Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
Your commercial boiler is furnished with combustion side
water or steam controls to meet our interpretation of the
American Society of Mechanical Engineers (ASME) Safety
Code for Controls and Safety Devices for Automatically
Fired Boilers, No. CSD-1.
Installation shall conform to the requirements of the
authority having jurisdiction, or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI-Z223.1/
NFPA-54 (latest revision). Where required by the authority
having jurisdiction, the installation shall conform to the
American Society of Mechanical Engineers (ASME) Safety
Code for Controls and Safety Devices for Automatically Fire
Boilers, No. CSD-1.
CSD-1 controls and this installation may be subject to
approval by local inspectors. Additional parts or equipment
may be required. Consult local authorities having
jurisdiction before the installation of the boiler.
CSD-1 controls furnished with commercial boilers are
applicable to boilers with inputs above 400,000 Btu/hr.
(Models 500-1500)
Additional parts required by CSD-1 standards may be
necessary to make this boiler compliant. This supplemental
instruction manual should be used in conjunction with the
Installation, Operation and Maintenance manual for your
specic boiler.
CSD-1 Component Installation
Based on parts listed in Installation, Operation and
Maintenance manual for your particular boiler, the following
changes should be made:
Complete Boiler Material List - See Table #1: CSD-1
Complete Boiler Material List.
See Table #2: CSD-1 Component Carton Material List
for component carton material list which replaces the
corresponding list in the installation manuals.
• See Table #3: CSD-1 Electronic Ignition Base Material
• Installed locations of additional components see Figures
For CSD-1 combustion side control, light off sequence is as
follows:
1.
2.
3.
4.
A longer pilot ame recognition time is a design
feature of this module and is correct.
Gas Pressure Requirements
• Maximum allowable inlet gas pressure (natural gas
• Verify inlet gas pressure is at least 5” w.c. but no
• If gas pressure entering the building is greater than 14”
C. Also, an independent pilot gas line which includes
manual shutoff valve, pressure regulator and
safety shutoff valve, two leak test valves on
main gas valve, and manual shutoff valve located
downstream of the main gas valve are added. See
List.
1a and 1b.
Turn on power. Set thermostat to call for heat.
Ignition starts to spark and lights pilot ame.
Ignition continues sparking about 12 seconds after pilot
lights.
Main burners ignite.
NOTICE
only) to controls in CSD-1 gas train is 14” w.c. (½
psig).
greater than 14” w.c.
w.c., installing contractor must provide overpressure
protection on downstream piping to prevent buildup of
downstream pressures in excess of 14” w.c. in event
the fuel system pressure regulator fails.
Combustion Side Control :
• Models 300 and 400, no changes are required to
existing gas trains.
• Models 500 through 1500 requirements include:
A. Intermittent pilot control module is required to
have maximum 15 second pilot ame establishing
period and ability to perform safety shutdown and
lockout in event of loss of ame signal at pilot.
B. The intermittent pilot module and manual reset
switch are used to replace the existing pilot
module.
• Alternatively, gas pressure entering the building may
be reduced with additional gas pressure regulator
outdoors. If inlet gas pressure to this additional
regulator is less than 14” w.c., then overpressure
protection may not be required.
• Consult local authority(s) having jurisdiction before
installing gas supply piping to the boiler.
2
Page 3
MATERIAL LISTS
Table #1: CSD-1 Complete Boiler Material List
Sections
Model
10001912SA-3100011
1100110112SA-3110011
120011113SA-3120011
1300112112SA-3130011
1400113112SA-3140011
1500114133SA-4150011
a. Boilers having total inputs of 400 MBH or less as complying with ANSI Z21.13 (Models 300 and 400), the standard combustion
b. There are additional parts on base assemblies for boilers having total inputs from 500 to 1,500 MBH (Models 500 to 1500)
c. For steam boilers, there is an additional CSD-1 steam trim carton for gravity or condensate pump return (Part# 41257103)
LInnerR300 CSD-1 400 CSD-1500 CSD-1
300121SA-130011
400131SA-140011
5001411SA-150011
6001512SA-260011
70016111SA-270011
8001712SA-380011
90018111SA-390011
side controls meet CSD-1 and no changes to the standard component carton are required.
to meet CSD-1. See “Table 2: CSD-1 Component Carton Material List” for details.
or an additional CSD-1 steam trim carton for boiler feed pump return (Part# 41257104). See appropriate CSD-1 Steam
Trim Carton Material List (Tables 5a and 5b) for details.
CSD-1 Component Carton
a & b
Steam
Trim
Carton
d
CSD-1
Carton
AC
Jacket
End
Panel
Carton
Base
End
Panel
Carton
Table #2: CSD-1 Component Carton Material List
550001664550001665550001666
DescriptionStock No.Unit
300 Base Assembly CSD-1550001670Ea.1
400 Base Assembly CSD-1550001671Ea.1
500 Base Assembly CSD-1550001672Ea.1
300 Intermediate Jacket Carton550001673Ea.1
400 Intermediate Jacket Carton550001674Ea.1
Control Panel Assembly550001801Ea.
