Ducane 97G2DF110CV20 Instruction/Installation Manual

Page 1
INSTALLATION INSTRUCTIONS
Warm Air Gas Furnace
Downow Air Discharge
97G2DFV
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
Direct Vent & Non-Direct Vent
Table of Contents
Unit Dimensions ........................................................ 2
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Parts Arrangement..................................................... 3
Gas Furnace .............................................................. 4
Shipping and Packing List ......................................... 4
Safety Information ..................................................... 4
General ...................................................................... 6
Combustion, Dilution & Ventilation Air ....................... 7
Installation ............................................................... 10
Filters ....................................................................... 12
Duct System ............................................................ 12
Venting Practices ..................................................... 15
Condensate Piping .................................................. 31
Gas Piping ............................................................... 34
Electrical .................................................................. 36
Testing for Proper Venting and Su󰀩cient Combustion
Air for Non-Direct Vent Applications ........................ 44
Unit Start-Up ............................................................ 45
Blower Performance ................................................ 48
Service..................................................................... 50
Planned Service ...................................................... 52
Repair Parts List ...................................................... 52
Manufactured By
Allied Air Enterprises LLC
A Lennox International, Inc. Company
215 Metropolitan Drive
508405-01 Page 1 of 53Issue 2332
*P508405-01*
(P) 508405-01
Page 2
9/16
(14)

Unit Dimensions

9/16
(14)
Flue Condensate Trap Assembly
Furnished for external field installation on either side of unit. (See installation instructions for additional information.)
A
B
AIR
FLOW
9/16
(14)
33
(838)
COMBUSTION
AIR INTAKE
7
(178)
EXHAUST AIR
GAS PIPING INLET
(Either Side)
9-1/8 (232) Right 6-9/16 (167) Left
OUTLET
2-1/16 (52)
1 (25)
Front Panel
2 (51)
Either Side
5
(127)
RETURN AIR
B
OPENING
2-1/4
(57)
9/16
(14)
TOP VIEW
27-3/4
(705)
19-7/16
(494)
ELECTRICAL INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
6-7/16 (163)
Either Side
9 (229)
Either Side
3/4
(19)
C
Supply
Air
3/4
(19)
19-1/4
(489)
Supply
FRONT VIEW SIDE VIEW
Capacity
070-16 17-1/2 446 16-3/8 416 16 406
090-20 110-20
in. mm in. mm in. mm
21 533 19-7/8 504 19-1/2 495
A B C
Air
3/4
(19)
508405-01Page 2 of 53 Issue 2332
Page 3

Parts Arrangement

Blower Assembly
Control Box
Access Panel
Combustion Air
Inducer
Gas Valve
Burner Box
Assembly
Figure 1.
508405-01 Page 3 of 53Issue 2332
Page 4

Gas Furnace

Shipping and Packing List

This Category IV gas furnace is shipped ready for
installation in the downow position.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in LP/propane gas applications.
This unit can be installed as either a Direct Vent or a Non­Direct Vent gas central furnace.
NOTE: In Direct Vent installations, combustion air is taken
from outdoors and ue gases are discharged outdoors.
Non-Direct Vent installations, combustion air is taken from
indoors or ventilated attic or crawl space and ue gases are discharged outdoors. See Figure 2 and Figure 3 for application involving roof termination.
Package 1 of 1 contains:
1 - Assembled Gas Unit
1 - Bag assembly containing the following:
1 - Snap bushing
1 - Snap Plug
1 - Wire tie
1 - Condensate trap
1 - Condensate trap cap
1 - Condensate trap clamp
1 - 2” diameter debris screen
1 - 3/4” Threaded street elbow
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Please refer to specication sheets for available
accessories.

