Dunkirk 4ES1.50C, 3ES1.00C, 4ES1.75C, 4ES1.85C, 3ES1.00 Installation & Operation Manual

...
Page 1
O|L-F|REDCAST |RONSTF.AM
BO|
Installation
Operation
RepairParts
Theseinstructionsmustbeaffixedonoradjacenttotheboiler.DUNKIRKBOILERS
DUNKIRK,NEWYORK14048- 716366-5500
Page 2
I/2" NPT
TANKLESS
HEATER
, o i
F , t , t i
, t , * ,
LEFT SIDE
3/4 _ NPT
_LOW UMIT
CONTROL ON COIL PLATE
I/2" NPT
PRESSURETROL
PRESSURE GAUGE
COMBINATION
\
1-1/2" NPT RETURN
i
FRONT
T
27"
WATER
IJNE
_l
2-I/2" NPT
SUPPLY
iq°p
i-i/2" NPT
i SKIM TAPPING
i
'L
,-V2 ° NPTi
RETURN
REAR
5/4" ASNE
POP SAFETY
VALVE
35
EMPIRE OIL-FIRED STEAM BOILER RATINGS
BOILER MODEL NO.
With Without
Tankless Tankless
Coil Cotl
3ESt O0C 3ES100 3 3ES1.25C 3ES1,25 3 3ES1.35C 3ES1.35 3 4ES1,50C 4ES1,50 4 4ES1.75C 4ES1 75 4 4ES1.85C 4ES1.85 4
* MBH = 1,000 BTUpet hour
No.
9ec.
Input
*MBH
140 175
189
2!0
245 259
Nesting
Capacity
*MBH
118 145 156 177
204 215
Net
I=B-R
Rating
"MBH
89 109 117 133
153
161
Not I-S-R
Rating
Sq. Ft,
Radiation
371 454
488 554
638 671
*Tonldelm
Cell
Ratings
GPM*
2.75 3,10
3.25
3.50
3.85 4,00
Typl©al
Chimney
Size and
Height
8" x 8' x 15' 8" x 8' x 15' 8" x 8' x 15' 8' x 8' x 15'
8" x 8" x 15' 8" x 8' x 20'
CIMF31SIONS- INCHES
A B C
16% 7 9 16½ 7 9
16% 7 9 20% 8 11 20% 8 11 20% 8 11
BTUH = British Thermal Unit Per Hour GPH _ Gallons per Hour Oil at 140,000 BTU per Gallon
** Heating Capacity is based on a 13% CO2 with a -,02' w.c, draft over fire, and a #1 smoke or less. The testing on the boilers
was done in accordance with lhe DOE. (Department of Energy) test procedure
NewYorkCityMEANumber134-98-E Selectionofboilersizeshouldbe basedupon"Net1=8=RRatingbeing
equaltoorgreaterthanthesq.ft.of radiationalreadyinstalledinthe building.
TheNetI=B=R Ratingsshownarebasedonanallowanceof1.333in accordancewiththefactorsshownonthe 1=B=RStandardas publishedby TheHydronicsInstitute.
Theseboilersmusthavea non-combustiblebaseifinstalledon acombustible floor.Two-inchcladlitepadmaybeused.Theseboilersarelowpressure
sectionalcastironboilersconstructedandhydrostaticallytestedfora maximum workingpressureof 15psiin accordancewithA.SME. (AmericanSocietyof MechanicalEngineers)SectionIVStandardsfor castironheatingboilers.They arecapacityratedinaccordancewiththecodeofthe1=B=R(Hydronics
Institute).
Page 3
RulesforSafeInstallationandOperation
1. Readthe Owner'sManualforSafeOperationcarefully.Failuretofollow therulesforsafeoperationandtheinstructionscancausea malfunctionof the boilerand result in death,_rious bodily injury, and/or property
damage.
2. Checkyourlocalcodesandutilityrequirementsbeforeinstallation.The installationmustbeinaccordancewiththeirdirectives,orfollowNFPA31
- InstallationofOilBurningEquipment,latestrevision.
3. Beforeservicing,allowboilertocool.Nwaysshutoffanyelectricityand oiltoboilerwhenworkingonit.Thiswillpreventanyelectricalshocksor
burns.
4. Inspectoillineandconnectionsforleaks.
5. Be certainoil burnernozzleis size required.Overfiringwill resultin earlyfailureofthe boilersections.Thiswill causedangerousoperation.
6. Nevervent this boiler into an enclosedspace.Alwaysvent to the outside.Neverventto anotherroomor insidea building.
7. Besurethereisadequateairsupplyforcompletecombustion.
8. Followa regutarserviceandmaintenancescheduleforefficientand safeoperation.
9. Keepboilerareacleanandfreeofcombustiblematerial,gasolineand otherflammablevaporsandliquids.
This boiler has been designed for residentialinstallations. If used for commercial
applications,alljurisdictionalrequirementsmustbe met.This mayrequirewiringandlor pipingmodifications.Themanufactureris notresponsibleforany changesto the original
design.
BeforeYouStart
Check to be sure you have the dght size boiler beforestartingthe installation.See ratingand capacitytableon precedingpage.Checkthe
ratingplateontheboiler. You mustsee that theboileris suppliedwiththe properoil,freshair for
combustion,and a suitableelectricalsupply.Also, the boiler must be connectedto a suitableventingsystemand an adequatepipingsystem.
Finally,a thermostat,properlylocated,is neededforcontrolofthe heating system.If youhaveanydoubtsas to thevariousrequirements,checkwith local authorities and obtain professionalhelp where needed. THE
OPERATING INSTRUCTIONSand THE FINAL CHECKS AND ADJUSTMENTSare vitalto the properandsafe operationof the heating
system.Takethetimeto besuretheyarealldone.
Thefollowingstepsareallnecessaryforproperinstallationandsafe operationof yourboiler.
