Dupont Suva HP Series, Suva HP81, Suva HP80, Suva 404A Technical Information

DuPont™ Suva
refrigerants
Technical Information
P–HP
®
DuPont™
®
HP
Refrigerants
Properties, Uses,
Storage, and Handling
DuPont™ Suva® HP80 (R-402A) refrigerant
®
DuPont™ Suva DuPont™ Suva
HP81 (R-402B) refrigerant
®
404A (HP62) refrigerant
DuPont™ Suva® HP Refrigerants
Proper ties, Uses, Stora ge, and Handling
Table of Contents
Page
Introduction ................................................................................................................. 1
Background................................................................................................................ 1
Suva® HP Refrigerants ............................................................................................... 1
Uses ............................................................................................................................. 1
Physical Properties ..................................................................................................... 2
Chemical/Thermal Stability ........................................................................................ 2
Stability with Metals .................................................................................................... 2
Thermal Decomposition ............................................................................................10
Compatibility Concerns if R-502 and Suva® HP Refrigerants Are Mixed ...................10
Materials Compatibility ............................................................................................10
Elastomers ................................................................................................................10
Motor Materials .........................................................................................................12
Desiccants ................................................................................................................13
Refrigeration Lubricants ............................................................................................13
Safety ...........................................................................................................................13
Inhalation Toxicity......................................................................................................13
Cardiac Sensitization.................................................................................................15
Skin and Eye Contact................................................................................................15
Spills or Leaks........................................................................................................... 15
Combustibility of Suva® HP Refrigerants ...................................................................15
Air Monitors and Leak Detection ..............................................................................16
Types of Detectors ....................................................................................................16
Nonselective Detectors..........................................................................................17
Halogen-Selective Detectors .................................................................................17
Compound-Specific Detectors ...............................................................................17
Fluorescent Additives ............................................................................................17
Storage and Handling ................................................................................................17
Shipping Containers in the U.S..................................................................................17
Bulk Storage Systems ...............................................................................................18
Converting Bulk Storage Tanks from R-502 to Suva® HP Refrigerants..................19
Material Compatibility Concerns ............................................................................19
Handling Precautions for Suva® HP Refrigerant Shipping Containers .......................19
Recovery, Recycle, Reclamation and Disposal .......................................................20
Recovery ...................................................................................................................21
Recycle .....................................................................................................................21
Reclamation ..............................................................................................................21
Disposal ....................................................................................................................21
Introduction
Background
Chlorofluorocarbons (CFCs), which were devel­oped over 60 years ago, have many unique prop­erties. They are low in toxicity, nonflammable, noncorrosive, and compatible with other materials. In addition, they offer the thermodynamic and physical properties that make them ideal for a variety of uses. CFCs are used as refrigerants; as blowing agents in the manufacture of insulation, packaging, and cushioning foams; as cleaning agents for metal and electronic components; and in many other applications.
However, the stability of these compounds, coupled with their chlorine content, has linked them to depletion of the earth’s protective ozone layer. As a result, DuPont has phased out production of CFCs and introduced environmentally acceptable alterna­tives, such as the DuPont™ Suva family.
®
HP refrigerant
In addition, DuPont has formulated a mixture based on all-HFC refrigerants, which results in no ozone depletion factor. This refrigerant is called Suva
®
404A (HP62), and its composition is:
HFC-125 HFC-143a HFC-134a
®
404A
Suva
(HP62), wt% 44 52 4
The individual components of the three mixtures are listed in Table 1 to show their chemical names and formulae. In addition, the physical properties of the Suva
®
HP refrigerants are listed in Table 3.
Uses
The Suva® HP refrigerants can be used in virtually all R-502-based applications, either as a result of retrofiting existing equipment that uses R-502 or following development of new equipment designed to use the Suva
®
HP products.
Suva® HP Refrigerants
The products designated as Suva® HP refrigerants are intended as replacements for R-502 in medium­and low-temperature refrigeration systems. The
®
Suva
HP refrigerant family contains two different types of refrigerants. Both types involve the use of refrigerant blends to achieve alternatives that will act very much like R-502 in refrigeration systems.
The first type of blends incorporate the following refrigerants in two compositions to optimize differ­ent performance characteristics:
HCFC-22 HFC-125 Propane
Suva® HP80
(R-402A), wt% 38 60 2
Suva® HP81
(R-402B), wt% 60 38 2
R-502 currently serves a wide range of applications in the refrigeration industry. It is used widely in supermarket applications, in food service and ware­housing, for transport refrigeration, in cascade sys­tems for very low temperatures, and other assorted applications. It offers good capacity and efficiency without suffering from the high compressor dis­charge temperatures that can be seen with HCFC­22 single-stage equipment.
Suva® HP80 and HP81, which contain HCFC-22, are each formulated to optimize different perfor­mance characteristics.
®
HP80 offers compressor discharge temper-
Suva atures equivalent to R-502, with improved capac­ity versus R-502, and slightly lower theoretical efficiency.
Table 1
Refrigerant Information
Refrigerant Chemical Name Formula CAS No. Molecular Wt.
HCFC-22 Chlorodifluoromethane CF2HCl 75-45-6 86.47 HFC-125 Pentafluoroethane CF HFC-134a 1,1,1,2-Tetrafluoroethane CF HFC-143a 1,1,1-Trifluoroethane CF HC-290 Propane C3H
CHF
3
2
F 811-97-2 102.0
3CH2
3CH3
8
354-33-6 120.02
420-46-2 84.08 74-98-6 44.1
The DuPont Oval Logo, DuPont™, The miracles of science™, and Suva® are trademarks or registered trademarks of E. I. du Pont de Nemours and Company.
1
Suva® HP81 offers the highest efficiency versus R-502, with slightly better capacity. However, the higher HCFC-22 content results in compressor discharge temperatures in the range of 14°C (25°F) higher than that of R-502, which makes Suva
®
HP81 most suited for medium-temperature systems such as ice machines.
®
Suva
404A (HP62) offers the best overall proper­ties when compared with R-502. Capacity and effi­ciency values should be equivalent to R-502, and compressor discharge temperatures may be up to 9°C (14°F) lower than R-502, which may equate to longer compressor life and better lubricant stability.
In addition, the heat transfer characteristics of
®
all the Suva
HP products appear to be better than R-502, so any loss of compression efficiency may be offset by improvements in heat transfer.
Due to the differences in operating characteristics described above, Suva cally selected for different applications. Suva
®
HP80 and HP81are typi-
®
HP81 is preferred where higher energy efficiency and capacity are needed and where the higher dis­charge temperatures will not create operating diffi-
®
culties. Both Suva are full-range R-502 replacements, with Suva
HP80 and Suva® 404A (HP62)
®
HP80 preferred for retrofitting of existing systems,
®
and Suva ment. Suva
404A (HP62) preferred for new equip-
®
404A (HP62) can also be used for
retrofitting existing equipment where HFCs are desired. Table 2 shows markets that currently use each of these refrigerants.
