Dwyer 2500 User Manual

INSTRUCTIONS FOR THE
2500 SERIES
MICROPROCESSOR BASED
TEMPERATURE CONTROL
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
December, 1998 Page 1 949-1190-1
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
m
m
m
TABLE OF CONTENTS
MODEL IDENTIFICATION ...................................................................... 4
INSTALLATION ....................................................................................... 4
WIRING ................................................................................................... 5
FRONT PANEL KEY FUNCTIONS.........................................................6
MENU SELECTIONS.............................................................................8
PRIMARY MENU ....................................................................................8
SECONDARY MENU ..............................................................................8
SECURE MENU....................................................................................10
ALARM TYPE AND ACTION ................................................................12
SPECIFICATIONS ................................................................................ 14
DIAGNOSTIC ERROR MESSAGES ..................................................... 15
DIMENSIONS ....................................................................................... 16
© 1995, LOVE CONTROLS DIVISION, DWYER INSTRUMENTS, INCORPORATED. ALL RIGHTS RESERVED. NO PORTION MAY BE COPIED WITHOUT THE EXPRESS WRITTEN CONSENT OF LOVE CONTROLS.
949-1190-1 Page 2 December, 1998
GETTING STARTED
1. Install the control as described on page 4.
2. Wire your control following the instructions on page 4 and drawing on page 5.
3. Most controls do not need many (if any) program changes to work on your process. For best results if programming changes are necessary, make all the necessary changes in the Secure Menu (page 10) before making changes to the Secondary Menu (page 8). If error messages occur, check the Diagnostic Error Messages on page 15 for help.
Take the example of a Model 25011 that comes from the factory pro­grammed for type J thermocouples. Suppose for this example you wish to change the input to type K and limit the set point range between 0° and 1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX key until the display shows Inp and press the DOWN ARROW until the display shows CA. Don't forget to press the ENTER key to retain your setting.
Next, press the INDEX key to display F-C. Press the DOWN ARROW until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt selections). Press the UP ARROW until the display shows 0. Press ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until the display shows 1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds the display will switch back to the temperature reading. If you want to return faster, press the UP ARROW and ENTER keys (at the same time) and then press the DOWN ARROW and INDEX keys ( again at the same time). This will 'back out' of the menu and immediately display the temperature reading.
December, 1998 Page 3 949-1190-1
MODEL IDENTIFICATION
Model 2 5
Output
Alarm
0 = No 1 = Yes
Mount the instrument in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. Prepare the panel by cutting and deburring the required opening.
From the front of the panel, slide the housing through the cut out. The housing gasket should be against the housing flange before installing.
Input
1 = Thermocouple, J,K,T,E,N,L 2 = RTD, DIN, NIST, Ni 120
INSTALLATION
1 = SSR 2 = 5 VDC 3 = Relay 5 = Current
From the rear of the panel slide the mounting collar over the housing. Hold the housing with one hand and using the other hand, push the collar evenly against the panel until the springs are compressed. The ratchets will hold the mounting collar and housing in place.
It is not necessary to remove the control chassis from the housing for installation. If the control chassis is removed from the housing, you must follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure to exercise good ESD practices may cause damage to the control.
949-1190-1 Page 4 December, 1998
WIRING
Do not run thermocouple or other input wiring in the same conduit as power leads. Use only the type of thermocouple or RTD probe for which the control has been programmed. Maintain separation between wiring of sensor, auxilliary in or out, and other wiring. See the "Secure Menu" for input selection.
For thermocouple input always use extension leads of the same type designated for your thermocouple.
For supply connections use No. 16 AWG or larger wires rated for at least 75°C. Use copper conductors only. All line voltage output circuits must have a common disconnect and be connected to the same pole of the disconnect.
Wiring to housing terminals while chassis is re­moved may cause distortion of the internal connec­tor and possible damage to the connector when the chasis is re-installed. It is strongly recomended that the control housing be wired with the chassis in­stalled.
Control wiring is shown below.
December, 1998 Page 5 949-1190-1
FRONT PANEL KEY FUNCTIONS
Set Point Lamp Alarm Lamp Temperature Display °F Indicator
Set Point Display Decimal point on lower display flashes The °F/°C indicator while ramping func- will flash while Self­tion is active. Tune is operating.
°
°
°C Indicator
Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next menu item. May also be used in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a menu item, or selects the item to ON. The maximum value obtainable is 9999 or 999.9.