1. LOCATINGTHEBOILER
2. OILSUPPLYANDPIPING
3. FRESHAIR FORCOMBUSTION
4. PIPINGCONNECTIONS
5. CHIMNEY& VENTPIPECONNECTIONS
6. ELECTRICALWIRING
7. THERMOSTATLOCATION
8. CHECKING&ADJUSTING
9. MAINTENANCE
Page 4
Locatingthe Boiler
If yourboileris partof a plannedheatingsystem,locateit as nearlyas
possiblewhereshownon yourplan.If boileris to be partof an existing system,it is usuallybestto put it wherethe old onewas.If youplanto
changelocation,youwill needadditionalmaterialsaswellasan adequate base.Thefollowingrulesapply:
1. The boilermustbelevelandlocatednearpiping.
2. Usea raisedbaseiff]oorcanbecomewetordamp.
3. Theventpipeconnectionshouldbeas shortaspossible.
4. Maintainclearancesforfiresafetyaswellasservicing.SeeFigure2for minimumclearances.18"clearancemustbemaintainedatasidewhere
passageisrequiredforaccessto anothersidefor cleaning,servicing, inspection,or replacementofanypartsthatnormallymayrequiresuch
attention.Boilersmustbe installedat least6"fromcombustiblematerial onallsidesandabove.Allowat least24"frontclearancefor servicing.
Allowat least18"leftsideclearanceforservicingboilersequippedwith
atanklesscoil.
5. FRESHAIRfor combustionmustbeavailableatthefrontoftheboiler. FRESHAIRfor ventilationmustbeavailabletothefrontANDrearof
theboiler.Airpassagesmustbefreeofobstructionsatalltimes.
Ventilatingandcombustionairmustenterboilerroomwithout restrictions.
6. The floor suppo_ng the boiler must be non-combustible.If it is combustible,placetheboileron 2" cladlitepad.Thepadmustbeunder
theentireboilertoprotectthefloor.
7. Besureinstallationisinaccordancewiththerequirementsofthelocal authoritieshavingjurisdiction.Compliancewiththeseregulationsis required.In theabsenceof localcodes,followNFPA31- Insbtlationof
OilBurningEquipment.
Q 6" MIN. 18" WITH COIL
_
_" 6" MIN. "
I_// . I BOILER
I-----2, .,..------IFRO.T
6" MIN.
SeRVraceL_NeLL,.------e_.ec_rRic
F_LPtFE ] I I[ s_,rrc_
GENERAL PRINCIPAL REQUiREMEnTS FOR A TYPICAL INSTALLATION
m_
Page 5
Fresh Air for Combustion
WARNING
NOTE
Be sure to provide enough fresh airfor combustion. Enough air ensures proper combustion and assures that no hazard will develop due to
the lackof oxygen.
If you use a fireplaceor a kitchenor bathroomexhaustfan,you
shouldinstallan outsideairintake.Thesedeviceswill robthe boiler andwaterheaterof combustionair.
You must providefor enough fresh air to assurepropercombustion.The fire in the boiler uses oxygen. It must have a continuous supply. The air in a house contains only enough oxygen to supply the burner for a short time. Outside air mustenter the house to replace that used by the burner. Study foIIowingexampIes 1 and 2to determineyour fresh air requirements. EXAMPLE 1:Boiler Located in Unconfined Space
If your boiler is in an open area (unpartitioned basement) ina conventional house, the air that leaks through the cracks around doors and windows will usually be adequate to provide air for combustion. The doors should not fit tightly. Do not caulkthecracks aroundthe windows.
An unconfinedspace isdefined as aspace whose volume isnot lessthan 50 cubic feet per 1,000Btu per hour of the total inputrating of all appliances
installedin that space. EXAMPLE 2: Boiler Located in Confined Space
A, All Air from Inside the Building: The confined space shall be provided
with two permanent openings communicating directly with an additional
room(s) of sufficientvolume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all
combustion equipment installed in the combined space shall be considered in making this determination. Each opening shall have a
minimumfree area of one square inch per 1,000Btu per hourof thetotal inputratingofall combustionequipment inthe confinedspace, but not less
than 100 squareinches. One opening shall be within 12 inches ofthe top
andonewithin 12 inchesof the bottom of theenclosure.See Figure 4. Example: Your boiler is rated at 100,000 Btu per hour. The water heater
is rated at 30,000 Btu per hour. The total is 130,000 Btu per hour. You need two grilles, each with 130 square inchesof FREE opening. Metal
grilles have about 60% FREE area. To find the Iouveredarea needed,
multiply the FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in. Iouvered area). In thisexample twogrilles, each having an 8"x 30" (240 sq.in,) Iouvered area would be used. Fig. 4 shows the grille locations.
B. All Air from Outdoors: The confined space shall be provided with two
permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawlor attic)thatfreely communicatewith the outdoors.
1.When directly communicatingwith the outdoors, each opening shallhave a minimum free area of one squareinchper 4,000 Btu per hour of total
inputratingof all equipment in theenclosure.
2. When communicatingwith the outdoors through ve_cal ducts, each opening shall have a minimumfree areaof one square inch per 4,000 Btu perhour of total input ratingof all equipmentin theenclosure.
3.Whencommunicatingwiththeoutdoorsthroughhorizontalducts,each openingshall havea minimumfreearea of onesquareinchper
2,000 Btu per hour of totalinput ratingof all equipmentin the enclosure.
4. Whenductsareused,theyshallbeof thesamecross-sectionalarea asthe freeareaof theopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshal{benotlessthanthreeinches.
VENTILATING -'_--i GRII.LE I
i I ' 1
i ,11 II ',
AIR GRILLE _
Fresh Air Duct Capacities for Ducts Supplying Fresh Air to boiler in tightly constructed houses. British Thermal Units per
hour Input (Btuh)*.
Fresh Air Duct Size
31/2"x 12" 8* x 8"
8" x 12" 8" x 16"
1/4"Mesh
Screen Btuh
144,000 256,000
384,000 512,0O0
Wood
Louvers Stuh
36,000
64,000 96,000
128,000
Metal
Louvers Btuh
108,000 !92,000 288,000 384,000
*Based on opening covered by IA" mesh screen, wood louvers, or mela{ louvers
FRESH
Page 6
Boilers With Tankless Heater Coil
Boilersmaybefactorypackagedwithatanklessheatercoil.Theuseof this
coileliminatesthe needforahot waterstoragetank.Instantaneousheatingof waterinthecoil willprovidea flowof hotwaterfor domesticuse- ifproper watersupplylinecontrolsareused.