Thermodynamic tables in English and SI units are available in Bulletins T-HP80-ENG, T-HP80-SI, T-HP81-ENG, T-HP81-SI, T-HP62-ENG, and
®
T-HP62-SI for Suva
®
Suva
404A (HP62).
HP80, Suva® HP81, and
Chemical/Thermal Stability
Stability with Metals
Stability tests for refrigerant with metals are typi­cally performed in the presence of refrigeration lubricants. Results of sealed tube stability tests available for R-502/mineral oil and alkylbenzene lubricants have shown long-term stability in contact with copper, steel, and aluminum in actual refrig­eration systems. Mineral oils, alkylbenzene, mix­tures of mineral oil/alkylbenzene and polyol esters (POE) are all possible candidates for use with
®
Suva
HP80 and HP81; POE are proposed lubri-
cants for use with Suva The method followed was generally the same as
ASHRAE 97 with several minor modifications. A 3-mL volume of refrigerant/lubricant solution was heated in the presence of copper, steel, and alumi­num coupons in an oven for 14 days at 175°C (347°F). Both the neat lubricant and a mixture of lubricant and refrigerant (50/50 volume ratio) were tested. Visual ratings were obtained on both the liquid solutions and the metal coupons after the designated exposure time. The visual ratings range from 0 to 5, with 0 being best.
®
404A (HP62).
Table 2
DuPont™ Suva® HP Refrigerant
Market Applications
Product Medium Temperature Low Temperature
Suva® HP81 Ice Machines To Be Determined
®
HP80 Supermarket Supermarket
Suva
®
404A
Suva
(HP62) All
Food Service Vending Supermarket
Transport Transport
Food Service
Physical Properties
General physical properties of the Suva® HP refrig­erants are shown in Table 3. Pressure-enthalpy dia­grams for the Suva
Figures 1–6.
Additional physical property data may be found in other DuPont publications. Bulletin ART-18 contains viscosity, thermal conductivity, and heat capacity data for saturated liquid and both saturated and superheated vapor. ART-18 also contains heat capacity ratios for saturated and superheated vapor.
®
HP refrigerants are shown in
After the visual ratings were obtained, sample tubes were opened and the lubricant and refrigerant (if present) were analyzed. The lubricant was typically checked for halide content and viscosity, while the refrigerant was examined for the presence of de­composition products. Table 4 summarizes typical data for Suva
®
HP refrigerants. Visual ratings are listed for the neat lubricant, the lubricant/refriger­ant solution, and the three metals that were present in the lubricant/refrigerant solutions. Viscosity was determined on the unused lubricant, the tested neat lubricant, and the lubricant tested in the presence of refrigerant. Decomposition products were deter­mined in some cases. Typical measurements for decomposition products is in the low parts per million (ppm) range.
®
Suva
HP81 tests with various lubricants indicate it has adequate chemical stability with these lubri­cants. In addition, we believe that HP80 will have similar behavior due to the same refrigerants being used in the formulation. Suva
®
404A (HP62) tests with common POE lubricants indicate that chemi­cal stability of Suva
®
404A (HP62) with common
metals used in refrigeration systems is acceptable.
2
Table 3
General Property Information
Physical Property Unit (R-402A) (R-402B) (HP62)
Molecular Wt, avg. g/mol 101.55 94.71 97.6 Boiling Point, 1 atm °C –49.2 –47.4 –46.5
°F –56.5 –53.2 –51.6
Freezing Point °C n/a n/a n/a
°F
Critical Temperature °C 75.5 82.6 72.1
°F 167.9 180.7 161.7
Critical Pressure kPa 4135 4445 3732
psia 599.7 644.8 541.2
lb/ft
lb/ft
3
3
3
3
3
3
Critical Density kg/m
Liquid Density at 25°C (77°F) kg/m
Density, Saturated Vapor kg/m
at –15°C (5°F) lb/ft
Specific Heat at 25°C (77°F) Liquid kJ/kg•K 1.37 1.34 1.53
Btu/lb•°F 0.328 0.320 0.367
Vapor, 1 atm kJ/kg•K 0.755 0.725 0.870
Btu/lb•°F 0.181 0.173 0.207
Vapor Pressure at 25°C (77°F) kPa 1337 1254 1255
psia 194.0 181.9 182.0
Heat of Vaporization kJ/kg 194.0 210.0 202.1
at Boiling Point Btu/lb 83.5 90.3 87.0
Thermal Conductivity at 25°C (77°F)
Liquid W/m•K 6.91E-2 7.35E-2 6.83E-2
Btu/hr•ft•°F 4.00E-2 4.25E-2 3.94E-2
Vapor, 1 atm W/m•K 1.266E-2 1.205E-2 1.346E-2
Btu/hr•ft•°F 7.32E-3 6.96E-3 7.78E-3
Viscosity at 25°C
(77°F)
Liquid Pa•s 1.38E-4 1.45E-4 1.28E-4 Vapor, 1 atm Pa•s 1.29E-5 1.28E-5 1.22E-5
Flammability Limit vol% None None None
in Air, 1 atm Ozone-Depletion Potential (CFC-12 = 1) 0.02 0.03 0.0 Halocarbon Global (CFC-11 = 1) 0.63 0.52 0.94
Warming Potential TSCA Inventory Status Reported/Included? Yes Yes Yes Inhalation Exposure Limit AEL* ppm 1000 1000 1000
(8- and 12-hr TWA)
Suva® HP80 Suva® HP81 Suva® 404A
541.7 530.7 484.5
33.82 33.13 30.23 1151 1156 1048
71.86 72.14 65.45
19.93 16.90 18.20
1.24 1.05 1.14
* AEL (acceptable exposure limit) is an airborne inhalation exposure limit established by DuPont which specifies time-weighted
average concentrations to which nearly all workers may be repeatedly exposed without adverse effects.