Safety Information

Figure 2.
DANGER
DANGER OF EXPLOSION!
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the oor and may be di󰀩cult to smell. An LP/propane leak detector should be
installed in all LP applications.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
This unit is CSA International certied to ANSI Z21.47 and
CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel
Gas Code (ANSI Z223.1/NFPA 54). The National Fuel Gas
Code is available from the American National Standards Institute, Inc., 11 West 42nd Street, New York, NY 10036.
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
Figure 3.
In order to ensure proper unit operation in non-direct vent applications, combustion and ventilation air supply must
508405-01Page 4 of 53 Issue 2332
Page 5
be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Locations and Clearances
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit nameplate and in the table in Figure 14. Accessibility
and service clearances must take precedence over re
protection clearances.
NOTE: When furnace is installed on a combustible oor, a downow combustible ooring base must be installed between the furnace and the oor.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are
located no less than 18 inches (457 mm) above the oor.
The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE: Furnace must be adjusted to obtain a temperature rise within the range specied on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure.
This gas furnace must be installed so that its electrical components are protected from water.
Figure 4.
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE: This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units (Figure 4), it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating
compartment. With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately
prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
This gas furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms.
This furnace design has NOT been CSA certied for
installation in mobile homes, recreational vehicles, or outdoors.
Never use an open ame to test for gas leaks. Check all
connections using a commercially available soap solution
made specically for leak detection.
Use of Furnace as a Construction Heater
Units may be used for heating of buildings or structures under construction, if the following conditions are met to ensure proper operation.
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT UNLESS ALL OF THE FOLLOWING CRITERIA ARE MET:
a. Furnace must be in its nal location. The vent system
must be permanently installed per these installation instructions.
b. Furnace must be installed as a two pipe system
and one hundred percent (100%) outdoor air must be provided for combustion air requirements during construction.
508405-01 Page 5 of 53Issue 2332
Page 6
c. A room thermostat must control the furnace. The use
of xed jumpers that will provide continuous heating is
prohibited.
d. The input rate and temperature rise must be set per
the furnace rating plate.
e. Supply and Return air ducts must be provided and
sealed to the furnace. Return air must be terminated outside of the space where furnace is installed.
f. Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
g. MERV 11 or greater air lters must be installed in
the system and must be regularly inspected and maintained (e.g., regular static checks and replaced at end of life) during construction.
h. Blower and vestibule access panels must be in place
on the furnace at all times.
i. The furnace heat exchanger, components, duct
system, and evaporator coils must be thoroughly
cleaned following nal construction clean−up.
j. Air lters must be replaced upon construction
completion.
k. All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must
be veried in accordance with these installation
instructions.
EQUIPMENT MAY EXPERIENCE PREMATURE COMPONENT FAILURE AS A RESULT OF FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS. FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS VOIDS THE MANUFACTURER’S EQUIPMENT LIMITED WARRANTY. ALLIED AIR DISCLAIMS ALL LIABILITY IN CONNECTION WITH INSTALLER’S FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS.
NOTWITHSTANDING THE FOREGOING, INSTALLER IS RESPONSIBLE FOR CONFIRMING THAT THE USE OF CONSTRUCTION HEAT IS CONSISTENT WITH THE POLICIES AND CODES OF ALL REGULATING ENTITIES. ALL SUCH POLICIES AND CODES MUST BE ADHERED TO.

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing one of these furnaces:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.
• When the furnace is installed in non-direct vent applications, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
• When the furnace is installed in a non-direct vent applications, do not block the furnace combustion air
opening with clothing, boxes, doors, etc. Air is needed
for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of the condensate drain system.
NOTE: The Commonwealth of Massachusetts stipulates these additional requirements:
• Gas furnaces shall be installed by a licensed plumber
or tter only.
• The gas cock must be “T handle” type.
• When a furnace is installed in an attic, the passageway to and service area surrounding the equipment shall
be oored.
CAUTION
These units should not be installed in areas normally subject to freezing temperatures.
508405-01Page 6 of 53 Issue 2332
Page 7