IMPORTANT
Donot usea tanklesscoilif yourwateris excessivelyhardwithlimeor otherdepositswhichwillaccumulateinsidethecoil.
Forsummerrunningwithcoilyou needtofill boilerwithwaterandaddthe L6006limitcontrolto the coil.Thiswill maintainwatertemperaturein the
boilerand bringtheburneronwhennecessary.
TANKLESSCOlL PIPING
PipingisshowninFigure7B.A temperingvalve(mixingvalve)is
recommended.
LowLimit(whenused)- 140° F
Thesesettingscanbechangedafteryouhavesomeideahowthe system responds.If moredomestichotwateris required,the lowlimitsettingcan
alsoberaised.
_NT_pERE_ _OT WATER
¢OL_ WATE_ _N_ET
WLV_
Page 7
Installation-SystemPiping
Thenearboilerpiping,thatisthe pipingaroundtheboiler,mustbeconsidered aspartofthe boilerforproperwaterlevelcontrol,andto producedrysteam.
Correctnearboilerpipingis crucialtothe properoperationoftheboilerand theheatingsystem.Followtheserecommendationscarefully.
1.Placeboilerintheselectedlocation,as nearchimneyaspossible.
2. Installthepopsafetyvalve,usingthefurnished3/a" 90" ell,intothe3/4" pipenippleonthebackof theboiler.Makea dischargepipe,using3/4"pipe (notfurnished)to carrythe wateror steamto a nearbydrain.Do not connectthe dischargepipe directlyto a drain but leavean airgap.No shutoffofany descriptionshallbeplacedbetweenthe popsafetyvalveand theboiler,or ondischargepipes
betweensuchsafetyvalvesandthe atmosphere.Installationof thepop safetyvalveshallconformtotherequirementsoftheANSI/ASMEBoiler
and Pressure Vessel Code, Section IV The manufactureris not responsibleforanywaterdamage.
3.Thisboileris equippedwithtwo 21/2"supplyconnectionson topand two 1V2"returnconnections,oneeachon frontand backsidesof the boiler.Unusedconnectionsmust
4.Recommendednearboilerpipingfor gravityreturnsys-temsisshown in Figure8. Thisconfigurationusesonesupplyandonereturntapping. Pipingoff bothboilertap-pingsis recommendedon units5 sectionand larger.
Note:Usebothsupplytappingsonboilers5 sectionandlarger.
PtPES_E
Page 8
5.Forinstailerschoosingto usebothsupplytappings,Figure8Ashowsthe correctwayto pipethissystem.Figure8Bshowsthewrongwaytopipe
a headerwithtworisers.
, Headersmustbe fittedwithheaderoffsetsor swingjoints, or be
equippedwith expansionjoints, so that thermalexpansionand contractionofthe headerwillnat damagetheboiler.Headersshall netbewelded.
, Systemtakeoffsfromtheheadermustbebetweentheequalizerand
therisertothe headernearesttheequalizer.Systemtakeoffsmust neverbebetweentworisers.
6.Systemtakeoffsfromtheheadermustneverbe bull-headed.Ifthesteam maingoesintwodirections,theremustbetwotakeoffsfromtheheader, oneforeachmain.
7. All boilersingravityreturnsystemsmustbeequippedwitha Hartford LoopasshowninFigures8and8A.
8. Whenpipingtheverticalrisersfromtheboilertotheheader,thebottom ofthe headermustbea minimumof 24inchesabovethewaterlevel
lineantherightsideoftheboiler(i.e.51inchesabovethefloor).
9. Steamriser(s)andheadershallbe272"pipesize.
10. Equalizerlineshailbeminimum1 1/2"pipesize.
11. The boilerhasa 1V2"tappinginrearsecflanfarskimming.
_EA_{ MAINS
HART_ORO
CLOSE
N|PPLE
MAIN VENT
D_Y RETURN
M_[N
Page 9
THIS, PIPING
COMMON
tS INCORRECT
MISTAKES
TO SHOW
©
L
12. The near boilerpipingshall includea 1 1/2"ballvalveinthereturn pipingasshowninFigure8Afarbottomblowdawnanddraining.
13. Forgravityreturnsystems,thebottomof theloweststeamcarrying pipe,beita dryreturn,ortheendofthesteammain,mustbeatleast 28"abovethenormalwaterlevellineanthedghtsideoftheboiler.
Thisisknownas"DimensionA."
14. Forpumpedreturnsystems,followthecondensatepumporbailerfeed pumpmanufacturer'sinstructionsforproperinstallationandhookup.
15. Inconnectingthecoldwarer supplytothewaterinletvalve,makesure
thata deanwatersupplyisavailable.Whenthewatersupplyis froma wellor pump,asandstrainershouldbeinstalledatthepump.
FORUSEWITHCOOLINGUNITS
A.
This boiler, when used in connection with chilledwater systems,must
be installed so that the chilled water is piped in parallel with the heating boiler. Appropriate valves must be used to prevent the chilled water
from enteringthe heating boiler(Fig. g).
B.Whenthis boileris connectedto heatingcoilslocatedin air handlingunit.,
wherethey may be exposedto refrigeratedaircirculation,the piping systemshall be equippedwith flow controlvalves or other automatic
meansto preventgravitycirculationof theboilerwaterduringthecoolinc cycle.
'_rd,.vE8 A & m
VALVESC & Q
_R _OUNG
Page 10
ChimneyandChimneyConnection
CHECKYOURCHIMNEY
Followlocalcodes.Inthe absenceof localcodes,followANSI/NFPA31 Installationof OilBurningEquipment,latestedition.
Thisisaveryimportantpartof yourheatingsystem.Noboiler,however efficientitsdesign,canperformsatisfactorilyifthechimneythatservesitis
inadequate.Checkyourchimneytomakecertainthatit isthe rightsize, properlyconstructedandinsoundcondition.
Itischeapertorebuildapoorchimneythanto payexcessivefuelbills.If
yoursisanoldmasonrychimney,a newsteellineror anew
prefabricatedchimneymaybethebestsolution.Thefollowingchartshows recommendedminimumchimneysizesbasedonTable3andFigure6 of
theI:B:R TestingandRatingStandardfor HeatingBoilers,Sixth
Edition,June1989.
