Check Out Certifi cate ......................................... 35
Safety Symbols & Warnings
The following defi ned symbols are used throughout this
manual to notify the reader of potential hazards of varying
risk levels.
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions
COMPLETELY before installing!!
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible
materials, gasoline and other fl ammable vapors
and liquids.
DO NOT obstruct air openings to the boiler room.
Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may
result in personal injury or loss of life.
TO THE OWNER - Installation and service of this
boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with
boiler for future reference.
When this product is installed in the
Commonwealth of Massachusetts the installation
must be performed by a Licensed Plumber or
Licensed Gas Fitter.
!
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal
injury.
-- All boilers are design certifi ed for installation on noncombustible fl oor.
(3)
Air Cushion
Tank
Water
Content
(Gals.)
High
Altitude
Input
-- For installation on combustible fl oors use combustible fl oor kit.
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be
reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea
level. Reduce input rate 4% for every 1000 ft (304m) above sea level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer
before selecting boiler for installations having unusual piping and pickup requirements, such as
intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected
on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and
radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination High Limit/Low Water Cutoff
Control, Intermittent Electric Ignition Pilot System, Vent Damper Relay, Temperature/Pressure Gauge, Circulator
With Return Piping To Boiler, Main Gas Burners, Gas Control (Includes Automatic Gas Valve, Gas Pressure
Regulator, Intermittent Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve,
Spill Switch, Rollout Switch, Combination Gas Control, Automatic Vent Damper. Not Shown Are: Wiring Harness,
Thermocouple, Non-linting Safety Pilot.
4
Page 5
4 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury
.
1.
Installation must conform to requirements of authority
having jurisdiction or, in absence of such requirements,
to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2.
Where required by authority having jurisdiction,
installation must conform to the Standard for Controls
and Safety Devices for Automatically fi red Boilers,
ANSI/ASME CSD-1.
3.
Boiler series is classifi ed as Category I. Vent
installation shall be in accordance with "Venting of
Equipment ," of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or applicable provisions of local
building codes.
4.
Boiler has met safe lighting and other performance
criteria with gas manifold and control assembly on
boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Boiler shall be installed such that gas ignition system
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and
service, (circulator replacement, condensate trap,
control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney as
possible and centrally located with respect to heat
distribution system as practical.
7.
Allow 24 inches (610mm) at front and right side for
servicing and cleaning.
8.
When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to
permit replacement of another appliance such as water
heater.
!
WARNING
Fire hazard. Do not install boiler on combustible
fl ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible
fl ooring special base must be used. (See Replacement
Parts Section.) Boiler can not be installed on carpeting. Minimum clearances to combustible
construction are:
TOP ....................................18 IN. (457mm)
FRONT .........................................ALCOVE *
FLUE CONNECTOR ................. 6 IN. (152mm)
REAR ................................... 4 IN. (102mm)
CONTROL SIDE ..................... 9 IN. (229mm)
OTHER SIDE ........................... 3 IN. (76mm)
HOT WATER PIPING ................ Per Local Code
NOTE: Greater clearances for access should supersede fire
protection clearances.
* Defi nition of Alcove is three sided space with no wall in
front of boiler. ANSI standard for alcove is 18 inches from
front of appliance to leading edge of side walls as shown
below.
Figure 2 - Clearance to Combustibles
Minimum Clearances to Combustible
Construction (as seen from above)
4"
3"
BOILER
Front
9"
18"
5
Page 6
5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
• Engineered Installations. Must be approved by
authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35
cfm per Mbh for all appliances located within space.
Additional requirements where exhaust fans installed.
Interlock each appliance to mechanical air supply
system to prevent main burner operation when
mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all
appliances in space. Use a different method if
minimum volume not available.
о Standard Method. Cannot be used if known air
infi ltration rate is less than 0.40 air changes per
hour. See Table 3 for space with boiler only. Use
equation for multiple appliances.
3
Volume ≥ 50 ft
x Total Input [Mbh]
о Known Air Infi ltration Rate. See Table 3 for
space with boiler only. Use equation for multiple
appliances. Do not use an air infi ltration rate
(ACH) greater than 0.60.
