Dunkirk DXL-50 User Manual

Page 1
DXL SERIES II
CAST IRON GAS FIRED BOILERS
Models
DXL-50
DXL-75 DXL-100 DXL-125 DXL-150 DXL-1 70 DXL-200
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2008 Certified Company
An ISO 9001-2008 Certified Company
Tested For 100 psi.
ASME
Working Pressure
Manufacturedby:
ECRInternational,Inc.
2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com
P/N 2400009041, Rev. B [09/2012]
Page 2
4½"
¼¼
¼
C
A
4
Figure 1 - Dimensions
1- DIMENSIONS
"E"
"F"
"B"
"A"
"C"
3½"
4¼"
4½"
1¼" Supply
14"
4¼"
27"
5½"
3"
1¼" Return
"D"
2½"
Table 1 - Dimensions
Boiler No.
50 ½" 11"5½" 4" 30¾"
75 ½" 15 7½" 5" 30¾" 36¾" 6" 1¼" 100 ½" 15 7½" 6" 30¾" 37¼" 6½" 1¼" 125 ½" 18"9½" 6" 30¾" 37¼" 6½" 1¼" 150 ½" 18"9½" 7" 30¾" 37¾" 7" 1¼" 170 ½" 22¾"11½" 7" 30¾" 38¾" 7" 1¼" 200 ½" 22¾"11½" 8" 30¾" 38¾" 8" 1¼"
Natural Gas
Inlet*
ABCDEF
Dimensions
36¾"
Pump size Supply &
Return Tappings
6" 1¼"
2
Page 3
2 - SAFETY SYMBOLS & WARNINGS
!
1- Dimensions .....................................................2
2 - Safety Symbols & Warnings .............................3
3 - Ratings & Data - Natural Gas & Propane Gas ...... 4
4 - Installation Procedure .....................................5
5 - Ventilation & Combustion Air ............................ 6
6 - Supply And Return Piping ................................7
7 - Vent Installation ........................................... 12
8 - Vent System Modifi cation ............................... 12
9 - Vent Damper Installation & Instructions ........... 13
10 - Connecting Gas Service ............................... 14
11 - Electrical Section ........................................ 15
12 - Wiring Diagram - Intermittent Ignition ........... 16
13 - Lighting Instructions ................................... 18
14 - Sequence Of Operation ................................ 19
15 - General Instructions .................................... 19
16 - Checking Gas Input Rate To Boiler ................. 21
17 - Setting The Control ..................................... 22
17 - System Start-Up ......................................... 23
17 - Limit Control Troubleshooting ...................... 24
18 - System Troubleshooting ............................... 25
Parts, Kits and Accessories.................................. 27
Warranty .......................................................... 33
Check Out Certifi cate ......................................... 35
Safety Symbols & Warnings
The following defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions COMPLETELY before installing!!
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room. Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may result in personal injury or loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
3
Page 4
3 - RATINGS & DATA - NATURAL GAS & PROPANE GAS
Table 2 - Ratings and Capacities
(2)
Boiler
No.
(1)
Input
Mbh
(1)
Heating
Capacity
Mbh
Net AHRI
Rating
Water
Mbh AFUE
No.
of
Burners
Recommended
50 50 42 37 83.5 1 15 2.4 45,000
75 75 63 55 83.1 2 15 4.0 67,500 100 100 83 72 83.0 2 30 4.0 90,000 125 125 104 90 82.0 3 30 5.6 112,500 150 150 124 108 83.0 3 30 5.6 135,000 170 170
139
121 82.0 4 30 7.2 153,000
200 200 165 143 82.0 4 30 7.2 180,000
EXPLANATORY NOTES
-- All boilers are design certifi ed for installation on noncombustible fl oor.
(3)
Air Cushion
Tank
Water
Content
(Gals.)
High
Altitude
Input
-- For installation on combustible fl oors use combustible fl oor kit.
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea
level. Reduce input rate 4% for every 1000 ft (304m) above sea level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer
before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination High Limit/Low Water Cutoff
Control, Intermittent Electric Ignition Pilot System, Vent Damper Relay, Temperature/Pressure Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Gas Control (Includes Automatic Gas Valve, Gas Pressure Regulator, Intermittent Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Combination Gas Control, Automatic Vent Damper. Not Shown Are: Wiring Harness, Thermocouple, Non-linting Safety Pilot.
4
Page 5
4 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury
.
1.
Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
2.