Control Panel Assembly CSD-1 300/400550001869Ea.11
Control Panel Assembly CSD-1 500550001870Ea.1
Top Front Panel 300109009216Ea.1
Top Front Panel 400109009217Ea.1
Top Front Panel 500109009210Ea.1
Boilers having total inputs of 400 MBH as complying with ANSI Z21.13 (Models 300 and 400), the standard combustion side controls
meet CSD-1 and no changes to the standard component carton are required.
300 CSD-1400 CSD-1500 CSD-1
3
Page 4
MATERIAL LISTS
Figure 1a - CSD-1 500 Gas TrainFigure 1b - CSD-1 500 Gas Train
5
14
4
15
32
16
17
3
19b
7
8
20
30
33
9
10
11
13
2
1
Table #3: CSD-1 Electronic Ignition Base Material List
ItemDescriptionPart No.Qty.
1¾” 90 Street Elbow Back 146930401
2¾” Manual Shutoff Valve146570011
3¾” x 2” Nipple Black 146072012
4¾” Tee Black 146930761
5¾” x ¼” Bushing 10600021
6¼” x 2” Nipple Black 13100181
7¼” Street Elbow Black 146570071
8¼” Manual Shutoff Valve146570021
9¼” x 2½” Nipple Black 146070002
10¼” Gas Pres. Regulator, 6” w.c. 146570041
11¼” Magnetic Valve w/Connector Assembly433571031
12⅛” NPT x ⅛” Tube M. Connector146570191
13¼” x ⅛” Bushing 146570081
14Control STP W/Alarm11400071
15Control Mounting Panel, CSD-1 24 GA Galv 1090068331
Steam Side Control - Two low water cutoff devices and
two pressuretrols, one with auto reset and the second with
Figure 2 - Steam Boiler Feed Pump Return
manual reset, are required. In order to make the two
low water cutoff devices work in the appropriate
sequence, manufacture recommends locating both
devices at same end of boiler.
There are three different control systems for three different
types of condensate returns.
Identify the three different types of condensate returns:
• Gravity return - condensate is returned by gravity.
• Condensate pump return - condensate is returned
by pump(s), controlled by the water level in the
condensate receiver tank.
• Boiler Feed Pump Return - condensate is returned by
pump(s), controlled by the water level in the boiler.
Gravity Return And Condensate Pump Return
With gravity and condensate pump return, additional
control components are the same. See Table #5a and
Figure #2 for tappings.
• Tappings B & B location shown in Figure #2.
Figure 3 - Steam Gravity and Condensate Pump Return
Installation shown in Figure #3, Primary LWCO and
Pressuretrol with gauge glass set.
Normal
Water Line
• Tappings D or F (Figure #2)- Manual reset pressuretrol
and ¼” 90° brass syphon.
• Tappings E & F - Secondary LWCO (w/manual reset).
Use in conjunction with primary LWCO equipped on
boiler.
When using two LWCOs, place manual reset lower than
automatic LWCO. Water must be visible in gauge glass
when manual reset trips.
• Figure 3 shows how to raise automatic (Series 67)
LWCO 1-inch.
• Remove 1” from long side of ¼” diameter 90° brass
siphon tube.
• Remove nipple in series 67 and replace with 1 ½” long
nipple and street elbow.
• Water level control device located on condensate
receiver tank and controls condensate return pump is
not supplied.
Table #5a: CSD-1 Steam Trim Carton Material List for Gravity Return
or Condensate Pump Return (Part No. 41257103)
ItemDescriptionPart No.Qty.
1LWCO w/Manual Reset (secondary)2400073881
2Bushing, Steel or Cast 1” x 1¼”146570161
3Pressure Switch Control, Manual Reset146623111
490° Brass Syphon, ¼”146430041
5ELB,ST,1/2”,45 DEG.BRASS2400075411
6NIPPLE 1/2” X 1/2”LG BRASS2400075421
WATER LEVEL
29” TO FLOOR
5
Page 6
BOILER FEED PUMP RETURN
Boiler feed pump return additional parts See Table #5b.
See Figure #2 for installed locations of additional parts.
•Tappings B & B - Water gauge glass set and
pressuretrol (requires ttings 4-7 in Table #5b).
•Tapping D - Steam gauge and pressuretrol (requires
tting 8 in Table #5b).
•Tappings E & F - LWCO (auto and manual) and
pump control. Installer supply and size the steam
(top) and water (bottom) equalizing pipe lengths so
the horizontal cast line on the control body is 28”
above oor. Secondary control is 24” above the oor.
See Figure #2.
Table #5b: CSD-1 Steam Trim Carton Material List For
Boiler Feed Pump Return (Part No. 41257104)
ItemDescriptionPart No.Qty.
