1. Important Safety Information................................................................................................................................. 3
7. Booster Set User Maintenance ............................................................................................................................ 25
9. Pressure Set Point Adjustment............................................................................................................................ 29
11. VASCO V209 and V214 Pump Controllers ................................................................................................... 37
Dutypoint Limited
Shepherd Road
Gloucester
GL2 5EL
United Kingdom
2
1.Important Safety Information
1.1Health & Safety at Work Act 1974
Section 6(a) of this Act requires manufacturers to advise their customers on the safety and the handling
precautions to be observed when installing, operating, maintaining and servicing their products. The user’s
attention is therefore drawn to the following:
–The appropriate sections of this manual must be read before working on the equipment.
–Installation, operating and maintenance must only be carried out by suitably trained/qualified
personnel.
–Normal safety precautions must be taken and appropriate procedures observed to avoid accidents.
Refer to Dutypoint for any technical advice or product information. It is the responsibility of the customer
and/or the contractor:
–To ensure that anyone working on the equipment is wearing all necessary protective gear/clothing;
–Is aware of appropriate health & safety warnings and to read the information in this manual.
1.2Safety Messages and Hazard Statement
Table 1.1:Hazard Notice Definitions
Message LevelDefinition
DANGERA hazardous situation which, if not avoided, will result in death or serious
injury
WARNINGA hazardous situation which, if not avoided, could result in death or serious
injury
CAUTIONA hazardous situation which, if not avoided, could result in minor injury or
moderate injury
ELECTRICAL HAZARDRisks associated with electricity will cause hazards if not properly avoided
NoteA situation which may arise resulting in undesirable conditions and/or will not
cause direct hazards to persons
1. Important Safety Information
1.3Qualified Personnel
WARNING
This product is indented for operation by qualified personnel only
–Only qualified personnel are allowed to install or operate this equipment
–Qualified personnel are defined as trained staff, who are authorised to install, commission and maintain
equipment, systems and circuits in accordance with relevant laws and regulations. Personnel must be familiar
with the instructions and safety procedures described in this document.
–This product should not be used by anyone with mental disabilities, or anyone without the relevant experience
and knowledge, unless they have received instructions on using the equipment and on the associated risks, or
are supervised by a responsible person.
–Children must be supervised to ensure they do not play on or around the equipment.
1.4Environmental Protection
All local regulations and codes regarding emissions and waste disposal must be followed. This may include:
–Reporting of emissions to appropriate authorities
–Sorting, recycling and disposal of solid or liquid waste
3
1. Important Safety Information
–Clean-up of spills
–Separate disposal of electrical components from domestic waste
1.5Mechanical Device Servicing
–Familiarise yourself with the relevant contents of this manual
–Installation, maintenance and repair work must only be carried out by trained, skilled and suitably
qualified personnel.
–Disconnect or lock-out the power source to ensure that the item(s) will remain inoperative. Locking
out the equipment by switching off the release mechanism or set value WILL NOT prevent accidental
starting.
–Allow the item(s) to cool if over-heated.
–CLOSE the isolating valves on the suction and discharge connections of the affected item(s).
–If working on pump, VENT slowly and cautiously – Refer to the relevant section of this manual.
–DRAIN the pump(s).
1.6Pump Hand Control Mode (Where Fitted)
In the 'HAND' position the pump(s) controlled by the switch will normally run at full speed and completely
independently of any control devices, and can result in pump(s) running against a closed valve head if there
is no draw. This can cause the system to be maintained at the maximum pressure produced by the pump
plus any incoming pressure and additional pressure caused by water surge and can potentially damage the
pump and other parts of the system.
The 'HAND' option should only be used with a competent operator in attendance, or when there is a
continued demand sufficient to provide constant flow through the pumps to maintain the running pressure
of the system to an acceptable level.
1.7Personal Protective Equipment
Use personal safety equipment according to the site conditions and employer regulations. This may include,
but may not be limited to:
–Hard hat
–Safety goggles with side shields
–Protective footwear
–Protective gloves
–Respirator
–Ear protection
–First aid kid
–Safety devices
1.8Precautions Before Commencing Work
Ensure that the following safety precautions are complied with before commencing work:
–Provide a suitable barrier around the work area
–Ensure all safety guards and in place and secure
–Ensure you have a clear path of exit
–Ensure that the product cannot roll or fall over and cause damage to persons or property
–Ensure all lifting equipment is in good condition and rated for the intended task
–Use a lifting harness, safety line and respirator as required
–Allow hot components to cool before handling them
–Ensure that product has been thoroughly cleaned
–Disconnect and lock out power supply, ensuring that it cannot be accidentally re-connected
–Check for any risk of explosion before using hand tools
4
1.9Precautions During Work
–Never work alone
–Always wear protective clothing and hand protection
–Stay clear of suspended loads
–Always use appropriate lifting devices
–Beware of risks of sudden starts of any automated equipment such as level control
–Beware of starting jerks of electric motors - these can be powerful
–Do not exceed the stated operating limits of equipment
–Do not remove vent plugs from a pressurised system - ensure pressurised components are relieved
of pressure before disassembly
–Ensure guards are in place during operation
1.10Hazardous Fluids and Chemicals
If hazardous chemicals come into contact with skin or eyes, use the following procedures:
ConditionAction
Chemicals or
hazardous fluids in
eyes
Chemicals or
hazardous fluids on
skin
1)Hold your eyelids apart forcibly with your fingers
2)Rinse the eyes with eyewash or running water for at least 15 minutes
3)Seek medical attention
1)Remove contaminated clothing
2)Wash the skin with soap and water for at least 1 minute
3)Seek medical attention
1. Important Safety Information
1.11Electrical Safety - High Voltages
This information is especially applicable when Variable Speed Controllers (Inverters) are fitted to pumps.
When the inverter variable speed drive head is connected to the power supply the components of the power
unit as well as certain components of the master control unit – are also connected to the power supply.
DANGER!
Touching these components can seriously endanger life!
–Before removing the frequency inverter cover, the system must be disconnected from the power supply
–After switching off the power supply wait at least 5 minutes before starting work on or in the inverter drive head
- the capacitors in the intermediate circuit must be given time to discharge completely via the discharge
restors.
ELECTRICAL HAZARD
Up to 800V can be present - if there are faults this can be higher
–All work carried out when the frequency inverter is open must be performed only by suitably qualified and
properly authorised personnel.
5
1. Important Safety Information
ELECTRICAL HAZARD
THE SYSTEM MUST ONLY BE OPERATED WHEN IT HAS BEEN CORRECTLY EARTHED AND PIPES BONDED TO
EARTH IN ACCORDANCE WITH IEE REGULATIONS
–When connecting external control wires care must be taken not to short circuit adjacent components. Bare
cable ends which are not in use must be insulated.
1.12Electronic Safety Devices
–Inverter drives contain electronic safety devices which switch off the control element in the event of
a fault developing.
–A motor can also be stopped by ‘mechanical blocking’
–If it is switched off electronically, the motor is disconnected from the mains voltage supply via the
electronics in the inverter drive.
–Voltage fluctuation and power failures (temporary outages) can cause the motor to switch itself off.
WARNING
A motor will have zero current but will remain energised as it stops
–Take necessary precautions - the motor is not voltage-free in the circuit itself
WARNING
Repair of faults can cause items to start up again unexpectedly
–Ensure the motor is isolated before commencing any work
WARNING
High voltage tests of inverters may damage the electrical components.
–Bridge before the incoming/outgoing terminals L-L2-L3 and U-V-W.
–To avoid incorrect metering by capacitors incorporated in the electronic circuits, isolate the motor from the
inverter drive head.
1.13Spare Parts
WARNING
Use of non-genuine spare parts may cause damage to equipment, damage to property and voiding of
warranty
–Use genuine, Dutypoint-approved spare parts only
–If in doubt, contact Dutypoint Service on 01452 300590.
6
1. Important Safety Information
1.14Transportation and Lifting
WARNING: LIFTING HAZARDS
–Stay clear of suspended loads
–Observe accident prevention regulations in force
–Do not damage the cables during transports; so not squeeze, bend or dray the cable
–Always keeps the cable ends dry
–Secure the unit against tipping over and slipping until it is mounted and fixed in its final location
–Lift and handle the product carefully, using suitable lifting equipment (stacker, crane, crane mounting device,
lifting blocks, sling ropes, etc.)
–Always lift the unit by its lifting handle
WARNING: ASSEMBLED SYSTEMS ARE HEAVY
–Failure to properly lift and support this equipment can result in serious physical injury and/or equipment
damage,
–Lift equipment only at the specifically identified lifting points.
–Lifting devices such as eye bolts, slings and spreaders must be rated, selected and used for the entire load being
lifted
–Select the appropriate lifting points
1)Inspect the package
a)Inspect the package for damage or missing items upon delivery
b)Note any damaged or missing items on the shipping paperwork and contact Dutypoint
immediately
c)File a claim with the shipping company if anything is out of order
d)If the product has been picked up at a distributor, file a claim with the distributor
2)Inspect the unit
a)Remove packing materials from the product
b)Dispose of all packing materials in accordance with local regulations
c)Inspect the product to determine if any parts have been damaged or are missing
d)If applicable, unfasten the product by removing any screw, bolts or straps. For your personal
safety, be careful when you handle nails and straps.
e)Contact Dutypoint if you have any issues.
1.15Storage
The product must be stored in a covered and dry location free from heat, dirt and vibrations.
