Dunkirk 4ES1.50C, 3ES1.00C, 4ES1.75C, 4ES1.85C, 3ES1.00 Installation & Operation Manual

...
O|L-F|REDCAST |RONSTF.AM
BO|
Installation
Operation
RepairParts
Theseinstructionsmustbeaffixedonoradjacenttotheboiler.DUNKIRKBOILERS
DUNKIRK,NEWYORK14048- 716366-5500
I/2" NPT
TANKLESS
HEATER
, o i
F , t , t i
, t , * ,
LEFT SIDE
3/4 _ NPT
_LOW UMIT
CONTROL ON COIL PLATE
I/2" NPT
PRESSURETROL
PRESSURE GAUGE
COMBINATION
\
1-1/2" NPT RETURN
i
FRONT
T
27"
WATER
IJNE
_l
2-I/2" NPT
SUPPLY
iq°p
i-i/2" NPT
i SKIM TAPPING
i
'L
,-V2 ° NPTi
RETURN
REAR
5/4" ASNE
POP SAFETY
VALVE
35
EMPIRE OIL-FIRED STEAM BOILER RATINGS
BOILER MODEL NO.
With Without
Tankless Tankless
Coil Cotl
3ESt O0C 3ES100 3 3ES1.25C 3ES1,25 3 3ES1.35C 3ES1.35 3 4ES1,50C 4ES1,50 4 4ES1.75C 4ES1 75 4 4ES1.85C 4ES1.85 4
* MBH = 1,000 BTUpet hour
No.
9ec.
Input
*MBH
140 175
189
2!0
245 259
Nesting
Capacity
*MBH
118 145 156 177
204 215
Net
I=B-R
Rating
"MBH
89 109 117 133
153
161
Not I-S-R
Rating
Sq. Ft,
Radiation
371 454
488 554
638 671
*Tonldelm
Cell
Ratings
GPM*
2.75 3,10
3.25
3.50
3.85 4,00
Typl©al
Chimney
Size and
Height
8" x 8' x 15' 8" x 8' x 15' 8" x 8' x 15' 8' x 8' x 15'
8" x 8" x 15' 8" x 8' x 20'
CIMF31SIONS- INCHES
A B C
16% 7 9 16½ 7 9
16% 7 9 20% 8 11 20% 8 11 20% 8 11
BTUH = British Thermal Unit Per Hour GPH _ Gallons per Hour Oil at 140,000 BTU per Gallon
** Heating Capacity is based on a 13% CO2 with a -,02' w.c, draft over fire, and a #1 smoke or less. The testing on the boilers
was done in accordance with lhe DOE. (Department of Energy) test procedure
NewYorkCityMEANumber134-98-E Selectionofboilersizeshouldbe basedupon"Net1=8=RRatingbeing
equaltoorgreaterthanthesq.ft.of radiationalreadyinstalledinthe building.
TheNetI=B=R Ratingsshownarebasedonanallowanceof1.333in accordancewiththefactorsshownonthe 1=B=RStandardas publishedby TheHydronicsInstitute.
Theseboilersmusthavea non-combustiblebaseifinstalledon acombustible floor.Two-inchcladlitepadmaybeused.Theseboilersarelowpressure
sectionalcastironboilersconstructedandhydrostaticallytestedfora maximum workingpressureof 15psiin accordancewithA.SME. (AmericanSocietyof MechanicalEngineers)SectionIVStandardsfor castironheatingboilers.They arecapacityratedinaccordancewiththecodeofthe1=B=R(Hydronics
Institute).
RulesforSafeInstallationandOperation
1. Readthe Owner'sManualforSafeOperationcarefully.Failuretofollow therulesforsafeoperationandtheinstructionscancausea malfunctionof the boilerand result in death,_rious bodily injury, and/or property
damage.
2. Checkyourlocalcodesandutilityrequirementsbeforeinstallation.The installationmustbeinaccordancewiththeirdirectives,orfollowNFPA31
- InstallationofOilBurningEquipment,latestrevision.
3. Beforeservicing,allowboilertocool.Nwaysshutoffanyelectricityand oiltoboilerwhenworkingonit.Thiswillpreventanyelectricalshocksor
burns.
4. Inspectoillineandconnectionsforleaks.
5. Be certainoil burnernozzleis size required.Overfiringwill resultin earlyfailureofthe boilersections.Thiswill causedangerousoperation.
