Dunkirk ESB0365, ESB3100, ESB4125, ESB4150, ESB5175 Installation Manual And Operating Instructions

...
EMPIRE STEAM II
OIL-FIRED CAST IRON BOILER
MODEL NUMBERS: ESB0365 ESB3100. ESB4125 ESB4150. ESB5175 ESB5200. ESB6225 ESB7275
,f
DUNKIRK 85 Middle Road
Dunkirk, NY 14048 Phone (716) 366-5500 Fax. 1716) 366-1209
www. dunkirk corn
An ECR International Brand )C_ f
An ISO 9001-2000 Certified Company
P/N 1305029, Rev ! 0 [08/04]
P/N# 1305029, Rev
Safety Symbols and Warnings 2 Ratings, Data, and Dimensions 3
Installation Procedure 4
Ventilation and Combustion Air 5 Connecting Supply and Return Piping Steam 7
Venting System Inspection and Installation 8 Oil Tank and Piping 8
Electrical Wiring 9 Thermostat Operation 9 Normal Sequence of Operation 11 Operating Instructions 11
Maintenance Procedures 14 Replacement Parts List 15
Service Checklist 20
KEEP THIS MANUAL NEAR BOILER j_
RETAIN FOR FUTURE REFERENCE
The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels
ndicates an imminently hazardous situation'_
hich, if not avoided, WILL result in death or I
r!o,s!nj,,y: j
dicates a potentially hazardous situation I
hich, if not avoided, COULD result in death I
serious injury, j/
ndicates a potential hazardous situation I
hich, if not avoided, MAY result in minor or I
oderate injury. It may also be used to alert I
gainst unsafe practices. .t)
1 0 [08/04] Printed in USA Made In USA
MPORTANT: Read the following instructlons_
OMPLETELY before mstalhngll
1. Keep boiler area clear and free from com- bustible materials, gasoline and other flam-
mable vapors and liquids.
2. DO NOT obstruct air openings to the boiler
room.
3. Modification, substitution or elimination of factory equipped, supplied or specified com-
ponents may result in property damage, per- sonal injury or the loss of life.
4. TO THE OWNER - Installation and service of this boiler must be performed by a qualified
installer.
5. TO THE INSTALLER - Leave all instructions
with the boiler for future reference.
6. When this product is installed in the Com- monwealth of Massachusetts the installation
must be performed by a Licensed Plumber or
_Licensed Gas Fitter.
J
All installations of boilers and venting should be done only by a qualified expert and in accordance with the appropriate Pennco manual. Installing or venting a boiler or any other gas appliance with improper methods
or materials may result in serious injury or death due to fire or to asphyxiation from poisonous gases such as carbon monoxide
which is odorless and invisible.
_.. J
0@
Tested For 15 LBS
ASME
/_,,or kllig Pressure
ESB0365 0.65 ESB3100 1.00 ESB4125 1.25 ESB4150 1.50 ESB5175 1.75 ESB5200 2.00 ESB6225 2.25 ESB7275 2.75
NOTES:
78 116 145 170
iiiiiiiii,1_teiaimiiiiiiiiiii!
59
87 109 128
246 363
454
533
wa_er
66 6
101 6 126 7 148 7
iii/iSq_are!iiiil
8x8x15 8x8x15 8x8x15 8x8x15
91 140 .60 80B 140 140 .85 80B 175 140
210 140 245 202 152 633 176 8 8x8x15 140 1.50 80B 280 227 170 708 197 8 8x8x15 140 1.75 70B 315 251 188 783 218.3 8 8x12x15 140 2.00 45B 385 307 230 958 267.1 8 8x12x15 140 2.25 45B
1. Add suffix"T" to denote boiler with tanktess heater•
2. I=B=R burner capacity is based on an oil heating value of 140,000 Btu/gat. and with 13% CO2.
3. Net ratings based on 170°F temperature in radiators and include 33% allowance for normal piping and pick-up toad. Consult manufacturer
for unusual piping and pick-up temperatures•
4. For altitudes above 2,000 ft. ratings maybe reduced at the rate of 4% for every 1,O00 ft. above sea level.
5. No771esizes with an H designation are Hago brand, all others are Delevan.
6. The electrical service is 120 Volts, 15 Amps, 60 Hz.
7. The MEA hum ber for the ESB series is 182-86E.
8. The MEA number for the AFG Beckett Burner used in the ESB series is 213-83-E.
DIMENSIONS (See FIG, A)
ESB-3S 16.375" 6.5" 6.0" ESB4S 20.25" 8.5" 6.0" ESB-5S 23.875" 10.25" 7.0" ESB-6S 27.5" 8.3125" 8.0" ESB-7S 31.125" 8.3125" 8.0"
TANKLESS WATER HEATER CAPACITIES
ESB0365 0.65 L-24 Available on request 11 8 ESB3100 1.00 L-24 4.5 11 8
ESB4125 1.25 L-24 4.5 13 9 ESB4150 1.50 L-24 4.5 13 9 ESB5175 1.75 L-24 5.0 15 10 ESB5200 2.00 L-24 5.0 15 10 ESB6225 2.25 L-24 5.0 17 11 ESB7275 2.75 L-24 5.0 19 12
A.S.H.E PRESSURE
f_RELZEF VALVE
V u
I FIG. A ]
STANDARD EQUIPMENT: Crated boiler, flush jacket, oil burner, target watt/liner, ASME relief valve, steam water level gauge, steam pressure gauge, steam pressure control, mechanical low water cut-off, drain valve, wiring harness, burner electric disconnect, plastic cover, 2" supply tapping, 1½" return tapping, skim
port, and primary control. (NOTE: For tankless heater units, add tankless hot water coil, and 4006 limit
control.)