Combustion, Dilution & Ventilation Air

If this unit is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.
NOTE: In Non-Direct Vent Installations, combustion air is
taken from indoors and ue gases are discharged outdoors.
the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This reprinted material is not the complete and o󰀩cial position
of ANSI on the referenced subject, which is represented only by the standard in its entirely.
In Canada, refer to the CSA B149 Installation codes.
CAUTION
WARNING
Insu󰀩cient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine base swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
In the past, there was no problem in bringing in su󰀩cient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, appliance vents, chimneys, and replaces force additional
air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this
section to install these furnaces to ensure e󰀩cient and safe
operation. You must consider combustion air needs and
requirements for exhaust vents and gas piping. A portion
of this information has been reprinted with permission from
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-red appliances require air for the combustion process. If su󰀩cient combustion air is not available, the furnace or other appliance will operate ine󰀩ciently
and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such
as exhaust fans which force air out of the house. When replaces, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is required to ensure proper combustion and to prevent a down draft.
Insu󰀩cient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is
installed in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement
or large equipment room with a volume greater than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to
be unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the “Air from Outside” section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space
508405-01 Page 7 of 53Issue 2332
Page 8
containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the
conned space either from inside the building or from
outside.
Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in
by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm²) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm²). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 5.
It is also permissible to bring air for combustion from a ventilated attic (Figure 9) or ventilated crawl space (Figure
10).
Figure 6. Equipment in Conned Space - All Air from
Outside
(Inlet Air from Crawl Space and Outlet Air to
Ventilated Attic)
Figure 5. Equipment in Conned Space - All Air from
Inside
Air from Outside
If air from outside is brought in for combustion and
ventilation, the conned space shall be provided with two
permanent openings. One opening shall be within 12” (305 mm) of the top of the enclosure and one within 12” (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645 mm² per .59 kW) per hour of the total input rating of all equipment in the enclosure (see Figure 6 and Figure 7).
When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm²) per 2,000 Btu (.56 kW) per hour of the total input rating of all equipment in the enclosure. See Figure 8.
When ducts are used, they shall be of the same cross­sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In
calculating free area, the blocking e󰀨ect of louvers, grilles,
or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and
grilles must be xed in the open position or interlocked
with the equipment so that they are opened automatically during equipment operation.
508405-01Page 8 of 53 Issue 2332
Page 9
Figure 7. Equipment in Conned Space - All Air from
Outside
(All Air Through Ventilated Attic)
Ventilation Louvers
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
Inlet Air (Minimum 12 in. (305mm) above
Attic Floor)
* See Maximum Vent Lengths table
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.
Figure 9. Equipment in Conned Space
(Inlet Air from Ventilated Attic and Outlet Air to
Outside)
Roof Terminated
Exhaust Pipe
Figure 8. Equipment in Conned Space - All Air from
Outside
WARNING
If this unit is being installed in an application with combustion air coming in from a space serviced by an
exhaust fan, power exhaust fan, or other device which
may create a negative pressure in the space, take care when sizing the inlet air opening. The inlet air opening
must be sized to accommodate the maximum volume of exhaust air as well as the maximum volume of
combustion air required for all gas appliances serviced by this space.
Inlet Air
Minimum
Ventilation
Louvers
(Crawl Space)
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
Furnace
12 in. (305mm)
above Crawl Space Floor
*Intake Debris Screen Provided
* See Maximum Vent Lengths table
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour of the total input rating of all equipment in the enclosure.
2
Figure 10. Equipment in Conned Space
(Inlet Air from Ventilated Crawl Space and Outlet Air
to Outside)
508405-01 Page 9 of 53Issue 2332
Page 10