Where required by authority having jurisdiction, installation must conform to the Standard for Controls and Safety Devices for Automatically fi red Boilers, ANSI/ASME CSD-1.
3.
Boiler series is classifi ed as Category I. Vent installation shall be in accordance with "Venting of Equipment ," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
4.
Boiler has met safe lighting and other performance criteria with gas manifold and control assembly on boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Boiler shall be installed such that gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney as possible and centrally located with respect to heat distribution system as practical.
7.
Allow 24 inches (610mm) at front and right side for servicing and cleaning.
8.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as water heater.
!
WARNING
Fire hazard. Do not install boiler on combustible ooring or carpeting. Failure to follow these instructions could result in death or serious injury.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement
Parts Section.) Boiler can not be installed on carpeting. Minimum clearances to combustible
construction are:
TOP ....................................18 IN. (457mm)
FRONT .........................................ALCOVE *
FLUE CONNECTOR ................. 6 IN. (152mm)
REAR ................................... 4 IN. (102mm)
CONTROL SIDE ..................... 9 IN. (229mm)
OTHER SIDE ........................... 3 IN. (76mm)
HOT WATER PIPING ................ Per Local Code
NOTE: Greater clearances for access should supersede fire
protection clearances. * Defi nition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
Figure 2 - Clearance to Combustibles
Minimum Clearances to Combustible
Construction (as seen from above)
4"
3"
BOILER
Front
9"
18"
5
Page 6
5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
• Engineered Installations. Must be approved by authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if minimum volume not available.
о Standard Method. Cannot be used if known air
infi ltration rate is less than 0.40 air changes per hour. See Table 3 for space with boiler only. Use equation for multiple appliances.
3
Volume 50 ft
x Total Input [Mbh]
о Known Air Infi ltration Rate. See Table 3 for
space with boiler only. Use equation for multiple appliances. Do not use an air infi ltration rate (ACH) greater than 0.60.
Volume 21 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s) communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in
2
per 4 Mbh of total
input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2 Mbh of total input rating of all appliances in enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides and back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for application information.
National Gas and Propane Installation Code Requires providing air supply in accordance with:
• Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
• Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code for specifi c air supply requirements for enclosure or structure where boiler is installed, including air supply openings and ducts.
Table 3 - Ventilation & Combustion Air
Input Mbh
Standard
Method
50 2500 10500 5250 3500 2625 2100 1750
75 3750 15750 7875 5250 3938 3150 2625
100 5000 21000 10500 7000 5250 4200 3500
125 6250 26250 13125 8750 6563 5250 4375
150 7500 31500 15750 10500 7875 6300 5250
170 8500 35700 17850 11900 8925 7140 5950
200 10000 42000 21000 14000 10500 8400 7000
Known Air Infi ltration Rate Method ACH (Air Changes Per Hour)
0.1 0.2 0.3 0.4 0.5 0.6
6
Page 7
6 - SUPPLY AND RETURN PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• Connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from fl oor or allowable safe point of discharge.
• Be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line.
• Have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or place any obstruction in discharge line.
• Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing.
• Allow complete drainage of the valve and the discharge line.
• Be independently supported and securely anchored to avoid applied stress on the relief valve.
• Be as short and straight as possible.
• Terminate with plain end (not threaded).
• Be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
Figure 3 - Safety Relief Valve
RELIEF VALVE
DISCHARGE
LINE
Check local
codes for
maximum
distance
from fl oor
or allowable
safe point of
discharge.
7
Page 8
6 - SUPPLY AND RETURN PIPING
IMPORTANT: Circulators in the following illustrations are mounted on the system supply side, but mounting on the system return side is also acceptable practice.
Figure 4 - Circulators Mounted on Supply System, Boiler Used In Confi guration to Chiller System.
See Special Conditions, Page 9
1.
Boiler, used in connection with a refrigeration system, must be installed so chilled medium is piped in parallel with boiler with appropriate valves to prevent chilled medium from entering boiler. See Figure 4 .
2.
Boiler piping system of hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with fl ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
3.
Hot water boilers installed above radiation level or as required by authority having jurisdiction must be provided with a low water cut-off device.
4.
When a boiler is connected to a heating system that utilizes multiple zoned circulators, each circulator must be supplied with a fl ow control valve to prevent gravity circulation.
5.
Hot water boilers and system must be fi lled with water and maintained to a minimum pressure of 12 psi.
6.
