSING REMOVAL
3/4 [19.05]
CONDUIT OPENING
Ø4-3/4 [120.65] FLANGE
3-7/8 [98.43] SQ HOUSING
Ø4
[101.60]
FACE
5
[127.00]
0.D.
BEZEL
5-1/2
[139.70]
O.D.
MOUNTING 
RING
SNAP RING GROOVE
Ø4-3/4 [120.65]
MOUNTING HOLE
®
Bulletin B-36A
DIFFERENTIAL PRESSURE SWITCH/GAGE TRANSMITTER
Specifications – Installation and Operating Instructions
Figure A
The Series 3000 PHOTOHELIC®SGT is a versatile 3-in-1 instrument combining a
time-proven Magnehelic switches and a 4-20 mA pressure transmitter. It is designed to measure and control positive, negative or differential pressure of air or other non-combustible, non­corrosive gases. Gage reading is unaffected by switch or transmitter operation. Switch set points are easily adjusted with knobs located on gage face. Applied pressure and switch set points are fully visible at all times. Deadband is one pointer width, less than 1% of full scale. Each set point controls a DPDT relay and both can be interlocked to provide variable deadband control. The 2-wire transmitter operates independently, driven by a separate external 10-35 VDC power supply. Separate zero and span potentiometers are provided inside the rear electronics package for easy field adjustment.
PHYSICAL DATA Ambient Temperature Range: 20 to 120˚F (-6.7to 49˚C). Maximum Pressure: 2 psi (13.8 kPa) for ranges up to 5˝ w.c.; 5 psi (35 kPa) for
ranges 6, 10˝ w.c.; 10 psi (69 kPa) for ranges 20, 30˝ w.c.; 25 psi (170 kPa) for above ranges.
Accuracy: ±2% of full scale at 70˚F (21.1˚C) (3% on -0). Pressure Connections: 1/8˝ NPT(F). Case Finish: Baked dark gray epoxy enamel. Conduit Opening: 3/4˝. Standard Accessories: (2) 3/16˝ tubing to 1/8˝ NPT brass adapters for rubber or
vinyl tubing, (1) mounting ring. (1) snap ring, (4) 6-32 x 2˝ mounting screws, instructions.
Compatibility: Use only with air or other non-combustible, non-corrosive gases. Weight: 4 lb, 12oz (2.15 kg).
ELECTRICAL SPECIFICATIONS (Switches) Power Supply: 117 VAC. Current Consumption: 5 watts average. Contact Rating: 10A @ 24 VDC or 120 VAC, 6A @ 240 VAC.
®
differential pressure gage, low/high limit pressure
INSTALLATION
1. Location: Select a clean, dry, vibration-free location where ambient
temperatures will be between 20 and 120˚F (-6.7 and 49˚C). Tubing supplying pressure to the instrument can be practically any length but long runs will increase response time slightly.
2. Position: The PHOTOHELIC vertical plane. Operation at other angles may affect accuracy and/or require zero adjustment. Most models can be specially calibrated at the factory for other positions if specified at time of ordering. Ranges below 1˝ w.c. must be used only with scale vertical.
3. Mounting: Normal mounting is flush or through panel as shown in Figure B. Allow 4-3/8˝ space behind the unit for electrical enclosure removal. Make 4-3/4˝ diameter hole in panel. When installing multiple units, it may be preferred to obtain a Model 730E, 120 mm chassis punch as manufactured by Greenlee Tool Co. and available from your machine tool distributor.
Insert PHOTOHELIC case from rear and seat the snap ring in its groove. Thread the (4) 6-32x2˝ machine screws into mounting ring, back it against snap ring and tighten screws to back of panel. An alternative to flush mounting is the optional A-371 Surface Mounting Bracket. Unit is mounted in this bracket as described above and bracket is then surface mounted. Contact factory for details.
®
SGT is factory calibrated for use with scale in a
®
SGT from front of panel, slip the mounting ring over the
ELECTRICAL SPECIFICATIONS (Transmitter) Power Supply: 10.0 to 35 VDC. Output Signal: 4-20 mA DC, 2-wire (limited at 38 mA). Loop Resistance: 0-1250 ohms. Current Consumption: 38 mA DC, maximum. Span and Zero Adjustment: Multi-turn potentiometers, internally accessible Thermal Errors: ±1% per 50˚F typical Warm-Up Time: 10 minutes.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361 U.S.A.
Figure B
Phone: 219/879-8000 www.dwyer-inst.com Fax: 219/872-9057 e-mail: info@dwyer-inst.com
4. Zeroing & Pneumatic Connections: After unit is installed in its final mounting
COVER MOUNTING  SCREWS
FLEXIBLE CONDUIT
SUPPORT CONDUIT FROM PANEL
SECTION B
SECTION A
SECTION C
SECTION D
SECTION E
position, use the screw at bottom of front cover to adjust pointer for exact zero reading. This must be done with both pressure ports open and vented to atmosphere.