DOWN ARROW: Decrements a value, changes a menu item, or selects the item to OFF. The minimum value obtainable is ­1999 or -199.9.
ENTER: Pressing ENTER stores the value or the item changed. If not pressed, the previously stored value or item will be retained. The display will flash once when ENTER is pressed.
UP ARROW & ENTER: Pressing these keys simultaneously brings up the secondary menu starting at the alarm, tune, or cycle item (depending on programming). Pressing these keys for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow backing up one menu item, or if at the first menu item they will cause the display to return to the primary menu. If an alarm condition has occurred, these keys may be used to reset the alarm.
INDEX & ENTER: Pressing these keys simultaneously and holding them for 5 seconds allows recovery from the various error messages. The following menu items will be reset:
ALiH: Alarm inhibit OPEn InP: Thermocouple error message bAd InP: RTD error message CHEC CAL: Check calibration error message
Correct the problems associated with the above conditions first before using these reset keys. More than one error could be present. Caution is advised since several items are reset at one time.
949-1190-1 Page 6 December, 1998
While in the Primary or Secondary menu, if no key is pressed for a period of 30 seconds, the display will return to the HOME position displaying the temperature value. The time is increased to 1 minute when in the Secure menu.
NOTE: To move to the primary menu quickly from any other menu, press the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security level. To change security levels change the password value using the UP & DOWN ARROW keys and pressing the ENTER key. Refer to the password table below for the correct value to enter for the security level desired. The SECr menu item security level may be viewed or changed at any time regardless of the present security level. The password values shown in the table cannot be altered, so retain a copy of this page for future reference. This will be the only reference made to password values in this instruction book.
PASSWORD TABLE
SECURITY LEVEL
MENU SECURITY Primary Locked
Secondary Locked Secure Locked
Primary Unlocked Secondary Locked Secure Locked
Primary Unlocked Secondary Unlocked Secure Locked
Primary Unlocked Secondary Unlocked Secure Unlocked
DISPLAYED VALUE
WHEN VIEWED
1
2
3
4
PASSWORD
VALUE TO ENTER
1110
1101
1011
111
December, 1998 Page 7 949-1190-1
MENU SELECTIONS
PRIMARY MENU Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value.
SP Set Point Adjust, Control Point. SECONDARY MENU
Hold UP ARROW & ENTER. Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the value in the display. Press ENTER to retain the value.
ALLo Alarm Low: The Low Alarm point is usually set below the Set Point. ALHi Alarm High: The High Alarm Point is usually set above the Set
Point.
The next two Menu Items are for output codes 1,2,or 3. If your control has output code 5, skip to the Out Menu Item.
CY Cycle Rate and output selection: Select OnOF, 1, 2 to 80 seconds
total cycle time. ONOF A setting of ONOF allows the control to operate as a
simple on/off mode. This setting forces the control to turn off at set point, and on at the set point plus the differential (SP_d). When selected the tunE, Pb, rES, OFS, rtE, and ArUP selections in the Secondary menu and the SPOL and SPOH selections in the Secure menu are suppressed.
1 A setting of 1 is recommended for solid state outputs
(SSR or 5VDC).
2 to 80 Time Proportioning Control is adjustable in 1 sec. steps.
Recommended for mechanical outputs (relays, solenoids,etc.). For best contact life, a time should be selected as long as possible without causing the process to wander.
SP_d Set Point On-Off Differential. Select 1 to 999°F. This value will be
negative for reverse acting set points, and positive for direct acting
949-1190-1 Page 8 December, 1998
outputs. Set the value for the amount of temperature difference between the turn off point (set point) and the turn on point. Only appears if CY is set to ONOF.
Out Fixed at ProP. For Current (Code 5) outputs only.
tunE Tuning Choice: Select SELF or Pid.
SELF The Controller will evaluate the Process and select the
PID values to maintain good control. The ramp function (rt) can not be selected while SELF tunE is active. The temperature descriptor will flash while SELF tunE is active. The control will switch to Pid tunE when the tuning function is complete.
Pid Manually adjust the PID values. PID control consists of
three basic parameters, Proportional Band (Gain), Re­set Time (Integral), and Rate Time (Derivative).
Pb Proportional Band (Bandwidth). Select 5 to 5000 °F (3 to
2778 °C).
rES Automatic Reset Time. Select OFF, 0.1 to 99.9 minutes.
Select OFF to switch to OFS.
OFS Manual Offset Correction Select OFF, 0.1 to 99.9%. Select
OFF to switch to rES.
rtE Rate Time. Select OFF, 0.01 to 99.99 minutes, Deriva-
tive.
