Durastar DRAC14 User Manual

DURASTAR.COM
FORM NO. ADS-220
1
SPECIFICATION SHEET
DRAC14 Series
AIR CONDITIONERS
COOLING EFFICIENCY: 14 SEER/12.5 EER
1.5 TO 5 TONS [5.28 to 17.6 kW]
PRODUCT FEATURES
• Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability for single, multi-family and light commercial applications.
• Painted louvered steel cabinet
• Easily accessible control box
• Condenser coils constructed with copper tubing and enhanced aluminum fins
• Grille/Motor mount for quiet fan operation
• Filter Drier (shipped – not installed)
DURASTAR.COM
2
DRAC14 Series
TABLE OF CONTENTS
Model Number Identification ............................................................................3
Available SKUs ..............................................................................................3
Electrical & Physical Data ................................................................................4
Weighted Sound Power ..................................................................................4
Unit Dimensions ............................................................................................5
Refrigerant Line Size Information ..................................................................6-7
Performance Data ..........................................................................................8
Limited Warranty ............................................................................................9
Model Number Identification/Available SKUs
DRAC14 Series
3
DR AC A 14 24 A J 1 N A
Brand Product
Category
SEER Capacity
BTU/HR
Major Series* Voltage Type Controls Minor
Series**
Durastar A - Air Conditioners A - R410A
14 - 14 SEER 18 - 18,000 [5.28 kW]
24 - 24,000 [7.03 kW]
30 - 30,000 [8.79 kW]
36 - 36,000 [10.55 kW]
42 - 42,000 [12.31 kW]
48 - 48,000 [14.07 kW]
60 - 60,000 [17.58 kW]
A - 1st Design
B - 2nd Design
C - 3rd Design
J - 1ph, 208-230/60 1 - Single-stage N - Non-Communicating
A - 1st Design
Air Conditioners*
[ ] Designates Metric Conversions
Available SKUs
Models
DRAC14A18AJ1NA
DRAC14A24BJ1NA
DRAC14A24CJ1NA
DRAC14A30BJ1NA
DRAC14A36BJ1NA
DRAC14A36CJ1NA
DRAC14A42CJ1NA
DRAC14A48BJ1NA
DRAC14A60AJ1NA
Electrical and Physical Data/Weighted Sound Power
DRAC14 Series
DURASTAR.COM
4
Physical Data
Model No.
DRAC
14A18A
DRAC
14A24B
DRAC
14A24C
DRAC
14A30B
DRAC
14A36B
DRAC
14A36C
DRAC
14A42C
DRAC
14A48B
DRAC
14A60A
Nominal Tonnage
1.5
2.0
2.0
2.5
3.0
3.0
3.5
4.0
5.0
Valve Connections
Liquid Line O.D. – in.
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Suction Line O.D. – in.
5/8
3/4
3/4
3/4
3/4
3/4
7/8
7/8
7/8
Refrigerant (R410A) furnished oz.¹
82
89
85
98
122
128
135
146
228
Compressor Type
Scroll
Outdoor Coil
Net face area – Outer Coil
11.1
11.2
13.7
13.7
18.3
21.9
18.3
21.9
21.9
Net face area – Inner Coil
Tube diameter – in.
0.375
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Number of rows
1
1
1
1
1
1
1
1
2
Fins per inch
22
22
22
22
22
22
22
22
22
Outdoor Fan
Diameter – in.
18
18
22
22
22
24
22
24
24
Number of blades
2
2
2
2
2
3
3
3
3
Motor hp
1/10
1/10
1/12
1/8
1/5
1/5
1/4
1/5
1/3
CFM
1697
2105
2077
2121
2702
3430
3174
3571
3360
RPM
1100
1075
841
1075
819
850
1075
850
1085
watts
108
148
76
155
149
228
244
235
311
Shipping weight – lbs.
135
131.5
171
144.5
166
201
184
225
274
Operating weight – lbs.
128
124.5
164
137.5
159
194
176
205
254
Electrical Data
Line Voltage Data (Volts-Phase-Hz)
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Maximum overcurrent protection (amps)²
20
25
25
25
30
35
35
45
60
Minimum circuit ampacity³
13
15
15
17
19
21
23
26
35
Compressor
Rated load amps
9.7
11.2
11.2
12.8
14.1
15.4
16.7
19.9
26.4
Locked rotor amps
46
60.8
60.8
64
77
84
109
109
134
Condenser Fan Motor
Full load amps
0.5
0.6
.36
0.7
1.2
1.0
1.3
1
1.7
Locked rotor amps
1.3
1.3
1
1.2
2
2
2.5
2.3
3.2
¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instrucitons for information about set length and additional
refrigerant charge required. ²HACR type circuit breaker of fuse. ³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Electrical and Physical Data
Weighted Sound Power Level (dBA)
Model
Standard Rating (dBA)
DRAC14A18A 70 DRAC14A24B 68 DRAC14A24C 74 DRAC14A30B 73 DRAC14A36B 71 DRAC14A36C 73 DRAC14A42C 75 DRAC14A48B 75 DRAC14A60A 76