D248 Series
i Ln
Cast
Iron Commercial
Steam Boiler
INSTALLATION1 OPERATION &
MAINTENANCE MANUAL
'%%
"llllllllllllllllllllllllllllllllllh,,
............ ,,,,, ..........
..... ',',',' ........................
,,,,,,,,,,,,,,,,,,,,,,, .....
I,
,_ " ,, ' ........... ' ,, ,, i, I ," ,,, ,,", ,,
,,,,,,,,,,,,,,,,,,,
US
Manufactured by:
ECR International, Inc.
220! Dwyer Avenue. Utica NY 13501
web site www ecnnternatlonal coin
H
P/N# 240009137, Rev B [06/2013]
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Safety Symbols .................................................. 2
Boiler Ratings & Capacities .................................. 3
Rules For Safe Installation & Operation .................. 4
Locating The Boiler ............................................. 5
Combustion Air, Chimney & Vent Pipe Connection ... 5
Minimum Vent Pipe CLearance, . ............................ 5
Installation ........................................................ 5
Ventilation And Combustion Air ............................ 6
Vent Installation ................................................. 8
Assembly Of Bases, Starting Section Assembly ...... 12
Attaching Draft Hoods ......................................... 13
Installing Boiler Jacket Panels .............................. 14
Control Mounting And Installation ......................... 17
Tappings ........................................................... 19
Boiler Trim, Water Trim, Water Trim Assembly ........... 19
Boiler Piping ...................................................... 20
Boilers Used With Refrigeration System .................. 20
Boiler Piping, High Limit, Pipe Sizing ...................... 20
Piping Diagrams ................................................ 21
Connecting Gas Service ...................................... 23
Electrical Wiring ................................................. 24
Installing Thermostat .......................................... 24
Adjust Thermostat Heat Anticipator ....................... 24
Stage Firing Multiple Base Boilers .......................... 24
Wiring Diagrams ................................................ 25
Operation and Service ......................................... 27
Functions & Operation, Trial/Pilot Ignition .................. 27
Main Burner Operation, System Troubleshooting ......... 27
Component & Spark Ignition Check ........................ 27
Startup & Checkout, Start system .......................... 28
Pilot Flame Adjustment, Check Burner Input ............ 28
Pilot System Troubleshooting Table ............................ 29
Checking & Adjusting ......................................... 30
Cleaning And Maintenance .................................. 31
SAFETY SYMBOLS
Indicates a hazardous situation which, if not
avoided, WILL result in death or serious injury.
Indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
Indicates information which should be followed to
ensure proper installation and operation.
KEEP THIS MANUAL NEAR BOILER,
RETAIN FOR FUTURE REFERENCE.
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
Input/size
(Mbh)
Output (1)
Net AHRI
Ratings (2)
Flue Outlet No.
& Size
Chimney
Size (6) Flue
Collector
Size to
Chimney
Horsepower
Gross
Output (4)
Pressure Drop
Therrn. Boiler (5)
Eft.
Thru Water
300 233
400 310
500 388
700 543
800 620
900
1000 775
11OO 853
1200 930
1300 1008
1400 1085
1500 1163
1700 1318
i800 i395
i900 i473
2000 1550
8"x20' 8
10"x2O' 10
12"x20' 12
12"x20' 12
12'x20! 12
14
14'x20' 14
14"x201 i4
16"x20' 16
16"x20' 16
16"x20' 16
18"x20' 18
18"x20 18
18',X2Oi i8
18!'x20' 18
20,x20' 20
20"x20!
20'!x20 20
16;21
6.96
9.25
11.58
13.88
18.51
20184
23,13
25.46
27.76
30.09
32.39
34.72
37.0i
39.34
4i]64
46.27
77.5
77.5
77.5
77;5
77.5
77.5
77.5
77:5
77.5
77.5
77.5
77.5
77.5
77:5
77.5
77:5
77.5
77:5
2100 1628
2200 1705
2300 1783
2400 1860
2500 1938
2600 . 2015
2700 2093
2800 2i70
2900
3000 2325
1) Ratings are at sea level to 2,000 feet. For altitudes above 2,000 feet, reduce all ratings 4% for each 1,000 feet above sea level
2) Net steam ratings based on an allowance of 1.333 (300-1600), 1.327 (1700), 1.319 (1800), 1.313 (1900), 1.307 (2000), 1.301 (2100), 1.296 (2200),
1.292 (2300), 1.290 (2400), and 1.288 (2500-3000). Contact Technical Support before selecting boiler for installations having unusual piping and pick-up
factors, such as intermittent system operations, extensive piping systems, etc.