Bypass piping is an option which gives the ability to adjust the supply boiler water temperature to fi t the system or the condition of the installation. This method of piping, however, is not typically required for base­board heating systems. Typical installations where bypass piping is used are as follows:
A. This method is used to protect boilers from con-
densation forming due to low temperature return water. Generally noticed in large converted grav­ity systems or other large water volume systems.
Figure 5 & 6, Page 9.
B. These methods are used to protect systems using
radiant panels and the material they are encased in from high temperature supply water from the boiler
and protect the boiler from condensation.
NOTE#1: When using bypass piping, adjust
valves V1 & V2 until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping
as the supply and return piping.
8
Page 9
6 - SUPPLY AND RETURN PIPING
Figure 5 - Bypass Piping Automatic Mixing Valve
TO SYSTEM
WATER INLET
EXPANSION
TANK
FROM SYSTEM
CIRCULATOR
SHUT-OFF VALVE
PRESSURE REDUCER VALVE
CHECK VALVE
BOILER
BALL VALVE
3 WAY MIXING VALVE
ALTERNATE
CIRCULATOR
LOCATION
AIR SEPARATOR
HOSE BIB
Figure 6 - Bypass Piping - Fixed Low Temp Only Manual Mixing Valve
TO SYSTEM
WATER INLET
SYSTEM
CIRCULATOR
EXPANSION
TANK
V2V1
BOILER
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
7. Installation using circulators and zone valves are
shown in Figure 7, 8, 9 and 10 Pages 10, and 11. For further piping information refer to AHRI Installation and Piping Guide.
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
8. Install discharge piping from safety relief valve. See
Warning, Page 7.
9
Page 10
6 - SUPPLY AND RETURN PIPING
Figure 7 - Single Zone System With DHW Priority
Figure 8 - Multi Zone System With Circulators And DHW Priority
10
Page 11
6 - SUPPLY AND RETURN PIPING
Figure 9 - Multi Zone System With Zone Valves And DHW Priority (With Circulator)
Figure 10 - Multi Zone System With Zone Valves And DHW Priority (With Zone Valve)
11
Page 12
7 - VENT INSTALLATION
WARNING
!
Boiler and venting installations shall be performed by a qualifi ed expert and in accordance with the appropriate manual. Installing or venting boiler or other gas appliance with improper methods or materials may result in serious injury or death due to fi re or to asphyxiation from poisonous gases such as carbon monoxide with is odorless and invisible.
!
WARNING
Do not connect boiler to any portion of mechanical draft system operating under positive pressure.
1.
The vent pipe must slope upward from the boiler not less then ¼ inch for every 1 foot (21mm/m) to vent terminal.
2.
Horizontal portions of the venting system shall be supported rigidly every 5 feet and at the elbows. No portion of the vent pipe should have any dips or sags.
3.
This boiler series is classifi ed as a Category I. Vent installation shall be in accordance with "Venting of Equipment," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or applicable provisions of the local building codes.
4.
Inspect chimney to make certain it is constructed according to NFPA 211. The vent or vent connector shall be Type B or metal pipe having resistance to heat and corrosion not less than that of galvanized sheet steel or aluminum not less than 0.016 inch thick (No. 28 Ga).
5.
Connect fl ue pipe from draft hood to chimney. Bolt or screw joints together to avoid sags. Flue pipe should not extend beyond inside wall of chimney. Do not install manual damper in fl ue pipe or reduce size of ue outlet except as provided by the latest revision of ANSI Z223.13.. Protect combustible ceiling and walls near fl ue pipe with fi reproof insulation. Where two or more appliances vent into a common fl ue, the area of the common fl ue must be at least equal to the area of the largest fl ue plus 50 percent of the area of each additional fl ue.
8 - VENT SYSTEM MODIFICATION
When an existing boiler is removed from a common venting system, the system is likely to be too large for the proper venting of the appliances sill connected to it. If this situation occurs, the following test procedure must be followed:
REMOVAL OF BOILER FROM VENTING SYSTEM
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1.
Seal an unused opening in the common venting system.
2.
Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they operate at maximum speed. Do not operate a summer exhaust fan. Close fi replace dampers.
4.
5.
6.
7.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
After it has been determined that each appliance remaining connected to a common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas burning appliances to their previous condition of use.
Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel gas Code, ANSI Z223.1/NFPA 54. When re-sizing any portion of the common venting system, the common venting system should be re-sized to approach the minimum size determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
12
Page 13
9 - VENT DAMPER INSTALLATION & INSTRUCTIONS
DAMPER INSTALLATION NOTE: Refer to Figure 10 for steps 1-6.
