DURO-LAST® PARAPET FL ASHING
Duro-Last® Parapet Flashing is made with Duro-Last specially formulated roofing membrane. The combination of reinforced membrane and prefabrication ensures a long lasting, watertight flashing. The membrane is available in white, tan, gray and dark gray colors as well as in the Designer Series membranes (slate gray Shingle-Ply, sandstone Shingle-Ply and Rock Ply).
Heat welding (hot-air) is used to seam sections of parapet flashing together and also to seam the parapet flashing to the Duro-Last membrane on the roof deck. Welds can be made with a hand-held unit or automatic welder.
The flashing can be mechanically attached or a dhered to walls. No matter the method of attachment, mechanical fasteners must be used to secure
roof-to-wall transitio ns and chang es in slope, such as steps in the wall profile.
The example drawings on this page will help in understan ding the f ollowing installation guidelines as well as aid in the understanding the fastener tab spacing that is specified when ordering these prefabricated flashings.
DATA SHEET
Mechanical Attachment:
If the parapet flashing is to be extended up the wall a short distance and
terminated, such as shown in Example #1, the termination h eight must be at least 8 in. above the roof deck. If the termination height exceeds 28 in. at least one row of fasteners must be used to attach the flas hing to the wall as shown in example #2.
When multiple rows of fasteners are required, such as shown in Example #3,
the maximum spacing between rows, or between a row of faste ners and the
top of the wall, is 28 in. Refer to the Duro-Last Mechanically Attached Systems specification for
substrate and fastener requirements.
Adhered Attachment:
Parapet flashing may be adhered to the wall with adhesive supplied by Duro-Last. The minimum termination height is 8 in. above the roof deck. If
the termination height exceeds 60 in., at least one row of mechanical
fasteners must be used. On tall walls multiple rows of fasteners may be required. The maximum
spacing between rows, or between a row of fasteners and the top of the
wall, is 60 in. Refer to the Duro-Last Adhered System specification for substrate and
adhesive requirements.