Dunkirk CCB-150 User Manual

Model
CCB-150
COMBI
WALL MOUNTED
GAS BOILER
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
cod. 3541F060
ECRInternational,Inc.
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
P/N# 240010632, Rev. B [07/17/2014]
Figure 1 - Overall Dimensions
DIMENSIONS
Top View
Side View Front View
Rear View
1 = 1“ MPT Supply Water to Heating System (Out)
2 = 3/4” MPT Tap Water Outlet 3 = 3/4” FPT Gas Inlet 4 = 3/4” MPT Tap Water Inlet 5 = 1” MPT Return Water From
Heating System (IN)
Bottom View
2
TABLE OF CONTENTS
1 - Introduction ................................................................................................................... 4
2 - Important Safety Information ........................................................................................... 5
3 - General view and main components .................................................................................. 6
4 - Locating Boiler ............................................................................................................... 9
5 - Hydronic Piping ............................................................................................................11
6 - Combustion Air And Vent Piping - Category I (Chimney Vent) ............................................ 15
6 - Combustion Air And Vent Piping of direct vent and Category III .......................................... 17
6 - Combustion Air And Ventilation ....................................................................................... 19
7 - Gas Supply Piping ......................................................................................................... 22
8 - Electrical Connections ................................................................................................... 23
9 - Start Up Procedure ....................................................................................................... 24
10 - Operating Instructions ................................................................................................. 26
11 - General Maintenance And Cleaning ................................................................................ 33
12 - Ratings And Capacities ................................................................................................ 34
13 - Trouble Shooting......................................................................................................... 37
Wiring diagram ............................................................................................................... 38
Repair Parts List .............................................................................................................. 40
3
1 - INTRODUCTION
1.1 Designated Use
• Hot water heating boiler.
• Indoor installation.
• Closet or alcove installation.
• Catagory I or III Venting.
• Direct vent boiler.
• For use with natural gas or liquefi ed petroleum gases (LP/propane).
• Directly heat potable water. Indirect heating is acceptable.
1.2 The unit MUST NOT:
• Heat water with non-hydronic heating system chemicals present (example, swimming pool water).
• Exceed 185°F (85°C) system design temperature.
• Exceed MWAP 43.5 PSIG
1.3 Operational Features
• Modulating: 3-1 turn down.
• Integral Dual Limit.
Information and specifi cations outlined in this manual in effect at the
time of printing of this manual. ECR International, Inc. reserves the right to
discontinue, change specifi cations or system design at any time without
notice and without incurring any obligation, whatsoever.
4
2 - IMPORTANT SAFETY INFORMATION
!
2.1 General
Boiler installation shall be completed by qualifi ed agency. See glossary for additional information.
WARNING
!
2.3 Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements:
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could
• Canada
result in death or serious injury. Read this manual and understand all requirements before beginning installation.
2.2 Become familiar with symbols identifying potential hazards.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not
2.4 Requirements for Commonwealth of Massachusetts:
Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which includes but is not limited to:
• Installation by licensed plumber or gas fi tter.
2.5
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD1.
avoided, WILL result in death or serious injury.
United States
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
• National Electrical Code, NFPA 70.
• Natural Gas and Propane Installation Code, CAN/CSA B149.1.
• Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, CSA C22.1
.
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
5
3 - GENERAL VIEW AND MAIN COMPONENTS
Figure 2 Component Listing
6
3 - GENERAL VIEW AND MAIN COMPONENTS
Item
Number
5 Sealed Chamber
7 Gas Inlet
8 Domestic Hot Water (DHW) Outlet
9 Domestic Cold Water (DHW) Inlet
10 Supply System
11 System Return
16 Modulating Fan
19 Combustion Chamber
20 Burner Assembly
22 Burner
26 Combustion Chamber Insulation
27 Copper Heat Exchanger
28 Exhaust Manifold
29 Exhaust Outlet Manifold
32 Heating circulating pump
36 Automatic Air Vent
39 DHW Flow Regulator
42 DHW Temperature Sensor
44 Gas Valve
81 Ignition and Detection Electrode
95 3 Way Diverter Valve
114 Water Pressure Switch
136 Flow Meter
194 DHW Flate Plate Heat Exchanger
278 Double Sensor - High Limit NTC
297 Air Pressure Switch
364 Condensate Union
Description
Unit Weight - 74 LBS (33.5 kg) Shipping Weight - ~ 78 LBS (35.5 kg)
7
3 - GENERAL VIEW AND MAIN COMPONENTS
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Disconnect electrical power supply and turn off gas at shutoff valve before attemting to remove boiler jacket. Failure to follow these instructions could result in death or serious injury.