Figure 11 - Damper Motor Wiring
Vent Damper
Vent Outlet
DAMPER INSTRUCTIONS
Figure 12 - Vent Damper Placement
Damper Motor
1.
Place vent damper on or as close to vent outlet of
boiler as possible. See Figure 12 .
2.
Remove vent damper motor cover.
3.
Feed damper wire harness connector through bracket hole on damper motor frame.
4.
Tighten locknut onto damper wire harness connector.
5.
Plug damper connector into socket on damper motor frame.
6.
Replace damper motor cover and wire damper. See
Figure 11 .
1.
Verify only boiler is serviced by vent damper. See
Figure 12 .
2.
Clearance of not less than 6 inches between vent damper and combustible material must be maintained. Additional clearance should be allowed for service of vent damper.
3.
Vent damper must be in the open position when appliance main burners are operating.
4.
Vent damper position indicator must be in a visible location following installation.
5.
The thermostat's heat anticipator must be adjusted to match the total current draw of all controls associated with boiler during heating cycle.
13
Page 14
10 - CONNECTING GAS SERVICE
!
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
Figure 13 - Gas Piping
General
• Use piping materials and joining methods acceptable to authority having jurisdiction. In absence of such requirements of National Fuel gas Code, ANSI Z223.1/ NFPA 54
• Size and install gas piping system to provide suffi cient gas supply to meet maximum input at not less than minimum supply pressure. See Table 5 .
• Support piping with hooks straps, bands, brackets, hangers, or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for liquefi ed petroleum gas.
• Install fi eld sourced manual main shutoff valve, ground joint union, and sediment trap upstream of gas valve.
See Figure 13 .
Table 5 - Gas Pressure
Natural Gas Propane
Min. Supply Pressure 5" w.c. 11" w.c.
Max. Supply Pressure 13.5" w.c. 13.5" w.c.
Manifold Pressure 3.5" w.c. 10.5" w.c.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS/HOUR
(Gas Pressure = 0.5 psig or less, Pressure Drop = 5 in. w/c)
Table 4 - Pipe Sizes
Length of
Pipe (Feet)
10 175 360 680 1400
20 120 250 465 950
30 97 200 375 770
40 82 170 320 660
60 66 138 260 530
80 57 118 220 460
100 50 103 195 400
For additional information refer to the National Fuel Gas Code Handbook.
Nominal Iron Pipe Size
½” ¾” 1” 1¼”
!
DANGER
Fire Hazard. Do not use matches, candles, open ames, or other methods providing ignition source. Failure to comply will result in death or serious injury.
Leak Check Gas Piping
Pressure test boiler and gas connection before placing boiler in operation.
Pressure test over 1/2 psig (3.5 kPa). Disconnect boiler and its individual gas shutoff valve from gas supply system.
Pressure test at 1/2 psig (3.5 kPa) or less. Isolate boiler from gas supply system by closing manual gas shutoff valve.
Locate leakage using gas detector, noncorrosive detection fl uid, or other leak detection method acceptable to authority having jurisdiction. Do not use matches, candles, open fl ames, or other methods providing ignition source.
Correct leaks immediately and retest.
14
Page 15
11 - ELECTRICAL SECTION
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before making electrical connections. Failure to do so could result in death or serious injury.
Electrical Wiring See wiring diagrams on the following two pages for
details.
Electrically bond boiler to ground in accordance with requirements of authority having jurisdiction. Refer to National Electrical Code, ANSI/NFPA 70.
Thermostat Installation
1.
Thermostat should be installed on an inside wall about four feet above the fl oor.
2.
NEVER install a thermostat on an outside wall.
3.
Do not install a thermostat where it will be affected by drafts, hot or cold pipes, sunlight, lighting fi xtures, televisions, a fi replace, or a chimney.
4.
Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners.
5.
Instructions for the fi nal adjustment of the thermostat are packaged with the thermostat (adjusting heating anticipator, calibration, etc.)
15
Page 16
12 - WIRING DIAGRAM - INTERMITTENT IGNITION
Figure 14 - Intermittent Electronic Ignition Control (240009076)
!
WARNING
Modifi cation, substitution or elimination of factory equipped, supplied or specifi ed components may result in personal injury or loss of life.
16
Page 17
12 - WIRING DIAGRAM - INTERMITTENT IGNITION
Figure 15 - Intermittent Electronic Ignition Control (240009076)
17
Page 18
!