NOTE: Protect the product against humidity, heat sources and mechanical damage
NOTE: Do not place heavy weights on the packed product
NOTE: See section on storage limits
7
1. Important Safety Information
8
2.Specifications
Table 2.2:ScubaTANK WX Range Specifications
ApplicationsWater with no gas or aggressive substances
Flow Range0.8 - 3.1 litres/sec
Pressure Range2.0 - 7.0 bar
Liquid
Temperature
Ambient
Temperature
HumidityMax 50%
Controller TypeModus VASCO
ProtectionLow water level via probe control
Tank Construction GRP construction
NOTE: An additional 250mm minimum clearance is required above the overall height
NOTE: Inlet centre: 62mm below the open tank top height
–The area should be dry, frost-free and well ventilated, away from extremes of temperature. All
pipework must be adequately protected from freezing.
–Adequate provision should be made for drainage, leakage damage protection and service access.
–The tank is free standing and is provided with fixing feet for secure fastening to the floor.
3.2Cleaning the Filter
This check is required every 6 months for the first year of operation as the system may still contain
sediment. After this, an annual check is normally sufficient to keep the filter clear of sediment.
11
3. Installation Sequence
Figure 3.3:Filter Cleaning Process
1. Turn isolator level to OFF
(position perpendicular to
pipework)
4. Replace all parts and turn
isolator lever to ON position
(parallel to pipework)
3.3Hydraulic Connection
–All pipework must be in accordance with local Water Authority regulations.
–The discharge pipework must be sized according to the system demand.
–All pipework must be securely supported and not over-stressed.
–The overflow and the warning pipe (if fitted) must be piped to a suitable location.
3. Remove filter and rinse
under water to remove build up
2. Remove hex cap
and o-ring
3.4Electrical Supply
WARNING: ALL ELECTRICAL WORK MUST BE CARRIED OUR BY A SUITABLY QUALIFIED
PERSON FOLLOWING THE LATEST IEE REGULATIONS
–The system must only be operated when it has been correctly earthed and pipes bonded to earth in accordance
with the latest IEE regulations
WARNING: CONTROLLER ELECTRIC SHOCK DANGER. THE CONTROLLER CONTAINS
HIGH VOLTAGE
–Never open the controller or work with any electrical connections within it unless the electrical supply to the
unit is isolated.
–Wait a further 2 minutes after isolation for the internal circuitry to discharge.
–The electrical supply feed to the ScubaTANK should be a dedicated line to minimise electromagnetic
interference.
–The electrical supply rating must be at least double the FLC, assuming all pumps operate together
(see Table 3.5: ScubaTANK Breaker Ratings.)
–The control panel isolator cable should be connected via a suitably rated external MCB.
NOTE: The probe relay settings are factory preset and should conform with information in
Pump
FLC
ScubaTANK
Model
Twin Pump
ScubaTANK
Model
WX1 (Single
Pump)
Breaker
Rating
WX2 (Twin
Pump)
Breaker
Rating
the wiring diagram. Adjustment will invalidate the warranty.
Figure 3.4:Common Fault Volt Free Contact Wiring Details
MAXIMUM 230V - 5AMP
2× BLACK
FROM
INVERTER
1
3.5How to Seal a Horizontal Split Tank (Applicable to -HS Models)
NOTE: This section applies only to ScubaTANK WX models with horizontal split tanks.
These have the -HS designation.
WARNING
The flange sealant is very adhesive
2× RED
FROM
INVERTER
2
–Ensure it is aligned correctly before applying it to the flange.
–Remove paper backing as you progress along the flanges
–Check that you have the correct number of fixing components, i.e. nut, bolt, washers and arboseal.
–Ensure the flanges are free from grease and grit or other substances which may damage or prevent the flange
sealant from sticking,
–Ensure the flange sealant black strip is applied approx 5mm from the inner edge of the flange, water side.
13
3. Installation Sequence
NOTE: Ensure you follow the procedure according the images and instructions below.
Figure 3.5:Applying split tank sealant
Nut and bolt arrangement.Ensure flanges are clean
and free from grease, grit
etc.
✓
When applying sealant to
the next flange, ensure a
overlap.
Flange sealant overlaps like
this.
Note: some sealant may
squeeze out from between
the flanges. This is normal.
Apply flange sealant
ensuring the black strip is
water side.
×
DO NOT LEAVE A GAP
BETWEEN SEALS
When the flange seals have been applied to the bottom section, the top section of the tank is carefully lifted
onto it. A podger/screwdriver may be used to align the bolt holes by pushing it through the top flange hole,
through the flange seal and through the lower flange hole. A bolt may be pushed through to hold it in place
while the other holes are located. It is recommended that all bolts are pushed through before tightening
begins. Recommended torque: 40Nm (30lb/ft)
3.6Bolt Tightening Sequence for Split Tank Flange Assembly
After all the nuts have been spun onto the bolts by hand, you may begin tightening sequentially from the
first bolt to its diagonal opposite and continue in a clockwise or anticlockwise direction.
1)First time around, just pinch the nuts with a spanner;
2)Second time around, apply 30% recommended torque;
3)Third time around, apply 60% recommended torque;
4)Fourth time around, apply 100% recommended torque.
3.7Level Probe Details
There are 5 terminals within the probe holder:
14
3. Installation Sequence
Table 3.6:ScubaTANK Level Probe Holder Details
E1Solenoid Cut-Off ProbeShortest probe (300mm)
E2Solenoid Cut-In Probe100mm longer than the cut out probe
E3Low Level Probe50mm shorter than the common probe
E4Common ProbeLongest probe
E5Note used in standard ScubaTANK models
Before shipment, all Dutypoint pump sets are pre-commissioned. Whilst important procedures such as
venting and rotational direction checks need to be carried out on site, initial parameters including pressure
settings and delay timers will be adjusted to suit the site conditions previously advised to Dutypoint.
In practice, a system can almost invariably be made to perform more efficiently if further re-commissioning
is carried out on site.
Please note that engineer visits by Dutypoint are priced at one visit to commission one pump set. If there
are multiple units on a site, special terms can be negotiated. To arrange a commissioning visit, please call
the Technical Service Help line 01452 300590.
The following checks should be carried out at the initial installation before any run tests are performed.
WARNING
–Ensure that you have read and understood Section 1. Important Safety Information.
4. Booster Set Commissioning
4.2Pipework and mechanical components
1)Ensure that the mounting area and any associated groundwork provides adequate support for the
pump set.
2)Ensure all supports/brackets are in place and secure.
3)Verify all pipe joints are sealed and tight.
4.3Electrical
WARNING
–These checks MUST be carried out by a competent electrician.
–Ensure that the power source is sufficient to allow the running of two (twin pump sets) or three (triple pump
sets) pumps together.
1)Check the motor voltage and frequency information on all the motor nameplates and on controllers
etc. correspond with that of the source power supply.
2)Check that all electrical connections are correctly made and secure. Pay particular attention to Earth
and bonding connections.
3)Carry out specific checks for Earth bonding.
4)Carry out NICEIC certification checks as required for the installation, e.g Earth Loop Impedance,
Insulation Tests, etc.
5)Carry out any other pre-start checks recommended by the pump manufacturer. Refer to the pump
manual in the Appendix of this manual. DO NOT POWER UP AT THIS STAGE.
4.4Low Level Float Switch Wiring (Optional)
Terminal 1 and 3 require a normally closed contact in order to allow the pump set to operate. To facilitate
this the unit will be supplied with a wire loop between 1 and 2. To install a low level float switch this loop
has to be removed and the float switch wired to operate as an open on fail scenario.
17
4. Booster Set Commissioning
If 2 or more float switches are required (due to twin compartment or multiple tanks) all float switches are
wired into terminals 1 and 2 in parallel.
Figure 4.7:Terminal Wiring
111234
LOW
LEVEL
FLOAT
4.5Final Checks Before Commissioning
1)Re-check all equipment for any accidental damage caused during installation.
2)Carry out the pre-charging and venting procedures described next.
4.6Pressure Vessel Pre-Charging
Figure 4.8:Pressure Vessel Pre-charge
132456789
12
FAILED SIGNAL
FROM INVERTERS
3245678 910
If installing a Dutypoint FS-series float switch,
the following terminals should be used:
BROWN: Terminal 1
BLACK: Terminal 2
BLUE: Not used - terminate safely
Required Pressure (bar)
Before commissioning starts the pre-charge of the pressure vessels should be checked.
On variable speed systems the pre-charge air pressure for vessels should be 90% of the maximum pressure
generated by the pump in the pipework system
e.g: If the maximum pressure generated by the pump in a system is 6 bar, this will require a pre-charge
pressure of 6 × 90% = 5.4 bar.
To verify the pre-charge pressure:
1)First check that the expansion or pressure vessel(s) are totally drained of water, and that the system
is switched off and no electrical parts are live.
2)Locate the charging valve on each vessel, accessed by removing the plastic cover on the top of the
vessel
3)Connect a portable pressure gauge with a measuring range compatible with the expected pressures
in your application, which has a flexible hose and Schrader-type connector to the charging valve.
4)Check the pre-charge pressure above the diaphragm in each pressure vessel correspond to criteria
given in the text above.
5)If necessary, release or add additional air to correct.
4.7Venting Pumps
It is important to bleed all air from the pump body before initial start-up.