ArUP Anti- Reset Wind-up Feature: Select On or OFF.
On When ArUP is On the accumulated Reset Offset value
will be cleared to 0% when the process input is not within the Proportional Band.
OFF When ArUP is OFF, the accumulated Reset Offset
Value is retained in memory when the process input is not within the Proportional Band.
rt Ramp Time: Select OFF, 00.01 to 99.59 (HH.MM). When value
is entered, control calculates a ramp slope from the current temperature to SP over the time entered. Changing rt or SP (or pressing ENTER at either menu item) restarts the ramp function, and re-calculates the slope. The right hand decimal point of the lower display will flash while the ramp function is active. Self tunE can not be selected while the ramp function is active. Selecting OFF will stop a current ramp and drive the output as necessary to reach set point
InPC Input Correction: Select ±500 °F (±278 °C). This feature allows the
input value to be changed to agree with an external reference or to
December, 1998 Page 9 949-1190-1
compensate for sensor error. Note: InPC is reset to zero when the input type is changed, or when decimal position is changed.
FiLt Digital Filter: Select OFF, 1 to 99. In some cases the time constant
of the sensor, or noise could cause the display to jump enough to be unreadable. A setting of 2 is usually sufficient to provide enough filtering for most cases, (2 represents approximately a 1 second time constant). When the 0.1 degree resolution is selected this should be increased to 4. If this value is set too high, controllability
will suffer.
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the value in the display. Press ENTER to retain the value.
SECr Security Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.
InP Input Type: Select one of the following. The selections are limited
to the input type you ordered. If you ordered a thermocouple input control, make your selection from the thermocouple list. If you ordered an RTD input, select fron the RTD list.
Thermocouple selections:
J-IC Type “J” Thermocouple. CA Type “K” Thermocouple. E- Type "E" Thermocouple. t- Type “T” Thermocouple. L- Type "L" Thermocouple. n- Type "N" Thermocouple.
RTD selections:
P385 100 ohm Platinum (DIN 0.00385 Ω/Ω/°C). P392 100 ohm Platinum (NIST 0.00392 Ω/Ω/°C). n120 120 ohm Nickel (US Industrial 0.00672 Ω/Ω/°C)
F-C Select temperature descriptor for Fahrenheit or Celcius.
F °F descriptor is On and temperature inputs will be
displayed in actual degrees Fahrenheit.
C °C descriptor is On and temperature inputs will be
displayed in actual degrees Celsius.
dPt Decimal Point Positioning: Select 0 or 0.0. This only effects the
Process Value, SP, ALLo, ALHi, and InPC.
0 No decimal Point is selected.
0.0 One decimal place is selected. If the Process Value
moves outside of the decimal point range ends (-199.9 to +999.9), the Process Value display will autorange to whole degree resolution. When the Process Value
949-1190-1 Page 10 December, 1998
returns to the decimal point range, the display will autorange back to tenth dergee resolution.
InPt Input Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an
Input is out of range (UFL or OFL displayed), shorted, or open the timer will start. When the time has elapsed, the controller will revert to a safe condition (Output Off, Flashing Display). If OFF is selected, the Input Fault Timer will not be recognized (time = infinite).
SPL Set Point Low: Select from the lowest input range value to SPH
value. This will set the minimum SP value that can be entered. The value for SP will stop moving when this value is reached.
SPH Set Point High: Select from the highest input range value to SPL
value. This will set the maximum SP value that can be entered. The value for SP will stop moving when this value is reached.
SPSt Set Point State: Select dir or rE.
dir Direct Action. As the input increases the output will
increase. Most commonly used in cooling processes.
rE Reverse Action. As the input increases the output will
decrease. Most commonly used in heating processes.
SPOL Set Point Output Low Limit: Select 0 to 100% but not greater than
SPOH. This item limits the lowest output value. This is useful for
adding a bias to the process when needed. Factory set to 0 for output codes 1,2, and 3. Factory set to 20 for output code 5 (20% output equals 4 mA output).
SPOH Set Point Output High Limit: Select 0 to 100% but not less than
SPOL for output codes 1, 2, or 3. Select 0 to 102% but not less
than SPOL for output code 5. This item allows setting the maximum output limit. This is useful with processes that are over powered. Adjustment to 102% allows setting current output to force a full on condition for output devices which do not have bias adjustments. Factory set to 100 for all output codes.
SPLP Set Point Lamp: Select O on or OoFF.