Volume ≥ 21 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second
opening commencing within 12 inches of bottom
enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in
2
per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2
Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure.
Provide minimum clearance of 1 inch on sides
and back and 6 inches on front of boiler (does not
supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements
for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for application information.
National Gas and Propane Installation Code Requires
providing air supply in accordance with:
• Section 8.2 and 8.3 when combination of appliances
has a total input of up to and including 400 Mbh (120
kW).
• Section 8.4 when combination of appliances has total
input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code
for specifi c air supply requirements for enclosure
or structure where boiler is installed, including air
supply openings and ducts.
Table 3 - Ventilation & Combustion Air
Input Mbh
Standard
Method
5025001050052503500262521001750
7537501575078755250393831502625
100500021000105007000525042003500
125625026250131258750656352504375
1507500315001575010500787563005250
1708500357001785011900892571405950
200100004200021000140001050084007000
Known Air Infi ltration Rate Method ACH (Air Changes Per Hour)
0.10.20.30.40.50.6
6
Page 7
6 - SUPPLY AND RETURN PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,
scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• Connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum
distance from fl oor or allowable safe point of discharge.
• Be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge
line.
• Have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug
or place any obstruction in discharge line.
• Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing.
• Allow complete drainage of the valve and the discharge line.
• Be independently supported and securely anchored to avoid applied stress on the relief valve.
• Be as short and straight as possible.
• Terminate with plain end (not threaded).
• Be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation
requirements.
Figure 3 - Safety Relief Valve
RELIEF VALVE
DISCHARGE
LINE
Check local
codes for
maximum
distance
from fl oor
or allowable
safe point of
discharge.
7
Page 8
6 - SUPPLY AND RETURN PIPING
IMPORTANT: Circulators in the following illustrations are mounted on the system supply side, but
mounting on the system return side is also acceptable practice.
Figure 4 - Circulators Mounted on Supply System, Boiler Used In Confi guration to Chiller System.
See Special Conditions, Page 9
1.
Boiler, used in connection with a refrigeration system,
must be installed so chilled medium is piped in parallel
with boiler with appropriate valves to prevent chilled
medium from entering boiler. See Figure 4 .
2.
Boiler piping system of hot water boiler connected to
heating coils located in air handling units where they
may be exposed to refrigerated air circulation must be
equipped with fl ow control valves or other automatic
means to prevent gravity circulation of boiler water
during cooling cycle.
3.
Hot water boilers installed above radiation level or
as required by authority having jurisdiction must be
provided with a low water cut-off device.
4.
When a boiler is connected to a heating system that
utilizes multiple zoned circulators, each circulator must
be supplied with a fl ow control valve to prevent gravity
circulation.
5.
Hot water boilers and system must be fi lled with water
and maintained to a minimum pressure of 12 psi.
6.
Bypass piping is an option which gives the ability to
adjust the supply boiler water temperature to fi t the
system or the condition of the installation. This method
of piping, however, is not typically required for baseboard heating systems. Typical installations where
bypass piping is used are as follows:
A. This method is used to protect boilers from con-
densation forming due to low temperature return
water. Generally noticed in large converted gravity systems or other large water volume systems.
Figure 5 & 6, Page 9.
B. These methods are used to protect systems using
radiant panels and the material they are encased in
from high temperature supply water from the boiler
and protect the boiler from condensation.
NOTE#1: When using bypass piping, adjust
valves V1 & V2 until desired system temperature
is obtained.
7. Installation using circulators and zone valves are
shown in Figure 7, 8, 9 and 10 Pages 10, and 11. For
further piping information refer to AHRI Installation
and Piping Guide.
!
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
8. Install discharge piping from safety relief valve. See
Warning, Page 7.
9
Page 10
6 - SUPPLY AND RETURN PIPING
Figure 7 - Single Zone System With DHW Priority
Figure 8 - Multi Zone System With Circulators And DHW Priority
10
Page 11
6 - SUPPLY AND RETURN PIPING
Figure 9 - Multi Zone System With Zone Valves And DHW Priority (With Circulator)
Figure 10 - Multi Zone System With Zone Valves And DHW Priority (With Zone Valve)
11
Page 12
7 - VENT INSTALLATION
WARNING
!