3
Figure 1. DuPont™ Suva® 404A (HP62) Pressure–Enthalpy Diagram (SI Units)
404A (HP62)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(SI Units)
4
Figure 2. DuPont™ Suva® 404A (HP62) Pressure–Enthalpy Diagram (English Units)
404A (HP62)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(English Units)
5
Figure 3. DuPont™ Suva® HP80 (R-402A) Pressure–Enthalpy Diagram (SI Units)
HP80 (R-402A)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(SI Units)
6
Figure 4. DuPont™ Suva® HP80 (R-402A) Pressure–Enthalpy Diagram (English Units)
HP80 (R-402A)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(English Units)
7
Figure 5. DuPont™ Suva® HP81 (R-402B) Pressure–Enthalpy Diagram (SI Units)
HP81 (R-402B)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(SI Units)
8
Figure 6. DuPont™ Suva® HP81 (R-402B) Pressure–Enthalpy Diagram (English Units)
HP81 (R-402B)
®
DuPont™
Suva
Pressure-Enthalpy Diagram
(English Units)
9
Note: Lubricant/refrigerant combinations shown throughout this report are for the purposes of com­paring the stability and compatibility of different lubricants with the Suva
®
HP products. No recom­mendation is made or implied that these combina­tions will operate successfully in refrigeration systems.
Thermal Decomposition
Like R-502, Suva® HP refrigerants will decompose when exposed to high temperature or flame sources. Decomposition may produce toxic and irritating compounds, such as hydrogen chloride and hydrogen fluoride. The decomposition products released will irritate the nose and throat. Therefore, it is important to prevent decomposition by follow­ing DuPont Material Safety Data Sheet (MSDS) recommendations for handling and use.
Compatibility Concerns if R-502 and Suva® HP Refrigerants Are Mixed
R-502 and Suva® HP refrigerants are chemically compatible with each other; this means that they do not react with each other and form other com­pounds. However, when the different refrigerants are mixed by accident or deliberately, they will form mixtures that can be very difficult to separate. Therefore, mixtures of R-502 and Suva
®
HP refrigerants cannot be separated in on-site recycle machines or in the typical facilities of an off-site reclaimer. These mixtures will have to be disposed of by incineration.
Also, mixtures of R-502 and Suva® HP refrigerants will have performance properties different from either refrigerant alone. These properties may not be acceptable for your systems. Therefore, we do not recommend mixing R-502 and Suva
®
HP refrig­erants in any systems. First remove the R-502 prop­erly (see page 21 for recovery discussion) and then charge the new refrigerant.
Materials Compatibility
Because the Suva® HP refrigerants will be used in many different applications, it is important to re­view materials of construction for compatibility when designing new equipment, retrofitting exist­ing equipment, or preparing storage and handling facilities. Because the Suva been designed as refrigerants, the compatibility data summarized here will include materials commonly used in refrigeration applications.
®
HP products have
Elastomers
Compatibility results for Suva® HP81 and Suva 404A (HP62) were developed with five different polymer and lubricant combinations. It was as­sumed that Suva
®
HP80 compatibility would be
similar to HP81. Recognize that these data reflect compatibility in
sealed tube tests, and that refrigerant compatibility in real systems can be influenced by the actual op­erating conditions, the nature of the polymers used, compounding formulations of the polymers, and the curing or vulcanization processes used to create the polymer. Polymers should always be tested under actual operating conditions before reaching final conclusions about their suitability.
The rankings shown in Table 5 are based on dupli­cate samples of each polymer subjected to aging at 150°C (302°F) for 30 days in various lubricant/ refrigerant combinations. Physical properties of the test samples were determined before and after ag­ing. The resulting ratings are based on 1 being best and 5 being worst for the purposes of comparison. The factors included in the overall assessment of compatibility included:
visual observations of material changes due
to aging
changes in weight and volume of the samples
due to aging
changes in hardness of the samples due to aging
changes in flexural properties of the samples
due to aging
recovery of weight and flexural properties after
refrigerant evaporation
The compounds tested were:
PTFE (Teflon
®
, commercial-grade skived sheet,
from Tex-O-Lon Mfg. Co.)
Neoprene W (from Precision Rubber Co.)
HNBR (hydrogenated nitrile butadiene, N1195
from Parker Seal Co.)
EPDM (ethylene propylene diene, commercial
grade, Kirkhill Rubber Co.)
NBR (BUNA N, nitrile butadiene, from Parker
Seal Co.)
Lubricants tested:
Mineral Oil, Suniso 3GS, Witco Corporation
Alkylbenzene, Zerol 150 TD, Shrieve Chemical
Products Inc.
Polyol Ester, Icematic SW32, Castrol
Polyol Ester, Arctic EAL22, Mobil
Chemical
®
10
Table 4
Stability of HP Refrigerants with Metals and Lubricants
Suva® HP81 with various lubricants
HP81 with HP81 with
Mineral Oil, Alkylbenzene, HP81 with
Property 3GS 150 TD Icematic SW32
Suniso Zerol Polyol Ester, Castrol
Viscosity of Neat Oil at 40°C (104°F), (mm)
2
/s (cSt) ND ND 29.6
Stability Tests Visual Ratings Neat Oil 0 ND 1,H Oil/Refrig 1,G,H 2,P 0 Copper 0 2,T 0 Iron 0 0 1,T Aluminum 0 0 0
Viscosity Change % Change Neat ND ND 5.0 % Change w/ Refrig ND ND –13.3
Decomposition Analysis [F-], ppm ND ND 7 [Cl-], ppm ND ND 7
(values for Suva® HP80 assumed to be comparable)
Suva® 404A (HP62) with various lubricants
®
404A (HP62) Suva® 404A (HP62) Suva® 404A (HP62) Suva® 404A (HP62)
Suva
with Mineral Oil, with Alkylbenzene, with with
Suniso Zerol Polyol Ester, Castrol Polyol Ester, Mobil
Property 3GS 150 TD Icematic SW32 Arctic EAL22
Viscosity of Neat Oil at 40°C (104°F), (mm)
2
/s (cSt) ND ND 29.6 23.7
Stability Tests Visual Ratings Neat Oil 0 0 1,H 0 Oil/Refrig. 1,G 2,P,G,H 0,G 1,G Copper 0 2,T 0 0 Iron 0 1,T 1,T,P 0 Aluminum 0 0 0 0
Viscosity Change % Change Neat ND ND 5.0 ND % Change w/ Refrig. ND ND ND ND
Visual Ratings: Stability Ratings: 0 to 5
ND = Not Determined 0 = Best
G = Gel 3 = Failed
T = Tarnish 5 = Coked
H = Haze
P = Precipitate
11
Table 5
Relative Ranking of Polymer/Refrigerant/Lubricant Compatibility
Polymer
Refrigerant/Lubricant PTFE HNBR Neoprene W EPDM NBR
R-502 neat 24221 R-502/Mineral Oil 24452 R-502/Alkylbenzene 24252
HP81 neat 24222 HP81/Mineral Oil 24452 HP81/Alkylbenzene 24252 HP81/Castrol Ester 24225 HP81/Mobil Ester 24215
404A (HP62) neat 21121 404A (HP62)/Mineral Oil 22452 404A (HP62)/Alkylbenzene 22352 404A (HP62)/Castrol Ester 24215 404A (HP62)/Mobil Ester 24215
(1 → 5; best → worst)
Motor Materials
In hermetic and semihermetic compressors, the compressor motor is normally cooled by direct contact with refrigerant returning from the evapora­tor. As a result, the motor must be compatible with the refrigerants and lubricants used in the refrigera­tion system.