Installation

Setting Equipment
WARNING
Do not install the furnace on its front, back or in the horizontal position. See Figure 13. Do no connect the return air ducts to the back of the furnace. Doing so
will adversely a󰀨ect the operation of the safety control
devices, which could result in personal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. Tilt the unit slightly
(maximum 1/2 in. from level) from back to front to aid in the draining of the heat exchanger. See Figure 12.
Shipping Bolt Removal
NOTE: Units with a 1/2 hp blower motors are equipped
with three exible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a at white plastic washer (rather than the rubber mounting grommet used with a exible mounting leg). See Figure 11. The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in Figure 14.
Units with 1/2 HP Blower Motor
Figure 12. Setting Equipment
Figure 13.
WARNING
Improper installation of the furnace can result in
personal injury or death. Combustion and ue products
must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices
such as a replace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property
damage could result.
Figure 11.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
The unit may be installed three ways in downow applications: on non-combustible ooring, on combustible ooring using an additive base, or on a reverse-ow cooling coil cabinet. Do not drag the unit across the oor in the downow position. Floor and furnace ange damage
will result.
Refer to Figure 14 for clearances in downow applications.
508405-01Page 10 of 53 Issue 2332
Page 11
Top 0
* Front 0
Back 0
Sides 0†
Vent 0
Floor NC‡
* Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
† Allow proper clearances to accommodate condensate trap.
‡ The furnace may be installed on a combustible wood oor if
an optional additive base is installed between the furnace and
the combustible oor.
Figure 14. Downow Application Installation
Clearances
Installation on Non-Combustible Flooring
1. Cut oor opening keeping in mind clearances listed on unit rating plate. Also keep in mind gas supply
connections, electrical supply, ue and air intake connections and su󰀩cient installation and servicing clearances. See Table 1 for correct oor opening size.
2. Flange warm air plenum and lower the plenum into the opening.
3. Set the unit over the plenum and seal the plenum to the unit.
4. Ensure that the seal is adequate.
Figure 15.
Installation on Combustible Flooring
1. When unit is installed on a combustible oor, a downow combustible ooring base must be installed between the furnace and the oor. The base must be
ordered separately. See Table 2 for opening size to
cut in oor.
CAUTION
The furnace and combustible ooring base shall not be
installed directly on carpeting, tile, or other combustible
material other than wood ooring.
Cabinet
Width
B cabinet (17.5”)
C cabinet (21”)
Catalog Number
11M60
11M61 22-3/4 578
Table 2. Combustible Flooring Base Opening Size
Front to Rear Side to Side
in. mm in. mm
18-3/4 476
22 559
Cabinet Width
B cabinet (17.5”)
C cabinet (21”) 20-1/8 511
NOTE: Floor opening dimensions listed are 1/4 in. (6 mm) larger than the unit opening. See dimension drawing on Page
2.
Front to Rear Side to Side
in. mm in. mm
16-5/8 422
19-3/4 502
Table 1. Non-Combustible Floor Opening Size
508405-01 Page 11 of 53Issue 2332
Figure 16.
Page 12
2. After opening is cut, set the combustible ooring base into opening.
3. Check berglass strips on the combustible ooring base to make sure they are properly glued and positioned.
4. Lower supply air plenum into the combustible ooring
base until plenum anges seal against berglass
strips.
NOTE: Be careful not to damage berglass strips. Check for a tight seal.
5. Set the furnace over the plenum.
6. Ensure that the seal between the furnace and plenum is adequate.
Installation on Cooling Coil Cabinet
NOTE: Downow combustible ooring kit is not used.
1. Refer to reverse-ow coil installation instructions for correctly sized opening in oor and installation of
cabinet.
2. When cooling cabinet is in place, set and secure the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3. Seal the cabinet and check for air leaks.
Figure 18.
Figure 19.

