Dunkirk DXL-50 User Manual

DXL SERIES II
CAST IRON GAS FIRED BOILERS
Models
DXL-50
DXL-75 DXL-100 DXL-125 DXL-150 DXL-1 70 DXL-200
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
An ISO 9001-2008 Certified Company
Tested For 100 psi.
ASME
Working Pressure
Manufacturedby:
ECRInternational,Inc.
2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com
P/N 2400009041, Rev. B [09/2012]
4½"
¼¼
¼
C
A
4
Figure 1 - Dimensions
1- DIMENSIONS
"E"
"F"
"B"
"A"
"C"
3½"
4¼"
4½"
1¼" Supply
14"
4¼"
27"
5½"
3"
1¼" Return
"D"
2½"
Table 1 - Dimensions
Boiler No.
50 ½" 11"5½" 4" 30¾"
75 ½" 15 7½" 5" 30¾" 36¾" 6" 1¼" 100 ½" 15 7½" 6" 30¾" 37¼" 6½" 1¼" 125 ½" 18"9½" 6" 30¾" 37¼" 6½" 1¼" 150 ½" 18"9½" 7" 30¾" 37¾" 7" 1¼" 170 ½" 22¾"11½" 7" 30¾" 38¾" 7" 1¼" 200 ½" 22¾"11½" 8" 30¾" 38¾" 8" 1¼"
Natural Gas
Inlet*
ABCDEF
Dimensions
36¾"
Pump size Supply &
Return Tappings
6" 1¼"
2
2 - SAFETY SYMBOLS & WARNINGS
!
1- Dimensions .....................................................2
2 - Safety Symbols & Warnings .............................3
3 - Ratings & Data - Natural Gas & Propane Gas ...... 4
4 - Installation Procedure .....................................5
5 - Ventilation & Combustion Air ............................ 6
6 - Supply And Return Piping ................................7
7 - Vent Installation ........................................... 12
8 - Vent System Modifi cation ............................... 12
9 - Vent Damper Installation & Instructions ........... 13
10 - Connecting Gas Service ............................... 14
11 - Electrical Section ........................................ 15
12 - Wiring Diagram - Intermittent Ignition ........... 16
13 - Lighting Instructions ................................... 18
14 - Sequence Of Operation ................................ 19
15 - General Instructions .................................... 19
16 - Checking Gas Input Rate To Boiler ................. 21
17 - Setting The Control ..................................... 22
17 - System Start-Up ......................................... 23
17 - Limit Control Troubleshooting ...................... 24
18 - System Troubleshooting ............................... 25
Parts, Kits and Accessories.................................. 27
Warranty .......................................................... 33
Check Out Certifi cate ......................................... 35
Safety Symbols & Warnings
The following defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions COMPLETELY before installing!!
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room. Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may result in personal injury or loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
3
3 - RATINGS & DATA - NATURAL GAS & PROPANE GAS
Table 2 - Ratings and Capacities
(2)
Boiler
No.
(1)
Input
Mbh
(1)
Heating
Capacity
Mbh
Net AHRI
Rating
Water
Mbh AFUE
No.
of
Burners
Recommended
50 50 42 37 83.5 1 15 2.4 45,000
75 75 63 55 83.1 2 15 4.0 67,500 100 100 83 72 83.0 2 30 4.0 90,000 125 125 104 90 82.0 3 30 5.6 112,500 150 150 124 108 83.0 3 30 5.6 135,000 170 170
139
121 82.0 4 30 7.2 153,000
200 200 165 143 82.0 4 30 7.2 180,000
EXPLANATORY NOTES
-- All boilers are design certifi ed for installation on noncombustible fl oor.
(3)
Air Cushion
Tank
Water
Content
(Gals.)
High
Altitude
Input
-- For installation on combustible fl oors use combustible fl oor kit.
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea
level. Reduce input rate 4% for every 1000 ft (304m) above sea level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer
before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination High Limit/Low Water Cutoff
Control, Intermittent Electric Ignition Pilot System, Vent Damper Relay, Temperature/Pressure Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Gas Control (Includes Automatic Gas Valve, Gas Pressure Regulator, Intermittent Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Combination Gas Control, Automatic Vent Damper. Not Shown Are: Wiring Harness, Thermocouple, Non-linting Safety Pilot.
4
4 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury
.
1.
Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2.
Where required by authority having jurisdiction, installation must conform to the Standard for Controls and Safety Devices for Automatically fi red Boilers, ANSI/ASME CSD-1.
3.
Boiler series is classifi ed as Category I. Vent installation shall be in accordance with "Venting of Equipment ," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
4.
Boiler has met safe lighting and other performance criteria with gas manifold and control assembly on boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Boiler shall be installed such that gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney as possible and centrally located with respect to heat distribution system as practical.
7.
Allow 24 inches (610mm) at front and right side for servicing and cleaning.
8.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as water heater.
!