6. Nevervent this boiler into an enclosedspace.Alwaysvent to the outside.Neverventto anotherroomor insidea building.
7. Besurethereisadequateairsupplyforcompletecombustion.
8. Followa regutarserviceandmaintenancescheduleforefficientand safeoperation.
9. Keepboilerareacleanandfreeofcombustiblematerial,gasolineand otherflammablevaporsandliquids.
This boiler has been designed for residentialinstallations. If used for commercial
applications,alljurisdictionalrequirementsmustbe met.This mayrequirewiringandlor pipingmodifications.Themanufactureris notresponsibleforany changesto the original
design.
BeforeYouStart
Check to be sure you have the dght size boiler beforestartingthe installation.See ratingand capacitytableon precedingpage.Checkthe
ratingplateontheboiler. You mustsee that theboileris suppliedwiththe properoil,freshair for
combustion,and a suitableelectricalsupply.Also, the boiler must be connectedto a suitableventingsystemand an adequatepipingsystem.
Finally,a thermostat,properlylocated,is neededforcontrolofthe heating system.If youhaveanydoubtsas to thevariousrequirements,checkwith local authorities and obtain professionalhelp where needed. THE
OPERATING INSTRUCTIONSand THE FINAL CHECKS AND ADJUSTMENTSare vitalto the properandsafe operationof the heating
system.Takethetimeto besuretheyarealldone.
Thefollowingstepsareallnecessaryforproperinstallationandsafe operationof yourboiler.
1. LOCATINGTHEBOILER
2. OILSUPPLYANDPIPING
3. FRESHAIR FORCOMBUSTION
4. PIPINGCONNECTIONS
5. CHIMNEY& VENTPIPECONNECTIONS
6. ELECTRICALWIRING
7. THERMOSTATLOCATION
8. CHECKING&ADJUSTING
9. MAINTENANCE
Locatingthe Boiler
If yourboileris partof a plannedheatingsystem,locateit as nearlyas
possiblewhereshownon yourplan.If boileris to be partof an existing system,it is usuallybestto put it wherethe old onewas.If youplanto
changelocation,youwill needadditionalmaterialsaswellasan adequate base.Thefollowingrulesapply:
1. The boilermustbelevelandlocatednearpiping.
2. Usea raisedbaseiff]oorcanbecomewetordamp.
3. Theventpipeconnectionshouldbeas shortaspossible.
4. Maintainclearancesforfiresafetyaswellasservicing.SeeFigure2for minimumclearances.18"clearancemustbemaintainedatasidewhere
passageisrequiredforaccessto anothersidefor cleaning,servicing, inspection,or replacementofanypartsthatnormallymayrequiresuch
attention.Boilersmustbe installedat least6"fromcombustiblematerial onallsidesandabove.Allowat least24"frontclearancefor servicing.
Allowat least18"leftsideclearanceforservicingboilersequippedwith
atanklesscoil.
5. FRESHAIRfor combustionmustbeavailableatthefrontoftheboiler. FRESHAIRfor ventilationmustbeavailabletothefrontANDrearof
theboiler.Airpassagesmustbefreeofobstructionsatalltimes.
Ventilatingandcombustionairmustenterboilerroomwithout restrictions.
6. The floor suppo_ng the boiler must be non-combustible.If it is combustible,placetheboileron 2" cladlitepad.Thepadmustbeunder
theentireboilertoprotectthefloor.
7. Besureinstallationisinaccordancewiththerequirementsofthelocal authoritieshavingjurisdiction.Compliancewiththeseregulationsis required.In theabsenceof localcodes,followNFPA31- Insbtlationof
OilBurningEquipment.
Q 6" MIN. 18" WITH COIL
_
_" 6" MIN. "
I_// . I BOILER
I-----2, .,..------IFRO.T
6" MIN.
SeRVraceL_NeLL,.------e_.ec_rRic
F_LPtFE ] I I[ s_,rrc_
GENERAL PRINCIPAL REQUiREMEnTS FOR A TYPICAL INSTALLATION
m_
Fresh Air for Combustion
WARNING
NOTE
Be sure to provide enough fresh airfor combustion. Enough air ensures proper combustion and assures that no hazard will develop due to
the lackof oxygen.
If you use a fireplaceor a kitchenor bathroomexhaustfan,you
shouldinstallan outsideairintake.Thesedeviceswill robthe boiler andwaterheaterof combustionair.