Accelerated aging tests were conducted with combinations of refrigerants, lubricants, and motor materials using sealed tube tests prepared according to ANSI/ASHRAE 97-1989. After aging, the mate­rials in the tubes were inspected visually and micro­scopically and tested physically and chemically to determine property changes.
Materials tested, and a summary of test results, are described below.
PET (polyethylene terephthalate, Mylar
PET film is used as phase and slot insulation in hermetic motors. Visual inspection of sealed tubes after aging in refrigerant environments revealed no extracts with refrigerant alone [R-502, Suva or Suva cloudiness and light precipitates when lubricants were present.
PET weight change on aging was small (<5%) and occurred with R-502/lubricant and HP81/lubricant combinations. Weight gain with Suva® 404A (HP62) /ester lubricants was 2% or less.
PET flexibility after aging was determined by a bend test. The results show excellent retention of flexibility on aging at 135°C (275°F). There is
®
)
®
404A (HP62)], but varying degrees of
®
HP81,
definite loss of flexibility when PET is aged in R-502/mineral oil or R-502/alkylbenzene at 150°C (302°F). This loss of flexibility does not occur when PET is aged in HP81 or Suva
®
404A (HP62)
with ester lubricants at 150°C (302°F).
Polyesterimide Enameled Motor Wire, amide-imide overcoated (NEMA NW 35C)
No extracts or precipitates were observed on aging the enameled wire in any of the lubricant/ refrigerant combinations. No blistering, crazing, or cracking was observed after aging. Retention of flexibility was confirmed by 1x bend tests of the wire after aging.
Dacron
®
/Mylar®/Dacron® lead wire
(Belden 14 AWG)
After aging of D-M-D samples in refrigerant/ lubricant environments, contents of the tubes were inspected for particulates, the tubes were cooled and opened, and the lead wire samples were subjected to bend tests. Minimal particulates or extracts were observed after aging. PET embrittlement, ranging from slight loss of flexibility to shattering, was observed when specimens were bent 135 degrees. The degree of embrittlement appeared to be a factor of the lubricant, rather than the refrigerant. All D-M-D samples were embrittled in the presence of mineral oil or alkylbenzene lubricants. Good flexibility was seen after aging with polyol esters in the presence of all refrigerants.
12
Summary
In summary, ester-based lubricants appear to cause much less effect on common motor materials than mineral oils or alkylbenzene lubricants. In all cases, the results appeared to be better than R-502 with lubricants commonly used with R-502.
Desiccants
In refrigeration systems, keeping the refrigerant and lubricant free of moisture is very important. Dryers filled with moisture-absorbing desiccant are typically used to prevent moisture accumulation. A desiccant used with R-502, UOP’s (formerly Union Carbide Molecular Sieve) 4A-XH-5, is not gener­ally compatible with highly fluorinated refrigerants such as the Suva
®
HP products. However, compat­ible molecular sieve desiccants, such as XH-9, have been developed. For loose-filled and solid core dryers, new desiccants are available that are also compatible with the new refrigerants and lubri­cants. Be sure to tell your parts wholesaler what refrigerants you plan to use when specifying the dryer for your system.
Refrigeration Lubricants
Most compressors require a lubricant to protect internal moving parts. The compressor manufac­turer usually recommends the type of lubricant(s) and proper viscosity that should be used to ensure acceptable operation and equipment durability. Recommendations are based on several criteria, which can include lubricity, miscibility, compatibil­ity with materials of construction, thermal stability, and compatibility with other lubricants. It is impor­tant to follow the manufacturers’ recommendations for lubricants to be used with their equipment.
Current lubricants used with R-502 have at least partial miscibility with R-502, which eases the problems of designing systems to allow lubricant return back to the compressor. Many refrigeration systems take advantage of this miscibility when considering lubricant return.
Note: Field experience has shown that Suva works successfully with mineral oil in many small hermetic systems where oil return is not a concern.
®
Refrigerants such as the Suva
HP products, with little or no chlorine present in them, may exhibit less miscibility with common lubricants used with R-502. Although many R-502 systems operating at low temperatures allow for reduced miscibility with the lubricant, it is important to know that the lubricants used with the Suva
®
HP refrigerants will return to the compressor using existing equipment designs.
®
HP81
Different compressor and equipment manufacturers will recommend lubricants to use with their equip­ment and the Suva
®
HP products. It would be diffi­cult to summarize all possible lubricant candidates that may be screened by various equipment manu­facturers. In addition, there will be continuing re­search and development of new lubricants that we may not have tested because the market for alterna­tive refrigerants continues to stimulate other market areas. Review your system needs with the equip­ment manufacturer, DuPont distributor, certified refrigeration service contractor, or other qualified party. Never assume the current lubricant in your refrigeration system will be acceptable with the
®
Suva
HP refrigerant you intend to use. Always review system components for compatibility with the new refrigerant and possibly a new lubricant.
Table 6 shows a summary of miscibility tests done with a 50/50 volume mixture of refrigerant and lubricant over a wide range of temperatures, with visual inspection for phase separation as the tubes are slowly warmed. This table does not show that any refrigerant/lubricant combination is acceptable, only whether the two appear to be miscible at the conditions shown.
Safety
Users must have and understand the applicable
®
Suva
HP refrigerant Material Safety Data Sheets.
Inhalation Toxicity
Suva® HP refrigerants pose no acute or chronic hazard when they are handled in accordance with DuPont recommendations and when exposures are maintained below recommended exposure limits, such as the DuPont acceptable exposure limit (AEL) of 1,000 ppm, 8- or 12-hour time-weighted average (TWA).
An AEL is an airborne exposure limit established by DuPont that specifies time-weighted average for airborne concentrations to which nearly all workers may be repeatedly exposed without adverse effects. The AEL for the Suva level as the threshold limit value (TLV) established for HCFC-22 and calculated for R-502 based on the TLVs for the components.