3) Ratings in square feet are computed at 240 Btuh/square foot for steam boilers.
4) Ratings based on 33,500 Btuh per horsepower.
5) Pressure drop based on given flow from single outlet and returning to single inlet at the opposite end of the boiler.
6) Chimney sizes shown are one option based on a typical venting system as shown in Figure 6, and sized according to the National Fuel Gas Code, assuming Type B
double wall vent and vent connectors, Other venting system designs are acceptable as shown on Flue Connection And Venting section of this manual. For further
chimney design and sizing information, consult the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision, or ASHRAE6 HVAC Systems and Equipment Handbook,
Chimney, Gas Vent, and Fireplace Systems, or the Standard for Chimneys, Fireplaces, Vents, and Sotid Fuet Burning Appliances. NFPA 211. Follow standard engineering
practice.
20"x20' 20
22"x20' 22
22"x20' 22
22"x20' 22
22"x20 22
24"x20'
24'!x201
24,x20' 24
24'!x20 24
48.60
50.90
53.22
55.52
57.85
60ii5
62.48
64178
67:10
69,40
77.5
77.5
77.5
77.5
77.5
77 5
77.5
77.5
77.5
77:5
Safety Information
iMPORTANT: Read the following
COMPLETELY before installing!!
Fire, explosion, asphyxiation and electrical shock
instructions
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
When Your Boiler Arrives
When boiler arrives be sure to save and refer to
instructions,
Inspect each item received for visible damage. If any
parts are damaged, report this to freight company
immediately and request them to call and make
inspection before you make any installation. Have
inspector prepare a signed report. Send copy of
report to manufacturer.
We must have the signed inspection report of the
freight company to prove their liability.
Keep boiler area clear and free from combustible
materials, gasoline and other flammable vapors
and liquids.
DO NOT obstruct air openings to the boiler room.
Modification, substitution or elimination of factory
equipped, supplied or specified components may
result in personal injury or loss of life.
TO THE OWNER = Tnstallation and service of this
boiler must be performed by a qualified installer.
TO THE INSTALLER = Leave all instructions with
boiler for future reference.
When this product is installed in the
Commonwealth of Massachusetts the installation
must be performed by a Licensed Plumber or
Licensed Gas Fitter.
1. Never test for leaks with an open flame, Use soap suds
to check all connections, This will avoid any possibility
of fire or explosion,
2. Boiler is configured for operation with natural gas,
Over-firing will result in premature failure of boiler sec-
tions and cause dangerous operation, Verify there is
adequate gas supply piping,
3. Never vent this boiler into enclosed space, Always con-
nect boiler to chimney and vent to outside, Never vent
to another room or inside abuilding,
4. Verify there is adequate air supply for complete com-
bustion,
5. Follow regular service and maintenance schedule for
efficient and safe operation,
Read these instructions carefully before beginning
the installation to be sure all packages have been
received. ]:t is recommended that you follow the
step=by=step instructions for best assembly results.
Before discarding any packing material carefully
examine for loose parts. Also store all parts received
where they will not be lost or damaged.
CODES GOVERNING INSTALLATION
Installation must conform to the requirements of the
authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1/NFPA54.
Where required by the authority having jurisdiction, the
installation must conform to the standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANS_/ASME CSD=I,
Installation
Boiler is designed to provide wide heating capacity range
with multiple burner modules, each equipped with its own
set of controls. For purposes of orientation, gas manifold
side of boiler is considered front. Instructions are written
for assembly of boiler starting with left side and working to
right side.
Hot water boiler installed above radiation level or as
required by the Authority having jurisdiction, must be
provided with a low water cutoff device at the time of boiler
installation.
Fire hazard. Do not install boiler carpeting. Failure
to follow these instructions could result in death or
serious injury.