Pre-Charge Pressure (bar)
18
4.8Procedure for flooded suction
Flooded Suction is defined as the condition where there is positive pressure on the suction (inlet) side of the
pump(s) as is the case where the storage tank water level is at the same or higher level than the pump bleed
point.
This procedure should be carried out individually for each pump in the pump set.
1)Open all valves on the suction (inlet) side of the pump.
2)Using the vent screw at the top of the pump (refer to Appendix to locate), allow any air in the pump
body and suction pipework to vent to atmosphere.
3)When water (under pressure from the storage tank feeding the pump on the suction side) escapes
through the vent screw hole - and no more air bubbles can be seen - close the vent screw.
4)Switch on the electrical supply to the pump motor and start the pump in AUTO mode. As each motor
starts verify that the direction of rotation correctly corresponds with the direction of the arrow shown
on the body of the pump. If rotation is backward STOP, switch off the pump and investigate.
5)Slowly open the valve on the discharge manifold outlet to the system allowing water to be pumped
into the system.
6)Switch off, re-close the discharge valve and repeat steps 3 to 6 several times to ensure that all air is
released from the pump body and local pipework.
The above procedure should be carried out individually for each pump in the pump set.
4. Booster Set Commissioning
4.9Procedure for Lift Suction
Lift Suction is defined where the water storage tank is at a lower level than the pump set. In this case a
negative pressure condition may exist at the pump suction.
NOTE: The "Lift Suction" mode of operation requires specific venting procedures. Please call
Dutypoint Systems Technical Support on +44 (0)1452 300590 for advice before
attempting to vent the pump(s).
The advised procedure should then be carried out individually for each pump in the pump set.
4.10Programming the Controller
Dutypoint Systems fit a design of Inverter/Controller that is most suitable for the design duty of the pump
set.
Manufacturer’s information for them is detailed in the Appendices to this manual.
Carefully follow the appropriate step-by-step setting-up procedures contained in the manual, ensuring that
any data required to be entered by the end user is accurately inserted where requested.
If in doubt please call Dutypoint Systems Technical Support on 01452 300590 for advice.
4.11Operation and Performance Tests
Having checked that the pump set is installed, pre-charged, vented in accordance with the procedures set
out earlier, carry out the following running tests before handing over the pump set for operational use.
1)Run each pump by selecting HAND (Manual) control.
2)Re-select to AUTO mode.
3)Create the conditions for a normal start and run and allow the selected ‘Duty’ pump to run. Whilst
running observe the pressure values. Verify the pump motor speeds up / slows down in accordance
with the desired control philosophy.
4.12Duty/Standby Twin Pump Sets
1)On Duty/Standby sets, wait for a normal stop to take place (or create the conditions where this would
happen) and check that the ‘Duty’ pump stops. Whilst stopped simulate a fault by inhibiting the
‘Duty’ pump and then recreate the conditions for a normal start to take place. Check that the
19
4. Booster Set Commissioning
‘Standby’ Pump now starts and runs in place of the inhibited ‘Duty’ pump and observe the pressure
values. Verify that the pump motor speeds up / slows down in accordance with the desired control
philosophy.
2)Wait for a normal stop to take place (or create the conditions where this would happen) and check
the ‘Standby’ pump stops. Whilst stopped undo the inhibit to the ‘Duty’ pump which should now
return to normal.
4.13Duty/Assist Twin Pump Sets
1)For ‘Duty/Assist’ applications, run the system up to pressure using the ‘Duty’ Pump only, then deliberately create the condition(s) which will require the ‘Assist’ Pump to operate as well. (e.g: open taps
to reduce the pressure in the system to a point where one pump only cannot maintain the required
output. Verify that the ‘Assist’ Pump starts and runs together with the ‘Duty’ Pump and that the
desired pressure is duly restored and maintained.
2)Close the taps again (thereby reducing the demand) and check the ‘Assist’ Pump slows down and
stops, allowing the ‘Duty’ Pump to continue on its own.
4.14Commissioning/Handover Check
1)Record any indicated voltage / amperage / pressure data / controller passwords for future reference.
2)Re-check all isolating valves are fully open and replace any cover(s).
3)With all the isolators ON and the switches and/or control programs set to AUTO, the pump set is now
fully operational in automatic control mode.
NOTE: No manual operation or attendance is required other than for routine servicing and
maintenance checks. Other than for maintenance purposes, the supply to the Controller(s)
and the Pump motor(s) should never be switched off.
20
5.Operating the Pump Set
5.1VASCO Display
The display screen on the VASCO is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated
by an audible signal.
Figure 5.9:VASCO Control Panel
STOP Motor
5. Operating the Pump Set
Enter
START Motor
Scroll Up/Down
Figure 5.10:Display shown when first powering VASCO
Release of display software
Release of inverter software
NOTE: One pump/VASCO combination will have been set as master (display name 00) and
others as slaves (e.g. display name 01). The term “INV:” will be replaced by the appropriate
display name, “00:” or “01:” etc. Various messages are then displayed.
The first row of the display gives the pump status as follows:
–Inv: ON XXX.X Hz - VASCO is powered and is powering the motor, showing its frequency
–Inv: ON Mot: OFF - VASCO is powered but motor is not running (i.e. motor/pump was stopped due to
minimum frequency being reached).
–Inv: OFF Mot: OFF - VASCO is not powered.
The following end user messages are displayed on the second row by pushing the scroll buttons:
Table 5.8:VASCO End User Messages
Inv: ON/OFF Mot: ON/OFF
p = XX.X [bar]
Inv: ON/OFF Mot: ON/OFF
f = XXX [Hz]
Inv: ON/OFF Mot: ON/OFF
V_in = XX.X [V] I=XX.X
Inv: ON/OFF Mot: ON/OFF
cosphi = XXX
Inv: ON/OFF Mot: ON/OFF
P = XXXXX [W]
p is the pressure value read by the pressure transducer. By pressing ENTER the
pressure set vale is displayed
f value is the supply frequency to the motor. On fox frequency control mode, by
pressing ENTER you can change the f value manually (word “set” is displayed),
press ENTER again to exit parameter setting (word “set” disappears).
V_in is the line voltage. This value is displayed only if motor is OFF. If motor is
NO, A value equal to the absorbed motor current.
cosphi index means the angle phi between the voltage and current absorbed
by the motor
P is the power in Watts supplied to the pump
21
5. Operating the Pump Set
Inv: ON/OFF Mot: ON/OFF
STATUS: NORMAL
Inverter Life
xxxxx h : xx m
Motor Life
p = XX.X [bar]
%f 25 50 75 100
%h XX XX XX XX
XXXXXXXXXXXXXXX
XXXXXXXX h : XX m
NORMAL status means no alarms. If an alarm occurs, a message blinks on the
display and an audible signal is activated.
Pressing ENTER accesses: VASCO lifetime, PUMP lifetime, consumption
statistic, alarm list.
To return to previous views, press ENTER.
WARNING: ADVANCED PARAMETERS. IMPROPER SETTINGS CAN COMPROMISE THE
INTEGRITY AND LIFE OF THE CONTROLLER AND PUMP
–You should only access and adjust parameters if you are trained to do so
–All full description of the advanced parameters is available in the appendix of this manual
–For further assistance, call the Dutypoint Technical Service line of 01452 300590.
Pressing ENTER when you are in the initial display will show the following menus:
Table 5.9:VASCO Menus
MENU’
Motor param.
MENU’
Control. param.
MENU’
IN/OUT. param.
MENU’
Connect. param.
MENU’
Change init.set. param.
Installer password required to enter level 1 (default 001)
Advanced password required to enter level 2 (default 002)
Installer password required to enter level 1 (default 001)
Installer password required to enter level 2 (default 001)
Advanced password required to enter level 2 (default 002)
To exit the Menu level and return to the initial display, press STOP button.
For full details on the VASCO controller see 11
. VASCO V209 and V214 Pump Controllers.
22
6.Pressure Vessel
The pressure vessel supplied as part of your Dutypoint product is used to absorb and
conserve the potential energy of pressurised liquid. Stored energy from liquid under
pressure is transferred to the water system when required.
6.1Installation Safety Notes
These notes are taken from the pressure vessel installation manual:
–This product is designed to hold water up to +110°C
–Never exceed the maximum working pressure and temperature of the expansion tank; ensure
appropriate controls are installed for this purpose.
–During installation prepare adequate systems for drainage to limit damage caused by leakage from
the tank, draining and venting.
–During installation the installer should account for external stress such as traffic, wind and
earthquakes.
–Always install the appliance in conformity to current legislation.
–This product must be installed and regularly inspected by qualified personnel only.
–The manufacturer shall not be held liable for any personal or material damage caused by the product
if installed and/or used improperly or in way anyhow diversely from manufacturer’s specifications.
–Exceeding temperature and pressure limits specified by the manufacturer will give cause to cancel
any guarantee covering the product as well as any manufacturer’s liability.
–For fluids other than water, check compatibility before installing.
–The appliance must be installed in a safe place with access for authorized personnel only.
–The appliance must be protected by an appropriate earthing systems or isolated from the system by
a dielectric joint.
6. Pressure Vessel
6.2Periodic Maintenance
Periodic maintenance is recommended at least twice a year and should be carried out by authorised
specialised personnel only.
1)First check that the expansion or pressure tank is totally drained of water, and that the system is
switched off and no electrical parts are live.
