Dunkirk ARTESIAN 220, ARTESIAN 340 Installation And Operating Instructions Manual

ARTESIAN 220 & 340
Instantaneous Indirect Water Heater
By Dunkirk Boilers
• INSTALLATION AND OPERATING INSTRUCTIONS
• ENGINEERING MANUAL
Manufacturer's Warning
Page 2
To reduce the possibility of injury due to scalding, a thermostatic mixing valve should be installed on all installations. Failure to do so will result in domestic water being delivered to the faucets at a temperature equivalent to the boiler water. All commercial installations requiring sustained water temperatures beyond 120°F, must label all fixtures alerting water users of a potential scalding hazard.
CONTENTS pg
Page 3
I. Product Description................................................................................................ 4
II. Specifications......................................................................................................... 4
III. Sizing A Water Heater For Installation................................................................ 7
Method A - Quick Residential............................................................................. 8
Method B - Detailed Residential........................................................................ g
Method C - Commercial....................................................................................13
IV. Before Starting Installation................................................................................19
V. Locating the Water heater..................................................................................19
VI. Piping ..................................................................................................................20
Zone Design
Boiler Side Piping .............................................................................................21
Domestic Piping ................................................................................................29
VII. Wiring..................................................................................................................33
VIII. Start-up and Check-out....................................................................................40
Appendix A.........................................................................................................40
I. Product Description
Page 4
The Indirect water heater is designed to generate domestic hot water in conjunction with a hot water boiler using forced boiler water circulation. This indirect water heater consists of a plain steel tank in which three smooth copper coils are located. The tank surrounded by 2" of Poly - urethane foam insulation, which is surrounded by an enamel coated plain steel jacket. The boiler water pumps through the tank and heats the domestic water in the coils.
Specifications
Page 5
Page 6
Ill. Sizing The Hot Water Heater For Installation
Page 7
IMPORTANT
The following procedures are used to size indirect water heaters based on the amount of hot water required during a given hour. In doing so, it is assumed that this demand will be spread out over the course of the entire hour.
THESE SIZING PROCEDURES ARE PROVIDED AS A GUIDE TO ASSIST THE PROFESSIONAL CONTRACTOR IN SIZING THE WATER HEATER. BECAUSE OF THE LARGE VARIETY OF DEMAND SITUATIONS ENCOUNTERED IN THE FIELD, THE MANUFACTURER CANNOT GUARANTEE THE SUITABILITY OF THESE PROCEDURES TO ALL INSTALLATIONS.
To properly apply the water heater to a particular system, the following 3 steps must be done:
1) Determine the domestic hot water requirements
2) Select the correct water heater/ boiler combination
3) Select a pump, zone piping size, and control system to provide proper water flow from the boiler through the water heater tank.
This manual presents three methods of sizing this water heater:
Method A: Quick Residential
Method B: Detailed Residential
Method C: Commercial
Note: The terms gross output and heating capacity are used interchangeably in this manual. Heating
Capacity is the gross output of boilers of less than 300,000 Btu/Hr input as defined by D.O.E. test procedures. Gross Output is the term generally used with boilers of greater than or equal to 300,000 Btu/Hr. input.
Method A: Quick Residential Sizing Method
Page 8
Table 4 shows some typical structures under which many single residence applications can be classified. This procedure will provide satisfactory results most of the time. Where greater accuracy is desired, use Method B.
1) Find the description that best fits the job and select the Water heater called for. Also, note the required boiler output under column (F).
2) The Water heater must be installed with a boiler having a gross output (DOE heating capacity) greater than or equal to that shown in column (F) of Table 4. If the Water heater is to be used with a boiler having a gross output less than that shown in table 4, use Method B.
If a boiler is to be installed with a water heater, first find a boiler, which will handle the space­heating load alone. If this boiler has a DOE heating Capacity greater than that shown in column (F) of table 4, do not add anything to the boiler selected for the Artesian.
If the boiler required for space heating alone has a DOE heating capacity less than that called for in column (F) of table 4, increase the size of the boiler selected to one with a DOE heating capacity greater than or equal to that show in column (F).
3) See figures 5-7 for more information on designing a water heater zone system. It is recommended that the zone be given priority.
Method B Detailed Residential Sizing Method Directions
Page 9
1) Record the total number of each type to fixture in column (c) of worksheet 1. A shower head is installed over a bathtub, count both the bathtub and shower head although only one fixture will be used at a time.
2) For each line, multiply the quantity entered in column (c) by the corresponding number in column (b). Enter the result in column (d).
3) Total column (d). This is the PEAK HOUR DEMAND
4) Multiply the Peak Hour Demand by 1.20. This is the adjusted peak hour demand
5) Select the water heater based on:
a) If a new boiler is to be installed with the Artesian:
* Go to table 1 and select a water heater which has a 140°F first hour rating greater than or
equal to the adjusted peak hour demand calculated on work sheet 1.
* Refer to required boiler output in Table 1. Record the required boiler output (heating
capacity) for the selected water heater in your work sheet.
* Determine the boiler required to satisfy the space heating requirement alone by
multiplying the space heating load by 1.15. Record this, as the boiler heating capacity required for space heating in your work sheet.
* Select the boiler with the larger of the above two heating capacities.
b) If the water heater is to be installed with an existing boiler:
* Go to table 1 and select a water heater which has a 140°F first hour rating greater than or
equal to the adjusted peak hour demand calculated above.
If the required boiler output for the selected water heater is greater than the heating
capacity of the existing boiler; the existing boiler is too small.
6) If a Whirlpool is on the job, see Appendix A.
7) Designing the water heater zone system. Refer to Table 1 for minimum boiler water flow, and circulator sizing. For further information on zone systems refer to figures 4-9.
Page 10
Method B - Detailed Residential Sizing Sample Calculations
Page 11
Example 1
A water heater is to be installed with a new boiler. The residence has the following fixtures: Bath #1 Bath #2
3 GPM Shower Head Vanity 30 Gal. Bathtub Vanity
Kitchen Laundry
Kitchen Sink Clothes Washer Automatic Dishwasher
The heat loss of the house is 80,000 BTU/hr
Note:
Although a four section boiler would be capable of heating the house (Net Rating = 82,000 BTU/hr), its DOE heating capacity is only 94,000 BTU/hr (Need 110,000 Btu/hr). For this reason, install a five section boiler that has a heating capacity of 125,000 BTU/hr.
Solution: The completed sizing sheet for this example is shown in figure 2. The adjusted peak hour demand
is 145 gallons per hour. From table 1, we see that a water heater 220 will fulfill this requirement with the appropriate boiler. Refer to Table 1 for required boiler output. If the model 220 is used in combination with a boiler capable of producing 110,000 Btu / hr. The output will give you 156 GPH first hour ratings. The circulator on the boiler must be capable of producing 3.4 GPM.
Page 12