6. Never install boiler on carpeting.
iiiiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii_!i _I!E!_ _i!_i_ _i6_!_i_i_i_ i_i_ii_i _ii_i_ ii_ i_i_ii i!E_i_ ;E;il;Jl _ii_i_!!_ il_ ili iilil ililil il _ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il_ ili iilil ililil il_ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il _ili iilil ililil il_ ilii ilil ililil il _ili i ilil ililil il _ili iilil ililil il _ili iilil ililil il_ ili iilil ililil il _ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il_ ili iilil ililil il _ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il_ ili iilil ililil il _ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il_ ili iilil ililil il _ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il_ ili iilil ililil il_ili i ilil ililil il _ili i ilil ililil il _ili iilil ililil il _ili iilil ililil il_ ilii ilil ililil il _ili i ilil ililil il _ili iilil ililil il _ili iilil ililil il_ ili iilil ililil il _ili i ilii_
Boiler Location
Locate boiler on level, non=combustible foundation as near
to chimney or flue as possible. Allow 24 inches at front and
sides of boiler for servicing and cleaning. When installed in
utility room, the door should be wide enough to allow the
largest boiler parts to enter, or permit replacement of any
other appliance in the same room.
Tnstalling contractor must provide ventilated
foundation for boiler when installing:
• Over a room
• Over electrical wiring or cables of any kind
• Tf concrete floor is "green," or water is channeled
under concrete floor
Combustion Air
Provide combustion and ventilation air in accordance
with the section "Air for Combustion and Ventilation", of
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
applicable provisions of the local building codes.
Chimney And Vent Pipe Connection
This is a very important part of the heating system. It must
be clean, the right size, properly constructed and in Good
Condition. No boiler can function properly with a bad
chimney. See Pages 6-::L0 for specific venting instructions.
Flue pipe should be same size as draft hood outlet from boiler
to flue collector. See Chart 1 for Typical Chimney Size. Main-
rain a minimum upward slope of 1/4 inch per linear foot from
boiler to the chimney. Fasten joints together with sheet metal
screws to prevent sagging.
Minimum Vent Pipe Clearance
If the vent pipe must go through a crawl space, double
wall vent pipe should be used. Where vent passes through
a combustible wall or partition, use a ventilated metal
thimble. The thimble should be 4 inches larger in diameter
than vent pipe. If boiler is installed with single wall
galvanized type vent pipe, it must have 6 inches clearance
between its surface and any combustible material. If
UL listed type B (insulated) vent pipe is used, clearance
between it and combustible material to be as listed by pipe
manufacturer.
Top 52" 52"
Front Alcove Alcove
Flue Collector 6 " 6"
Rear 18" 24"
Sides 18" 24"
Steam/Water 1" 1"
Piping
Greater clearances (24") for access should supersede
fire protection clearances.
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii !! i!!!i i ! i ii !!L! i ii iii! ! i i i i i iJ i i! :! ¸:! iiiiiiiili!i :!i611 !!i !ii! ii !i itli !ii!ii6!i iiiiii
Asphyxiation hazard. Ensure enough air is available
for proper combustion, avoiding hazard due to lack
of oxygen.
300 i 75 300 75 150
500 i 125 500 125 250
700 2 175 700 175 350
900 2 225 900 225 450
ii!ii ii; i
1100 3 275 1100 275 550
Air openings to combustion area must not be
obstructed. Follow Chart 2 to insure adequate
combustion air is maintained.
1300 3 325 1300 325 650
1500 3 375 1500 375 750
1700 4 425 1700 425 850
1900 4 475 1900 475 950
2100 5 525 2100 525 1050
2300 5 575 2300 575 1150
2500 5 625 2500 625 1250
2700 6 675 2700 675 1350
2900 6 725 2900 725 1450
* Unconfined area: A space whose volume is not less than 50 cubic feetper 1000 Btu
per hour of all appliances installed in that space (cubic feet of space = height x width
x length).
** Confined area: A space whose volume is less than 50 cubic feet per 1000 Btu per
hour of all appliances installed in that space (cubic feet of space = height x width x
length).
Figure I Figure 2
Combustion
Air
_ _, ODeninas
Y
f
Combustion Air supplied from
outside the building
Important Vent=Piping Note: Sloped vent pipe at
least 1/4" for every 1" to the vent terminal.
lo
Provide combustion and ventilation air in accordance
with the section "Air for Combustion and Ventilation",
of the National Fuel Gas Code, ANSI Z223.:[/NFPA 54,
or applicable provisions of the local building codes.
2o
Boiler is located in unconfined space in building or
conventional construction frame, masonry or metal
building, infiltration normally is adequate to provide a_r
for combustion and ventilation. However, if equipment
is located in building of tight construction (See National
Fuel Gas Code, ANSI Z223.:[), boiler area should be
considered as confined space. If there is any doubt,
install air supply provisions in accordance with latest
revision of National Fuel Gas Code.