2)Check and, if necessary reset the pre-charge pressure, using the instruction in 4.6 Pressure Vessel
Pre-Charging. Ensure that the pressure does not exceed the value specified in the procedure.
6.3General Maintenance and Repair
Disconnect all electrical equipment before starting on any maintenance jobs or checking the installation
pressure and temperature. The pre-charge pressure should be checked and if necessary corrected during any
maintenance work.
6.4Pressure Vessel Pre-Charge Instructions
1)First check that the expansion or pressure tank is totally drained of water, and that the system is
switched off and no electrical parts are live.
2)Refer to Figure 6.11: Pre-Charging a Pressure Vessel. Remove the air vent cover.
3)Unscrew the air valve cap.
4)Connect a pressure gauge. Verify that the pre-charge pressure is correct. If it is low then the vessel
pre-charge must be corrected by additional inflation of the diaphragm.
5)When the pre-charge pressure is correct replace the air valve cap and vent cover.
23
6. Pressure Vessel
Figure 6.11:Pre-Charging a Pressure Vessel
6.5Diaphragm Replacement
To replace a diaphragm:
1)Empty the expansion tank
2)Remove the pre-charging by releasing the air vent.
3)Loosen the M8 screws fastening the flange
4)Remove the flange
5)Extract the diaphragm and replace it
2
3
4
6.6Installing a Replacement Vessel
Read these instructions carefully before installing the product:
1)Make sure the product is in good condition. If the product is damaged do not start on installation but
take it back to the seller for immediate replacement.
2)The product must be installed in the position (vertical or horizontal) specified in the technical
specifications.
3)While the system is cold, measure the static pressure with a gauge, at the point where the tank has
to be installed.
4)Set the pre-charge pressure, using the procedure earlier in this section. Ensure that the pressure does
not exceed the value specified in the procedure.
5)The appliance must be supplied with efficient and sufficient safety and control facilities, in particular
the safety valve must be connected to the appliance and be free from interference and must be
gauged to the quantity of fluid to be discharged. The safety valve should also be designed to ensure
that the pressure does not permanently exceed the maximum tolerated pressure (a temporary
pressure peak, limited to 10% of the maximum tolerated pressure, is allowed).
6)Make sure the cap of the valve is fitted tightly after pre-loading and that there is no leakage.
24
7.Booster Set User Maintenance
Routine user maintenance for Dutypoint pump sets.
Dutypoint pump sets have been designed to keep major maintenance requirements to a minimum. Planned
maintenance of the pumps and other principal components should therefore be undertaken at the intervals
recommended in the manuals referenced below.
It is essential that a full test following the Pre-Commissioning procedure on is carried out on an annual basis.
In addition, the operator in charge should routinely make visual checks of the equipment during use, noting
particularly any unusual noises or vibrations. This will give an immediate indication of any irregularity in the
operation of the system.
DANGER!
Do not commence any work until:
–You have read 1. Important Safety Information
–You have the appropriate personal protective equipment
–You have all necessary safety equipment to hand
7. Booster Set User Maintenance
Refer to the appropriate manufacturer’s information that is provided in the appendices of this manual for
the equipment being serviced.
Table 7.10:Periodic User Checks for Pump Sets
TimingChecks
Weekly1)Visually check the complete pump set
2)Observe the running of the pump(s) and note any unusual vibrations or sounds.
Quarterly1)Visually check the complete pump set
2)Observe the running of the pump(s) and note any unusual vibration, etc.
3)Check the cooling fan and vents on the Control Unit(s) and clear any dust or
other obstructions
4)Operate each manual isolating valve three times to ensure continued efficient
working
6-monthlyThe pressure vessel should be drained and the pre-charge pressure checked. See
6.4 Pressure Vessel Pre-Charge Instructions for more details.
12-monthly
(essential)
Carry out the full pre-commissioning procedure to verify safe operation - see 4.
Booster Set Commissioning.
25
7. Booster Set User Maintenance
26
8. XPW Pump Maintenance
8.XPW Pump Maintenance
The following information is an extract from the pump manufacturer’s documentation.
8.1Routine Maintenance
The pump requires no detailed maintenance except to:
–Periodically verify that the suction grate is clear
–Periodically with the power off, check the condition of the cables and electrical power and earth
connections.
8.2Pump Replacement
DANGER!
Risk of electric shock
–Before beginning any work on the pump you must isolate the electrical supply and make sure that it cannot be
accidentally reconnected.
–Wait for a further 2 minutes for the internal circuitry to discharge BEFORE opening or working with any electrical
connections.
–It is the installer’s responsibility to ensure that the installation is in compliance with local regulations and all
electrical guidelines.
WARNING
Electrical pumps should never be used outside the limitations described in the technical specifications
–Replacement pumps should remain in their original packaging until installation.
8.3Replacement Procedure
1)Before installation, check the new pump and verify its integrity and that it is the correct type/rating.
Contact the supplier if there are any anomalies.
2)Locate the 4× plastic screw covers protecting the M6 screws securing the tank lid. Remove the covers
and screws and lift off the tank lid to access the old pump.
3)Disconnect the pump pipework.
4)Disconnect the pump electrical cable, noting the cable colour coding.
5)Insert the replacement pump into the tank and reconnect the pipework.
6)Feed the pump cable through the watertight glands and make the electrical connections to the
controller as noted in step 4 above, verifying that the earth connection is securely made.
7)Fix the power cable to the delivery pipe using suitable strap.
8)Replace the covers on the controller.
9)Test the system, checking rotation direction (see below).
10)When testing is complete, replace the tank lid and screw it down, refitting the plastic caps
WARNING: EXCESSIVE FORCE CAN DAMAGE EQUIPMENT
–To avoid damage, do not use excessive force when screwing the pipe to the pump discharge outlet.
27
8. XPW Pump Maintenance
8.4Checking the Direction of Rotation
NOTE: This operation will be performed dry and must not last more than a few seconds.
If the direction of rotation is reversed due to incorrect connection or controller programming, the pump
performance will be significantly lower than the nominal values. To verify a correct connection, proceed as
follows:
1)Start the electrical pump before it is submerged. Correct rotation is in a counter- clockwise direction
as viewed from above.
2)With the pump operating, installed and submerged, use a clamp meter to measure the current. If the
rotation is reversed, you will see values about double those indicated on the name plate.
3)Correct before using the system.
28
9.Pressure Set Point Adjustment
Note: This procedure should only be undertaken by an experienced and qualified installer
or engineer. Failure to follow the procedure correctly may cause damage to the product
and invalidate any product warranty. The installer is responsible for ensuring that the
required value is suitable for the product. Check the appropriate pump curves prior to
adjustment.
1)Press STOP button (red)
2)Press the down arrow until you see ‘MENU / ENT TO ACCESS’ then press the ENTER button. Refer to
Figure 5.9: VASCO Control Panel.
3)You will open the ‘INSTALLER PARAMETERS’ or ‘CONTROL PARAMETERS’ menu (depending on model).
Press the ENTER button again.
4)You will be promoted to enter the password. Press ENTER again until the last zero flashes, then press
the up arrow to show a ‘1’ - the default password is 001. Press ENTER again.
5)Press the DOWN arrow until you see ‘SET VALUE’, then press ENTER again.
6)Use the UP and DOWN arrows to adjust the pressure to the required value.
7)Press ENTER to save the value then:.
–Single pump models: press the RED STOP button three times to return to HOME screen, then
press GREEN START button
–Multi-pump models: press the RED STOP button twice, then ENTER to transfer settings to the
SLAVE inverter(s)
9. Pressure Set Point Adjustment
8)Follow the instructions to adjust the pressure vessel pre-charge to suit the new required value - see
6.4 Pressure Vessel Pre-Charge Instructions.
29
9. Pressure Set Point Adjustment
30
10. Troubleshooting
10.Troubleshooting
Troubleshooting VASCO-equipped booster sets. The information in this section is common
to all VASCO-equipped Dutypoint booster sets. For more detailed troubleshooting
information that is specific to the type and model of pump controller used, please refer to
the manufacturer’s literature in the Appendix.
WHEN A FAULT FIRST OCCURS:
–Turn off the main power to the pump set and leave off for 1 minute
–Switching power back on and re-energising the system may be sufficient to clear the fault
WARNING: IF PUMP COSPHI IS LOWER THAT THE DRY-RUNNING COSPHI FOR AS LEAST
2 SECONDS, VASCO WILL STOP THE PUMP. VASCO WILL TRY TO RUN THE PUMP AT 10,
20, 40, 80 AND 160 MINUTES, THEN THE PUMP WILL STOP. IF DRY RUNNING
PROTECTION OCCURS, VASCO WILL ATTEMPT TO START THE PUMP AUTOMATICALLY
–Cut the power supply before performing any maintenance
–VASCO will stop the pump if the input motor current is higher than the set motor current for an extended time.
By pressing the START button it is possible to run the pump again.
–VASCO will stop the pump if the input voltage is higher than the set voltage for an extended time. By pressing
the START button it is possible to run the pump again. VASCO will stop the pump if the input voltage is lower
than the set voltage for an extended time. By pressing the START button it is possible to run the pump again.
Table 10.11:Common Error Messages
Messag
ePossible Cause(s)Solutions
ACTIVE
DIG. IN. 1
ACTIVE
DIG. IN. 3
Digital input 1 contact
is opened - system
indicates ‘External
On/Off’
Digital input 3 contact
is opened - system
indicates ‘Low Water
Level’
1)Verify that an external signal (e.g. BMS) is set to deactivate
the pump set
2)The error should reset automatically when Digital Input 1
contact is closed
1)Check incoming mains pressure is as expected
2)Check water level in tank.
