Duro-Last EPS Types II and VIII User Manual

DURO-GUARD® EPS TYPES II AND VIII
FLAT AND TAPERED PANELS
Description:
®
Duro-Guard insulations consisting of a superior closed-cell, lightweight and resilient expanded polystyrene (EPS). They meet or exceed the requirements of ASTM C 578, Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation.
Available in both flat and tapered panels in order to meet thermal insulation needs as well as provide slope for proper roof drainage.
Provides long-term thermal insulation value.
Does not contain CFCs or HCFCs.
Superior moisture resistance.
100% recyclable.
Available in two densities per ASTM C 578:
o Type II, 1.50 pcf. o Type VIII, 1.25 pcf.
Refer to Table 3 for physical properties.
Recommended Uses:
Mechanically attached Duro-Last roof systems.
Adhered/Fully Bonded Duro-Last roof systems.
Duro-Bond
Metal retrofit roof systems.
EPS Type II and Type VIII are premium
®
roof systems.
Figure 1. Duro-Guard EPS Types II and VIII Flat
Tapered Panels:
Typical sizes:
o 4 ft. x 4 ft. (1220 mm x 1220 mm). o 4 ft. x 8 ft. (1220 mm x 2440 mm). o Thicknesses: 0 to 40 inch (0 to 1016 mm).
Precut cricket and saddle systems are available.
Taper designs and shop drawings are
available.
Custom sizes are available.
Underwriters Laboratories Inc.:
Refer to Duro-Last’s UL Listings (TGFU.R10128) for assembly details (www.ul.com).
Factory Mutual Global:
Refer to FM Approval’s RoofNav for details on FM Approved systems (www.roofnav.com).
Flat Panels:
Typical sizes:
o 4 ft. x 4 ft. (1220 mm x 1220 mm). o 4 ft. x 8 ft. (1220 mm x 2440 mm). o Thickness: Up to 40 inch (1016 mm).
o Custom cut “flute filler” for metal roofs is available.
* Contact Duro-Last for additional slope options.
Duro-Last, “World’s Best Roof” and Duro-Guard are registered marks owned by Duro-Last, Inc.
1 of 2 www.duro-last.com 800-248-0280
Updated: 11/4/2013
Figure 2. Duro-Guard EPS Types II and VIII Taper
TABLE 1. TYPICAL TAPER PANEL DIMENSIONS
ID SLOPE* Thickness A1 ” per 12” 1% A2 ” per 12” 1% A3 ” per 12” 1% A4 ” per 12” 1% C1 ¼” per 12” 2% C2 ¼” per 12” 2% C3 ¼” per 12” 2% C4 ¼” per 12” 2% E1 ½” per 12” 4% E2 ½” per 12” 4% E3 ½” per 12” 4% E4 ½” per 12” 4%
EPS panels can be formed
up to 40” thick.
The starting thickness of
the tapered panels can be
custom ordered based on
project requirements.
/4/
ast.co
800
80
DURO-GUARD® EPS TYPES II AND VIII
Installation:
Duro-Guard EPS panels and Duro-Last membrane must never be in direct contact. Refer to the appropriate Duro-Last specification for slip sheet and cover board requirements.
Panels must be kept dry before, during and after installation. Install only as much insulation as can be covered the same day with completed roofing.
The use of multiple layers of insulation with joints staggered a minimum of 6 inches between layers is recommended to eliminate thermal bridging.
Butt panel edges together and stagger joints of adjacent panels.
Boards must be neatly fitted to roof deck and around penetrations with no gaps greater than ¼ inch.
Refer to the appropriate Duro-Last roof system specification and detail drawings for deck preparation and attachment requirements.
Precautions must be taken to ensure that new concrete decks have fully hydrated and do not continue to release moisture.
Panel Attachment:
Panels may be attached to the roof deck using mechanical fasteners or insulation adhesive. It is acceptable to use these products in combination.
Mechanical Attachment
When installing multiple layers (which may include insulation, cover boards and thermal barriers) it is acceptable to mechanically secure through all layers.
Use fasteners and plates supplied by or approved by Duro-Last, Inc.
Adhesive Attachment
o Insulation adhesive must be supplied by
Duro-Last, Inc. Refer to the adhesive’s product data sheet for application guidelines. Acceptable products:
®
o Duro-Grip o Duro-Grip o Duro-Grip o Duro-Grip
Insta-Stik™.
®
Olybond®.
®
Millenium Weather-Tite®.
®
CR-20.
Subsequent layers of insulation and approved cover boards may also be attached with insulation adhesive.
Maximum panel dimensions are 4ft. x 4ft.
Storage:
Insulation must be protected from open flame and kept dry at all times.
Factory applied packaging is intended only for protection during transit. Slit or remove the packaging to prevent accumulation of condensation.
TABLE 2. TYPICAL THERMAL VALUES
THICKNESS* R-Value
inches mm TYPE II TYPE VIII
1.00 25 4.5 4.2
1.50 38 6.7 6.3
2.00 51 9.0 8.4
2.50 64 11.2 10.5
3.00 76 13.5 12.6
3.50 89 15.7 14.7
4.00 102 17.0 16.8
4.50 114 20.2 18.9
5.00 127 22.5 21
5.50 140 24.7 23.1
6.00 152 27.0 25.2
* Contact Duro-Last for additional thickness options.
TABLE 3. TYPICAL PHYSICAL PROPERTIES
Property Test Method Type II
Density
(nominal)
R-Value
(per inch)
@25°F @40°F @75°F
Compressive
Strength
(10% deformation)
Flexural Strength ASTM C 203 35 psi
Dimensional
Stability
Water Vapor
Permeance
Water Absorption ASTM C 272 3.0%
Flame Spread ASTM E 84 20
Smoke Developed ASTM E 84 150 - 300
ASTM C 303 1.50 pcf
ASTM C 518
or
C 177
ASTM
D 1621
ASTM
D 2126
ASTM E 96 3.5 perm
4.76
4.55
4.17
15 – 21
psi
Type
VIII
1.25 pcf
4.55
4.25
3.92
13 – 18
psi
30 psi
2.0%
Store elevated (at least 3”) and completely covered with a weatherproof covering such as a tarpaulin.
Do not use panels which are wet or damaged.