13 - LIGHTING INSTRUCTIONS
!
WARNING
If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
• This appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to
light this burner by hand.
• Before operating smell all around appliance area for gas. Be sure to smell next to fl oor because some gas is heavier than air and will settle to the oor.
• Use only your hand to turn the gas shutoff valve. Never use tools. If valve will not turn by
hand, do not try to repair it, call a qualifi ed ser- vice technician. Force or attempted repair may result in fi re or explosion.
• Do not use this appliance if any part has been under water. Immediately call a quali-
ed service technician to inspect appliance and to replace any part of control system and any gas control which has been under water.
OPERATING INSTRUCTIONS FOR INTERMITTENT PILOT SYSTEM
1.
STOP! Read the safety information to the left.
2.
Set the thermostat to lowest setting.
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
Figure 16 - Intermittent Pilot
NOTICE
Before lighting any type of pilot burner (standing or intermittent), verify the hot water boiler and system are full of water to minimum pressure of 12 psi in the system, also verify system is vented of air. Set operating control of thermostat to “below” normal setting. Refer to following appropriate lighting instruction.
LIGHTING PROCEDURE FOR BOILER WITH INTERMITTENT PILOT SYSTEM
For Your Safety, Read Before Operating!!
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light appliance by hand.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switches; do not use any phone in your building.
5.
Turn gas control knob clockwise to “OFF.”
6.
Wait (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “What To Do If You Smell Gas” in the safety information to the left. If you don’t smell gas, go on to the next step.
7.
Turn gas control knob counterclockwise to “ON.”
8.
Turn on all electric power to the appliance.
9.
Set thermostat to desired setting.
10.
If the appliance will not operate, follow the instructions “
To Turn Off Gas To Appliance
service technician or your gas supplier.
TO TURN OFF GAS TO THE APPLIANCE
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if service is to be performed.
3.
Push in gas control knob slightly and turn clockwise
to "OFF." DO NOT FORCE.
4.
Call qualifi ed service technician.
” , and call qualifi ed
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
18
Page 19
14 - SEQUENCE OF OPERATION
Thermostat actuates on call for heat, completing circuit to control. Completed circuit to control will fi rst activate circulator and damper which will close end switch inside damper. Completes circuit to ignition system, ignition takes place.
In event boiler water temperature exceeds high limit setting on boiler mounted high limit control, power is interrupted between control system and ignition system. Power remains off until boiler water temperature drops below high limit setting. Circulator continues to operate under this condition until thermostat is satisfi ed.
In event fl ow of combustion products through boiler venting system becomes blocked, blocked vent safety switch shuts main burner gas off. Similarly, if boiler fl ue-way becomes blocked, ame rollout safety switch shuts main burner gas off. See Figure 17 . If either of these conditions occur, do not attempt to place boiler back into operation. Contact certifi ed service agency.
Integral Draft Hood
Burner
Door
Burners
Orifi ces
Figure 17 - Blocked Vent Safety Switch, Roll-
out Safety Switch
Blocked Vent Safety Switch
Rollout Switch 4 Section Boiler
Rollout Switch
2,3,5
Section Boiler
Manifold
Base
Jacket Base Panel
15 - GENERAL INSTRUCTIONS
Before seasonal start-up, have a certifi ed service agency check boiler for soot and scale in fl ues, clean burners and check gas input rate to maintain high operating effi ciency.
!
WARNING
This procedure should be followed to clean fl ue gas passageways:
1.
Label all wires prior to disconnection when servicing controls. Wiring errors could cause improper and dangerous operation.
Verify proper operation after servicing Service agency will verify system is fi lled with water to
minimum pressure and open air vents, if used, to expel any air accumulated in the system. Check entire piping system and, if any leaks appear, have them repaired.
Circulators need to be checked and maintained. Refer to circulator manufacturer's instructions.
Inspect venting system at the start of each heating season. Check vent pipe from boiler to chimney for signs of deterioration by rust or sagging joints. Repair if necessary. Remove vent pipe at base of chimney or fl ue and using a mirror, check vent for obstruction and verify vent is in good working order.
Boiler fl ue gas passageways may be inspected by a light and mirror. Remove burner door. See Place trouble lamp in fl ue collector through draft relief opening. With mirror positioned above burners, fl ue gas passageways can be checked for soot or scale.
Figure 20, Page 20
2.
3.
4.
5.
6.
When cleaning process is complete, restore boiler components to their original position. Use IS-808 GE silicone (available from distributor) to seal around fl ue collector and boiler castings.