3)The error should reset automatically when Digital Input 3
contact is closed
31
10. Troubleshooting
Messag
e
NO
WATER(DRY RUN
COSPHI)
Possible Cause(s)Solutions
Minimum pressure
requirement not
reached within set
period
Air lock in pump1)Press the red STOP button on the inverter drive(s) to stop
No water in break tank 1)Check incoming mains pressure is as expected;
1)Turn off main electrical isolator
2)Close discharge isolation valve
3)Vent pumps
4)Turn on main electrical isolator
5)Check unit runs up to set pressure and pump motors shut
down
6)Open discharge valve slowly ensuring set pressure is
maintained
the unit.
2)Disconnect the pump(s) by loosening the union directly
underneath the lid, above the pump discharge pipeline.
3)Lean/tilt the pump(s) over as far as possible to enable air to
escape.
4)Reconnect the pump union(s).
5)Press the green START buttons to resume normal operation.
6)Verify normal operation.
2)Check the water level in the tank.
Table 10.12:Fault Finding
ProblemsPossible CausesSolutions
Pump will
not start
Low (or zero)
output
discharge
rate
Pump
vibrates
and/or is
noisy
No electrical powerCheck and rectify
Blown fuseCheck and rectify
Overload trip/MCBCheck and (if necessary) reset the overload trip
value.
The rotating part(s) of the pump
is/are partially or completely
obstructed
e.g: impeller obstructed by foreign
matter
Pump not primed - WARNING:
running the pump ‘dry’ can cause
serious damage to the mechanical
seal.
Valve in suction pipework closed or
partially closed
Incorrect pump rotationCheck and rectify.
Pump is cavitatingIncrease the discharge back pressure slightly by
The rotating part(s) of the pump is
(are) partially or completely
obstructed.
e.g: impeller obstructed by foreign
matter.
Motor bearings wornCheck and rectify
Strip the pump to inspect and rectify
Having first checked the mechanical seal for
damage, prime and air-bleed the pump and try
again
Check all appropriate valves are fully open.
progressively closing a manual isolating valve on
the discharge side until the cavitation stops.
Strip the pump to inspect and rectify
32
ProblemsPossible CausesSolutions
Overload Trip Pipework or the pump chamber has
a partial blockage.
Momentary loss of one phase of
power supply
Discharge flow rate too highReduce the discharge flow rate by increasing the
Overload trip setting too low for
rated duty
Pump Runs
Continuously
Break Tank
Overflowing
(ScubaTANK
WX models
only)
Contact Dutypoint Service on 01452 300590
Solenoid valve jammed open due to
debris
Probe relay settings have been
adjusted
Loss of power to probe relaysCheck for the two green lights marked ‘Un’. If
Check and rectify
Check and try again
discharge back pressure slightly, progressively
closing a manual isolating valve on the
discharge side, then try again
Check and (if necessary) reset the overload trip
value
Clean the solenoid valve diaphragm by following
this procedure:
1)Press red STOP button(s) on inverter control
panel(s)
Figure 10.13: Correct Probe Relay Settings
(ScubaTANK WX Models Only) in the control
panel. Note: these settings should never
normally be adjusted. Only change them to
match the required settings shown.
either are not illuminated there is a problem
with the power supply to the probe relays.
Contact Dutypoint Technical Service on 01452
300590 for assistance.
Water level indicator: off
when water level is low
10.1Fault Codes: Advanced
WARNING
Improper settings can compromise the integrity and life of the controller and pump
–You should only access the Installer and Advanced menus if you are trained to do so;
–A full description of these is available in the Appendix to this manual;
70
Tt
Un
R
Sensitivity
Level
Tt
2
0.1
St
70
Tt
Un
R
–For further assistance, call the Dutypoint Technical Service line on 01452 300590.
Table 10.13:VASCO Controller Alarm Messages
MessageAlarm DescriptionPossible Solutions
OVERCURRENT
MOT.
Motor overload: input current of the
motor is higher than the rated motor
current setting parameter.
Motor voltage drop caused by the
inverter causes the motor input current
to be higher than rated. Contact motor
manufacturer to check if motor is
capable of accepting this current.
–Make sure that the motor current setting
parameter is higher than rated.
–Add 15% to the motor current setting
–Reset the inverter using the red STOP
button, then attempt to run the pump
system again.
34
MessageAlarm DescriptionPossible Solutions
NO WATER
(DRY RUN
COSPHI)
OVER TEMP.
INV.
NO
COMMUNICATI
ON
Motor cosphi is lower than the set
value of dry running cosphi
Inverter over temperature–Make sure than ambient temperature is
Communication between Master and
slave(s) has been interrupted
–Check pump is primed
–Check the set value of dry running cosphi.
Dry running cosphi is approximately 60%
of the rated cosphi (at rated frequency)
listed on the motor plate.
If pump’s cosphi is lower than the set
dry-running cosphi for at least 2 seconds, VASCO
stops the pump. VASCO will then attempt to run
the pump every 10, 20, 40, 80, 160 minutes and
then the pump is stopped.
Note: see dry running warning statement
Warning: if pump cosphi is lower that the
dry-running cosphi for as least 2 seconds, Vasco
will stop the pump. Vasco will try to run the
pump at 10, 20, 40, 80 and 160 minutes, then
the pump will stop. if dry running protection
occurs, Vasco will attempt to start the pump
automatically.
less than 40°C (104 °F).
–Check if auxiliary cooling fan is working
properly and if mounting space is
adequate for proper cooling.
–Reduce the PWM value (Advance
Parameter Menu)
–Check the wiring connections
–Make sure that Master is not in the menu
level. If so, exit from the menu level.
–In the STATUS of the slave (where alarm is
displayed). Try to reset the alarm by
pushing the STOP button.
–Check each inverter is addressed correctly:
a)Master = 00
b)Slave 1 = 01
10. Troubleshooting
c)Slave 2 = 02, etc.
MIN. VALUE
ALARM
IGBT TRIP
ALARM
OVER VOLTAGE Supply voltage too highCheck possible causes of over voltage
UNDER
VOLTAGE
ADDRESS
ERROR
ALARM SLAVE XXSlave XX error detected by masterCheck the status of the slave.
Measured value has reached the lowest
value accepted by the system.
The current drawn by the load exceeds
the capacity of VASCO. VASCO is still
able to continue to power the load for
10 minutes with an output current of
101% of nominal and for 1 minute
with an output current of 110% of
nominal
Supply voltage too lowCheck possible causes of under voltage
Same address as other VASCOs in the
group
–Check possible causes reaching minimum.
value (i.e. broken pipe, open pressure relief
valve, etc.)
–Check the minimum alarm value setting
–Increase the ramp-up time
–Make sure that the load current is at least
10% below the VASCO nominal current
–Check the voltage drop along the supply
cable to the motor
The address of each VASCO needs to be different.
35
10. Troubleshooting
MessageAlarm DescriptionPossible Solutions
SENSOR FAULT Sensor error–Check the pressure transducer
–Check the wiring of the transducer
NO LOADNo loadCheck is load is properly connected to VASCO
terminals
MAX. VALUE
ALARM
KEYBOARD
FAULT
ACTIVE
DIG.IN.X
Measured value has reached the
maximum value accepted by the
system.
A button on the keyboard has been
pressed for more than 150 seconds.
Digital input X opened/closedCheck the input digital configuration (IN/OUT
–Check possible causes of reaching
maximum value
–Check the max. alarm value setting
–Make sure buttons are not depressed.
–If problem persists, call Dutypoint
Technical Service on 01452 300590.
parameters menu)
36
11. VASCO V209 and V214 Pump Controllers
11.VASCO V209 and V214 Pump Controllers
11.1Introduction
VASCO is a variable frequency drive designed to control and protect pumping systems by varying the output
frequency to the pump. VASCO can be applied to both new and existing pumping systems, and provides:
–energy and cost savings
–simplified installation and an overall lower pumping system cost
–longer life of the pumping system and relevant components
–improved reliability
VASCO, when connected to any pump, manages the system operation to maintain a certain constant
physical quantity (pressure, differential pressure, flow, temperature, etc.) regardless of the conditions of use.
The pump is operated only when needed thus avoiding unnecessary energy consumption.
VASCO at the same time is able to:
–protect the motor from overload and dry running
–implement soft start and soft stop to increase the system life and reduce current peaks
–provide an indication of current consumption, voltage, and power
–maintain a record of run time and display any errors and/or failures reported by the system
–control up to two additional pumps at a constant speed (Direct On Line)
–connect to other VASCO units for combined operation
Through the use of inductive filters (optional) VASCO eliminates dangerous surges that are induced in long
cables, making VASCO suitable for control of submersible pumps.
11.2Important Safety Information
The manufacturer strongly suggests carefully reading this operation manual before using and installing its
products. Any operation (installation, maintenance and repair) must be carried out by trained, skilled, and
qualified personnel. Failure to observe and follow the instructions in this manual may result in dangerous
and potentially lethal electric shock. Pay attention to all standard safety and accident prevention
regulations
DANGER OF ELECTRIC SHOCK
–Disconnect VASCO from the main power supply before commencing any work.
–Do not remove, for any reason, the cover and the cable plate without having first disconnected the device from
the main power supply and having waited at least 5 minutes.