Filters

Figure 17.
Return Air Opening - Downow Units
Return air may be brought in only through the top opening of
a furnace installed in the downow position. The following
steps should be taken when installing plenum:
1. Bottom edge of plenum should be anged with a hemmed edge (see Figure 18 or Figure 19).
2. Sealing strips should be used to ensure an airtight seal between the cabinet and the plenum.
3. In all cases, plenum should be secured to top of furnace using sheet metal screws.
4. Make certain that an adequate seal is made.
This unit is not equipped with a lter or rack. A eld provided lter is required for the unit to operate properly. Table 3 lists recommended lter sizes.
A lter must be in place whenever the unit is operating.
Furnace Cabinet Width Filter Size
17-1/2”
21”
Table 3.
16 x 25 x 1 (1)

Duct System

Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE: This furnace is not certied for operation in heating mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.8 inches w.c. Operation at these conditions may result in improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection
(by reected light) of the heat exchanger for leaks after the
508405-01Page 12 of 53 Issue 2332
Page 13
furnace is installed. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE: Return air must not be drawn from a room where
this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This
reverse ow of the ue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the
house by the furnace duct system.
Use berglass sealing strips, caulking, or equivalent
sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.
Pipe & Fittings Specications
All pipe, ttings, primer and solvent cement must conform
with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards.
The solvent shall be free owing and contain no lumps,
undissolved particles or any foreign matter that adversely
a󰀨ects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratication,
or separation that cannot be removed by stirring. Refer to
Table 4 below for approved piping and tting materials.
Piping and Fittings Specications
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468 ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings) PVC-DWV (Drain Waste & Vent)
Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656
PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235 PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm ULC-S636
ECCO Polypropylene Vent
TM
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235,
F493
D3138
MARKING
ULCS636PVC & CPVC Solvent Cement
ULC-S636
ULC-S636
CAUTION
Solvent cements for plastic pipe are ammable liquids
and should be kept away from all sources of ignition.
Do not use excessive amounts of solvent cement when
making joints. Good ventilation should be maintained to
reduce re hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
IMPORTANT
The exhaust and intake connections are made of PVC.
Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional
solvent cement to make connections to the PVC tting
in the unit.
508405-01 Page 13 of 53Issue 2332
Table 4.
Use PVC primer and solvent cement or ABS solvent
cement meeting ASTM specications, refer to Table 4.
As an alternate, use all purpose cement, to bond ABS,
PVC, or CPVC pipe when using ttings and pipe made of
the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used as vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of tting and male end of pipe to depth of tting socket.
Canadian Applications Only
Pipe, ttings, primer and solvent cement used to vent (exhaust) this appliance must be certied to ULC S636 and
supplied by a single manufacturer as part of an approved
vent (exhaust) system. When bonding the vent system to
the furnace, use ULC S636 approved One-Step Transition
Cement to bond the pipe to the ue collar. In addition, the
Page 14
rst three feet of vent pipe from the furnace ue collar must
be accessible for inspection.
Table 5 lists the available exhaust termination kits. All vent
terminations are PVC.
Joint Cementing Procedure
All cementing of joints should be done according to the
specications outlined in ASTM D 2855.
NOTE: A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1. Measure and cut vent pipe to desired length.
2. Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe
may remove cement from tting socket and result in a
leaking joint.
3. Clean and dry surfaces to be joined.
4. Test t joint and mark depth of tting on outside of pipe.
5. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket
surface of tting and male end of pipe to depth of tting
socket.
6. Promptly apply solvent cement to end of pipe and
inside socket surface of tting. Cement should be
applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply
second coat to end of pipe.
NOTE: Time is critical at this stage. Do Not allow primer to dry before applying cement.
STANDARD CONCENTRIC
Outdoor
VENT
Capacity
070
090
110
1
2 inch to 1-1/2 inch reducer required, must be eld provided.
* Requires eld-provided and installed 1-1/2” exhaust accelerator.
** Kit 51W11 is provided with a 1-1/2” accelerator, which must be used for all 70,000 furnace installations. When using 1-/2 in. piping,
the pipe must be transitioned to 2 in. pipe when used with the Flush Mount Kit.
† Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.
†† The 44W92 concentric kit is provided with a 1-1/2” accelerator, which must be installed on the exhaust outlet when this kit is used
with the 70,000 furnaces. When using 1-1/2 in. piping, the pipe must be transitioned to 2 in. pipe when used with the Concentric Kit.
PIPE DIA.
(in.)
1
1-1/2 YES YES
2 YES YES YES
2-1/2" YES YES YES
3 YES YES YES
2 YES YES YES YES
2-1/2" YES YES YES YES
3 YES YES YES YES
2 YES YES YES YES
2-1/2" YES YES YES YES
3 YES YES YES YES
Exhaust
Accelerator
(Dia. X Length)
1-1/2" x 12" 2" x 12" 51W11**
Outdoor Exhaust
Accelerator
(Dia. X Length)
Flush Mount
Kit
1-1/2"
Concentric Kit
71M80
OR
+44W92++
2" Concentric
Kit
69M29
OR
+44W92++
3" Concentric
Kit
60L46
OR
44W93+
Table 5. Outdoor Termination Kits Usage
508405-01Page 14 of 53 Issue 2332
Page 15
7. Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. Do not turn ABS or cellular core pipe.
NOTE: Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.
8. After assembly, wipe excess cement from pipe at end of tting socket. A properly made joint will show a bead
around its entire perimeter. Any gaps may indicate
an improper defective assembly due to insu󰀩cient
solvent.
9. Handle joints carefully until completely set.