However, like R-502, exposure above the recom­mended exposure limit to the vapors of Suva® HP refrigerants by inhalation may cause human health effects that can include temporary nervous system depression with anesthetic effects such as dizziness, headache, confusion, loss of coordination, and even
®
HP refrigerants is the same
13
R-502
w/mineral oil
w/alkylbenzene
®
HP81
Suva
w/mineral oil
w/alkylbenzene
w/polyol ester
®
HP80
Suva
w/mineral oil
w/alkylbenzene
w/polyol ester
Table 6
Miscibility Summary
–60 +73 +80
2 phases 2 phases
(inversion)
–60 –27 +80 2 phases 1 phase
–60 +68 +80
2 phases 2 phases
(inversion)
–60 +16 +80
2 phases 1 phase
–60 +80
1 phase
–50 +65 +72
2 phases 2 phases
(inversion)
–50 +66 +72
2 phases 2 phases
(inversion)
–50 +72
1 phase
®
404A (HP62)
Suva
w/mineral oil
w/alkylbenzene
w/polyol ester
Note: All temperatures in °C
–60 +52 +80
2 phases 2 phases
(inversion)
–60 +57 +80
2 phases 2 phases
(inversion)
–60 +80
1 phase
14
loss of consciousness. Higher exposures to the va­pors may cause temporary alteration of the heart’s electrical activity with irregular pulse, palpitations, or inadequate circulation. Death can occur from gross overexposure. Intentional misuse or deliber­ate inhalation of Suva
®
HP refrigerant vapors may cause death without warning. This practice is ex­tremely dangerous.
A person experiencing any of the initial symptoms should be moved to fresh air and kept calm. If breathing is difficult, administer oxygen. If not breathing, administer artificial respiration. Call a physician.
Cardiac Sensitization
As with many other halocarbons and hydrocarbons, inhalation of Suva intravenous injection of epinephrine, to simulate human stress reactions, results in a cardiac sensiti­zation response. In humans, this can lead to cardiac irregularities and even cardiac arrest. The likeli­hood of these cardiac problems increases if you are under physical or emotional stress. The Suva refrigerants can cause these responses well above the AEL, but the effect level varies with people, and has not been fully determined.
If you are exposed to very high concentrations of Suva® HP refrigerants, move immediately from the area, and seek medical attention as a precaution. Do not attempt to remain in the area to fix a leak or perform other duties—the effects of overexposure can be very sudden.
Medical attention must be given immediately if someone is having symptoms of overexposure to
®
Suva
HP refrigerants. Do not treat the patient with drugs such as epinephrine. These drugs could in­crease the risk of cardiac problems. If the person is having trouble breathing, administer oxygen. If breathing has stopped, administer artificial respira­tion. Call a physician.
®
HP refrigerants followed by
®
HP
Skin and Eye Contact
At room temperature, Suva® HP refrigerant vapors have little or no effect on the skin or eyes. How­ever, in liquid form, they can freeze skin or eyes on contact, causing frostbite. If contact with liquid does occur, soak the exposed areas in lukewarm water, not cold or hot. In all cases, seek medical attention immediately.
Always wear protective clothing when there is a risk of exposure to liquid refrigerants. Where splashing of refrigerant may occur, always wear eye protection and a face shield.
Spills or Leaks
If a large release of vapor occurs, such as from a large spill or leak, the vapors may concentrate near the floor or in low elevation areas, which can displace the oxygen needed for life, resulting in suffocation.
Evacuate everyone until the area has been well ventilated. Re-enter the area only while using self-contained breathing apparatus. Use blowers or fans to circulate the air at floor or low levels.
Always use self-contained breathing apparatus or an air-line respirator when entering tanks or other areas where vapors might exist. Use the buddy sys­tem (a second employee stationed outside the tank) and a lifeline. Refer to the Material Safety Data Sheet for the specific Suva
®
HP refrigerant you
plan to use.
®
HP refrigerants have virtually no odor, and
Suva therefore can be extremely difficult to detect in enclosed areas. Frequent leak checks and the instal­lation of permanent leak detectors may be neces­sary for enclosed areas or machinery rooms. Refer to ASHRAE Standards 15 and 34 for machinery room requirements.
To ensure safety when using Suva
®
HP refrigerants
in enclosed areas:
1. Route relief and purge vent piping outdoors, away from air intakes.
2. Make certain the area is well ventilated at all times; use auxiliary ventilation, if necessary, to remove vapors.
3. Make sure the work area is free of vapors prior to beginning any work.
4. Install air monitoring equipment to detect leaks.
Combustibility of Suva® HP Refrigerants
Suva® 404A (HP62), HP80 and HP81 are not flam­mable in air at temperatures up to 100°C (212°F) at atmospheric pressure. However, mixtures of HP62, HP80 or HP81 with high concentrations of air at elevated pressure and/or temperature can become combustible in the presence of an ignition source.
®
Suva
404A (HP62), HP80 and HP81 can also be­come combustible in an oxygen enriched environ­ment (oxygen concentrations greater than that in air). Whether a mixture containing Suva (HP62), HP80 or HP81 and air, or Suva (HP62), HP80 or HP81 in an oxygen enriched atmosphere becomes combustible depends on the inter-relationship of 1) the temperature 2) the pressure, and 3) the proportion of oxygen in the
®
404A
®
404A
15
mixture. In general, Suva® 404A (HP62), HP80 or HP81 should not be allowed to exist with air above atmospheric pressure or at high temperatures; or in an oxygen enriched environment. For example:
HP62, HP80 or HP81 should NOT be mixed with air under pressure for leak testing or other purposes.
Refrigerants should not be exposed to open flames or electrical heating elements. High temperatures and flames can cause the refrigerants to decompose, releasing toxic and irritating fumes. In addition, a torch flame can become dramatically larger or change color if used in high concentrations of many refrigerants including R-500 or R-22, as well as many alternative refrigerants. This flame enhance­ment can cause surprise or even injury. Always recover refrigerants, evacuate equipment, and venti­late work areas properly before using any open flames.
Based on the above information, the following operating practices are recommended.
Refrigerant Recovery Systems
Efficient recovery of refrigerant from equipment or containers requires evacuation at the end of the recovery cycle. Suction lines to a recovery compressor should be periodically checked for leaks to prevent compressing air into the recovery cylinder during evacuation. In addition, the recovery cylinder pressure should be monitored, and evacuation stopped in the event of a rapid pressure rise indicating the presence of air. The recovery cylinder contents should then be ana­lyzed for NAG, and the recovery system leak checked if air is present. Do not continue to evacuate a refrigeration system that has a major leak.
Combustibility With Chlorine
Experimental data have also been reported which indicate combustibility of HCFC-22 (a component of HP80 and HP81) in the presence of chlorine.
Do Not Mix With Air For Leak Testing – Equipment should never be leak tested with a
pressurized mixture of HP62, HP80 or HP81 and air. Pressurized mixtures of dry nitrogen and HP62, HP80 or HP81 can be used for leak testing.
Bulk Delivery and Storage – Tanks should be evacuated prior to initial
filling, and should never be filled while under positive air pressure.