Boiler and venting installations shall be performed
by a qualifi ed expert and in accordance with the
appropriate manual. Installing or venting boiler
or other gas appliance with improper methods or
materials may result in serious injury or death due
to fi re or to asphyxiation from poisonous gases such
as carbon monoxide with is odorless and invisible.
!
WARNING
Do not connect boiler to any portion of mechanical
draft system operating under positive pressure.
1.
The vent pipe must slope upward from the boiler not
less then ¼ inch for every 1 foot (21mm/m) to vent
terminal.
2.
Horizontal portions of the venting system shall be
supported rigidly every 5 feet and at the elbows. No
portion of the vent pipe should have any dips or sags.
3.
This boiler series is classifi ed as a Category I. Vent
installation shall be in accordance with "Venting of
Equipment," of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or applicable provisions of the local
building codes.
4.
Inspect chimney to make certain it is constructed
according to NFPA 211. The vent or vent connector
shall be Type B or metal pipe having resistance to heat
and corrosion not less than that of galvanized sheet
steel or aluminum not less than 0.016 inch thick (No.
28 Ga).
5.
Connect fl ue pipe from draft hood to chimney. Bolt or
screw joints together to avoid sags. Flue pipe should
not extend beyond inside wall of chimney. Do not
install manual damper in fl ue pipe or reduce size of fl ue outlet except as provided by the latest revision of
ANSI Z223.13.. Protect combustible ceiling and walls
near fl ue pipe with fi reproof insulation. Where two or
more appliances vent into a common fl ue, the area of
the common fl ue must be at least equal to the area
of the largest fl ue plus 50 percent of the area of each
additional fl ue.
8 - VENT SYSTEM MODIFICATION
When an existing boiler is removed from a common
venting system, the system is likely to be too large for the
proper venting of the appliances sill connected to it. If
this situation occurs, the following test procedure must be
followed:
REMOVAL OF BOILER FROM VENTING SYSTEM
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining connected
to the common venting system are not in operation.
1.
Seal an unused opening in the common venting
system.
2.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other defi ciencies
which could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any other appliance not
connected to the common venting system. Turn on
any exhaust fans, such as range hoods and bathroom
exhausts, so they operate at maximum speed. Do
not operate a summer exhaust fan. Close fi replace
dampers.
4.
5.
6.
7.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
After it has been determined that each appliance
remaining connected to a common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fi replace dampers and
any other gas burning appliances to their previous
condition of use.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel gas Code, ANSI Z223.1/NFPA 54.
When re-sizing any portion of the common venting
system, the common venting system should be re-sized
to approach the minimum size determined using the
appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
12
Page 13
9 - VENT DAMPER INSTALLATION & INSTRUCTIONS
DAMPER INSTALLATION
NOTE: Refer to Figure 10 for steps 1-6.
Figure 11 - Damper Motor Wiring
Vent Damper
Vent Outlet
DAMPER INSTRUCTIONS
Figure 12 - Vent Damper Placement
Damper Motor
1.
Place vent damper on or as close to vent outlet of
boiler as possible. See Figure 12 .
2.
Remove vent damper motor cover.
3.
Feed damper wire harness connector through bracket
hole on damper motor frame.
Plug damper connector into socket on damper motor
frame.
6.
Replace damper motor cover and wire damper. See
Figure 11 .
1.
Verify only boiler is serviced by vent damper. See
Figure 12 .
2.
Clearance of not less than 6 inches between vent
damper and combustible material must be maintained.
Additional clearance should be allowed for service of
vent damper.
3.
Vent damper must be in the open position when
appliance main burners are operating.
4.
Vent damper position indicator must be in a visible
location following installation.
5.
The thermostat's heat anticipator must be adjusted to
match the total current draw of all controls associated
with boiler during heating cycle.
13
Page 14
10 - CONNECTING GAS SERVICE
!
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fi re
department.
Figure 13 - Gas Piping
General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements of National Fuel gas Code, ANSI Z223.1/
NFPA 54
• Size and install gas piping system to provide suffi cient
gas supply to meet maximum input at not less than
minimum supply pressure. See Table 5 .
• Support piping with hooks straps, bands, brackets,
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
liquefi ed petroleum gas.