MUST BE REQUIRED MIN* IMUM HEIGHT, MUST BE
AT LEAST 3 FT. HIGHER THAN HIGHEST PART OF
PASSAGE THROUGH ROOF. MUST BE AT
LEAST 2 FT. HIGHER THAN ANY NEIGHBORING OBJECT. MUST HAVE AN UNOBSTRUCTED TOP
OPENING,
MUST BE AT LEAST
4 INCHES THICK -
AND BE LINED.
_l_ CHFM_ I
.60- i 30 15
13Iol 80 15 i,81o2,00 20
FIECOMMENDED MtNiMUM _IMNEY SIZES
=!:
_ER_ LNER;
_!NNqY' i_DE I_
8"×8 ' 6' 6:5_x 6_' 8' x 8" 7' , 6_f;_"× 6_!4"
[:<]re#_@:(Y)88_ee 2,#_ if,,8J3_es_ _i, ad_3 feetIocblm_qeYhe_gP4_ [_!et la Fiqure 1@t
Foradditionalchimneydesignandsizinginformation,consulttheASHRAE 1996HVACSystemsandApplicationsHand-book,Chapter30,Chimney, GasVentandFireplaceSystems;ortheNationalStandardforChimneys, Fireplaces,VentsandSolidFuelBurningAppliances,ANSI/NFPA211.
CHIMNEYCONNECTORANDDRAFTREGULATOR
Yourboilerrequires7"diameterchimneyconnectorpipeon 3 section,8" diameterchimneyconnectorpipeon 4 section.Youmustalsouse a dralt regulatorpackedwithboiler.Properlyinstalled,theregulatorwillcontrolthe draftautomatically.Itis bettertoinstallitina horizontalsectionofthe pipe;but itmaybeinanangledorverticalsection.Justmakecertainthatthe"top"isat top- andthattheshortpipesectionwhichholdstheVaneishorizontal.Install
itascloseaspracticableto theboiler. Toinstallthechimneyconnector,startatthe boilerandpreferablytakeoff
fromthefluecollectorcollarwithanelbow- theninstallthedraftregulator next,makingit horizontal.Whentheregulatoris inplace,startatthechimney andworkbacktotheregulator.JointhetwosectionswithaDrawband.The horizontalpipemustslopeuptowardthechimneyatleast1/4inchperfoot.It mustnotleakandmustbefirmlysupported.Joinsectionswithatleasttwo sheet-metalscrews.Supporteverysecondsectionwithastovepipewire.
MINIMUMVENTPIPECLEARANCE
ALTERNATE POSITIONS
TOP
1
MUSTSLOPEUP AT LEAST 1/
PER FOOT OF HORIZONTALRUN DRAWBAND
LAST PIECE INSTALLED
I
I L
_,TIGHT. SMOOTH,
CORRECTLY SIZED.
I
I
t
I
&LEDIN
THIMBLE
TIGHT
DOOR
DRAFT REGULATOR VANE
Woodandothercombustiblematerialsmustnotbecloserthan18"fromany BALANCEDWEIGHT surfaceoftheventpipe.
Page 11
EquipmentandOptionalAccessories-WhatTheyDo
POPSAFETYVALVE
Youmusthavea popsafetyvalveonyourboiler.Steamexpandsasit isheated.
Ifthereisno placeforthesteamtoexpandinto,pressurewillbuildupinsidethe boilerandsystem.Shouldthishappen,the popsafetyvalvewillautomatically openata pre-determinedpressure.Thiswill relievethestrainontheboilerand system.Runapipefromthesafetyvalveoutlet(pipemustbesamesizeasoutlet andtheopenendmustnotbethreaded)toan opendrain,tuborsink,or other suitabledrainagepointnotsubjecttofreezing.Failuretodosomaycausewater damageorinjuryshouldreliefvalverelease.Do notcapoffthedrainlinefrom thisvalve!Eachpopsafetyvalveisprovidedwitha liftingdevicefortestingand shouldbetestedmonthlyduringtheheatingseason.Refertosafetyvalve manufacturer'sinstructionspackagedwithsafetyvalve.
STEAMPRESSUREGAUGE
Everysystemshouldhaveapressuregaugeinstalledintheboiler.Thisgauge enablesyoutomonitorthe pressureinthesystem.Ifthesafetydevicesfailtoshut
offyourboileratthepropersettings,notifyyourservicetechnicianimmediately
WATERLEVELGAUGE
Thewaterlevelin theboilercanbeseenthroughtheglasstubeinthewater levelgaugeatsideof boiler.Correctcoldboilerwaterlevelisstampedonside
jacketpanel.Whenmakingsteam,thewaterlevelwilldroponetothreeinches.
Thewaterlevelshouldbecheckedregularly.
STEAMPRESSURECONTROL
Thesteampressurelimitcontrol(pressuretrol)shutsofftheoiltotheburnerifthe steampressureintheboilerreachesthecut-offsetpoint(i.e.thesumofthecut-in
andthedifferentialsetpoints).Burnerretireswhenthesteampressuredropsto thecut-insetpoint.Systempressurerequirementsarebasedonthesizeand
conditionofthepipes,andtheload.
Forgoodsystemoperation,thecut-insettingofthe pressuretrolshouldnever be less than twicethe systempressuredrop. In a typicalsinglefamily residencewith a cleanonepipeheatingsystemandcastiron radiation,this meansthatthecut-inwillusuallybesetattheminimumsetting,i.e._/2psi.
Steamradiationis usuallysizedbasedon squarefeet of equivalentdirect
radiation(EDR).Thisis basedon a steampressureintheradiatorofjust less than1 psi.Therefore,in our examplesystemfromabove,wewouldsetthe differentialadjustmentat1psi,i.e.thesteampressurerequiredinthe radiators. Thiswillgiveusa cut-offsetpointd 1_12psi. Theaboveisan exampleofa typicalonepipesystem.Forlargersystemsor othertypesofsystemssuchas two pipesystems,orsystemswithconvectors or fan coil units,the pressuretrolsettingswill needto be determinedon a system-by-systembasis.