3o
Boiler is installed in unconfined space, in building of
tight construction, air for combustion and ventilation
must be obtained from outdoors or from spaces freely
communicating with outdoors. Permanent opening
or openings having total free area of not less than 1
square inch per 5,000 Btu per hour of total input rating
of all appliances shall be provided. Ducts may be used
to convey makeup air from outdoors and shall have
same cross-sectional area of openings to which they
are connected.
4. When air for combustion and ventilation is from inside
buildings, confined space shall be provided with two
permanent openings, one starting 12 inches from top
and one 12 inches from bottom of enclosed space. Each
opening shall have minimum free area of 1 square inch
per one thousand (1000) Btu per hour of total input
rating of all appliances in enclosed space, but must
not be less than one hundred (100) square inches.
Openings must freely communicate directly with other
spaces of sufficient volume so combined volume of all
spaces meets criteria for unconfined space. Figure 1.
5. When boiler is installed in confined space and all
air is provided from outdoors confined space shall
be provided with one or two permanent openings
according to methods A or B (listed below). When ducts
are used, they shall be of same cross sectional area as
free area of area of openings to which they connect.
Minimum dimension of rectangular air ducts shall be
not less than 3 x 3 inches or 9 square inches.
iiiiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiiii_!i ;_!ii! i_:i _i!i !i i_il L!i!i _i _! iiiii ii! _ii!i_i ililil ili:i i!iil i_i_i_: !_:i _!ii! i_!ii!ii!_ i! i_ ii_i _ ii :!_!i_!_:i !i_!i !!_!iJliill _i ii!i_i il ilili _!ill ji iii! _:i _:i iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii ii iiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii iiiiiiii ii:_:_:_i_i_i_i_i_i_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_ii_i_i:i_i:i!iiii ii
A. When installing two openings, one must commence B.
within 12 inches from top and other within 12
inches from bottom of enclosure. Openings shall
communicate directly, or by ducts, with outdoors
or spaces (:crawl or attic) that freely communicate
with outdoors. One of following methods must be
used to provide adequate air for ventilation and
combustion.
1) When directly communicating with outdoors,
each opening shall have minimum free area of
1 square inch per 4,000 Btu per hour of total
input rating of all equipment in enclosure. Refer
to Figure 2 on previous page.
2) When communicating with outdoors by
means of vertical ducts, each opening shall
have minimum free area 1 square inch per
4,000 Btu per hour of total input rating of all
appliances in the enclosed space.
3) If horizontal ducts are used, each opening
and duct shall have minimum free area 1
square inch per 2,000 Btu per hour of total
input rating of all appliances in the enclosed
space.
.
In calculating free area using louvers, grilles or
screens for above, consideration shall be given
to their blocking effect. Screens used shall not be
smaller than 1/4 inch mesh. If free area through
design of louver or grill is known, it should be used
in calculating size opening required to provide free
area specified. If design and free area is not known,
it may be assumed that wood louvers will have 20=
25% free area and metal louvers and grilles will
have 60-75% free area. Louvers and grilles should
be fixed in open position or interlocked with boiler
so they are opened automatically during boiler
operation.
One permanent opening, commencing within 12
inches of top of enclosure, shall be permitted where
equipment has clearances of at least 1 inch from
sides, 1 inch from back, and 6 inches from front
of boiler. Opening shall directly communicate with
outdoors or shall communicate through vertical
or horizontal duct to outdoors or spaces (:crawl
or attic) that freely communicate with outdoors.
Openings must have minimum free area of 1
square inch per 3000 Btu per hour of total input
rating of all equipment located in enclosure. Free
area must be no less than sum of areas of all vent
connectors in confined space.
iiiiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiii iiiii iiiiii iiiiU_!i_i!!_ii_iiiiiiiJ!iii_iii_!_i_ii!_ii!iL!_ii_iim: i: i!_ ii_ill i i¸i iiiii i i¸i iiiii ii ¸i iiiii i i ¸iiiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii ii ¸i iiiii i i¸ iiiiii i i¸i iiiii i i¸i iiiii ii ¸i iiiii i i ¸iiiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ¸i iiiii i i ¸i iiiii i i¸ iiiiii i i¸i iiiii ii ,,
Vent connectors serving appliances vented by
natural draft shall not be connected into any
portion of mechanical draft systems operating
under positive pressure.
4_
1. The vent pipe must slope upward from the boiler
not less than 1/4" for every 1' to the vent terminal.