(A) For positive pressure, connect tubing to HIGH PRESSURE port and vent LOW
PRESSURE port to atmosphere.
(B) For negative pressure (vacuum), connect tubing to LOW PRESSURE port and
vent HIGH PRESSURE port to atmosphere.
When either port will be left open to atmosphere, we suggest installation of optional A-331 Filter Vent Plug to keep gage interior clean.
(C) For differential pressure, connect higher pressure to HIGH PRESSURE port
and lower pressure to LOW PRESSURE PORT.
NOTE: If the PHOTOHELIC
®
SGT is on over-pressured beyond its full scale range, pointer could jump from full scale back to zero and remain there until the excess pressure condition is relieved. Users should be aware that this condition would cause a false indication of zero pressure and subsequently affect set­points and transmitter output signal.
SWITCH/GAGE WIRING CONNECTIONS
To make electrical connections, remove the (3) cover screws and slide cover off. All wiring should be fed through flexible conduit attached to conduit opening at bottom of electrical package. Conduit should be attached to the panel of other suitable support to avoid excess strain on the instrument. See Figure C.
Figure D
CAUTION: Do not apply electrical current to terminals in Sections B and C.
Separate Ground Wire attachment is provided for by a No. 6-32 screw on the
mounting bracket near the conduit opening.
Single Set-Point instruments are furnished with the right or high set-point components and circuitry in place. These are connected to Sections A and B of the terminal board. The left or low set-point components are omitted.
2. Circuit Style: The PHOTOHELIC
®
is available with several factory installed optional internal circuits. They are identified as to style by a label shown in Figure E. This label is mounted prominently on the terminal board of each instrument. The letter H denotes a circuit in which the relay can be made to latch or remain energized after pressure increase to its set-point.
The letter L denotes a circuit in which the relay can be made to latch or remain de-energized after pressure decreases to its set-point. Two letters are required to fully identify a dual set-point. Two letters are required to fully identify a dual set-point unit. Thus, circuit style HH, which is standard, is a dual set-point circuit which has provisions for latching on pressure increase to either set-point. Single relay units are identified by the letters SR followed by H for the standard unit or L for the special low latch unit. Units for use with other than standard 117 VAC will be so indicated on the label.
Figure C
1. Low/High Set-Point Wiring Connections
The rear terminal board contains connections for low and high set-points, holding coil circuits and line power supply. Transmitter connections are located behind this terminal board. See TRANSMITTER WIRING CONNECTIONS for complete information.
Section A contains DPDT connections for the right or high set-point and Section D contains identical connections for the left or low set-point.
Terminals in Section B are for control of the holding coil circuit for the right, high set-point and Section C contains identical connections for the left, low set-point. These holding coil circuits are typically used to allow latching set-points with manual reset or for adjustable deadband operation with one set-point wired to reset the other. See paragraphs 3 and 4 for details. Do Not Connect Line Current to Sections B or C. Section E (L1 and L2) contains power supply connections for the control unit transformer primary. The transformer in turn supplies reduced voltage power for the LED, phototransistor, amplifier unit, load relay pull-in and holding coils. Connections must always be made to this section for the unit to operate. Standard units require 117 VAC but options are available for other power sources. See label on terminal board for correct voltage and circuit style.
2
Figure E
3. Dual Set Point Automatic Reset: Circuit Style HH is used for simple on-off
switching applications. To place in service, connect load circuits to the appropriate terminals in Section A (Figure D) for the right set-point and Section D for the left set-point. Note that the N.O. contacts are open when the gage pressure pointer is to the left of the set-pointers. No connections are necessary in Sections B and C. Make external ground connections as required and connect power to Section E for the control unit. To use circuit style LL for automatic reset, a jumper wire must be installed between the upper and lower terminals in Sections B and/or C.
4. Dual Set Point Manual Reset: Circuit Style HH may also be used for manual reset applications where it is desired to have maintained contact on either relay following pressure increase above its set-point. Load or signal connections are made to the appropriate terminals in Sections A and D (as in paragraph 3 above). Connect terminals in Sections B and C through normally closed switches or push buttons as shown in Figure F. Use of “dry­circuit” type switches such as Dwyer Instruments, Inc. Part No. A-601 with palladium, gold, etc. or rotary wiping action type contacts is recommended. Make external ground connections as required and connect power to Section E for the control unit.
Circuit style LL is used for manual reset applications which require that contact be maintained following pressure decrease below the set-point. Load connections are made to the appropriate terminals in Sections A and D. A normally open type manual reset switch such as Dwyer Instruments, Inc. Part No. A-601 is connected to the terminals in Sections B and C. The circuit must be reset or “armed” by momentarily closing the switch while the black pointer is to the right of the set-point. From that point on, the circuit will latch on pressure decrease below the set-point and remain latched on pressure increase until manually reset with the optional switch.
Loading...
+ 2 hidden pages