The cut-insetpointisdeterminedbythesystempressuredroptothe furthest
radiatoror terminalunit.Doublethesystempressuredropasa safetyfactor,
resultinginthe rulethatthe cut-insettingshouldneverbe lessthantwicethe systempressuredrop. Thedifferentialset#ointis thesteampressurerequiredattheterminalheating
units.
Nowyourboilerwill operateinthe correctpressurerange.It will maintain enoughsteampressureto sendthe steamouttothe furthestradiator,andnot
go overtheoptimumsteampressurethatisrequiredat theradiators.
67D-t LOWWATERCUT-OFF
Thefloat-typelowwatercut-offshutsofftheburnerwhenthewaterlevelis belowasafepoint.Theburnerwillstartwhenthewaterisrefilledtoa minimumsafelevel.
WATERFEEDER(Optional)
Awaterfeederworkswiththelowwatercut-off(LWCO)tomaintaina minimumsafelevelofwaterforboileroperation.It'susedtokeeptheboiler
runningbycompensatingforminorevaporativesteamleaks,andtoprevent freeze-upsif thehomeownersareawayanda returnlineshouldspringa
leak,Theautomaticwaterfeederisa safetydevice,nota convenienceitem.Itisnotdesignedto maintaina "normal"waterline.The
waterfeederdoesnottaketheplaceofa responsiblepersonmonitoringand maintainingthe"normal"waterline.Steamboilersrequirepersonal
attention.
Four electric water feedersare offeredby McDonnell-Millerwhichare compatiblewiththe 67D-1LWCO.The model#101Aand #WF2-U-120 waterfeedersareusedwith120voltwiringcircuits,asfoundanthissteam
boiler.The McDonnell-Millermodel#101A-24and#WF2-U-24areused with 24 volt circuits,whichmay be usefulin a retrofitinstallationwhich
alreadyhasa 120voltto 24volttransformer. TheWF2-U-120and WF2-U-24(Uni-Match)waterfeedersareequipped
witha solidstateelectroniccontrolwhichfeedswaterwhensignaledbythe LWCO.Thewaterfeedrate isfieldadaptablefar 1,2, or 4 gpm.These waterfeedershavean adjustableslideswitchtomatchthetimingcyclean theLWCO.Whenusinga McDonnell-MillerLWCOtheslideswitchneeds toselectposition#1.The timingcyclecreatesaninitialdwellperiodofone
minuteto allowcondensateto be returnedto the boiler.If afterthedwell periodthewaterhasnatreachedtheminimumsafelevelandcompletedthe
LWCOcircuit,thenwateris fedat theselectedflowratefaroneminute.The dwellpedodistheninitiatedagainfar oneminute.Ifthewaterlevelhasstill
not reachedthe minimumsafe level,then wateris addedagain at the selectedflowrateforoneminute.Thiscyclecontinuesuntilwaterreaches the minimumsafe levelandthe circuitis completed.DunkirkRadiator recommendsusingaUni-Matchwaterfeederataflawrateof1or2gpm.If the steamboilerrequireshigherflowrateson a regularbasisa service
technicianshouldbenotified. The1OlAwaterfeedermaybe used,howeverthewaterfeed rateistoo
high and needsto be regulatedor throttled.The IO1Awillfeedupto 6 gpm,muchgreaterthanthedesiredflowrateof 1-2gpm.Also,thereisno dwellperiodto providea marginfor condensateto returnto the boiler. Thesetwofactorsincreasethechancesofoverfeedingwaterto thesteam
boiler.Excessivewaterinthesteamboilerwillproducenoise Consultthe water feedermanufacturer'sinstallationguidelinesfor more
detailson waterfeederselection,recommendedpipingarrangement,and start up procedures. Dunkirk Radiator supports McDonnell-Miller's
recommendationtoarrangetheinstalledpipingsoa brokenuniontest can beimplemented.
DRAINVALVE
Thismanualvalveprovidesa meansofdrainingallwaterfromtheboilerand system.Itshouldbeinstalledinthe3/a"teewherethewatersupplyline enterstheboiler(Fig.8).Youcanalsousethisvalveto lowerthewaterlevel ifit istoo high.
Page 12
STEAMVENTS
Beforea steamsystemwill operateproperly,suitablesteamventsmustbe
installedin eachradiatoras wellasthe returnmain.Somesystemsrequire steamtrapsinthereturnlineat theradiationunit.
The"Hartfordloop"isa pipingarrangementwhichmustbeincluded(Fig.8) forproperoperationofthesteamsystem.
BOILERSWITHTANKLESSCOILSONLYFlowRegulatorandWater
TemperingValve
Ifyouhavea TanklessCoilfordomestichotwater,thesetwopartscanbe
used.Thiswillprovideyouinstantaneoushotwaterthatis neither
scaldinghotnormerelytepid.The FlowRegulatorisplacedinthecoldwater linetothecoil.It assuresa steadyflowofwatersothatthecoilcanproperly heatit. It prevents"spurts"of "half-heated"water.Thisisimportantwherethe waterpressureisexcessivelyhighorvariable.TheWaterTemperingValve is atee whichis connectedata junctionbetweenthehotwaterlinefromthe coilandacoldwaterbranchfromthesupplyline.Itmixeshotandcoldwater as requiredto furnisha temperedsupplyof watertothe house.Thewater willbejustthe righttemperatureforyouruse.Thisisimportanton a steam systemto preventscaldingtemperaturesat thefaucets.Bothpartsareself-
containedandautomatic.
Starting Your Boiler
HOWASTEAMSYSTEMOPERATES
Thewaterintheboilerisheateduntilit reachestheboilingpoint.Asthe waterboilsit turnsintosteam.Thesteamrisesfromthetopof thewater throughthesupplymainto theradiationunits.As it passesthroughthe
radiatorsitreleasesitsheatandcondensesintowater.Thewaterreturns tothe boilerthroughthe returnmain.
FILLINGSYSTEMWITHWATER
Onsteamheatingsystemstheboileris partiallyfilledwithwater.Itisvery
importantto theproperoperationoftheentiresystemthatyourboilerbe filledto theproperlevel.Thecorrectwaterlevelon coldstartconditionis abouthalfwayupthe glasswaterlevelgaugeasmarkedon theboiler jacket.Tofill:
1.Closetheboilerdrainvalve.