Remove Boiler Jacket
1.
Unscrew screws (A).
2.
Pivot jacket upwards. See fi gure 3.
3.
Raise Jacket up and off boiler. See fi gure 4.
Figure 3 - Jacket Removal - Screw
Locations
Figure 4 - Pivot Jacket and Raise to Remove
3
2
A
A
1
8
4 - LOCATING BOILER
4.1 Boiler Location Considerations
• Ambient room temperature always above 32°F (0°C) to
Figure 5 - Boiler Clearances
prevent freezing.
• Approved for installation in closets.
• Protect gas ignition system components from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.).
• Wall mount only.
• Access to outdoors to meet minimum and maximum pipe lengths for combustion air and vent piping. See section 6.
• Drainage of water (or water - antifreeze solution) during boiler service or from safety relief valve discharge. See section 5.
• Access to system water piping, gas supply, and electrical service. See sections 5, 7 and 8.
• Clearances to combustible materials and service clearances. See Table 2 and fi gure 5.
• The boiler must not be installed on carpeting.
BC
F
Boiler
(Front View)
F
FLOOR
A
Boiler
D
(Side View)
Front
F
TABLE 1: BOILER CLEARANCES
Dimension
Top (A)
Left Side (B))
Right Side (C)
Front (D)
Back (E)
Bottom (F)
Combustion Air/piping
Vent piping
(1)
Required distances measured from boiler jacket.
(2)
Service, proper operation clearance recommendation.
Combustible
Materials
(1)
16” (41cm) 16" (41cm)
0" (0 cm) 1” (3 cm)
0" (0 cm) 1” (3 cm)
0" (0 cm) 1" 3 cm)
0" (0 cm) 0” (0 cm)
0" (0 cm) 12" (30 cm)
0" (0 cm) 3/8" (1 cm)
6" (15 cm) 6" (15 cm)
Service
(1)(2)
9
4 - LOCATING BOILER
!
4.2 Pre-pipe supply and return water connections
with factory fi ttings before wall mounting.
4.3 Wall Mounting
Mount boiler on wall using wall mounting bracket included with unit.
• Structure must be capable of supporting boiler weight plus 60 lbs (28 kg). See page 7.
• Wall mount bracket has 2 slots, spaced at
(23.5cm) on center
• Attach wall mount bracket level on wall.
• Boiler must engage with wall mount bracket. See fi gure 6.
Boiler weight exceeds 75 pounds (34 kg). Do not lift boiler onto wall without assistance.
.
!
CAUTION
9¼”
NOTICE
Lift boiler using chassis. Using front jacket, vent piping, water or gas fi ttings to lift boiler may cause damage to the boiler.
Figure 6 - Wall Mounting Bracket
2
(2.4cm)
9¼” (23.5cm)
2
(2.4cm)
10
5 - HYDRONIC PIPING
5.1 General
• Install piping in accordance with authority having jurisdiction.
NOTICE
Use two (2) wrenches when tightening and fi tting pipe to boiler's threaded fi ttings. Boiler's internal piping can be damaged if subjected to excessive torque.
• Support system piping and safety relief valve discharge piping. Boiler's internal piping and wall mount bracket can be damaged if subjected to excessive weight.