.
Remove burners from combustion chamber by raising burners up from manifold orifi ces and pulling toward front of boiler. See
Disconnect vent pipe from draft hood.
Remove top jacket panel.
Remove combination fl ue collector and draft hood from boiler castings by loosening nuts on hold down bolts located on each side of collector. See
Place sheet of heavy paper or similar material over bottom of base and brush down fl ue passageways. Soot and scale will collect on paper and is easily removed with the paper.
With paper still in place in base, clean top of boiler castings of boiler putty or silicone used to seal between castings and fl ue collector. Verify chips are not lodged in fl ue passageways.
Figure 17
.
Figure 17 .
19
Page 20
15 - GENERAL INSTRUCTIONS
Make visual check of main burner and pilot fl ames at start of heating season and again in mid-season. Main burner
Figure 20 - Combustion Chamber
ame should have well defi ned inner blue mantel with lighter blue outer mantel. Check burner throats and burner orifi ces for lint or dust obstruction.
See Figures 17 and 19
BURNERS
.
Figure 18 - Gas Burner Flame
Pilot fl ame should envelop to ½ inch of tip of pilot
Figure 19 - Gas Burner Pilot
thermocouple, ignition/sensing electrode or mercury sensor. See
GAS VALVE
ORIFICES
Figure 19 .
To adjust pilot fl ame, remove pilot adjustment cover screw and turn inner adjustment screw counterclockwise to increase or clockwise to decrease pilot fl ame.
Be sure to replace cover screw after adjustment to prevent possible gas leakage. See Figure 14, Page 16 .
Burners and pilot should be checked for signs of corrosion, rust or scale buildup.
Area around boiler must be kept clear and free of combustible materials, gasoline and other fl ammable vapors and liquids.
Free fl ow of combustion and ventilating air to boiler and boiler room must not be restricted or blocked.
Inspect fi eld sourced low water cutoffs annually, or as recommended by low water cutoff manufacturer. Flush oat type low water cutoffs per manufacturer's instructions.
Employ a qualifi ed service agency to make annual inspection of boiler and heating system. They are experienced in making the inspections outlined above, and, in event repairs or corrections are necessary, trained technicians can make the proper changes for safe operation of the boiler.
20
Page 21
16 - CHECKING GAS INPUT RATE TO BOILER
ce
cess G
O
rating Control
ated I
de
ler
• Adjust gas input to boiler by removing protective cap on pressure regulator increase input and counterclockwise
,
and turning screw clockwise to
to decrease
input.
• Manifold pressures are taken at outlet side of gas valve.
• To check for proper fl ow of natural gas to boiler, divide input rate shown on rating plate by heating value of gas obtained from local gas company. This determines number of cubic feet of gas required per hour.
• With all other gas appliances off, determine fl ow of gas through meter for two minutes and multiply by 30 to get hourly rate.
• Make minor adjustments to gas input as described above.
• Change burner orifi ces if fi nal manifold pressure
Burner Access
varies more than plus or minus 0.3 inches water column from specifi ed pressure.
• Primary air adjustment is not necessary, therefore air shutters are not furnished as standard equipment.
Figure 21 - High Limit Control Location
High Limit and
Operating Control
Located Inside Boiler
Door
nsi
Boi
• Air shutters can be furnished on request where required by local codes or conditions.
CHECK SAFETY CONTROL CIRCUIT. Test ignition
system safety shutoff device after placing boiler in operation.
1.
Pilot: With main burner operating, turn pilot gas
adjusting screw clockwise until pilot gas is turned off. Within 90 seconds main gas control closes, shutting off gas to main burner.
2.
High Limit Control: Remove cover and note
temperature setting. Decrease this setting to minimum and operate boiler. When the boiler water temperature exceeds the control temperature setting, the control will open the circuit, closing the automatic main gas valve. See Figure 21 .
Gas Valve
21
Page 22
17 - OPERATING THE BOILER - SETTING THE CONTROL
Wiring An Indirect Water Heater
SETTING
When installing with indirect water heater, signal from indirect must be separated from heating zone signals and wired appropriately.
If you choose not to separate indirect signal from heating zones, Economy Feature should be turned off to insure boiler supplies adequate temperature to heat the indirect tank.
Setting The Control
Settings can be checked using the TEST/SETTINGS Button. See page 23 for details.
Setting The High Limit
The high limit is factory set at 190°F. To adjust, turn
HI TEMP dial A until desired setting is displayed.