O on Lamp ON when Output is ON. OoFF Lamp OFF when Output is ON.
December, 1998 Page 11 949-1190-1
ALARM TYPE AND ACTION (if present)
Caution: In any critical application where failure could cause expensive product loss or endanger personal safety, a redundant limit controller is required.
When setting an alarm value for an absolute alarm (ALt = AbS), simply set the value at which the alarm is to occur.
When setting the alarm value for a deviation alarm (ALt = dE), set the difference in value from the Set Point (SP) desired. For example if a low alarm is required to be 5 degrees below the SP, then set ALLo to -5. If a high alarm is required 20 degrees above the SP, then set ALHi to +20. If SP is changed, the alarm will continue to hold the same relationship as originally set.
The diagram at the below shows the action and reset functions for both absolute and deviation alarms.
ABSOLUTE ALARMS
DEVIATION ALARMS
When Alarm Power Interrupt, ALPi, is programmed ON and Alarm Reset, ALrE, is programmed for Hold, the alarm will automatically reset upon a power failure and subsequent restoration if no alarm condition is present.
WARNING: IF INHIBIT IS ON AND A POWER FAILURE OCCURS DURING A HIGH
, RESTORATION OF POWER WILL NOT CAUSE THE ALARM TO OCCUR
ALARM
THE PROCESS VALUE DOES NOT FIRST DROP BELOW THE HIGH ALARM
IF
SETTING CREATED ALARM
BY THIS ACTION. BE SURE TO TEST ALL COMBINATIONS OF HIGH AND LOW
INHIBIT ACTIONS BEFORE PLACING CONTROL INTO OPERATION.
. DO NOT USE THE ALARM INHIBIT FEATURE IF A HAZARD IS
949-1190-1 Page 12 December, 1998
The following menu items apply only to the alarm.
AL Alarms: Select OFF, Lo, Hi, or HiLo.
OFF Alarms are turned OFF. No Alarm menu items appear
in the Secondary and Secure menus.
Lo Low Alarm Only. ALLo appears in the Secondary
Menu.
Hi High Alarm Only. ALHi appears in the Secondary
Menu.
HiLo High and Low Alarms. Both share the same Alarm
Relay output.
ALt Alarm Type: Select AbS or dE
AbS Absolute Alarm that may be set anywhere within the
values of SPL and SPH and is independent of SP.
dE Deviation Alarm that may be set as an offset from SP.
As SP is changed the Alarm Point will track with SP.
ALrE Alarm Reset: Select OnOF or Hold.
OnOF Automatic Reset.
Hold Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5 sec.
ALPi Alarm Power Interrupt: Select On or OFF .
On Alarm Power Interrupt is ON.
OFF Alarm Power Interrupt is OFF. ALiH Alarm Inhibit: Select On or OFF.
On Alarm Inhibit is ON. Alarm action is suspended until
the process value first enters a non-alarm condition.
OFF Alarm Inhibit is OFF. ALSt Alarm Output State: Select CLOS or OPEn.
CLOS Closes Contacts at Alarm Set Point.
OPEn Opens Contacts at Alarm Set Point. ALLP Alarm Lamp: Select O on or OoFF.
O on Alarm Lamp is ON when alarm contact is closed.
OoFF Alarm Lamp is OFF when alarm contact is closed.
December, 1998 Page 13 949-1190-1
SPECIFICATIONS
Selectable Inputs: Thermocouple or RTD as ordered. Input Impedance:
Thermocouple = 3 megohms minimum. RTD current = 200 µA.
Sensor Break Protection: De-energizes control output to protect system. Set Point Range: Selectable (See range chart page 16 ). Display: Two 4 digit, 7 segment 0.56" high LEDs. Control Action: Reverse (usually heating), Direct (usually cooling) select-
able.
Proportional Band: 5 to 5000 °F or equivalent °C. Reset Time (Integral): Off or 0.1 to 99.9 minutes. Rate Time (Derivative): Off or 0.01 to 99.99 minutes. Cycle Rate: 1 to 80 seconds, and on-off. On - Off Differential: Adjustable 1° F to 999°F in 1° steps (equivalent °C). Alarm On - Off Differential: 2° F or equivalent in °C. Accuracy: ±0.25% of span, ±1 least significant digit. Resolution: 1 degree or 0.1 degree, selectable. Line Voltage Stability: ±0.05% over the supply voltage range. Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)
maximum.
Common Mode Rejection: 140 db minimum at 60 Hz. Normal Mode Rejection: 65 db typical, 60 db at 60 Hz. Isolation: Relay and SSR outputs 1500 VAC. Current output 500VAC.