2. Openthevalvesat thetopandbottomoftheglasswaterlevelgauge.
Alsoopenthedrainvalveatthe bottomofthegauge.
3. OpenthefilIvalveandatlowwatertorunintotheboiler.
WARNING- Neverrunwater intoahotemptyboiler,
4.Allowboilertofill untilwaterrunsoutthe gaugedrainvalve.Then
closethegaugedrainvalve.
5.Continuetofillboileruntilwaterreachestheindicatedwaterline.This
Checking and Adjusting
isabouthalfwayuptheglasstube.Alwayskeepthewateratthislevel whensystemisoff.
IMPORTANT
Skimminga newsteamboileronan existingsystemmustbedoneseveral timesto removeall oil,greaseandsediment.Thereshouldbe a teewitha plugpipedtothesupplylineoftheboilerinordertoproperlyskimtheboiler. Wheneverthewaterin the glassgaugebecomesdiscolored,yourboiler
shouldbeskimmed. Whenskimming,makesureto pipetheopenendof thetee tothefloorora
drainto preventanyonefrom beingburnedbythe steamand hotwater whichwillbereleased.
TheFloatLowWaterCut-offshouldbe blowndownafterskimming.Following blowdown,allowtheboilertocoolandthenaddfreshwaterslowly.
Thefloatchamberof thelowwatercut-offmustbeflushedcleanandmaintained clearof sedimentto allowfree movementof the float.This mustbe done
frequentlyduring initial operationof the boilerand at least once per week thereafter.Followinstructionsontagattachedto control.Neverthrottlea steam radiatorvalve on a one-pipesystem.It mustbe fully openor fully closed. Otherwisewaterisheldintheradiatorunits.Thiswillcauseknockingsounds. Skimmingmayberequiredagainafterafewdaysoperation.
CHECKINGCONTROLS
To checkthe LowWaterCut-Off,turnoff powerto theboileror turnthe thermostatdown to the lowestsetting.Drainwaterto belowthe visible
bottomof thewatergaugeglass.Turnpoweronandturnthe thermostatto callfor heat.Whenthe boilerisequippedwiththefloattypeLWCO,theoil
burnershouldnotrunonacallfor heatwhenthewaterislow. To check the pressurelimit, run the boileruntil the pressurereaches
systemdemand.Thenturn the pressurescrewanddropthe pressure settinguntiltheboilershutsdown.Thiswillshowthatthe pressurelimitis operatingproperly.
If youhaveinstalledyourown boiler,we recommendthat youcallfor an
inspectionby a servicetechnician.The peace of mind and assured
performanceare wellworththe cost involved.Hecanquicklymakethe
necessarychecksandadjustments.
OIL BURNERADJUSTMENT
Suggestednozzlesandpreliminaryburnersettingsarefoundon page20. Referto youroil burnerownersmanualfor checkingandadjustingthe
burner.
ADJUSTOPERATINGCONTROLSInstructionsfor eachcontroland
burnerareincluded. Betthermostatheatanticipatorat.20.Instrucfionsforthefinaladjustmentof
thethermostatarepackagedwiththethermostat. CHECKTHERMOSTATOPERATION
Whensetabovetemperatureindicatedon the thermometer,boilerburner shouldstart. Makecertainthe thermostatturnsoff the boilerwhenroom
temperaturereachesthe selectedsettingand startsthe boileroperating whenroomtemperaturefallsafewdegrees.
Finally,setthethermostatforthedesiredtemperature.Specialconditionsin
yourhomeandthelocationofthethermostatwillgovernthissetting.
Page 13
MaintainingYourBoiler
Checkthe waterleveleverydayor two.Verifythe watertineshownby operatingthe drainvalvean thegauge.Be suretop and bottom valves
on gaugeare alwaysopen so thatactualwater levelwill be shown atalltimes,
POPSAFETYVALVE
Thisvalveshouldopenautomaticallywhenthesteampressureexceedsthe safelimit(perinstructionspackagedwithvalve).Shoulditeverfailto open undertheseconditions,shut downyoursystem.Havethevalvereplaced immediately,The pop safetyvalve shouldbe testedmonthlyduringthe heatingseason.Refertothevalvemanufactureflsinstructionspackagedwith thepopsafetyvalve.
LOWWATERCUT-OFF
TheLowWaterCut-offwillin_rrupttheelectricalcurrenttotheburnerwhen thewaterlinein the boilerdropsto a low level.It isveryimportanttokeep
thefloatchamberfreefromsediment,a conditionessentialto dependability. To keep any accumulationfrom interferingwith floatactionis to "BLOW DOWN"or flushoutthecontrolregularly.Thismustbedonetwo-threetimes thefirstweekafterinstallationandonceaweekthereafterduringtheheating season.Doitwhiletheboileris inoperation.Firstnotewaterlevelingauge glass.Openblow-offvalveatbottomof control,waterwillpourout,flushing awaysediment.Drainuntilwaterisclear,abouta pail,thenclosevalve.If waterlevelingaugeglasshasdropped,addwaterto boilertorestorelevel.
Consultlow water cut-offmanufacturersinstructionsincludedwithboiler. NOTE:Openingblow-offvalvecheckscut-offoperationtoo.As floatdrops
withfallingwaterlevel,burnerswillshutoff.Aftervalveisclosedandnormal operatingconditionsarerestored,burnerswillresumefiring. Boilersshouldnot be drainedbetweenheatingseasons.Onlywhenthe waterin thesystembecomesdirtyshouldtheboilerbe drained,flushedor boiledout,andrefilled.Steamboilersmaybeentirelyfilledwithwaterduring
thesummermonthsto excludeair.
CLEANINGYOURBOILER
Undernormaloperatingconditions,withthe burnersproperlyadjusted,we recommendthat you have the flue passages,burneradjustment,and operationof the controlschecked once each year by a Service
Technician. Before the start of each season (orwheneversystemhasbeen
shutdownforsometime)recheckthe wholesystemforleaks...andrecheck theboilerandventpipefor leaks.Replaceor patchanyboilersealsthatare faulty.