(Setting range: 130°F - 220°F)
Setting The Low Limit
Low limit is designed to maintain temperature in boiler suitable for domestic hot water. Low limit is factory set to OFF. Prior to adjusting, remove the jumper (not equipped
on all units) B. Then turn LO Temp dial C clockwise until desired
temperature is displayed. For Proper operation, low temperature limit setting should be at least 10° below high
Temperature
Limit Setting (130°-220°F) Factory 190°F
Economy Dial
1,2,3,4,5,HI)
limit setting. For cold start operation, low limit must be turned OFF. If low limit temperature cannot be set above
140°F, remove jumper B. (Setting range: OFF or 110°-
200°F).
Dynamic Display
Setting The Economy Feature
Economy Feature is factory set for 1 zone heating
system. To adjust, turn the ECONOMY dial D until the
number displayed equals the number of heating zones. The Economy Feature conserves fuel by reducing boiler temperature. If heating system is unable to supply needed heat to the house, Economy dial should be turned to lower setting (example: In a three zone house, turn dial to 2 or
1). Conversely, if boiler provides adequate heat, added fuel savings can be achieved by selecting a higher setting (example: 4 or 5). If heating and indirect water heater signals were not separated when wiring control, Economy Feature should be turned OFF to insure boiler supplies adequate temperature to heat the indirect tank.
Activation Thermal Pre-Purge (Optional)
Activation of this feature is not recommended for boiler supplying domestic hot water.
Fuel Smart HydroStat has a Thermal Pre-Purge feature to maximize effi ciency. When activated, control will purge higher boiler temperatures down to 135°F at start of any thermostat call and supply the latent energy in the boiler to the heating zone that is calling. During the purge cycle,
the display will indicate Pur. If the heat is not suffi cient to
satisfy the thermostat, control will energize burner. Feature works with single and multi-zone heating systems utilizing circulators or zone valves. No change in wiring is needed.
To Activate Thermal Pre-Purge
Push and hold the TEST/SETTINGS button for 20 seconds. Display will read Pur On. To deactivate this feature, push
and hold button a second time for 20 seconds. Display will
read Pur OFF.
Disables economy function. Will allow boiler to fi re
OFF
LO
1 2 3 4 5
HI
High
(OFF or LO,
Jumper
Temperature
and Real Time
Verifi cation
of Setting
Adjustments.
until hi-limit temp is reached and re-fi re with a 10° subtractive differential.
Provides lowest level of fuel savings. Use this set­ting only if the house does not stay warm at higher settings.
Recommended setting for single zone systems.
Recommended setting for Two zone systems.
Recommended setting for Three zone systems.
Recommended setting for Four zone systems.
Recommended setting for Five zone systems.
Provides highest level of fuel savings.
B
Water
Decimal Point
(Indicates heat call)
Differentials
are automatic
and will vary
based on
control settings
and boiler
temperature
Low Temperature Limit Setting
(OFF or 110°-
200°F) Factory
Off
Diagnostic LEDs
and Test Buttton
22
Page 23
17 - OPERATING THE BOILER - SYSTEM START-UP
System Start-up
At initial start-up, with Economy feature active, control establishes 145°F target temperature. To test the high limit shut-off function, Economy Dial must be turned to OFF. Once tested, restore the Economy setting. If heating demand is high, target will increase over time to satisfy heat load. to reduce potential for condensing, control will allow boiler to heat to 120°F prior to energizing the circulator.
How Thermal Targeting Works
Thermal targeting technology analyzes thermostat activity and continually evaluates how much heat the house requires. When it is very cold outside, heat demand is high and Fuel Smart HydroStat will raise boiler's target temperature to provide needed heat to the home. When outside temperature is milder, heat demand is lower. During these periods, Fuel smart HydroStat will lower boiler's target temperature saving fuel while continuing to provide comfort to the house.
LED Legend
TARGET/HI LIMIT
Illuminates when boiler temperature has reached target temperature or high limit setting. When economy feature is active, the control utilizes thermal targeting technology to operate boiler at reduced target temperatures (during off-peak demand) or at high limit setting (during peak demand). When boiler water temperature reaches the target or high limit temperature, LED illuminates and burner shuts down. Boil water continues to circulate and heat the house as long as thermostat call continues. The LED will stay lit until boiler temperature drops to predetermined differential. The LED illuminates regularly during normal operation.
BURNER
Illuminates whenever the burner is running (B1 is powered).
