DURO-GUARD® EPS FIBERGLASS FACER
FLAT AND TAPERED PANELS
Description:
®
Duro-Guard
insulation consisting of a superior closed-cell,
lightweight and resilient expanded polystyrene (EPS)
which is factory laminated to a durable fiberglass
facer. It meets or exceeds the requirements of ASTM
C 578, Standard Specification for Rigid, Cellular
Polystyrene Thermal Insulation.
• Available in both flat and tapered panels in
order to meet thermal insulation needs as well
as provide slope for proper roof drainage.
• May be used directly under Duro-Last
membranes. This saves labor by eliminating
the need for installing a separate cover board
or slip sheet.
• Use with mechanically attached or Duro-Bond®
systems. Membrane shall not be adhered to
this product.
• Provides long-term thermal insulation value.
• Does not contain CFCs or HCFCs.
• Superior moisture resistance.
• 100% recyclable.
• Type VIII, 1.25 pcf, per ASTM C 578.
• Refer to Table 3 for physical properties.
Recommended Uses:
EPS Fiberglass Facer is a premium
Figure 1. Duro-Guard EPS Fiberglass Facer (Top Layer)
Tapered Panels:
• Typical sizes:
o 4 ft. x 4 ft. (1220 mm x 1220 mm).
o 4 ft. x 8 ft. (1220 mm x 2440 mm).
o Thicknesses: 0 to 40 inch (0 to 1016 mm).
• Precut cricket and saddle systems are
available.
• Taper designs and shop drawings are
available.
• Custom sizes are available.
• Mechanically attached Duro-Last roof systems.
®
• Duro-Bond
roof systems.
• Metal retrofit roof systems.
Underwriters Laboratories Inc:
• May achieve UL Class A fire rating on
noncombustible decks without the use of a
cover board. Refer to Duro-Last’s UL Listings
(TGFU.R10128) for assembly details
(www.ul.com).
Factory Mutual Global:
• Refer to FM Approval’s RoofNav for details on
FM Approved systems (www.roofnav.com).
Flat Panels:
• Typical sizes:
o 4 ft. x 4 ft. (1220 mm x 1220 mm).
o 4 ft. x 8 ft. (1220 mm x 2440 mm).
o Thickness: Up to 40 inch (1016 mm).
Duro-Last, “World’s Best Roof” and Duro-Guard are registered marks owned by Duro-Last, Inc.
1 of 2 www.duro-last.com 800-248-0280
Updated: 11/4/2013
Figure 2. Duro-Guard EPS Fiberglass Facer Taper
TABLE 1. TYPICAL TAPER PANEL DIMENSIONS
ID SLOPE* Thickness
A1 ⅛” per 12” 1%
A2 ⅛” per 12” 1%
A3 ⅛” per 12” 1%
A4 ⅛” per 12” 1%
C1 ¼” per 12” 2%
C2 ¼” per 12” 2%
C3 ¼” per 12” 2%
C4 ¼” per 12” 2%
E1 ½” per 12” 4%
E2 ½” per 12” 4%
E3 ½” per 12” 4%
E4 ½” per 12” 4%
* Contact Duro-Last for additional slope options.
EPS panels can be
formed up to 40” thick.
The starting thickness of
the tapered panels can
be custom ordered based
on project requirements.
DURO-GUARD® EPS FIBERGLASS FACER
Installation:
• Duro-Guard EPS Fiberglass Facer may be
used directly under the Duro-Last
membrane. Care should be taken to ensure
that “bare” EPS is never in direct contact
with the membrane. Refer to the appropriate
Duro-Last specification for slip sheet and
cover board requirements.
• Panels must be kept dry before, during and
after installation. Install only as much insulation
as can be covered the same day with
completed roofing.
• The use of multiple layers of insulation with
joints staggered between layers a minimum of
6 inches is recommended to eliminate thermal
bridging.
• Butt panel edges together and stagger joints of
adjacent panels.
• Boards must be neatly fitted to roof deck and
around penetrations with no gaps greater than
¼ inch.
• Refer to the appropriate Duro-Last roof system
specification and detail drawings for deck
preparation and attachment requirements.
• Precautions must be taken to ensure that new
concrete decks have fully hydrated and do not
continue to release moisture.
Panel Attachment:
improper storage, handling or installation by
others.
TABLE 2. TYPICAL THERMAL VALUES
THICKNESS* R-Value
inches mm TYPE VIII
1.00 25 4.2
1.50 38 6.3
2.00 51 8.4
2.50 64 10.5
3.00 76 12.6
3.50 89 14.7
4.00 102 16.8
4.50 114 18.9
5.00 127 21
5.50 140 23.1
6.00 152 25.2
* Contact Duro-Last for additional thickness options.
TABLE 3. TYPICAL PHYSICAL PROPERTIES
Property Test Method Type VIII
Density
(nominal)
R-Value
(per inch)
@25°F
@40°F
@75°F
Compressive Strength
(10% deformation)
ASTM C 303 1.25 pcf
ASTM C 518
or
C 177
ASTM D 1621 13 – 18 psi
4.55
4.25
3.92
Mechanical Attachment
• When installing multiple layers (which may
include insulation, cover boards and thermal
barriers) it is acceptable to mechanically secure
through all layers.
• Use fasteners and plates supplied by or
approved by Duro-Last, Inc.
Storage:
• Insulation must be protected from open flame
and kept dry at all times.
• Factory applied packaging is intended only for
protection during transit. Slit or remove the
packaging to prevent accumulation of
condensation.
• Store elevated (at least 3”) and completely
covered with a weatherproof covering such as
a tarpaulin.
• Do not use panels which are wet or damaged.
Limitations:
• Duro-Last, Inc. will not be responsible or liable for
any defects or problems related to building or roof
design by others, to deficiencies in construction,
to dangerous conditions on the job site, or to
Flexural Strength ASTM C 203 ≥ 30 psi
Dimensional Stability ASTM D 2126 ≤ 2.0%
Water Vapor
Permeance
Water Absorption ASTM C 272 ≤ 3.0%
Flame Spread ASTM E 84 20
Smoke Developed ASTM E 84 150 - 300
ASTM E 96 ≤ 3.5 perm
m
Duro-Last, “World’s Best Roof” and Duro-Guard are registered marks owned by Duro-Last, Inc.
2of 2www.duro-l
Updated: 11
-248-02
2013