• Size central heating pump (and domestic hot water pump, if used) for system requirements only. Internal heat exchanger pump compensates for pressure drop through boiler internal piping and heat exchanger.
• Thoroughly clean and fl ush system before connecting to boiler.
• If oil is present in system water, use approved detergent to wash system.
• Flush system to remove any solid objects such as metal chips, bers, or Tefl on tape, etc.
5.2 Water System Characteristics
• Water in the heating system must have protection of metallic materials against corrosion.
• Filling water and subsequent replenishing, must be clear, with hardness under 150 ppm CaCO3,
A. treated with approved conditioning chemicals
to ensure prevention of corrosion and attack on metals and plastics, that gases do not form,
B. and bacterial or microbial masses do not proliferate
in low temperature systems.
• Hardness exceeding 150 ppm CaCO3, appropriate water softening treatment and/or use of suitable anti-fouling agents must be provided.
Water contained in the system must be checked at least yearly and have:
A. pH above 7 and under 8.5 (under 8 with presence
of components in aluminum or light alloys), B. iron content (Fe) less than 0.5 mg/l, C. copper content (Cu) less than 0.1 mg/l, D. total content of chlorides, nitrates and sulfates less
than 50mg/l, E. must contain conditioning chemicals in
concentration suffi cient to protect system for a
year.
There must be no microbial or bacterial loads in low temperature systems. Conditioners, additives, inhibitors and anti-freeze fl uids can be used only if manufacturer guarantees they are suitable for use in heating systems and they do not cause damage to heat exchanger or other components and/or materials of boiler and system. Use of generic chemicals not specifi cally suitable for use in heating systems and/or incompatible with boiler materials and system is forbidden.
Conditioning chemicals must ensure complete deoxygenation of water and contain specifi c protective agents for yellow metals (copper and its alloys), anti-fouling agents for limescale at least up to 150 ppm CaCO3, pH neutral stabilizers and, in low temperature systems, specifi c biocides for use in heating systems.
In systems with continuous intake of oxygen (e.g. fl oor systems without anti-diffusion pipes, open expansion vessels), or intermittent (e.g. in case of frequent replenishing), a separator must be provided. Regarding domestic hot water (DHW), no type of treatment which could prevent its possible food use can be provided for.
• Poison hazard. Ethylene glycol is toxic. Do not
• Never use automotive or standard glycol antifreeze,
• Ethylene glycol can attack gaskets and seals used
• Use only inhibited propylene glycol solutions
• Thoroughly clean and fl ush any system that used
• Provide user with Material Safety Data Sheet
Do not expose boiler to freezing temperatures.
5.3 Special Conditions
• System piping exposed to freezing conditions: Use
• Boiler installed above radiation level (or as required by
• Boiler used in connection with refrigeration system.
• System piping connected to heating coils located in air
WARNING
!
use ethylene glycol.
even ethylene glycol made for hydronic systems.
in hydronic systems.
certifi ed by fl uid manufacturer as acceptable for use with closed water heating system.
glycol before installing new Boiler.
(MSDS) on fl uid used.
NOTICE
inhibited propylene glycol solutions certifi ed by fl uid manufacturer for use with closed water heating system. Do not use automotive or ethylene glycol.
authority having jurisdiction) shall have low water cutoff protection.
Install piping in parallel with boiler, with appropriate valves to prevent chilled medium from entering boiler.
handling unit exposed to refrigerated air circulation. Install ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle
.
11
5 - HYDRONIC PIPING
!
WARNING
Burn and Scald Hazard. Safety relief vlave could discharge steam or hot water during operation. Install discharge piping per these instructions. Failure to do so could result in death or serious injury.
5.4 Safety Relief Valve
NOTICE
Boiler rated at 43.5 psig (.30MPa) maximum allowable working pressure. Boiler provided with 30 psig (.21MPa) safety relief valve.
• Install safety relief valve using pipe fi ttings provided with boiler. See fi gure 7.
• Install safety relief valve with spindle in vertical position.
• Do not install shutoff valve between boiler and safety relief valve.