All installations must conform to the requirements of the authority having jurisdiction. Such applicable requirements take precedence over the general
instructions of this manual.
Where required by the authority having jurisdiction, the installation must conform to the American Society
of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,
ANSI/ASME No. CSD-1.
Locate boiler in front offinat position before removing crate. Provide a level solid base as near chimney as possible and centrally located with respect to the heat distribution system as practical.
Allow 24 inches in the front, top and right hand side for servicing and cleaning, or removing tankless water heating coil.
It is recommended that 24 inches be allowed in back
of boiler for convenience when skimming hole is used.
When installed in a utility room, the door should be wide enough to allow the largest boiler part to enter,
or to permit replacement of another appliance such as a water heater.
The boiler shall be installed such that the oil ignition system components are protected from water (dripping, spraying, rain etc.) during appliance operation and service.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY- The boiler must not be installed on
carpeting or vinyl flooring. Minimum clearances to combustible construction are:
TOP ........................................ 24 IN.
FRONT ................................... 24 IN.
FLUE CONNECTOR ................ 9 IN.
REAR ..................................... 24 IN.
LEFT SIDE ............................... 6 IN.
RIGHT SIDE ............................ 241N.
MINIMUM CLEARANCES TO COMBUSTIBLE
CONSTRUCTION (AS SEEN FROM ABOVE)
T
24"
6" _24"--
24"
[
NOTE: Clearance for access should exceed fire protection clearance.
COMBUSTIONAIR REQUIREMENTS
(Minimum Opening Requirement)
91,000 19 100 23 46 140,000 28 140 35 70 175,000 35 175 44 88 210,000 42 210 53 106
245,000 49 245 61 122
280,000 56 280 61 140
A space w hose volume is not less than 50 cubic feet per 1000 BTU/Hour of all
appliances installed in that space (cubic feet of space = height x width x length) ** A space w hose volume is less than 50 cubic feet per I000 BTU/Hour of all
appliances installed in that space (cubic feet of space = height x w idth x length)
1. Ventilation of boiler room must be adequate enough to provide sufficient air to properly support combustion and venting.
2. When the boiler is located in an unconfined space in a building of conventional construction frame, masonry or metal, infiltration normally is adequate to provide air for combustion and ventilation. However, in any building which has been altered to conserve
energy or to minimize infiltration, the boiler area should be considered as a confined space. If there is anydoubt, install airsuppty provisions for combustion and ventilation in accordance with section 5.3, Air for Combustion and Ventilation, of the NFPA 54 1988
code, the recommendations that follow, or applicable provisions of the local building codes.
3. When the boiler is installed in an unconfined space, in a building of unusually tight construction,
air for combustion and room ventilation must be obtained from outdoors or from spaces freely
communicating with the outdoors. A permanent opening or openings having a total free area of not less than 1 square inch per 5,000 BTU per hour of
total input rating of att appliances shall be provided. Ducts may be used to convey make-up air from the
outdoors and shall have the same cross-sectional area of the openings to which they are connected.
4. When air for combustion and room ventilation is from inside buildings, the
confined space shall be provided with two permanent openings, one starting 12 inches from the top and one 12 inches from the
bottom of the enclosed space. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU per hour of the total input rating ofatl appliances in the enclosed space, but must not be less than 100 square
inches. These openings must freely communicate with the interior areas having adequate infiltration from the outside.
(Figure 1)
J _ i ¸
jl f C_O_NE'_ iL TYr=_ VErsT r_pE
VENf _'i "' E
_J
I FIGURE 1 I
5. When the boiler is installed in a confined space and atl air is provided from the outdoors, the confined
space shall be provided with two permanent openings, one commencing within 12 inches from the top and one commencing 12 inches from the bottom of the enclosure. The openings shall communicate directly,
or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. One of the following methods must be used to provide adequate air for ventilation and combustion.
A. When directly communicating with the outdoors,
each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (Figure 2)
/
CiUTLET _
AE_
!/ENI PEPE
INLET
AZR
\/ENTZLATZON LOUVERS FOR
UNIIEATED
CRAWL SPACE
/
I FIGURE 2 1
B. When communicating with the outdoors by
means of vertical ducts, each opening shall have a minimum free area I square inch per4,000 BTU per hour of totat input rating ofatt appliances inthe
enclosed space. (Figure 3)
I FIGURE 3 I
C. Ifhorizontal ducts are used, each opening shall have a minimum free area 1 square inch per
2,000 BTU per hour total input rating of all appliances in the enclosed space. (Figure 4)
VE_S
PIPE \)
/
iJ!llllll![Li_l/ll]llll_ i
D. When ducts are used, they shall be of the same cross sectional area as the free area of the area
of the openings to which they connect. The minimum dimension of rectangular air ducts shall
not be less than 3 inches.
6. In calculating free area using louvers, grills or screens for the above, consideration shall be given to their blocking effect. Screens used shall not be smaller than 1/4 inch mesh. If the free area through a design of louver or grill is known, it should be used
in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers wilt have 20-25% free area and metal louvers and grills
will have 60-75% free area. Louvers and grills shall
be fixed in the open position or interlocked with the boiler so that they are opened automatically during boiler operation.
Loading...
+ 14 hidden pages