You must providefor enough fresh air to assurepropercombustion.The fire in the boiler uses oxygen. It must have a continuous supply. The air in a house contains only enough oxygen to supply the burner for a short time. Outside air mustenter the house to replace that used by the burner. Study foIIowingexampIes 1 and 2to determineyour fresh air requirements. EXAMPLE 1:Boiler Located in Unconfined Space
If your boiler is in an open area (unpartitioned basement) ina conventional house, the air that leaks through the cracks around doors and windows will usually be adequate to provide air for combustion. The doors should not fit tightly. Do not caulkthecracks aroundthe windows.
An unconfinedspace isdefined as aspace whose volume isnot lessthan 50 cubic feet per 1,000Btu per hour of the total inputrating of all appliances
installedin that space. EXAMPLE 2: Boiler Located in Confined Space
A, All Air from Inside the Building: The confined space shall be provided
with two permanent openings communicating directly with an additional
room(s) of sufficientvolume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all
combustion equipment installed in the combined space shall be considered in making this determination. Each opening shall have a
minimumfree area of one square inch per 1,000Btu per hourof thetotal inputratingofall combustionequipment inthe confinedspace, but not less
than 100 squareinches. One opening shall be within 12 inches ofthe top
andonewithin 12 inchesof the bottom of theenclosure.See Figure 4. Example: Your boiler is rated at 100,000 Btu per hour. The water heater
is rated at 30,000 Btu per hour. The total is 130,000 Btu per hour. You need two grilles, each with 130 square inchesof FREE opening. Metal
grilles have about 60% FREE area. To find the Iouveredarea needed,
multiply the FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in. Iouvered area). In thisexample twogrilles, each having an 8"x 30" (240 sq.in,) Iouvered area would be used. Fig. 4 shows the grille locations.
B. All Air from Outdoors: The confined space shall be provided with two
permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawlor attic)thatfreely communicatewith the outdoors.
1.When directly communicatingwith the outdoors, each opening shallhave a minimum free area of one squareinchper 4,000 Btu per hour of total
inputratingof all equipment in theenclosure.
2. When communicatingwith the outdoors through ve_cal ducts, each opening shall have a minimumfree areaof one square inch per 4,000 Btu perhour of total input ratingof all equipmentin theenclosure.
3.Whencommunicatingwiththeoutdoorsthroughhorizontalducts,each openingshall havea minimumfreearea of onesquareinchper
2,000 Btu per hour of totalinput ratingof all equipmentin the enclosure.
4. Whenductsareused,theyshallbeof thesamecross-sectionalarea asthe freeareaof theopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshal{benotlessthanthreeinches.
VENTILATING -'_--i GRII.LE I
i I ' 1
i ,11 II ',
AIR GRILLE _
Fresh Air Duct Capacities for Ducts Supplying Fresh Air to boiler in tightly constructed houses. British Thermal Units per
hour Input (Btuh)*.
Fresh Air Duct Size
31/2"x 12" 8* x 8"
8" x 12" 8" x 16"
1/4"Mesh
Screen Btuh
144,000 256,000
384,000 512,0O0
Wood
Louvers Stuh
36,000
64,000 96,000
128,000
Metal
Louvers Btuh
108,000 !92,000 288,000 384,000
*Based on opening covered by IA" mesh screen, wood louvers, or mela{ louvers
FRESH
Boilers With Tankless Heater Coil
Boilersmaybefactorypackagedwithatanklessheatercoil.Theuseof this
coileliminatesthe needforahot waterstoragetank.Instantaneousheatingof waterinthecoil willprovidea flowof hotwaterfor domesticuse- ifproper watersupplylinecontrolsareused.
IMPORTANT
Donot usea tanklesscoilif yourwateris excessivelyhardwithlimeor otherdepositswhichwillaccumulateinsidethecoil.
Forsummerrunningwithcoilyou needtofill boilerwithwaterandaddthe L6006limitcontrolto the coil.Thiswill maintainwatertemperaturein the
boilerand bringtheburneronwhennecessary.
TANKLESSCOlL PIPING
PipingisshowninFigure7B.A temperingvalve(mixingvalve)is
recommended.
LowLimit(whenused)- 140° F
Thesesettingscanbechangedafteryouhavesomeideahowthe system responds.If moredomestichotwateris required,the lowlimitsettingcan
alsoberaised.
_NT_pERE_ _OT WATER
¢OL_ WATE_ _N_ET
WLV_
Loading...
+ 14 hidden pages