Figures 1 & 2,
2. Horizontal portions of the venting system shall be
supported rigidly every 5 feet and at the elbows. No
portion of the vent pipe should have dips or sags.
Flue Connection And Venting
Vent installations shall be in accordance with "Venting of
Equipment", of the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or applicable provisions of the local building
codes.
1. Consult dimensional drawing for number and size of
flue pipes required for each size boiler.
2. Maintain minimum upward slope of 1/4 inch per linear
foot from the boiler to chimney.
3. Run flue pipe directly as possible. Keep turns to a
minimum. Insert flue pipe into, but not beyond, inside
wall of chimney. Do not connect into a chimney serving
an open fireplace.
Insulate flue pipe where it passes near combustible
material.
5.
Rigidly support pipe with hangers and straps.
6.
Extend chimneys at least 2 feet above any object
within radius of 15 feet, including roof.
7.
Install hood on all flue pipes which extend through roof.
In most locations, venting of boiler relies on natural
draft. In as much as energy available from natural
draft is quite low, serious thought should be given to
vent system design, i.e., adequate size, use of gradual
transitions, tees, elbows, etc., close proximity of boiler
and chimney. On all boilers, vertical risers must be at
least as large as vent openings on draft=hood. Boiler
manufacturer makes no specific recommendations
regarding application of draft inducers that may be
used with this boiler. If draft inducer is used, it is up to
installing contractor and draft inducer manufacturer to
determine proper application.
Flue Connection And Venting - Continued
Simple vent system consists of 6-foot minimum vertical
rise immediately off draft-hood, as shown in Figure 3.
Terminate this vertical flue above building roof with suitable
rain cap at least 2 feet above surrounding obstructions,
i.e., parapets, adjacent buildings, penthouses, etc. This
type of vent system applies to single draft-hood boilers
ONLY, and has limited practical use, because it is restricted
to single-story boiler rooms and because of problems
encountered in roof flashing.
Vertical venting system shown in Figure 3 cannot be used
on multiple=base boilers because of physical interference of
multiple rain caps.
For multiple=base boilers, pant leg venting system shown in
Figure 4 can be applied, if desired.
Figure 3
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
Vent system shown in Figure 5 is commonly used. With
vent diameters sized to match flue outlets, minimum
vertical rise of 4 feet above draft=hood must be maintained
for proper operation. Refer to Chart 1 for typical chimney
sizes. Requirements for this type of system are: an
adequately sized chimney, adequate combustion air, and
outlet end of horizontal run must be no more than 6 feet
from chimney with no more than one 90 ° elbow in this run
as shown.
For installations where required minimum 4-foot vertical
rise cannot be maintained, diameter of horizontal run must
be increased one inch for each foot of riser reduction. This
procedure will reduce resistance of system, and if chimney
is adequate boiler will vent properly.
Figure 4
Figure 5
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
_
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
i i
Figure 6
Shown is suggested size of fixed
baffle for different size risers.
IMPORTANT; Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
Flue Connection And Venting = Continued
In certain cases where these short rises of less than 4
feet have been used, spillage of combustion products has
occurred at the draft-hoods farthest from the chimney.
Assuming the chimney is adequately sized, one acceptable
method to correct this spillage problem is to permanently
baffle the riser(s) closest to the chimney to reduce the
excess of room air entering those draft-hoods. DO NOT
BAFFLE ENOUGH TO CAUSE SPILLAGE. The use of fixed
baffles in the short risers above the boiler draft-hood are
acceptable as spelled out in American National Standard
NFPA 54/ANSI Z223.1 National Fuel Gas Code, latest
revision.
Fabricate these fixed baffles, using 20-gauge steel. See
Figure #6. Permanently attach the baffle to the inside of
the riser(s). Trial and error will dictate the degree to which
each should be positioned to avoid draft-hood spillage
at the far end of the boiler. Be careful to avoid bending
the fixed baffle so it will obstruct the flue gas flow in the
horizontal collector.
Removing Existing Boiler From Common Venting
System
When existing boiler is removed from common venting
system, common venting system is likely to be too large for
proper venting of appliances remaining connected to it.
At time of removal of existing boiler, following steps shall
be followed with each appliance remaining connected to
common venting system placed in operation, while other
appliances remaining connected to common venting system
are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
6. After it has been determined that each appliance remaining
connected to the common venting system properly vents
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
When resizing any portion of the common venting
system, the common venting system should be resized
to approach the minimum size as determined using the
appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.