• Install fi eld sourced manual main shutoff valve, ground
joint union, and sediment trap upstream of gas valve.
See Figure 13 .
Table 5 - Gas Pressure
Natural GasPropane
Min. Supply Pressure5" w.c.11" w.c.
Max. Supply Pressure13.5" w.c.13.5" w.c.
Manifold Pressure3.5" w.c.10.5" w.c.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS/HOUR
(Gas Pressure = 0.5 psig or less, Pressure Drop = 5 in. w/c)
Table 4 - Pipe Sizes
Length of
Pipe (Feet)
101753606801400
20120250465950
3097200375770
4082170320660
6066138260530
8057118220460
10050103195400
For additional information refer to the National Fuel Gas
Code Handbook.
Nominal Iron Pipe Size
½”¾”1”1¼”
!
DANGER
Fire Hazard. Do not use matches, candles, open
fl ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
Leak Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
•
Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from gas
supply system.
•
Pressure test at 1/2 psig (3.5 kPa) or less. Isolate
boiler from gas supply system by closing manual gas
shutoff valve.
•
Locate leakage using gas detector, noncorrosive
detection fl uid, or other leak detection method
acceptable to authority having jurisdiction. Do not
use matches, candles, open fl ames, or other methods
providing ignition source.
•
Correct leaks immediately and retest.
14
Page 15
11 - ELECTRICAL SECTION
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Electrical Wiring
See wiring diagrams on the following two pages for
details.
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to
National Electrical Code, ANSI/NFPA 70.
Thermostat Installation
1.
Thermostat should be installed on an inside wall about
four feet above the fl oor.
2.
NEVER install a thermostat on an outside wall.
3.
Do not install a thermostat where it will be affected
by drafts, hot or cold pipes, sunlight, lighting fi xtures,
televisions, a fi replace, or a chimney.
4.
Check thermostat operation by raising and lowering
thermostat setting as required to start and stop the
burners.
5.
Instructions for the fi nal adjustment of the thermostat
are packaged with the thermostat (adjusting heating
anticipator, calibration, etc.)
15
Page 16
12 - WIRING DIAGRAM - INTERMITTENT IGNITION
Figure 14 - Intermittent Electronic Ignition Control (240009076)
!
WARNING
Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may
result in personal injury or loss of life.
16
Page 17
12 - WIRING DIAGRAM - INTERMITTENT IGNITION
Figure 15 - Intermittent Electronic Ignition Control (240009076)
17
Page 18
!
13 - LIGHTING INSTRUCTIONS
!
WARNING
If you do not follow these instructions
exactly, a fi re or explosion may result
causing property damage, personal injury
or loss of life.
• This appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to
light this burner by hand.
• Before operating smell all around appliance area
for gas. Be sure to smell next to fl oor because
some gas is heavier than air and will settle to the
fl oor.
• Use only your hand to turn the gas shutoff
valve. Never use tools. If valve will not turn by
hand, do not try to repair it, call a qualifi ed ser-
vice technician. Force or attempted repair may
result in fi re or explosion.
• Do not use this appliance if any part has
been under water. Immediately call a quali-
fi ed service technician to inspect appliance and to
replace any part of control system and any gas
control which has been under water.
OPERATING INSTRUCTIONS FOR INTERMITTENT
PILOT SYSTEM
1.
STOP! Read the safety information to the left.
2.
Set the thermostat to lowest setting.
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the
pilot by hand.
Figure 16 - Intermittent Pilot
NOTICE
Before lighting any type of pilot burner (standing or
intermittent), verify the hot water boiler and system
are full of water to minimum pressure of 12 psi in
the system, also verify system is vented of air. Set
operating control of thermostat to “below” normal
setting. Refer to following appropriate lighting
instruction.
LIGHTING PROCEDURE FOR BOILER WITH
INTERMITTENT PILOT SYSTEM
For Your Safety, Read Before Operating!!
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light
appliance by hand.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switches; do not use
any phone in your building.
5.
Turn gas control knob clockwise to “OFF.”
6.
Wait (5) minutes to clear out any gas. If you then smell
gas, STOP! Follow “What To Do If You Smell Gas” in the
safety information to the left. If you don’t smell gas, go
on to the next step.
7.
Turn gas control knob counterclockwise to “ON.”