1Pressure Switch Control, Manual Reset146623111
2LWCO and Pump Control (primary)146263061
3LWCO, MAN RESET, CSD-1 APRVD, SHT PROBE2400073881
490° Brass Syphon, ¼”146430041
5Brass Nipple, ½” x 3½”146070242
6Brass Tee, ½” x ½” x ¼”146930512
7Brass Coupling, ½”146930522
8Bushing, ½” x ¼”10600011
6
Page 7
SEQUENCE OF OPERATION
Call For Heat
Control recognizes call for heat when power is applied
to 24V terminal on control module. Since control
receives signal from the thermostat, when call for heat is
terminated, heating cycle immediately terminates and all
control outputs will shut off.
Ignition Trial Period
Control energizes pilot gas valve and spark outputs for
ignition trial time of 12 seconds. If ame is sensed during
12 seconds of ignition trial, spark output is de-energized,
main gas valve is energized, and control enters steady heat
mode. If ame is not established within ignition trial period,
control de-energizes the spark and gas valve and operates
as described below in Ignition Failure/Re-try Sequence.
PILOT
If maximum number of ignition trials has not been
completed, control delays for 5 minute inter-purge period.
After the inter-purge, control attempts another ignition
trial. Refer back to Ignition Trial Period for details.
Steady-State Heating
Control keeps pilot gas valve and main gas valve energized
while continuously monitoring call for heat and ame
status. Control will remain in this steady-state heating
mode until power is removed by (a) thermostat satised,
(b) pressure switch opening, or (c) ame being lost.
If call for heat is satised, power is removed from control,
de-energizing pilot gas valve and main gas valve.
Ignition Failure/Re-Try Sequence
After an unsuccessful ignition trial, control checks to see
if maximum number of ignition trials (2 trials) has been
completed. If maximum number of ignition trials has been
completed, control will lockout. See Lockout (next page) for
details.
If ame is lost, control will shut off main gas valve within
one second, leave pilot gas on, and immediately start
ignition trial. Control checks to see if maximum number
of ame losses (2 per call for heat) has been reached.
If maximum number of ame losses has been reached,
control locks out. See Lockout section for details.
7
Page 8
SEQUENCE OF OPERATION
Gas Valve Sensing
If either or both the pilot and main gas valves are sensed
to be on when commanded to be off, or if no voltage
appears at gas valve output which was commanded on,
control will shut off all outputs and enter either “soft” or
“hard” lockout state. Main valve is interlocked with the pilot
valve and voltage can only be detected on main valve when
pilot valve is energized. Control locks out the rst time
as “soft” lockout, then retries after 5 minutes and enters
“hard” lockout state. Lockout should be manually reset as
described in “Lockout.”
Flame Present With Gas Off
If ame is sensed for longer than 2 seconds during a period
when gas valve should be closed, control will enter lockout.
Power Interruptions
Power interruptions less than 0.15 seconds will not
cause control to interrupt heat sequence while power
interruptions over 0.25 seconds will cause the control
to reset lockout and ignition trial counters. Power
interruptions of any duration will not cause a lockout or any
other operation requiring manual intervention.
Lockout
Controller automatically resets from rst lockout in 5
minutes. If second lockout occurs before call for heat is
satised, it will require manually resetting by depressing
red button on CSD-1 daughter board. This can be reached
with a pencil through the vent holes. A red LED will also
indicate lockout and can be seen through the vent holes.
8
Page 9
ELECTRICAL WIRE DIAGRAMS - GAS VALVE CONTROL WIRING
The suggested schematic wiring diagrams are included. Please use the appropriate one for the installation.
CSD-1 HONEYWELL VR8304M,H MAIN GAS VALVE CONTROL WIRING
9
Page 10
ALARM
CONTACTS
JUMPER
UT 1145-2
BOILER
STAT
COM
24 VAC
R
PILOT SAFETY
SHUTOFF
VALVE
BLACK
WHITE
BLUE
DD
MAIN GAS VALVE
ROBERT SHAW 7000 DE RHC
TRTH
SPARK
CABLE
TO PILOT
GREEN
SPARK
24V
GND
24V
ALARM
ALARM
PV
MV PV
MV
BLUE
WHITE
RED
YELLOW
RED
RED
CONTROL
1003-612A
WHITE
BLUE
TO CONTROL
BOX
GREEN
TO PILOT
GROUND
WHITE
GROUND
ELECTRICAL WIRE DIAGRAMS - GAS VALVE CONTROL WIRING
The suggested schematic wiring diagrams are included. Please use the appropriate one for the installation.
CSD-1 ROBERT SHAW 7000 DE RHC GAS VALVE CONTROL WIRING
10
Page 11
ELECTRICAL WIRE DIAGRAMS - CSD-1 STEAM BOILERS
WITH CONDENSATE PUMP/GRAVITY RETURN
11
Page 12
ELECTRICAL WIRE DIAGRAMS - CSD-1 STEAM BOILERS
WITH CONDENSATE PUMP/GRAVITY RETURN
3
12
Page 13
ELECTRICAL WIRE DIAGRAMS - CSD-1 STEAM BOILERS
WITH BOILER FEED PUMP RETURN
13
Page 14
ELECTRICAL WIRE DIAGRAMS - CSD-1 STEAM BOILERS
WITH BOILER FEED PUMP RETURN
3
14
Page 15
NOTES
15
Page 16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.