WARNING
Fire hazard. Do not install boiler on combustible ooring or carpeting. Failure to follow these instructions could result in death or serious injury.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement
Parts Section.) Boiler can not be installed on carpeting. Minimum clearances to combustible
construction are:
TOP ....................................18 IN. (457mm)
FRONT .........................................ALCOVE *
FLUE CONNECTOR ................. 6 IN. (152mm)
REAR ................................... 4 IN. (102mm)
CONTROL SIDE ..................... 9 IN. (229mm)
OTHER SIDE ........................... 3 IN. (76mm)
HOT WATER PIPING ................ Per Local Code
NOTE: Greater clearances for access should supersede fire
protection clearances. * Defi nition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
Figure 2 - Clearance to Combustibles
Minimum Clearances to Combustible
Construction (as seen from above)
4"
3"
BOILER
Front
9"
18"
5
5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
• Engineered Installations. Must be approved by authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if minimum volume not available.
о Standard Method. Cannot be used if known air
infi ltration rate is less than 0.40 air changes per hour. See Table 3 for space with boiler only. Use equation for multiple appliances.
3
Volume 50 ft
x Total Input [Mbh]
о Known Air Infi ltration Rate. See Table 3 for
space with boiler only. Use equation for multiple appliances. Do not use an air infi ltration rate (ACH) greater than 0.60.
Volume 21 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s) communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in
2
per 4 Mbh of total
input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2 Mbh of total input rating of all appliances in enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides and back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for application information.
National Gas and Propane Installation Code Requires providing air supply in accordance with:
• Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
• Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code for specifi c air supply requirements for enclosure or structure where boiler is installed, including air supply openings and ducts.
Table 3 - Ventilation & Combustion Air
Input Mbh
Standard
Method
50 2500 10500 5250 3500 2625 2100 1750
75 3750 15750 7875 5250 3938 3150 2625
100 5000 21000 10500 7000 5250 4200 3500
125 6250 26250 13125 8750 6563 5250 4375
150 7500 31500 15750 10500 7875 6300 5250
170 8500 35700 17850 11900 8925 7140 5950
200 10000 42000 21000 14000 10500 8400 7000
Known Air Infi ltration Rate Method ACH (Air Changes Per Hour)
0.1 0.2 0.3 0.4 0.5 0.6
6
6 - SUPPLY AND RETURN PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• Connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from fl oor or allowable safe point of discharge.
• Be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line.
• Have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or place any obstruction in discharge line.
• Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing.
• Allow complete drainage of the valve and the discharge line.
• Be independently supported and securely anchored to avoid applied stress on the relief valve.
• Be as short and straight as possible.
• Terminate with plain end (not threaded).
• Be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
Figure 3 - Safety Relief Valve
RELIEF VALVE
DISCHARGE
LINE
Check local
codes for
maximum
distance
from fl oor
or allowable
safe point of
discharge.
7
6 - SUPPLY AND RETURN PIPING
IMPORTANT: Circulators in the following illustrations are mounted on the system supply side, but mounting on the system return side is also acceptable practice.
Figure 4 - Circulators Mounted on Supply System, Boiler Used In Confi guration to Chiller System.
See Special Conditions, Page 9
1.
Boiler, used in connection with a refrigeration system, must be installed so chilled medium is piped in parallel with boiler with appropriate valves to prevent chilled medium from entering boiler. See Figure 4 .
2.
Boiler piping system of hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with fl ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
3.
Hot water boilers installed above radiation level or as required by authority having jurisdiction must be provided with a low water cut-off device.
4.
When a boiler is connected to a heating system that utilizes multiple zoned circulators, each circulator must be supplied with a fl ow control valve to prevent gravity circulation.
5.
Hot water boilers and system must be fi lled with water and maintained to a minimum pressure of 12 psi.
6.
Bypass piping is an option which gives the ability to adjust the supply boiler water temperature to fi t the system or the condition of the installation. This method of piping, however, is not typically required for base­board heating systems. Typical installations where bypass piping is used are as follows:
A. This method is used to protect boilers from con-
densation forming due to low temperature return water. Generally noticed in large converted grav­ity systems or other large water volume systems.
Figure 5 & 6, Page 9.
B. These methods are used to protect systems using
radiant panels and the material they are encased in from high temperature supply water from the boiler
and protect the boiler from condensation.
NOTE#1: When using bypass piping, adjust
valves V1 & V2 until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping
as the supply and return piping.
8
6 - SUPPLY AND RETURN PIPING
Figure 5 - Bypass Piping Automatic Mixing Valve
TO SYSTEM
WATER INLET
EXPANSION
TANK
FROM SYSTEM
CIRCULATOR
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BOILER
BALL VALVE
3 WAY MIXING VALVE
ALTERNATE
CIRCULATOR
LOCATION
AIR SEPARATOR
HOSE BIB
Figure 6 - Bypass Piping - Fixed Low Temp Only Manual Mixing Valve
TO SYSTEM
WATER INLET
SYSTEM
CIRCULATOR
EXPANSION
TANK
V2V1
BOILER
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
7. Installation using circulators and zone valves are
shown in Figure 7, 8, 9 and 10 Pages 10, and 11. For further piping information refer to AHRI Installation and Piping Guide.
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
8. Install discharge piping from safety relief valve. See
Warning, Page 7.
9
Loading...
+ 19 hidden pages