8.
Turn on all electric power to the appliance.
9.
Set thermostat to desired setting.
10.
If the appliance will not operate, follow the instructions
“
To Turn Off Gas To Appliance
service technician or your gas supplier.
TO TURN OFF GAS TO THE APPLIANCE
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if service is
to be performed.
3.
Push in gas control knob slightly and turn clockwise
to "OFF." DO NOT FORCE.
4.
Call qualifi ed service technician.
” , and call qualifi ed
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fi re
department.
18
Page 19
14 - SEQUENCE OF OPERATION
Thermostat actuates on call for heat,
completing circuit to control. Completed
circuit to control will fi rst activate circulator
and damper which will close end switch inside
damper. Completes circuit to ignition system,
ignition takes place.
In event boiler water temperature exceeds
high limit setting on boiler mounted high limit
control, power is interrupted between control
system and ignition system. Power remains
off until boiler water temperature drops below
high limit setting. Circulator continues to
operate under this condition until thermostat is
satisfi ed.
In event fl ow of combustion products through
boiler venting system becomes blocked, blocked
vent safety switch shuts main burner gas off.
Similarly, if boiler fl ue-way becomes blocked, fl ame rollout safety switch shuts main burner
gas off. See Figure 17 . If either of these
conditions occur, do not attempt to place boiler
back into operation. Contact certifi ed service
agency.
Integral Draft
Hood
Burner
Door
Burners
Orifi ces
Figure 17 - Blocked Vent Safety Switch, Roll-
out Safety Switch
Blocked Vent
Safety Switch
Rollout Switch
4 Section Boiler
Rollout Switch
2,3,5
Section Boiler
Manifold
Base
Jacket Base
Panel
15 - GENERAL INSTRUCTIONS
Before seasonal start-up, have a certifi ed service agency
check boiler for soot and scale in fl ues, clean burners and
check gas input rate to maintain high operating effi ciency.
!
WARNING
This procedure should be followed to clean fl ue gas
passageways:
1.
Label all wires prior to disconnection when servicing
controls. Wiring errors could cause improper and
dangerous operation.
Verify proper operation after servicing
Service agency will verify system is fi lled with water to
minimum pressure and open air vents, if used, to expel any
air accumulated in the system. Check entire piping system
and, if any leaks appear, have them repaired.
Circulators need to be checked and maintained.
Refer to circulator manufacturer's instructions.
Inspect venting system at the start of each heating
season. Check vent pipe from boiler to chimney for signs of
deterioration by rust or sagging joints. Repair if necessary.
Remove vent pipe at base of chimney or fl ue and using a
mirror, check vent for obstruction and verify vent is in good
working order.
Boiler fl ue gas passageways may be inspected by a light
and mirror. Remove burner door. See
Place trouble lamp in fl ue collector through draft relief
opening. With mirror positioned above burners, fl ue gas
passageways can be checked for soot or scale.
Figure 20, Page 20
2.
3.
4.
5.
6.
When cleaning process is complete, restore boiler
components to their original position. Use IS-808 GE
silicone (available from distributor) to seal around fl ue
collector and boiler castings.
.
Remove burners from combustion chamber by raising
burners up from manifold orifi ces and pulling toward
front of boiler. See
Disconnect vent pipe from draft hood.
Remove top jacket panel.
Remove combination fl ue collector and draft hood from
boiler castings by loosening nuts on hold down bolts
located on each side of collector. See
Place sheet of heavy paper or similar material over
bottom of base and brush down fl ue passageways. Soot
and scale will collect on paper and is easily removed
with the paper.
With paper still in place in base, clean top of boiler
castings of boiler putty or silicone used to seal between
castings and fl ue collector. Verify chips are not lodged
in fl ue passageways.
Figure 17
.
Figure 17 .
19
Page 20
15 - GENERAL INSTRUCTIONS
Make visual check of main burner and pilot fl ames at start
of heating season and again in mid-season. Main burner
Figure 20 - Combustion Chamber
fl ame should have well defi ned inner blue mantel with
lighter blue outer mantel. Check burner throats and burner
orifi ces for lint or dust obstruction.
See Figures 17 and 19
BURNERS
.