– Tank pressure should never be allowed to
exceed the tank manufacturer’s maximum allowable working pressure when filling with HP62, HP80 or HP81. Relief devices on either the tanks or the supply system should be
present and in good operating condition. – Tank pressures should be monitored routinely. – Air lines should never be connected to storage
tanks.
Filling and Charging Operations
– Before evacuating cylinders or refrigeration
equipment, any remaining refrigerant should
be removed by a recovery system. – Vacuum pump discharge lines should be free
of restrictions that could increase discharge
pressures and result in the formation of com-
bustible mixtures. – Cylinders or refrigeration equipment should
be evacuated at the start of filling, and
should never be filled while under positive
air pressure. – Filled cylinders should periodically be analyzed
for air (nonabsorbable gas or NAG).
Air Monitors and Leak Detection
Service personnel have used leak detection equip­ment for years when servicing equipment. Leak detectors exist not only for pinpointing specific leaks, but also for monitoring an entire room on a continual basis. There are several reasons for leak pinpointing or area monitoring, including:
• conservation of refrigerant
• protection of employees
• detection of fugitive or small emissions
• protection of equipment Leak detectors can be placed into two broad cate-
gories: leak pinpointers and area monitors. Before purchasing a monitor or pinpointer, several criteria should be considered, which include sensitivity, detection limits, and selectivity.
Types of Detectors
Using selectivity as a criterion, leak detectors can be placed into one of three categories: nonselective, halogen selective, or compound specific. In general, as the specificity of the monitor increases, so will the complexity and cost.
A different technology that can be employed to find leaks is by using a dye or other additive that is placed in the refrigeration system and is emitted with the leaking refrigerant and lubricant.
A detailed discussion of leak detection, along with a list of manufacturers of leak detection equipment, can be found in DuPont bulletin ARTD-27.
16
Nonselective Detectors
Nonselective detectors are those which will detect any type of emission or vapor present, regardless of its chemical composition. These detectors are typically quite simple to use, very rugged, inexpen­sive, and almost always portable. However, their inability to be calibrated, long-term drift, lack of selectivity, and lack of sensitivity limit their use for area monitoring.
Some nonselective detectors designed for use with R-502 may have a much lower sensitivity when used with Suva
®
HP refrigerants. However, newly designed detectors with good sensitivity for HFCs are now available. Be sure to consult with the manufacturer before selecting or using a nonselec­tive detector with Suva
®
HP refrigerants.
Halogen-Selective Detectors
Halogen-selective detectors use a specialized sen­sor that allows the monitor to detect compounds containing fluorine, chlorine, bromine, and iodine without interference from other species. The major advantage of such a detector is a reduction in the number of nuisance alarms—false alarms caused by the presence of some compound in the area other than the target compound.
With Suva
®
HP refrigerants, using compound­specific detectors may be difficult because the different mixtures often contain similar types of compounds. In an area where different refrigerant mixtures are used, these detectors may offer more specificity than is needed for normal leak manage­ment. Discuss these issues with the equipment manufacturers before making a purchase decision.
Fluorescent Additives
Fluorescent additives have been used in refrigera­tion systems for several years. These additives, invisible under ordinary lighting, but visible under ultraviolet (UV) light, are used to pinpoint leaks in systems. The additives are typically placed into the refrigeration lubricant when the system is serviced or charged. Leaks are detected by using a UV light to search for additive that has escaped from the system.
Recent innovations in dye technology have allowed fluorescent additives to be used with HFCs and new refrigerant mixtures. However, before adding addi­tives to a system, the compatibility of the specific dye with the lubricant and refrigerant should be tested.
These detectors are typically easy to use, feature higher sensitivity than the nonselective detectors (detection limits are typically <5 ppm when used as an area monitor and <1.4 g/yr [<0.05 oz/yr] when used as a leak pinpointer) and are very durable. In addition, due to the partial specificity of the detector, these instruments can be easily calibrated.
Compound-Specific Detectors
The most complex detectors, which are also the
Storage and Handling
Shipping Containers in the U.S.
Suva® HP refrigerants are liquefied compressed gases. According to the U.S. Department of Trans­portation (DOT) a nonflammable compressed gas is defined as a nonflammable material having an absolute pressure greater than 40 psia at 21°C (70°F) and/or an absolute pressure greater than 104 psia at 54°C (130°F). See Table 7 for the appropriate DOT designation.
most expensive, are compound-specific detectors. These units are typically capable of detecting the presence of a single compound without interference from other compounds.
Table 7
DOT Designations
DOT Proper Shipping Name (HP80/81) Compressed Gas N.O.S. (Contains
Pentafluoroethane and Chlorodifluoromethane)
[404A (HP62)] Compressed Gas N.O.S. (Contains
Hazard Class (All) Nonflammable Gas DOT/IMO Hazard Class (HP80/81) 2
[404A (HP62)] 2.2 UN/NA Number (All) UN 3163 DOT Labels (All) Nonflammable Gas DOT Placard (All) Nonflammable Gas
Pentafluoroethane and Trifluoroethane)
17
A list of the different types of containers that can be used to ship Suva
®
HP refrigerants in the United States, along with their water capacities, dimen­sions, DOT specifications, and net weights, are provided in Table 8. All pressure relief devices used on the containers must be in compliance with the corresponding Compressed Gas Association (CGA) Standards for compressed gas cylinders, cargo, and portable tanks.
The 15-lb, 30-lb, and 123-lb cylinders designed for refrigerant applications will be painted the colors shown in Table 8, with labels that bear the name of the product in the same color. For clarification, the colors are:
®
Suva
HP80 PMS 461 Light brown
®
Suva
HP81 PMS 385 Green brown
®
Suva
404A (HP62) PMS 021 Orange
Disposable cylinders, known as a Dispos-A-Can
®
(or DAC), fit into a box with the measurements given in Table 8. When used to ship Suva
®
HP refrigerants to the stationary refrigeration market, the cylinders will have the same outlet fittings as cylinders of R-502.
The 123-lb cylinders are equipped with a nonrefill­able liquid vapor CGA-660 valve. With this two­way valve, refrigerant can be removed from the cylinder as either vapor or liquid, without inverting the cylinder. The vapor valve handwheel is located on the top of the valve assembly. The liquid handwheel is on the side of the valve and attached to a dip tube extending to the bottom of the cylin­der. Each is clearly identified as vapor or liquid.
The 4,400-gal cylinder is known as an ISO tank. The dimensions referenced in Table 8 represent the frame in which the container is shipped. The tank itself has the same length of 20 ft and an outside diameter of approximately 86 in. ISO tanks are used for export shipments of refrigerants from the United States.