5VDC output is not isolated and must not share a common ground with the input.
Supply Voltage: 100 to 240 VAC, nom., +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 VDC, nom., +10 -20%.
Power Consumption: 5VA maximum. Operating Temperature: -10 to +55 °C (+14 to 131 °F). Storage Temperature: -40 to +80 °C (-40 to 176 °F). Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at
55 °C non-condensing.
Memory Backup: Non-volatile memory. No batteries required. Control Output Ratings:
1. SSR, 2.5 A @ 240 VAC at 25 °C. Derates to 1.25 A @ 55 °C.
2. Relay, Form C contact (SPDT), 10 A @ 240 VAC resistive.
3. Alarm Relay, Form A contact (SPST). 3A @ 240 VAC resistive.
4. Switched Voltage (non-isolated), 5 VDC @ 20mA.
5. Proportional Current (isolated), 0 to 20 mA, selectable, into 600 ohms maximum.
Weight: 369 g (13 oz). Agency Approvals: UL, C-UL E83725. Front Panel Rating: IP66, (UL Type 4X).
949-1190-1 Page 14 December, 1998
DIAGNOSTIC ERROR MESSAGES
DISPLAY
UFL
or
OFL
bAd
InP
OPEn
InP
CHEC
CAL
No
display
lighted
MEANING
Underflow or Overflow: Process value has ex­ceeded input range ends.
UFL or OFL will se­quence to display one of these messages if the InPt is set for a time value. For RTD inputs RTD is open or shorted.
For THERMOCOUPLE inputs thermocouple is open.
Check calibration ap­pears as an alternating message if the instru­ment calibration nears tolerance edges. Check calibration ap­pears as a flashing mes­sage if the instrument calibration exceeds specification.
Display is blank. Instru­ment may not be getting power, or the supply voltage is too low.
SP OUTPUTS
Set point
output active
Alarms active
Set point
output inactive
Alarms active
Set point
output active
Alarms active
Set point
output inactive
Alarms active
Set point
output inactive
Alarms inactive
ACTION REQUIRED
Input signals may normally go above or below range ends. If not, check input and correct.
To reset use the INDEX & ENTER keys. When InPt (input fault timer) has been set for a time, the outputs will be turned off after the set time. Setting the time to OFF causes the outputs to remain active, however UFL or OFL will still be displayed. Correct or replace sensor. To reset use the INDEX & ENTER keys.
Remove the instrument for service and / or recalibration. To reset use the INDEX & ENTER keys.
Remove the instrument for service and / or recalibration. To reset use the INDEX & ENTER keys.
Check that the power supply is on, or that the external fuses are good.
FAIL
tESt
CHEC SP CHEC ALLO CHEC ALHi
CHEC
SPL
or
CHEC
SPH
Fail test appears upon power up if the internal diagnostics detect a fail­ure. This message may occur during operation if a failure is detected. Displays flash.
This message will ap­pear upon power up if the set point is set out­side of the SPL or SPH values.
This message appears at power up if SPL or SPH values are pro­grammed outside the input range ends.
Set point
output inactive
Alarms inactive
Set point
output inactive
Alarms active
Set point
output inactive
Alarms inactive
The display alternate between FAIL tESt and one of the following mes­sages: FACt dFLt: Memory may be corrupted. Press the ENTER key and the DOWN ARROW key to start the factory default procedure. Re­check controller programming. rEt FACt: Can not recover from error, return to factory for service.
Correct the SP or adjust the SPL or SPH values by programming new values.
Correct the SPL or SPH values by programming new values.
December, 1998 Page 15 949-1190-1
Thermocouple Types
DIMENSIONS
°
°
INPUT RANGES
Input Type
Range
RTD Types
Input Type
Range
Type J or L
-100 to +1600
1°F
-73 to +871
1°C
100 Ohm Platinum
0.00385 DIN Curve
1°F
1°C
-200 to +2500
-129 to +1371
-328 to +1607
-200 to +875
Type K
100 Ohm Platinum
0.00392 Nist Curve
-328 to +1607
-200 to +875
Type T
-350 to +750
-212 to +398
Type E
-100 to +1800
-73 to +982
120 Ohm Nickel
0.00628 US Industrial Curve
Type N
-100 to +2372
-73 to +1300
-112 to +608
-80 to +320
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
949-1190-1 Page 16 December, 1998
m
m
www.love-controls.com
m
Loading...