Figure 18 - Gas Burner Flame
Pilot fl ame should envelop ⅜ to ½ inch of tip of pilot
Figure 19 - Gas Burner Pilot
thermocouple, ignition/sensing electrode or mercury
sensor. See
GAS VALVE
ORIFICES
Figure 19 .
To adjust pilot fl ame, remove pilot adjustment cover screw
and turn inner adjustment screw counterclockwise to
increase or clockwise to decrease pilot fl ame.
Be sure to replace cover screw after adjustment to prevent
possible gas leakage. See Figure 14, Page 16 .
Burners and pilot should be checked for signs of corrosion,
rust or scale buildup.
Area around boiler must be kept clear and free of
combustible materials, gasoline and other fl ammable
vapors and liquids.
Free fl ow of combustion and ventilating air to boiler and
boiler room must not be restricted or blocked.
Inspect fi eld sourced low water cutoffs annually, or as
recommended by low water cutoff manufacturer. Flush
fl oat type low water cutoffs per manufacturer's instructions.
Employ a qualifi ed service agency to make annual
inspection of boiler and heating system. They are
experienced in making the inspections outlined above,
and, in event repairs or corrections are necessary, trained
technicians can make the proper changes for safe operation
of the boiler.
20
Page 21
16 - CHECKING GAS INPUT RATE TO BOILER
ce
cessG
O
rating Control
ated I
de
ler
• Adjust gas input to boiler by removing protective cap on
pressure regulator
increase input and counterclockwise
,
and turning screw clockwise to
to decrease
input.
• Manifold pressures are taken at outlet side of gas
valve.
• To check for proper fl ow of natural gas to boiler, divide
input rate shown on rating plate by heating value of
gas obtained from local gas company. This determines
number of cubic feet of gas required per hour.
• With all other gas appliances off, determine fl ow of gas
through meter for two minutes and multiply by 30 to
get hourly rate.
• Make minor adjustments to gas input as described
above.
• Change burner orifi ces if fi nal manifold pressure
Burner Access
varies more than plus or minus 0.3 inches water
column from specifi ed pressure.
• Primary air adjustment is not necessary, therefore
air shutters are not furnished as standard
equipment.
Figure 21 - High Limit Control Location
High Limit and
Operating Control
Located Inside Boiler
Door
nsi
Boi
• Air shutters can be furnished on request where
required by local codes or conditions.
CHECK SAFETY CONTROL CIRCUIT. Test ignition
system safety shutoff device after placing boiler in
operation.
1.
Pilot: With main burner operating, turn pilot gas
adjusting screw clockwise until pilot gas is
turned off. Within 90 seconds main gas control closes,
shutting off gas to main burner.
2.
High Limit Control: Remove cover and note
temperature setting. Decrease this setting to minimum
and operate boiler. When the boiler water temperature
exceeds the control temperature setting, the control
will open the circuit, closing the automatic main gas
valve. See Figure 21 .
Gas Valve
21
Page 22
17 - OPERATING THE BOILER - SETTING THE CONTROL
Wiring An Indirect Water Heater
SETTING
When installing with indirect water heater, signal from
indirect must be separated from heating zone signals and
wired appropriately.
If you choose not to separate indirect signal from heating
zones, Economy Feature should be turned off to insure
boiler supplies adequate temperature to heat the indirect
tank.
Setting The Control
Settings can be checked using the TEST/SETTINGS Button.
See page 23 for details.
Setting The High Limit
The high limit is factory set at 190°F. To adjust, turn
HI TEMP dial A until desired setting is displayed.
(Setting range: 130°F - 220°F)
Setting The Low Limit
Low limit is designed to maintain temperature in boiler
suitable for domestic hot water. Low limit is factory set to
OFF. Prior to adjusting, remove the jumper (not equipped
on all units) B.
Then turn LO Temp dial C clockwise until desired
temperature is displayed. For Proper operation, low
temperature limit setting should be at least 10° below high
Temperature
Limit Setting
(130°-220°F)
Factory 190°F
Economy Dial
1,2,3,4,5,HI)
limit setting. For cold start operation, low limit must be
turned OFF. If low limit temperature cannot be set above
140°F, remove jumper B. (Setting range: OFF or 110°-
200°F).