Test/Settings Button
To test low water cut-off: Press and hold TEST/SETTINGS button for 5 seconds. Display will read LCO.
LOW WATER
Illuminates if boiler is in a low water condition. Control will prevent burner operation during this condition.
NOTICE
System must be checked by a qualifi ed heating professional prior to resuming operation.
WARNING
!
Burn and scald hazard. Do not add water until boiler has fully cooled. Failure to follow these instructions could result in death or serious injury.
T-STAT
Illuminates whenever there is a call for heat from any thermostat, zone device or indirect.
The red Low Water light should illuminate and burner circuit (B1 and B2) should energize.
To View Current Settings: Press and release the TEST/ SETTINGS button in short intervals to sequentially display following settings:
The display will return to boiler temperature (default) if TEST/SETTINGS button is not pressed for 5 seconds.
23
Page 24
17 - OPERATING THE BOILER - LIMIT CONTROL TROUBLESHOOTING
Fahrenheit/Celsius Change
Control has the ability to operate in degrees Fahrenheit (default setting) or Celsius.
To change from Fahrenheit to Celsius:
1.
Set low limit to 112°F
2.
Set high limit to 112°F
3.
Display will delay 2 seconds and then display an "F".
4.
Push the LWCO Test Button to change setting to "C".
5.
Reset the limit dials to the correct settings.
When control is in Celsius mode, a "c" appears in temperature display as third digit whenever temperature is below 100°C.
WARNING
!
Burn and scald hazard. Do not add water until boiler has fully cooled. Failure to follow these instructions could result in death or serious injury.
Table 6 - LIMIT CONTROL TROUBLESHOOTING
Temperature Display Exceeds
High Limit Setting
No Domestic Hot Water from
Tankless Coil
Boiler will Not Maintain Low
Limit Temperature
Under normal operation, boiler temperature continues to rise after control shuts off the burner. This condition, known as "thermal stacking", results from hot boiler surfaces continuing to release heat into the boiler.
Make sure low limit setting on Control is properly set. If low limit setting is dialed fully counter clockwise, it shuts off the low temperature
maintenance feature.
Check for overlapping high temperature setting. If high limit setting is below low limit setting, control will default to high limit setting.
To change from Celsius to Fahrenheit:
1.
Set low limit to 44°C.
2.
Set high limit to 44°C.
3.
Display will delay 2 seconds and then display a "c".
4.
Push the LWCO test button to change settings to "F".
5.
Re-set limit dials to correct settings.
Temperature Display Differs
from Boiler Temperature
Pressure Gauge Temperature
Reading
TSTAT Light (Green LED) is
Not On
Low Water Light (RED LED)
is On
Temperature variances can result from differing water temperatures within the boiler or different reaction times of the two devices. If the control temperature is signifi cantly below the temperature pressure gauge temperature, make sure the thermistor is inserted all the way to the end of the well. DO NOT USE ANY HEAT TRANSFER PASTE OR GREASE.
The TSTAT light indicates when there is a call for heat. If a call is known to be present and this light is on, check the wiring to the T-T terminals.
READ WARNING ABOVE. Low water condition is a serious and potentially dangerous condition. Do not attempt to add water to a hot boiler. Allow boiler to fully cool before adding water.
1.
If heating system is fi lled with water, pull sensor out of well and inspect it. Verify the metal clip on the sensor is intact. This metal clip must be in contact with the inside of the copper well in order for control to sense presence of water. Check well does not have excessive build-up of heat transfer grease that may interfere with clip contacting well.
2.
Remove well and examine for excessive residue build-up. Clean and re-install.
24
Page 25
18 - SYSTEM TROUBLESHOOTING
TABLE 7 - SYSTEM TROUBLESHOOTING
If installed with indirect water heater, insure end switch in relay box
No Or Insuffi cient Domestic
Hot Water
House Will Not Get Or Stay
Warm
controlling indirect water heater is properly connected to cable 2 (see wiring diagram). This insures domestic water calls are prioritized. If cable 2 is not used, turn Economy Feature OFF.
1.
Check for air bond radiators.
2.
Check thermostat settings including het anticipator settings (common on non-digital thermostats).
3.
Check Economy settings. Economy feature, much like outdoor reset controls, lowers average boiler temperature, can slow or prevent house from coming up to temperature. Move to lower setting.
25
Page 26
NOTES
Page 27
Date Service Performed Company Name & Tech Initials Company Address & Phone #
Page 28
DUNKIRK BOILERS
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
Loading...