BOILERFLUEPASSAGES
FluePassagesbetweensectionsshouldbeexaminedyearlyandcleaned. Removevent pipe.Raisetoppanelof boilerandswingoutto exposeflue collector.Removefluecollectortop. Cleanpassagewaysbetweensections
witha flexiblehandlewirebrush.Removedirtfomthebottomoftheboiler and reassembleall parts.Be sureventpipeconnectionsto chimneyare
secureandnoobstructionsarepresent.
FOAMING,PRIMINGORSURGING
Thesetermsareusedtodescribeafluctuatingwaterline- whenwater leavestheboiler.
Itiscausedby anycombinationofthefollowing:
1.Threadingoilandorganicmatterintheboilerwater.(Mineraloil, orcore sanddoesnotcausesurging.)
2. Faultyquickventsthatdonot releaseairuntila sizeablepressureisbuilt up- replace.Ifdirty,cleansothatyoucaneasilyblowthroughvalve.
3. Improperheader design - whensteamflowsinoppositedirectionof equalizerlineon"Hartfordloop."Generallya 15"horizontalrunbetween
riserandmaintakeoffwill allowentrainedwaterto falloutofthesteam vaporsoitcan returnto boiler.(Seepage7,Fig.8)
4.Adjustmentof steamlimitcontroltoawidedifferentialincreasesdifficultyif quickventsare oldstyle,slow-releasingtypeor dirty.Alwayssetsteam limitcontroldifferentialaslowaspossible.
5.Soapanddetergentscauseextremesurging-cleanthoroughlyby skimmingtheboiler.
CAUTION
Neverrefilla hotboilerwithcoldwater-thedangerofthermalshockmay crackasection.
CAUTION
Neverallowelectricianor oil burnermechanicsto tryouttheirwork by turningon oil burnerfor evenonesecondunlessboileris filledto the properoperatinglevel.
SYSTEMCHECKSAFTERFIRSTSTARTING- STEAMSYSTEMS
Readthe instructionspackagedwithyourcontrolsand makechecksand adjustmentsaccordingly.Start the burnerand set the Thermostatfor the desiredroomtemperature.WhenadjustingtheSteamPressurecontrol,watch thesteamPressureGaugeanduseits pressurereading- asitwill bemore accuratethanthecontrol.(Anydifferencebetweenthe twowillbeduetotheir differentlocation.)
BOILERWATERTREATMENT
Inclosedhotwaterheatingsystems,negligibleamountsofmakeupwaterare used,and watertreatmentis not required.In steam systemswherethe systemistight,freefromleaks,andall the steamis returnedtotheboileras condensate,theamountofmakeupwateris small.Again,watertreatmentis notrequired. On steamsystemswith lessthan 90% of the steambeingreturnedas condensate,orwithveryhardor corrosivemakeupwater,treatmentmaybe desirable.Followthe recommen-dationsof theASME(AmericanSocietyof MechanicalEngineers)Boilerand PressureVesselCode,SectionVl, latest
version.
BETWEENHEATINGSEASONS
Boilersshouldnotbedrainedbetweenheatingseasons.Boilersinclosedhot waterheatingsystemsmaybeleftas is.Steamboilersshouldbeentirelyfilled withwaterduringthesummermonthsto excludeair.
Page 14
Oil Boiler/BurnerCleaningInstructions
1. ShutoffalIelectricaIpowertotheboiler/burnerandshutofffuelsupply.
2. Removethesheetmetalsmokepipefromthetopd theboiler.Inspect pipeandchimneyfor signsofcorrosionanddeterioration.Cleanbase ofchimney.
3. Removetopjacketpanel.
4. Removethetwobrasswingnutsholdingtheflueccllectorfop.
5. Checkthegasketontheundersideof thefluecollectorandreplaceas necessary.
6. Removetheoil burner(threecapscrews).-OR- Removetheoil burner/firedoorassembly(fourhex nuts).Thisis the
recommendedmethod,as it allows full accessto the combustion chamberandlesspotentialdamagetothetargetwallduringthecleaning
process.
7. Removetheburnerdrawerassembly.Cleananysootaccumulations.
8. Replacetheburnernozzlewiththeexactsizeandtyperecommended
forus onthisboiler.
Note:Changingto adifferentfiringrate,otherthanisrecommended,ortype
of nozzlemaychangethe performanceof this boilerand/orcausea hazardouscondition.
9. Cleanelectrodeassemblyandsetelectrodesasperburner manufacturersrecommendations.
10.Reinstalldrawerassemblyandcheckforproperheadlocationas per themanufacturer'srecommendations.
11.Inspectthetargetwail,blanket,andfiredoorinsulationforcrackingand
deterioration.If thereisanysignsofcrackingor deterioration,replace beforereassemblingtheboiler.
12.Removesootfromfiresidesurfacesbybrushingdiagonallythroughthe flue passages(see drawing).Care shouldbe taken so as not to
damagethetargetwallwiththefluebrush.
13.Carefullyvacuumsootaccumulationsfromthecombustionchamber
area,beingparticularlycarefulnottodamagethetargetwailandblanket
withthevacuum.Targetwallandblanketmustbeingoodconditionand
correctlyinstalledtoinsurepropercombustion.
\
oooooooooooo
ooooooo
%%%°°%%°2°
°j°o°2o%%%°2o°Co°2o °°°°%02°%°o%%°°°0%%°Oo°
14. Reinstalltheburner/firedoorassembly.
15. Reinstallthefluecollectortopandsecurewiththetwobrasswingnuts.
16. ReinstalIthetopjacketpanel.Reconnectthefluepipe.
17. Inspectandcleantheoil burnerblowerwheel.
18. Oilthe burnermotor(DONOTOVEROIL}.
19.Removetheoilpumpcoverandclean/replacethepumpscreen.Carefully reassemble.
20.Replacethefuelfilter(ifapplicable).
21.Reconnecttheelectricalandfuelsupplies.
22. Fire the burner,checkingfor propercombustionusingcombustiontest
equipment,makingadjustmentsasnecessary.
23.Insurethatallsafetycontrolsandoperatingcontrolsarefunctioning properly.
IMPORTANTOPERATINGANDMAINTENANCEREQUIREMENTSKEEPYOURBOILERANDTHEAREAAROUNDIT
CLEANNEVERBURNREFUSEORANYMATERIALOTHERTHANTHESPECIFIEDFUELINYOURBOILERHAVEYOUR
BOILERCHECKEDEACHYEARBYAQUALIFIEDTECHNICIAN
Page 15
_u me_javowalir_o_nven_ and servi_ calls _ ch_ these potn(s _m _ c_l for _r_ce.
