Dunkirk CHB-100 User Manual

CONTROL MODULE
REPLACEMENT KIT #550002965
INSTRUCTIONS
CHB-100, CHB-130 and CCB-150
Kit installation shall be completed by qualied agency.
WARNING
!
Read this instruction and understand all requirements,
including requirements of authority having jurisdiction, before beginning installation. Installation not complete until appliance operation veried per Installation, Operation & Maintenance Manual provided with boiler.
1.
Follow instructions TO TURN OFF GAS TO APPLIANCE found in Installation, Operation & Maintenance Manual. Verify all electrical power to boiler is turned off.
WARNING
!
Electrical shock hazard. Turn OFF electrical power supply at service panel.
2.
Remove front jacket casing per instructions found in Installation, Operation & Maintenance Manual.
WARNING
!
Burn hazard. Verify heat exchanger has cooled or use appropriate personal protection equipment.
Figure 1 - Control Housing Screw
Control Housing
Screw
Figure 2 - Control Housing Folded Down on Hinge
Back Cover
Screws
3.
Remove control housing screw on lower right of control housing. See gure 1.
4.
Slide control housing forward, it will fold down on its built in hinge. See gure 2
5.
Remove two back cover screws. Remove back cover. See gure 2.
6.
Disconnect all wiring connectors on control board. See gure 3.
7.
Remove 2 screws holding board in place. Slide board out. See gure 3.
8.
Replace board with new board, screw board in place. Connect wiring connectors on control board. See gure 3.
9.
Replace back cover.
10.
Fold control housing up and slide back into position. Secure with control housing screw. See gure 1.
Back Cover
Figure 3 - Screws Holding Board
Board Screws
P/N 240010533, Rev. A [07/2014]
CONTROL BOARD REPLACEMENT KIT
11.
Remove any call for heat or hot water.
12.
Turn gas and electric power ON.
13.
Power up boiler.
14.
Congure control for proper boiler size and type.
15.
To access the Parameter “tS” menu:
Press and hold Reset button for 10 seconds, display will read “tS”, release button.
Press the Reset button for 1 second, display will read “P01”.
Press Heating buttons to scroll the list of parameters. Press DFHW buttons to view or change a parameter. Two Parameters need to be set “P01 & P02” as shown in gure 4.
16.
To access Conguration menu:
Press DHW + & - (both) buttons and hold for 10 seconds; “b01” will appear ashing.
Press Heating buttons to scroll Conguration list. Press DHW buttons to view or change a setting.
Figure 4 - Enter Conguration Menu
CH
DHW
Figure 4 - Enter Parameter "tS" Menu
tS Menu CCB-150 CHB-100 CHB-130
P01
P02
Gas
Type
Boiler
Type
0=Natural
Gas; 1=LP
Gas
1 2 2
0=Natural
Gas; 1=LP
Gas
0=Natural
Gas; 1=LP
Gas
Conguration “b01” is only one to be changed per chart in Figure 6.
When proper size is selected, press and hold DHW + & - (both) buttons for 10 seconds to exit, or turn power off then on, or wait two minutes for auto exit.
Boiler is now ready for operation
17.
Verify proper operation by following START UP PROCEDURE in Installation, Operation & Maintenance Manual.
18.
Install front jacket casing following instructions found in Installation & Maintenance Manual.
Figure 6 - Proper Size Settings
Parameter Description Setting
b01
b01
b01
b01
Curve
Selection
CHB-100 0 CHB-130 1
CCB-150 2
Default =2
Loading...