The general construction of a one-ton returnable container is shown in Figure 7. Note that one end of the container is fitted with two valves. When the container is turned so that the valves are lined up vertically, the top valve will discharge vapor and the bottom valve will discharge liquid. The valves are protected by a dome cover. The valves are Su­perior Type 660-X1-B1.
One-ton containers are equipped with two fusible plugs in each end. The fusible metal in the plugs is designed to start melting at 69°C (157°F) and completely melt at 74°C (165°F). Containers should never be heated to temperatures higher than 52°C (125°F). One spring-loaded pressure relief valve is also located in each end of the container.
Bulk Storage Systems
DuPont sells storage systems, at cost, to their re­frigeration customers. The systems are prefabri­cated, tested, and ready to install on site. The units are designed to optimize economy, efficiency and safety in the storage and dispensing of DuPont refrigerants. The delivered systems include all components, such as storage tank, pumps, piping, valves, motors, and instrumentation as an integrated unit. All systems are equipped with dual pumps to provide an installed spare. The units are skid­mounted and require only placement on a con­crete pad and connection to electrical and process systems.
Table 8
Specifications of Shipping Containers for DuPont™ Suva® HP Refrigerants
Container Dimensions DOT Spec. Net Weight (lb) Color Code
15 lb Dispos-A-Can 30 lb Dispos-A-Can
123 lb Cylinder 55" H x 10" OD 4BA300 (HP81) 110
1,682 lb ton Cylinder 82" L x 30" OD 110A500W 5,000 gal Tank Truck MC-330 or -331 40,000 4,400 gal ISO 8' x 8.5' x 20' (frame) 51 170,000 lb Rail Car 114A340W
* Dispos-A-Can is a registered trademark of the DuPont Company.
®
* 7.5" x 7.5" x 14.5" 39 (HP81 Only) 13 PMS 385
®
10" x 10" x 17" 39 (HP80) 27 PMS 461
[404A (HP62)] 24 PMS 021
[404A (HP62)] 100
4BA400 (HP80) 110
18
Figure 7. One-Ton Returnable Container
A typical bulk storage system is shown in Figure 8. Your DuPont marketing representative can arrange for guidance on site selection, purchase, installa­tion, start-up, and maintenance.
Converting Bulk Storage Tanks from R-502 to Suva
®
HP Refrigerants
Before switching any R-502 storage system to
®
HP refrigerants, the existing storage equip-
Suva ment must be checked to verify that it is adequate. Storage tanks built to the specifications of the American Society of Mechanical Engineers (ASME) Pressure Vessel Code are required to have a metal nameplate indicating each tank’s maximum allowable working pressure (MAWP). This rating must be 320 psig or higher for use with all Suva
®
HP refrigerants. In addition, the set pressure of the tank relief device must also be checked and changed if necessary. This relief setting cannot be higher than the maximum working pressure listed on the nameplate, however.
We recommend that storage tanks be completely emptied of all R-502 liquid and vapor before intro­ducing the HP refrigerant. In general, converting a storage tank to HP refrigerant requires:
1. Removing all R-502 from the storage tank, lines, and equipment.
2. Evacuating the storage tank to 25–29 in of vacuum and purging with compressed dry nitrogen gas.
3. Making necessary repairs to the tank after initial evacuation and purging.
4. Repeating step 2 until R-502 and moisture levels are within acceptable limits.
®
5. Refilling the system with Suva
HP refrigerant.
This is a simplified outline of what is actually a lengthy procedure. Your DuPont marketing repre­sentative can assist in obtaining the equipment, instrumentation, and technical assistance to safely and effectively make the conversion.
Material Compatibility Concerns
Most metal components suitable for use with R-502 are also compatible with Suva
®
HP refrigerants. These include standard grades of carbon steel, aluminum, and copper. Some elastomeric or non­metallic components suitable for R-502 may not be adequate with the new refrigerants. Therefore, all elastomeric or nonmetallic components throughout the system must be identified and their compatibil­ity with Suva
®
HP refrigerants verified. For com­plete reliability, any component that cannot be properly identified should be replaced.
In a fluorocarbon storage system, elastomers are most commonly found in:
• Packing and seats of manual valves
• Pressure relief device seats
• Flange and manway gaskets
• Mechanical pump seals
• Wet-end pump gaskets and O-rings
• Filter O-rings
• Sight-glass gaskets
• Back-pressure regulator diaphragms and O-rings
Handling Precautions for Suva® HP Refrigerant Shipping Containers
The following rules for handling HP refrigerant containers are strongly recommended:
• Use personal protective equipment such as side
shield safety glasses, gloves, and safety shoes when handling refrigerant containers.
19
Figure 8. Typical Bulk Storage System
Pressure
Gauge
Liquid Level
Gauge
Tank
Internal Safety
Relief Valves
Manway
Excess Flow Valves
Vapor
Equalizing
Line
Relief Valves
Liquid Fill Line
FEED System
Flow Indicator
Check Valve
• Avoid skin contact with refrigerants, as they may cause frostbite.
• Never heat a container to temperatures higher than 52°C (125°F).
• Never apply direct flame or live steam to a container or valve.
• Never refill disposable cylinders with anything. The shipment of refilled disposable cylinders is prohibited by DOT regulations.
• Never refill returnable cylinders without DuPont consent. DOT regulations forbid transportation of returnable cylinders refilled without DuPont authorization.
• Never use a lifting magnet or sling (rope or chain) when handling containers. A crane may be used when a safe cradle or platform is used to hold the container.
• Never use containers as rollers, supports, or for any purpose other than to carry refrigerant.
• Protect containers from any object that will result in a cut or other abrasion in the surface of the metal.
• Never tamper with the safety devices in the valves or containers.
• Never attempt to repair or alter containers or valves.
Ball Valve
Back
Pressure
Regulator
1" Pipe
Filter
Flange
To Service
Thermometer
2" Pipe
Pump
Motor
• Never force connections that do not fit. Make sure the threads on the regulators or other auxil­iary equipment are the same as those on the container valve outlets.
• Keep valves tightly closed and valve caps and hoods in place when the containers are not in use.
• Store containers under a roof to protect them from weather extremes.
• Use a vapor recovery system to collect refrigerant vapors from lines after unloading.
Recovery, Recycle, Reclamation and Disposal
Responsible use of Suva® HP refrigerants requires that the product be recovered for re-use or disposal whenever possible. DuPont purchases used refrig­erant for reclamation through its distributor net­works in the United States, Canada and Europe. In the United States, all Suva be accepted as part of this program. Recovery and re-use of refrigerant makes sense from an environ­mental and economic standpoint. In addition, the U.S. Clean Air Act prohibits known venting of CFC, HCFC, and HFC refrigerants during the maintenance, servicing or disposal of refrigeration equipment.