Bu _ler may not _ iitng at proper re[@
Burner may be shortocyct ag,
po_r _ boile_
OonttoIs o_t of adjustment
What: to
Reset themsostat above room tem_raIu 8. Cean all flue passages and _'he'_nt pipe,
Nave burner c_ea_d and read ueted, C_eek _e_f_e size if there is _y doubt,
Have burner adjusted S_ort-r_cting {too frequent off and on) of bu[ner will cause s,aoti_ _f_r ar_df
or burner bec_e dirty at frequent in_ervaJs,dter eorreotino Itre drt conditior_....
also correct _he@n_ro_setting (or other _se e#_:heehorbcV_c4i_'_gl
Check thefm_sM he_[ _ntio pa,tor_d _rre_ _tt_, if neces_ry, per ine_r_t_or_
Check o,.,_ercurreetprotection Check to _ sure power supply circuit is "ON, Reset accordi_ to in_r_l_ie_s packed with coatro/& Check a_icontrol term_inatsan_ w#e ioinls,
HAV_ YOUR 8_RVIC_ TECHNICIAN CHECK ANY PROBLE_ YOU ARE UNAI_LE _ CORRECT.
Page 16
COLORCODE
BK = BI_CK
BL = BLUE
W = WHITE
G = GREEN
i_ =WIRE NUT
pARTNO, - 146-34-O47
2 X 4 JUNCTION
PART NO, _45-31-O82
HANDY BOX COVER (NOT SHOWN)
PART N0. _46-61-121
LOCK-NUT (2
PART NO.
I/2" CLOSE
PART NO. 146-07-030
HONEYWELL
PRESSURETROL _
PART NO. 146-62-015
- GROUND SCREW PART NO. 1€6-54-B02
-UNE VOLTAGE (GROUND)
LINE VOLTAGE (NEUT. LEAD)
\
_PRESSURETROL TO LWC.O HARNESS
PART NO, 433-00-873
OIL BURNER
PRIMARY RELAY
OPTIONAL LOW LIMIT
CONTROL FOR BOILERS WITH TANKLESS COIL
\ z z
TO 24v
THERMOSTAT
LOW VOLTAGE WiRiNG HARNESS NOT FURNISHED
L BURNER TO L.WC.O. HARNESS
PART NO - 433-00-872
LINE VOLTAGE (NOT LEAD)
#2 TERMINAL LWCO
PART NO, 433--00--874
67D-1 LW*C,O,
W_RINGTERMINAL DETAIL
'tJ
WH_E
FROM OIL BURNER
BLACK LEAD
FROM OiL BURNER
McDONNELL M_LLER
L W.C.O
PART NO. 146-26-042
4 X 4 OIL BURNER JUNCTION BOX
Page 17
Page 18
"_p_r_ Tsr_kle_ _i_ K_t4340_14 (ir_l:_s coJ_,_8{, and b_l_)
4
L_!
Page 19
(1 _69BI0! )
Page 20
BOILER
MODEL
3ES1.00(C)
3ES1,25(0)
3ES! .35(C)
4ES1,50(C)
4ES1,75(C)
4ES1,85(0)
SUGGESTED NOZZLES AND SETTINGS
FOR BECKETT AFG-M OIL BURNER SERIES
NOZZLE ACTUAL
0,85-60°W 1.00
1,10-70°B 1.25
1,20-70°B 1.35
1,25-60°B 1.50
1,50-60°B 1.75
1.75-60°B 1.85
PUMP
PRESSURE
(psig)
!40
140
!40
140
140
140
HEAD
ADJUSTMENT
1
1
1
3
3
AIR
SHUTTER
10 10
10 I0
10 10
AIR
BAND
1
1
2
2
3
4
OIL
BURNER
MODEL
AFG-50MB
AFG-50MD
AFG-50MD
AFG-50MD
AFG-50MD
AFG-50MD
FOR RIELLO R40 OIL BURNER SERIES
ACTUAL PU M P AI R OIL
BOILER NOZZLE TURBULATOR
MODEL (DELEVAN) INPUT PRESSURE SETTING GATE BURNER
RATE (gph) (psig) SETTING MODEL
3ES1,00(C) 0.85-60°W 1.00 150 2,0 3.00 F5 3ES1,25(C) 1.00-60°W 1.25 165 2.5 3.60 F5 3ESl.35(C) 1.10-60°W 1.35 165 3.5 4.25 F5
4ES1.50(C) 1.25-60°W 1.50 160 1.5 2.60 FIO 4ES1.75(C) 1.50-60°W 1.75 145 1,5 3.25 FIO
4ES1.85(C) 1.50-60°W 1.85 160 2.0 3.40 FIO
FOR CARLIN EZ OIL BURNER SERIES
BOILER NOZZLE I HEAD
[
MODEL (DELEVAN) ! SETTING
3ES1.00(C) 3ES1,25(C)
3ES1.35(C) 4ES1.50(C)
4ES1,50(C) 4ES1,65(C)
4ES1,85(0)
0.85x70ow
1.00x70°W 1, !Ox70°W
1.25x60°W 1,25x60°W
1.35x60°W 1,50x60°W
ACTUAL
INPUT
RATE (gph)
1.00
1.25
1.35
1.50
1.50
1.65
1.85
PUMP
PRESSURE
(psig)
150 150 150
150 150
150 150
0.85-1.00
0.85-1.00 1,10-1.25
1.10-1.25
0.85-!.00
1.50 ! ,50
AIR BAND
SET
POINT
0.65
0.90
1.!0 1,10
1,65
1.65
2.00
OIL
BURNER
MODEL
EZ-1 HP
EZ-1 HP EZ-I HP EZ-1 HP
EZ-2 HP EZ-2 HP EZ-2 HP
All burners fired at an over fire pressure of -0,02"wc.
Burner insertion depth of 2-1/8" allows burner tip to be 1/4" behind insulation, I NOTE: These settings are intended for ini-
I
tial start up only, Final adjustment must be
!
made using combustion test instruments, i
Loading...