–VASCO and pumping system must be grounded properly before operation. For the entire period VASCO is
powered, high voltage is present on the output terminals of the inverter whether or not the pump is running.
–Tightening all screws on the cover with washers is recommended before powering the device. Otherwise, there
may be a failure to connect the cover to ground, creating the risk of electric shock or even death.
37
11. VASCO V209 and V214 Pump Controllers
WARNING
–The device must be connected to main power supply via a switch to ensure the complete disconnection from
the network before any operation on the VASCO itself (including visual inspection) and/or on the connected
load.
–Avoid any shock or significant impact during transport.
–Check the VASCO immediately upon delivery and check for damage and/or missing parts. If either occurs,
immediately notify the supplier.
–Damages due to transport, incorrect installation, or improper use of the device will null and void the warranty
–Tampering or disassembly of any component will automatically void the warranty.
NOTE: The manufacturer cannot be held responsible for any damages to people and/or
property due to improper use of its products.
11.3Technical Specifications
P2 motor
Vin ±15%
Model
V2091 × 230V1 × Vin1591.14
V2141 × Vin2091.14.3
[V]
Max V out
[V]
3 × Vin71.5
3 × Vin113
Max I in
[A]
Max I out
[A]
power
[kW]
Weight
[kg]
–Power frequency: 50-60 Hz (±2%)
–Max. ambient temperature at nominal current: 40°C (104°F)
–Max. altitude at nominal current: 1000 m
–Grade of protection: IP55
–RS485 serial communication
–auxiliary cooling fan of the VASCO, used in wall mounted applications, has a protection rating of IP54
–VASCO is able to power the motor with a higher current for a short period of time according to the
linear relation: 101% of the nominal current for 10min., 110% nominal current for 1 minute.
.
38
11.4Electrical Wiring
Figure 11.14: Electrical Wiring Board
11. VASCO V209 and V214 Pump Controllers
Power SupplyOutput
Line: L1, L2, GND3~ motor: GND, U, V, W
1~ motor: earth, U (running), V
(common)
It is recommended to use cable lugs
Fans (Wall Mounted
Installations)
Fan: F1, F2
39
11. VASCO V209 and V214 Pump Controllers
Figure 11.15: Recommended line and motor cables stripping
Figure 11.16: Control Board Wiring
Analog inputs (10 or 15 Vdc)–AN1: 4-20 mA: sensor 1
–AN2: 4-20 mA: sensor 2
–AN3: 4-20 mA / 0 - 10 Vdc (settable by jumper C.C.): external set
–AN4: 4-20 mA / 0 - 10 Vdc (settable by C.C.): trimmer for
frequency regulation / external set 2
Digital inputs:–IN1: motor start & stop
–IN2: value set 1 & 2 switching
–IN3: sensor 1 & 2 switching
–IN4: motor start & stop + alarms reset
–0V
We recommend using only no voltage contacts.Opening or closing the
digital contacts (depending on software configuration set (see IN/OUT).
40
Digital outputs:Motor run signal:
NO1, COM1: closed contact with motor running
NC1,COM1: closed contact with motor stopped
Alarm signal:
NO2,COM2: closed contact without alarm
NC2,COM2: closed contact with alarm or no power supply
DOL1 pump relay:
NO3,COM3: closed contact with DOL1 running
NC3,COM3: opened contact with DOL1 running
DOL2 pump relay:
NO4,COM4: closed contact with DOL2 running
NC4,COM4: opened contact with DOL2 running
Relays are no voltage contacts. Max. voltage to the contacts is 250V
with maximum current of 5A.
RS485 for combo–S1+
–S1–G
It is recommended to respect the polarity linking more VASCOs in
series.
RS485 for ModBus–S2+
–S2–G
It is recommended to respect the polarity
11. VASCO V209 and V214 Pump Controllers
WARNING
The protections required upstream each VASCOs depends on the type of installation, and local regulations.
–We recommend to use overload protection with the characteristic curve of type C and type B circuit breaker,
sensitive to both AC and DC current
11.5Electromagnetic Compliance
To ensure electromagnetic compatibility (EMC) of the system, it is necessary to apply the following
measures:
–Always connect the device to ground.
–Use shielded signal cables by placing the screen at one end.
–Use motor cable as short as possible (<1 m / <3 ft). For longer lengths, it is recommended to use
shielded cables connecting the screen at both ends
–Separate signal, motor, and power supply cables.
NOTE: To enable the restoration of the display screen when there are electromagnetic
interference, VASCO periodically provides some fast “refresh” of the display.
41
11. VASCO V209 and V214 Pump Controllers
11.6Motor Mounted Installation
Figure 11.17: Motor Mounted Installation
WARNING
–Make sure the manufacturer that the electric motor is suited for operation in the inverter
In this application VASCO is cooled by the motor fan. Motor kit (available upon request) allows a solid
coupling of the two units and it is composed of:
NOTE: Make sure to properly attach the grid of the auxiliary cooling fan
In this application VASCO is cooled independently by its auxiliary cooling fan integrated in the radiator. The
wall mounting kit is comprised of:
–n.° 1 auxiliary fan 230V AC (VASCO 209,214)
–n.° 4 screws to fix cooling fan
–n.° 1 protection grill
–n.° 1 metal bracket in AISI 304
–n.° 4 screws to fix VASCO to wall bracket
11.8Operation and Programming
Setting Parameters are organized in 2 levels:
1)Installer level (MENU’ CONTROL PARAMETERS, MENU’ IN/OUT PARAMETERS, MENU’ CONNECTIVITY
PARAM.) A password is required for this level (default 001)
2)Advanced level (MENU’ MOTOR PARAMETERS). A password is required for this level (default 002)
Installer and Advanced levels can be entered only with the correct password; otherwise, it is impossible to
set up and/or modify any parameters (they can be only displayed).
The display screen on the VASCO is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated
by an audible signal.
11. VASCO V209 and V214 Pump Controllers
Figure 11.19: VASCO Control Panel
STOP Motor
Enter
START Motor
Scroll Up/Down
Figure 11.20: Display shown when first powering VASCO
Release of display software
Release of inverter software
NOTE: One pump/VASCO combination will have been set as master (display name 00) and
others as slaves (e.g. display name 01). The term “INV:” will be replaced by the appropriate
display name, “00:” or “01:” etc. Various messages are then displayed.
The first row of the display gives the pump status as follows:
–Inv: ON XXX.X Hz - VASCO is powered and is powering the motor, showing its frequency
–Inv: ON Mot: OFF - VASCO is powered but motor is not running (i.e. motor/pump was stopped due to
minimum frequency being reached).
–Inv: OFF Mot: OFF - VASCO is not powered.
The following end user messages are displayed on the second row by pushing the scroll buttons:
43
11. VASCO V209 and V214 Pump Controllers
Table 11.14:VASCO End User Messages
Inv: ON/OFF Mot: ON/OFF
p = XX.X [bar]
Inv: ON/OFF Mot: ON/OFF
f = XXX [Hz]
Inv: ON/OFF Mot: ON/OFF
Vin = XX.X [V] I=XX.X
Inv: ON/OFF Mot: ON/OFF
cosphi = XXX
Inv: ON/OFF Mot: ON/OFF
P = XXXXX [W]
Inv: ON/OFF Mot: ON/OFF
STATUS: NORMAL
Inverter Life
xxxxx h : xx m
Motor Life
p = XX.X [bar]
%f 25 50 75 100
%h XX XX XX XX
XXXXXXXXXXXXXXX
XXXXXXXX h : XX m
p is the pressure value read by the pressure transducer. By pressing ENTER the
pressure set vale is displayed
f value is the supply frequency to the motor. On fox frequency control mode, by
pressing ENTER you can change the f value manually (word “set” is displayed),
press ENTER again to exit parameter setting (word “set” disappears).
Vin is the line voltage. This value is displayed only if motor is OFF. If motor is
NO, A value equal to the absorbed motor current.
cosphi index means the angle phi between the voltage and current absorbed
by the motor
P is the power in Watts supplied to the pump
NORMAL status means no alarms. If an alarm occurs, a message blinks on the
display and an audible signal is activated.
Pressing ENTER accesses: VASCO lifetime, PUMP lifetime, consumption
statistic, alarm list.
To return to previous views, press ENTER.
WARNING: ADVANCED PARAMETERS. IMPROPER SETTINGS CAN COMPROMISE THE
INTEGRITY AND LIFE OF THE CONTROLLER AND PUMP
–You should only access and adjust parameters if you are trained to do so
–For further assistance, call the Dutypoint Technical Service line of 01452 300590.
Pressing ENTER when you are in the initial display will show the following menus:
Table 11.15:VASCO Menus
MENU’
Motor param.
MENU’
Control. param.
MENU’
IN/OUT. param.
MENU’
Connect. param.
MENU’
Change init.set. param.
To exit the Menu level and return to the initial display, press STOP button.
Table 11.16:Initial Configuration
When VASCO is switched on for the first time, the initial setting menu is displayed for the initial setting of
parameters to configure pump characteristics, pressure sensor range, and system characteristics. If the
initial setting procedure is not completed properly, it is impossible to run the pump. Initial setting procedure
can be repeated if necessary. The initial setting procedure can be repeated (by using the 2rd level password)
Installer password required to enter level 1 (default 001)
Advanced password required to enter level 2 (default 002)
Installer password required to enter level 1 (default 001)
Installer password required to enter level 2 (default 001)
Advanced password required to enter level 2 (default 002)
44
to reconfigure VASCO or if VASCO is installed in a different system. A brief description of parameters and
their allowable ranges are listed below
ParameterDefaultDescription
Language
XXXXXXX
Unit
XXXXXXX
Motor Type
Single/three phase
Rated Motor Amp.