Dynamic Display
Setting The Economy Feature
Economy Feature is factory set for 1 zone heating
system. To adjust, turn the ECONOMY dial D until the
number displayed equals the number of heating zones.
The Economy Feature conserves fuel by reducing boiler
temperature. If heating system is unable to supply needed
heat to the house, Economy dial should be turned to lower
setting (example: In a three zone house, turn dial to 2 or
1). Conversely, if boiler provides adequate heat, added
fuel savings can be achieved by selecting a higher setting
(example: 4 or 5). If heating and indirect water heater
signals were not separated when wiring control, Economy
Feature should be turned OFF to insure boiler supplies
adequate temperature to heat the indirect tank.
Activation Thermal Pre-Purge (Optional)
Activation of this feature is not recommended for boiler
supplying domestic hot water.
Fuel Smart HydroStat has a Thermal Pre-Purge feature to
maximize effi ciency. When activated, control will purge
higher boiler temperatures down to 135°F at start of any
thermostat call and supply the latent energy in the boiler
to the heating zone that is calling. During the purge cycle,
the display will indicate Pur. If the heat is not suffi cient to
satisfy the thermostat, control will energize burner. Feature
works with single and multi-zone heating systems utilizing
circulators or zone valves. No change in wiring is needed.
To Activate Thermal Pre-Purge
Push and hold the TEST/SETTINGS button for 20 seconds.
Display will read Pur On. To deactivate this feature, push
and hold button a second time for 20 seconds. Display will
read Pur OFF.
Disables economy function. Will allow boiler to fi re
OFF
LO
1
2
3
4
5
HI
High
(OFF or LO,
Jumper
Temperature
and Real Time
Verifi cation
of Setting
Adjustments.
until hi-limit temp is reached and re-fi re with a 10°
subtractive differential.
Provides lowest level of fuel savings. Use this setting only if the house does not stay warm at higher
settings.
Recommended setting for single zone systems.
Recommended setting for Two zone systems.
Recommended setting for Three zone systems.
Recommended setting for Four zone systems.
Recommended setting for Five zone systems.
Provides highest level of fuel savings.
B
Water
Decimal Point
(Indicates heat call)
Differentials
are automatic
and will vary
based on
control settings
and boiler
temperature
Low
Temperature
Limit Setting
(OFF or 110°-
200°F) Factory
Off
Diagnostic LEDs
and Test Buttton
22
Page 23
17 - OPERATING THE BOILER - SYSTEM START-UP
System Start-up
At initial start-up, with Economy feature active, control
establishes 145°F target temperature. To test the high
limit shut-off function, Economy Dial must be turned to
OFF. Once tested, restore the Economy setting. If heating
demand is high, target will increase over time to satisfy
heat load. to reduce potential for condensing, control
will allow boiler to heat to 120°F prior to energizing the
circulator.
How Thermal Targeting Works
Thermal targeting technology analyzes thermostat activity
and continually evaluates how much heat the house
requires. When it is very cold outside, heat demand is
high and Fuel Smart HydroStat will raise boiler's target
temperature to provide needed heat to the home. When
outside temperature is milder, heat demand is lower. During
these periods, Fuel smart HydroStat will lower boiler's
target temperature saving fuel while continuing to provide
comfort to the house.
LED Legend
TARGET/HI LIMIT
Illuminates when boiler temperature has reached target
temperature or high limit setting. When economy feature
is active, the control utilizes thermal targeting technology
to operate boiler at reduced target temperatures (during
off-peak demand) or at high limit setting (during peak
demand). When boiler water temperature reaches the
target or high limit temperature, LED illuminates and
burner shuts down. Boil water continues to circulate and
heat the house as long as thermostat call continues.
The LED will stay lit until boiler temperature drops to
predetermined differential. The LED illuminates regularly
during normal operation.
BURNER
Illuminates whenever the burner is running (B1 is
powered).
Test/Settings Button
To test low water cut-off: Press and hold TEST/SETTINGS
button for 5 seconds. Display will read LCO.
LOW WATER
Illuminates if boiler is in a low water condition. Control will
prevent burner operation during this condition.
NOTICE
System must be checked by a qualifi ed heating
professional prior to resuming operation.
WARNING
!