• Install discharge piping from safety relief valve. See gure 8.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or greater.
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location protecting user from scalding and properly drain piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve outlet and downstream of union (if used).
Figure 7 - Safety Relief Valve & Air Vent
(Viewed from front of boiler)
1” MPT
Coupling 1” NPT
Safety Relief
Valve
Street Elbow ¾”
Nipple 1 x 5”
Tee 1 x 1 x ¾”
• Terminate pipe with plain end (not threaded).
12
5 - HYDRONIC PIPING
Figure 8 - Safety Relief Valve Discharge
Piping
Safety Relief Valve
Check Local Codes for Maximum Distance to Floor
Gas Shutoff
Valve in Open position
13
Figure 9 - Hydronic Piping
278
27
95
5 - HYDRONIC PIPING
114
36
241
42
8 Domestic Hot Water Outlet
9 Domestic Cold Water Inlet
10 Heating System Supply
11 Heating System Return
27 Copper Exchanger For Heating And Hot Water
32 Heating Circulating Pump
36 Automatic Air Vent
42 DHW Temperature Sensor
95 Diverter Valve
114 Water Pressure Switch
136 Flow Meter
241 Automatic Bypass
278 Double Sensor (Safety + Heating)
9
- Plumbing circuit
32
136
1110 8
14
6 - COMBUSTION AIR AND VENT PIPING - CATEGORY I (CHIMNEY VENT)
WARNING
!
Boiler and venting installations shall be performed by a qualifi ed expert and in accordance with the appropriate manual. Installing or venting boiler or other gas appliance with improper methods or materials may result in serious injury or death due to fi re or to asphyxiation from poisonous gases such as carbon monoxide with is odorless and invisible.
!
WARNING
Do not connect boiler to any portion of mechanical draft system operating under positive pressure.
6.1 Check Your Chimney
Chimney must be clean, right size, properly constructed and in GOOD CONDITION.
1.
Installation must conform to requirements of the authority having jurisdiction or, in absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1.
2.
Increaser fi tting is required on this boiler for Category I venting, and 4” is minimum permissible vent diameter. This does not imply vent connector is intended to be 4” diameter pipe. Vent connector shall be sized according to appropriate venting tables in the National Fuel Gas Code and may be required to be larger than 4” diameter.
5.
Vent connector from boiler to chimney should run as directly as possible with as few elbows as possible.
6.
Common venting shall not be allowed. Boiler and other certifi ed appliances. appliances can share same chimney vent. Consult appropriate Vent Sizing Tables in National Fuel Gas Code for specifi c requirements of multiple appliance venting.
7.
Boiler is only appliance connected to vent, Type B vent pipe is recommended for vent connector.
8.
Slope pipe up from boiler to chimney not less than 1/4” per foot (21mm/m).
9.
End of vent pipe must be fl ush with inside face of chimney fl ue. Use sealed-in thimble for chimney connection.
10.
Fasten sections of vent pipe with sheet metal screws to make piping rigid. Use stovepipe wires to support pipe from above.
11.
Do not connect to fi replace fl ue.
12.
Do not install damper on this boiler.
Figure 10 - Combustion Air Fitting
3
3
NOTICE
Boiler installation for chimney venting is not complete unless increaser fi tting is located and secured.
3.
Venting into masonry chimney without liner, line chimney from top to bottom with either: A. Listed Type B vent pipe
B. Listed fl exible vent liner C. Poured ceramic liner.
4.
Outside chimneys should not be used unless they are (choose one of the following): A. Enclosed in a chase
B. Lined with Type B vent pipe C. Use listed fl exible vent liner D. Use certifi ed chimney lining system
Horizontal Venting requires fi eld supplied appliance adapter for the boiler fl ue outlet. Boiler is provided with a 3” vent connection, 3” x 4” increaser must be fi eld sourced for chimney application. This does not mean that the connection to the chimney will always be 4”.
15
Loading...
+ 33 hidden pages