I = XX.X [A]
Rated Motor Freq
f = XXX [Hz]
11.9Control Modes
Mode NameDescriptionAbbreviation
Constant value (default) VASCO changes the pump speed to keep the set value
Fix speedVASCO feeds the pump at set frequency, so the pump speed
Const. value 2 setthe two values are selected by opening or closing the digital
Fix speed 2 valueFix speed 2 val: the two values are selected by opening or
External speedcontrol motor frequency by using analogical input AN4ES
11. VASCO V209 and V214 Pump Controllers
XXXXEnd user communication language
barUnit
Three
phase
XXRated current of the motor as per its nameplate indication increased by
50Rated frequency of the motor as per its nameplate.
Type of motor connected
10%. The voltage drop caused by the inverter leads to higher input current
than nominal. Make sure the motor is capable of accepting the increased
current.
CV
constant regardless water demand
FS
is kept constant
CV2
input IN2
FS2
closing the digital input IN2
11.10Parameters
Table 11.17:Control Parameters
ParameterDefaultDescription
Max alarm value
XXX.X [bar]
Min alarm value
XXX.X [bar]
Ext. set enabling
ON/OFF
Set value
XXX.X [bar]
10Maximum value allowed in the system. If the
readen value goes over this value, an alarm
occurs and the pump is stopped. Pump is
automatically restarted if the readen value goes
below the maximum value for a period of at least
5 seconds.
0Minimum value allowed in the system. If the
readen value goes lower than this value, an alarm
occurs and the pump is stopped. Pump is
automatically restarted if the readen value goes
higher than the minimum value for a period of at
least 5 seconds.
OFFEnabling of set value changing by analogue input
AN3.
3Set value to be kept constant✓
Control Mode
C
V FS CV2 FS2 ES
✓✓✓✓✓
✓✓✓✓✓
✓✓
45
11. VASCO V209 and V214 Pump Controllers
ParameterDefaultDescription
Compensation
XXX.X [bar]
Set value 2
XXX.X [bar]
Compensation 2
XXX.X [bar]
Set value update
XX [s]
Operating freq.
XXX [Hz}
Operating freq 2
XXX [Hz}
Freq min control
XXX [Hz}
Stop delay
XX [s]
Control ramp
XXX.X [s]
Delta control
XXX.X [bar]
Delta start
XXX.X [bar]
Delta stop
XXX.X [bar]
KiKp and Ki parameters allow the dynamic control
Kp
Pump DOL 1
ON/OFF
Pump DOL 2
ON/OFF
COMBO
ON/OFF
Address
XX
Alternance
ON/OFF
Alternance
period.
ON/OFF
Control Mode
C
V FS CV2 FS2 ES
0Value compensation at the maximum frequency
for each pump. Acting on the green button you
can reverse the sign
3Set value to be kept constant✓
0Value compensation at the maximum frequency
for each pump. Acting on the green button you
can reverse the sign
5Time to update set value for compensation.✓✓
50Frequency value to feed the pump.✓
50Frequency value to feed the pump.✓
50Minimum frequency below which the pump tries
to stop
5Delay for which the pump tries to stop below
freq.min.control
20Ramp time from freq.min.control to min.motor
freq. If, during this time, the read value goes
below the (set value - delta control), VASCO
powers the motor again; otherwise, VASCO will
stop the pump
0.1Value drop below the set value required to restart
the pump during control ramp
0.5Value drop below the set value required to start
the pump from stop condition
0.5Value increase respect to set value which must be
passed so that there is a forced shutdown of the
pump
of system by VASCO; set values (Ki=50, Kp=005)
are usually enough to get a valid dynamic control.
OFFFunction to activate (ON) the first auxiliary pump
DOL 1 (Direct On Line pump)
OFFFunction to activate (ON) the second auxiliary
pump DOL 2 (Direct On Line pump).
OFFEnabling or disabling COMBO operation as
described in COMBO chapter
00VASCO address:
–00 master
–01 to 07 slaves
OFFFunction to allow alternating between the
VASCOs connected in COMBO (or pumps
connected in DOL) in order to allow equal use of
each pump in the group; master will reorganize
the starting priority of the pumps by checking the
life of each of them
0Maximum difference in terms of hours between
VASCOs in the group. 0 stays for 5 minutes
✓
✓
✓✓✓
✓✓✓
✓✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
✓✓
46
11. VASCO V209 and V214 Pump Controllers
ParameterDefaultDescription
Start delay AUX.
t = XX [s]
PI control.
Direct/Reverse
Periodic autorun
t = XX [s]
Dry run cosphi
X.XX
Restarts delay
XX [min]
0Delay time with which the slaves start after the
variable speed pump has reached the maximum
frequency and the pressure value has fallen
below set value – delta control
DirectDirect: increasing motor speed also measured
value increasesReverse: increasing motor speed,
measured value decreases.
0Pump periodic autorun after XX hours of
inactivity. Value 0 makes function
disabled.Warning, review the advice in chapter 1
0.65Cosphi value below which the unit stops the
motor and give “no water” alarm
10Restart delay after a dry running alarm. At each
tentative (max 5) restart delay will be doubled
Table 11.18:Motor Parameters
ParametersDefaultDescription
Rated motor Volt.
XXX [V]
Voltage boost
XX.X [%]
Rated motor amp.
XX.X [A]
Rated motor freq
XXX [Hz]
Max motor freq.
XXX [Hz]
Min motor freq.
XXX [Hz]
Ramp up time
XXX.X [sec]
Ramp down time
XXX.X [sec]
Ramp f min mot.
XXX.X [sec]
PWNM
XX.X [kHz]
XXXMotor rated voltage (as shown on motor nameplate).
0%Voltage increase during the motor start up. Warning: An excessive value
can seriously damage the motor. Contact the motor manufacturer for
further information
XXRated motor current as per its nameplate indication increased by 5%.
50Rated motor frequency as per its nameplate
50Maximum motor frequency. Note: by reducing the maximum motor
frequency, maximum current will be reduced as well
20Minimum motor frequency
4Ramp-up time to reach the speed required to achieve the set pressure (or
frequency value). Longer times delay the system reaching the preset value
but better protect system components. Excessively long ramp-up times
can create difficulties in VASCO setup, and can also cause false overload
alarms.
4Ramp-down time to reach zero speed. Longer times keep the system
pressurized, while protecting the system components. Excessively long
ramp-down times can create difficulties in VASCO setup. Excessively short
ramp-down times can cause false overload alarms
1.5Time to reach the minimum motor frequency and vice versa
8Carrier frequency (switching frequency). It is possible to choose PWM in
the range of 2.5, 4, 6, 8, 10 kHz
Higher values give a more sinusoidal wave with fewer losses for the motor
but higher losses for the inverter (increased inverter heating). If long
cables are used (>20 m / >76 ft) (submersible pump) it is recommended to
install an inductive filter between VASCO and the motor (available upon
request) and to set the value of PWM to 2.5 kHz.
This reduces the risk of voltage spikes, which can damage motor and cable
insulation.
Control Mode
C
V FS CV2 FS2 ES
✓✓
✓✓
✓✓✓✓✓
✓✓✓✓✓
✓✓✓✓✓
47
11. VASCO V209 and V214 Pump Controllers
ParametersDefaultDescription
F/f lin --> quad.
XXX [%]
Rotation sense
--> / <--
Autorestart
ON/OFF
Table 11.19:IN/OUT Parameters
ParameterDefaultDescription
Unit
XXXXX
F. scale sensor
XXX.X
Min value sensor
XXX.X
Offset input 1
[%]
Offset input 2
[%]
Offset input 3
[%]
Offset input 4
[%]
AN1,AN2 function
XXXXXX
Digital input 1
N.O./N.C.
Digital input 2
N.O./N.C.
Digital input 3
N.O./N.C.
Digital input 4
N.O./N.C.
Dig.In2/3 delay
[s]
85%V / f characteristic with which VASCO feeds the engine. The linear
characteristic corresponds to constant torque with variable speed. The
quadratic characteristic is normally used with centrifugal pumps. The
selection of torque characteristic should be done ensuring a smooth
operation, a reduction of energy consumption and a lower level of heat and
acoustic noise.
-->If, during the test, the motor runs in reverse, it is possible to change the
wiring sequence via software without physically changing wires at the
terminals.
OFFIf ON is selected, after a lack of voltage, VASCO returns to its normal status;
if VASCO was powering the pump before the voltage drop, it resumes
powering the pump automatically.
Warning: review the safety information earlier in this chapter.
