To assuretrouble-freeoperation,we recommend
thatyouhavethefluepassages,burner,combustion
chamber,burneradjustmentandoperationof the
controls checkedonce a year by a competent
servicetechnician,
Beforethe startofeachseason(or wheneverthe
systemhasbeenshutdownforsometime)re-check
the whole system for leaks, includingthe boiler
and ventpipe, Replaceor patchanyfaultyboiler
seals,Checkthe siliconerubbersealsaroundthe
fluecollector,betweenboilersections,andaround
thefire door,Ensurethatthere are no leaks,Use
RTVsiliconerubberadhesivesealant(availablein
caulkingguntubes)ratedfor 400°Fto replaceor
repairsealsin locationswhereoriginalsealshave
deteriorated,
Flue passagesbetweenboilersectionsshouldbe
examinedannuallyand cleanedif necessary,See
cleaninginstructionsthatfollow,
abel all wires prior to disconnectionwhen I
ervicing controls, Wiring errors can cause I
properanddangerousoperation,Verifyproper I
Perationafter se_icing: J
Drain it until pressure is reduced below the safe
limit, Then have the valve replaced immediately,
The relief valve should be tested monthly, Refer to
valve manufacturer's instructions packaged with
relief valve,
The expansion tank may become waterlogged or
may receive an excess of air. Frequent automatic
opening of the relief valve indicates water logging. A
high boiler temperature accompanied by unusually
low radiation unit temperature (and "knocking")
indicates excess air in tank.
To correct either condition, close the valve between
the boiler and the tank, Drain the tank until it is
empty, Check all the tank plugs and fittings, Tighten
as necessary, Open the valve between the boiler
and tank, Water will rise to the normal height in the
tank if you have an automatic fill valve (otherwise,
manually refill the system),
If system is to remain out of service during freezing
weather and does not contain antifreeze, always
drain it completely. Water left in to freeze will
crack the pipes and/or boiler.
Visually inspect the entire venting system once
a month for any signs of leakage or deterioration.
If the vent shows any signs of leaking, replace it
immediately,
Do not connect directly to a drain, but leave an air
gap. No shut-off of any description shall be placed
between the safety relief valve and the boiler, or
on discharge pipes between such safety valves
and the atmosphere. Installation of the safety relief
valve shall conform to the ANSI/ASME Boiler and
pressure Vessel Code, Section IV. The manufacturer
is not responsible for any water damage.
Where used, antifreeze solution must be checked
at least once a year in the manner recommended by
the manufacturer of the antifreeze. The antifreeze
includes a corrosion inhibitor that can become
depleted in time, causing the solution to become
corrosive. It is important that this be checked and
the inhibitor be replenished or the system be refilled
with fresh antifreeze solution, whichever may be
required.
Antifreeze must be non-toxic, and of a type
specifically intended for use in closed hydronic
heating systems, Under no circumstances should
automotive antifreeze be used,
This valve should open automatically when the
system pressure exceeds the safe limits (30
pounds per square inch). Should it ever fail to
open under this condition, shut down your system.
The tanktess coil gasket should be checked at
least twice a year, for leakage, and replaced if
necessary.