®
HP products will
20
Recovery
Recovery refers to the removal of refrigerant from equipment and collection in an appropriate con­tainer. As defined by the Air Conditioning and Refrigeration Institute (ARI), recovery does not involve processing or analysis of the refrigerants.
®
Suva
HP refrigerants may be recovered from re­frigeration equipment using permanent on-site equipment or many of the portable recovery devices now available in the marketplace. The portable devices contain a small compressor and an air­cooled condenser, and may be used for vapor (and in some cases, liquid) recovery. At the end of the recovery cycle, the system is evacuated thoroughly to remove vapors. In the United States, the Environ­mental Protection Agency (EPA) sets standards for recovery equipment. Before purchasing a specific recovery unit, check with the manufacturer to be sure that it contains proper materials of construc­tion and lubricant for the refrigerants you intend to recover.
Due to the fact that Suva
®
HP products are not azeotropes, it is important that all refrigerant is removed from a system during recovery or recycle. It is always recommended that refrigerant transfers be made liquid phase whenever possible to mini­mize composition changes in the products.
Recycle
Refrigerant recycle refers to reducing the contami­nant levels in used refrigerants by passing the re­frigerants through devices that separate out or reduce the amount of lubricant, water, acidity and particulates. Recycle is usually a field or shop pro­cedure with no analytical testing of refrigerant.
®
Suva
HP refrigerants may be recycled using many of the devices now available. In the United States, the EPA sets standards for these devices. Recycle
is already standard practice in many portions of the commercial refrigeration industry. Consult with the manufacturer before specifying a recycle device for any refrigerant.
®
If you routinely recycle Suva
HP refrigerants through several cycles, we recommend that you have the composition of the refrigerant checked periodically. This will prevent loss of performance in the unlikely event that the composition has shifted.
Reclamation
Reclamation refers to the reprocessing of used re­frigerant to new product specifications. Quality of the reclaimed product is verified by chemical analy­sis. In the United States, Suva
®
HP refrigerants are included in DuPont’s refrigerant reclamation pro­gram. Contact DuPont or one of our authorized distributors for further information.
Reclamation offers advantages over on-site refrig­erant recycling procedures because recycling sys­tems cannot guarantee complete removal of all contaminants. Putting refrigerants that do not meet new product specifications into expensive equip­ment may cause damage.
Disposal
Disposal refers to the destruction of used refriger­ant. Disposal may be necessary when the refriger­ant has become badly contaminated with other products and no longer meets the acceptance speci­fications of DuPont or other reclaimers. Although DuPont does not presently accept severely contami­nated refrigerant for disposal, licensed waste dis­posal firms are available. Be sure to check the qualifications of any firm before sending them used refrigerants.
21
For Further Information:
DuPont Fluorochemicals Wilmington, DE 19880-0711 (800) 235-SUVA
www.suva.dupont.com
Europe
DuPont de Nemours International S.A. 2 Chemin du Pavillon P.O. Box 50 CH-1218 Le Grand-Saconnex Geneva, Switzerland 41-22-717-5111
Canada
DuPont Canada, Inc. P.O. Box 2200, Streetsville Mississauga, Ontario
Canada L5M 2H3 (905) 821-3300
Mexico
DuPont, S.A. de C.V. Homero 206 Col. Chapultepec Morales C.P. 11570 Mexico, D.F. 52-5-722-1100
South America
DuPont do Brasil S.A. Alameda Itapecuru, 506 Alphaville 06454-080 Barueri São Paulo, Brazil 55-11-7266-8263
DuPont Argentina S.A. Casilla Correo 1888 Correo Central 1000 Buenos Aires, Argentina 54-1-311-8167
Pacific
DuPont Australia P.O. Box 930 North Sydney, NSW 2060 Australia 61-2-99236111
Japan
Mitsui DuPont Fluorochemicals
Co., Ltd. Chiyoda Honsha Bldg. 5-18, 1-Chome Sarugakucho Chiyoda-Ku, Tokyo 101-0064 Japan 81-3-5281-5805
Asia
DuPont Taiwan P.O. Box 81-777 Taipei, Taiwan 886-2-514-4400
DuPont China Limited P.O. Box TST 98851 1122 New World Office Bldg. (East Wing) Tsim Sha Tsui Kowloon, Hong Kong Phone: 852-734-5398 Fax: 852-236-83516
DuPont Thailand Ltd. 9-11 Floor, Yada Bldg. 56 Silom Road Suriyawongse, Bankrak Bangkok 10500 Phone: 66-2-238-0026 Fax: 66-2-238-4396
DuPont China Ltd. Rm. 1704, Union Bldg. 100 Yenan Rd. East Shanghai, PR China 200 002 Phone: 86-21-328-3738 Telex: 33448 DCLSH CN Fax: 86-21-320-2304
DuPont Far East Inc. 6th Floor Bangunan Samudra No. 1 JLN. Kontraktor U1/14, SEK U1 Hicom-Glenmarie Industrial Park 40150 Shah Alam, Selangor Malaysia Phone 60-3-517-2534
DuPont Korea Inc. 4/5th Floor, Asia Tower #726, Yeoksam-dong, Kangnam-ku Seoul, 135-082, Korea 82-2-721-5114
DuPont Singapore Pte. Ltd. 1 Maritime Square #07 01 World Trade Centre Singapore 0409 65-273-2244
DuPont Far East, Philippines 8th Floor, Solid Bank Bldg. 777 Paseo de Roxas Makati, Metro Manila Philippines Phone: 63-2-818-9911 Fax: 63-2-818-9659
DuPont Far East Inc. 7A Murray’s Gate Road Alwarpet Madras, 600 018, India 91-44-454-029
DuPont Far East Inc.—Pakistan 9 Khayaban-E-Shaheen Defence Phase 5 Karachi, Pakistan 92-21-533-350
DuPont Far East Inc. P.O. Box 2553/Jkt Jakarta 10001, Indonesia 62-21-517-800
The information contained herein is based on technical data and tests which we believe to be reliable and is intended for use by persons having technical skill, at their own discretion and risk. Because conditions of use are outside of DuPont control, we can assume no liability for results obtained or damages incurred through the application of the data presented.
© 2004. E. I. du PONT de NEMOURS AND COMPANY. ALL RIGHTS RESERVED. NO PART OF THIS MATERIAL MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY
ANY MEANS ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING, OR OTHERWISE WITHOUT THE PRIOR WRITTEN PERMIS­SION OF DUPONT.
(7/04) 235091D Printed in U.S.A. [Replaces: H-47122-4] Reorder No.: H-47122-5
Loading...