N.O.By selecting N.O. (normally open) VASCO runs the motor if the digital
N.O.By selecting N.O. (normally open) VASCO runs the motor if the digital
N.O.By selecting N.O. (normally open) VASCO runs the motor if the digital
N.O.By selecting N.O. (normally open) VASCO runs the motor if the digital
3Digital input IN2 & IN3 delay
Function logic for analogue input AN1,AN2 (independent, lower value,
higher value, difference 1-2)
input 1 is open; motor will be stopped if the digital input 1 is closed
By selecting N.C. (normally closed) VASCO runs the motor if the digital
input 1 is closed; motor will be stopped if the digital input 1 is opened
input 2 is open; motor will be stopped if the digital input 1 is closed
By selecting N.C. (normally closed) VASCO runs the motor if the digital
input 2 is closed; motor will be stopped if the digital input 1 is opened
input 3 is open; motor will be stopped if the digital input 1 is closed
By selecting N.C. (normally closed) VASCO runs the motor if the digital
input 3 is closed; motor will be stopped if the digital input 1 is opened
input 4 is open; motor will be stopped if the digital input 1 is closed
By selecting N.C. (normally closed) VASCO runs the motor if the digital
input 4 is closed; motor will be stopped if the digital input 1 is opened
Digital input IN1 has 1 second fix delay
48
Table 11.20:Connectivity Parameters
ParametersDefaultDescription
MODBUS address
XXX
MODBUS baudrate
XXXXX [bps]
MODBUS data format
XXXXX
11.11Protections and Alarms
Any time a protection occurs a blinking message is displayed together with an audible alarm; on STATUS in
the initial view, the protection is displayed; by pressing the STOP button. Only from this position (STATUS)
in the initial view is it possible to try to reset the alarm; if VASCO does not reset the alarm it is displayed
again together an audible sound.
Alarm MessageAlarm DescriptionPossible Solutions
OVERCURRENT MOT. Motor overload: input current of the
UNDER VOLTAGESupply voltage too lowCheck possible causes of undervoltage
OVER VOLTAGESupply voltage too highCheck possible causes of overvoltage
OVER TEMP. INV.Inverter over temperature–Make sure than ambient temperature
NO LOADNo loadCheck if load is properly connected to the
NO WATER
(DRY RUN COSPHI)
SENSOR FAULTSensor error–Check the transducer
1MODBUS address from 1 to 247
9600MODBUS baudrate from 1200 bps
RTU N81MODBUS data format: RTU N81,
motor is higher than the rated
motor current setting parameter.
Motor voltage drop caused by the
inverter causes the motor input
current to be higher than rated.
Contact motor manufacturer to
check if motor is capable of
accepting this current
Motor cosphi is lower than the set
value of dry running cosphi
11. VASCO V209 and V214 Pump Controllers
to 57600 bps
RTU N82, RTU E81, ETU O81
–Make sure that the motor current
setting parameter is higher than rated
–Check other possible causes of over
current
is less than 40 °C (104 °F).
–Check if auxiliary cooling fan is working
properly and if mounting space is
adequate for proper cooling
–Reduce the PWM value (Advance
Parameter Menu)
VASCO terminals
–Check that the pump is primed
–Check the set value of dry running
cosphi. Dry running cosphi is
approximately 60% of the rated cosphi
(at rated frequency) listed on the motor
plate
If pump’s cosphi is lower than the set
dry-running cosphi for at least 2 seconds,
VASCO stops the pump. VASCO tries to run the
pump every 10, 20, 40, 80, 160 minutes and
then the pump is stopped
WARNING: if dry running protection occurs,
VASCO will try to start the pump
automatically. Be sure to cut power supply to
VASCO before performing any maintenance.
–Check the wiring of the transducer
49
11. VASCO V209 and V214 Pump Controllers
Alarm MessageAlarm DescriptionPossible Solutions
MAX. VALUE ALARMMeasured value has reached the
MIN. VALUE ALARMMeasured value has reached the
IGBT TRIP ALARMThe current drawn by the load
NO COMMUNICATION Communication between Master
ADDRESS ERRORSame address as other VASCOs in
KEYBOARD FAULTA Button on the keyboard has been
ACTIVE DIG.IN.XDigital input X opened /closedCheck the input digital configuration (IN/OUT
ALARM SLAVE XXslave XX error detected by masterCheck the status of the slave
maximum value accepted by the
system
lowest value accepted by the
system
exceeds the capacity of VASCO.
VASCO is still able to continue to
power the load for 10 minutes with
an output current of 101% of
nominal and for 1 minute with an
output current of 110% of nominal
and slave(s) has been interrupted
the group
pressed for more than 150 seconds
–Check possible causes of reaching max
value
–Check the max alarm value setting
–Check possible causes reaching min
value (i.e. broken pipe, open pressure
relief valve, etc.)
–Check the min alarm value setting
–Increase the ramp-up time
–Make sure that the load current is at
least 10% below the VASCO nominal
current
–Check the voltage drop along the
supply cable to the motor
–Check the wiring connections
–Make sure the Master is not in the
Menu level; if so, exit from the level
–In the STATUS of the slave (where the
alarm is displayed) try to reset the
alarm by pushing STOP button
The address of each VASCO needs to be
different
–Make sure buttons are not depressed
–Call service assistance
Parameters menu)
11.12Dry Running
DANGER
If dry running protection occurs, VASCO will attempt to start the pump automatically.
–Be sure to cut power before attempting maintenance
NOTE: If the pump’s cosphi is lower than the dry-running cosphi for at least 2 seconds,
VASCO will stop the pump. VASCO will try to run the pump every 10, 20, 40, 80, 160
minutes and then the pump is stopped
VASCO will stop the pump if the input motor current is higher than the set motor current
for an extended time. By pressing the START button it is possible to run the pump again.
VASCO will stop the pump if the input voltage is higher than the set voltage for an
extended time. By pressing the START button it is possible to run the pump again. VASCO
will stop the pump if the input voltage is lower than the set voltage for an extended time.
By pressing the START button it is possible to run the pump again.
11.13COMBO Function (Systems with multiple pumps)
In the “Control parameters” menu it is possible to enable the COMBO function that allows serial
communication between up to 8 VASCOs, each one connected to a pump.
To achieve the COMBO function in a system consisting of several interconnected VASCOs, a pressure sensor
is connected to each VASCO. The value of the set pressure is communicated to the slaves via the serial port
50
11. VASCO V209 and V214 Pump Controllers
Figure 11.21: RS485 Serial Communication
VASCO’s communication is made through a private protocol using the RS485 port. Each VASCO must be
connected to each other by using a tripolar cable (0.5 mm2) wired on S+,S-,G pins on control board.
11.14Master Setup
1)Supply power to the VASCO inverter
2)If not yet completed, perform the initial configuration - see Table 1.3: Initial Configuration
3)Initial view is shown:
4)Scroll until:
5)Press ENT:
6)Press ENT
7)Insert password (default 001).
8)Scroll until:
MASTER: address 00
Inv: ON/OFF Mot: ON/OFF
p_mis=XX.X [bar]
Menu
ENT to access
Menu
Control param.
SLAVE 1: address 01
SLAVE 2: address 02
9)Set ON
10)Set:
11)Press STOP (red button)
12)Press STOP again
11.15Slave Setup
Follow master setup until point 11.
COMBO
ON/OFF
Address
xx
Alternance
ON/OFF
Start delay AUX
t = XX [s]
00VASCO’s address in parallel operation
–00: VASCO master
OFF Function to allow alternating between the VASCOs connected in parallel
in orderto allow equal use of each pump in the group; in this way Master
will reorganizethe starting priority of the pumps by checking the life of
each of them.
0Delay time with which the slaves start after the variable speed pump has
reachedthe maximum frequency and the pressure value has fallen below
set value – deltacontrol.
51
11. VASCO V209 and V214 Pump Controllers
NOTE: In case of failure of master in a Combo system, will be replaced by slave. As a
consequence, all parameters must be setup independently on each inverter, master
mode.
In case of alarm or failure of a pump in a Combo system, this pump’s operation will be
replaced (temporary or permanently) by another pump.
In case of failure of master in a Combo system, it will be replaced by the next slave after
about 1 minute. In order to enable master replacement Autorestart must be set ON in each
slaves
11.16Troubeshooting
LCD does not switch on after powering the VASCO–Check the connecting flat cable between the
Power line of VASCO is interrupted by the
differential protection contactor
When performing sensor test operation, SENSOR
OFF alarm occurs
Frequency and pressure oscillation on constant
pressure control mode
Measured pressure drops too much before VASCO
starts the pump.
ProblemSuggested Actions
LCD board (attached to the cover) and the
control board
–Check the fuses
–Check that the power cables are properly
connected
–Check the leakage current to ground of EMC
filter
–Following a rapid off/on the power supply, the
differential contact can interrupt the power.
After turning off the VASCO it is
recommended to wait at least 1 minute
before restarting
–Check that the sensor cable is properly
connected to the sensor device and to the
VASCO
–Make sure that the sensor and its cable are
not damaged
–Check that the operating range of sensor is of
4-20 mA type and the value of 15 V is within
the voltage feed range of the sensor
–Check if the water tank and its air pressure are
correctly set. It may be necessary to increase
the tank volume or reduce the pre-charge
pressure.
–Check the ki & kp parameters (Control
parameters menu). At first, it is suggestible to
increase the Ki value. If it not enough reduce
of one unit the Kp value
–Decrease the delta start value (Control
Parameters menu)
–Check to see if the water tank and it’s air
pressure are correctly set. It may be necessary
to increase the tank volume or reduce the
pre-charge pressure
–Modify the value of ki & kp parameters
(Control Parameters menu). At first, it is
suggestible to reduce the Ki value. If it is not
enough increase of one unit the Kp value
52
Dutypoint Limited
Shepherd Road
Gloucester
GL2 5EL
United Kingdom
T: +44(0)1452 300592
W: www.dutypoint.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.