Burn and scald hazard. Do not add water until boiler
has fully cooled. Failure to follow these instructions
could result in death or serious injury.
T-STAT
Illuminates whenever there is a call for heat from any
thermostat, zone device or indirect.
The red Low Water light should illuminate and burner circuit
(B1 and B2) should energize.
To View Current Settings: Press and release the TEST/
SETTINGS button in short intervals to sequentially display
following settings:
The display will return to boiler temperature (default) if
TEST/SETTINGS button is not pressed for 5 seconds.
23
Page 24
17 - OPERATING THE BOILER - LIMIT CONTROL TROUBLESHOOTING
Fahrenheit/Celsius Change
Control has the ability to operate in degrees Fahrenheit
(default setting) or Celsius.
To change from Fahrenheit to Celsius:
1.
Set low limit to 112°F
2.
Set high limit to 112°F
3.
Display will delay 2 seconds and then display an "F".
4.
Push the LWCO Test Button to change setting to "C".
5.
Reset the limit dials to the correct settings.
When control is in Celsius mode, a "c" appears in
temperature display as third digit whenever temperature is
below 100°C.
WARNING
!
Burn and scald hazard. Do not add water until boiler
has fully cooled. Failure to follow these instructions
could result in death or serious injury.
Table 6 - LIMIT CONTROL TROUBLESHOOTING
Temperature Display Exceeds
High Limit Setting
No Domestic Hot Water from
Tankless Coil
Boiler will Not Maintain Low
Limit Temperature
Under normal operation, boiler temperature continues to rise after control shuts off the
burner. This condition, known as "thermal stacking", results from hot boiler surfaces
continuing to release heat into the boiler.
Make sure low limit setting on Control is properly set.
If low limit setting is dialed fully counter clockwise, it shuts off the low temperature
maintenance feature.
Check for overlapping high temperature setting. If high limit setting is below low limit
setting, control will default to high limit setting.
To change from Celsius to Fahrenheit:
1.
Set low limit to 44°C.
2.
Set high limit to 44°C.
3.
Display will delay 2 seconds and then display a "c".
4.
Push the LWCO test button to change settings to "F".
5.
Re-set limit dials to correct settings.
Temperature Display Differs
from Boiler Temperature
Pressure Gauge Temperature
Reading
TSTAT Light (Green LED) is
Not On
Low Water Light (RED LED)
is On
Temperature variances can result from differing water temperatures within the boiler or
different reaction times of the two devices. If the control temperature is signifi cantly below
the temperature pressure gauge temperature, make sure the thermistor is inserted all the
way to the end of the well. DO NOT USE ANY HEAT TRANSFER PASTE OR GREASE.
The TSTAT light indicates when there is a call for heat. If a call is known to be present and
this light is on, check the wiring to the T-T terminals.
READ WARNING ABOVE. Low water condition is a serious and potentially dangerous
condition. Do not attempt to add water to a hot boiler. Allow boiler to fully cool before
adding water.
1.
If heating system is fi lled with water, pull sensor out of well and inspect it. Verify the
metal clip on the sensor is intact. This metal clip must be in contact with the inside of
the copper well in order for control to sense presence of water. Check well does not
have excessive build-up of heat transfer grease that may interfere with clip contacting
well.
2.
Remove well and examine for excessive residue build-up. Clean and re-install.
24
Page 25
18 - SYSTEM TROUBLESHOOTING
TABLE 7 - SYSTEM TROUBLESHOOTING
If installed with indirect water heater, insure end switch in relay box
No Or Insuffi cient Domestic
Hot Water
House Will Not Get Or Stay
Warm
controlling indirect water heater is properly connected to cable 2 (see
wiring diagram). This insures domestic water calls are prioritized. If cable
2 is not used, turn Economy Feature OFF.
1.
Check for air bond radiators.
2.
Check thermostat settings including het anticipator settings (common
on non-digital thermostats).
3.
Check Economy settings. Economy feature, much like outdoor reset
controls, lowers average boiler temperature, can slow or prevent
house from coming up to temperature. Move to lower setting.
25
Page 26
NOTES
Page 27
DateService PerformedCompany Name & Tech InitialsCompany Address & Phone #
Page 28
DUNKIRK BOILERS
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.