Venting Practices

Figure 20. Piping Suspension Guidelines
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from
a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3. Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn ON clothes dryers and any appliances not connected to the
common venting system. Turn ON any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Follow the lighting instructions. Turn ON the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5. After the main burner has operated for 5 minutes, test
for leaks of ue gases at the draft hood relief opening. Use the ame of a match or candle.
6. After determining that each appliance connected to the common venting system is venting properly, (step
3) return all doors, windows, exhaust fans, replace
dampers, and any other gas burning appliances to their previous mode of operation.
7. If a venting problem is found during any of the preceding tests, the common venting system must be
modied to correct the problems.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in
Appendix G. These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section.
508405-01 Page 15 of 53Issue 2332
Page 16
Figure 21.
Vent Piping Guidelines
This gas furnace can be installed as either a Non-Direct Vent or a Direct Vent gas central furnace.
NOTE: In non-Direct Vent installations, combustion air is
taken from indoors and ue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from
outdoors and ue gases are discharged outdoors.
Intake and exhaust pipe sizing - Size pipe according to
Table 6 and Table 7A through Table 7C. Table 6 lists the minimum vent pipe lengths permitted. Table 7A through
Table 7C lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination.
Capacity Min. Vent Length*
15 ft. or
070, 090, 110
* Any approved termination may be added to the minimum length listed.
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
1. In areas where piping penetrates joist or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2. When furnace is installed in a residence where unit
is shut down for an extended period of time, such
as a vacation home, make provisions for draining condensate collection trap and lines.
Exhaust Piping
Route piping to outside of structure. Continue with installation following instructions given in piping termination section.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
Table 6. Minimum Vent Pipe Lengths
In some applications which permit the use of several
di󰀨erent sizes of vent pipe, a combination vent pipe may
be used. Contact Allied Air Technical Service for assistance in sizing vent pipe in these applications.
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and may block the terminations.
CAUTION
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of combustion products into the living space.
508405-01Page 16 of 53 Issue 2332
Page 17
Use the following steps to correctly size vent pipe diameter.
070, 090,
110
Standard or Concentric? See Table 5
Intake or
Exhaust?
1-1/2”, 2”,
2-1/2”
or 3”
Furnace capacity?
1
Which termination?
2
Which needs most elbows?
3
How many?
4
Desired pipe size?
5
What is the altitude?
6
Use Table 7 to find max pipe length.
7
Figure 22.
508405-01 Page 17 of 53Issue 2332
Page 18
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
1 15
2 10 46 24
3
4 36 14 85 63 28 107 88 88
5 31 9 80 58 23 102 83 83
6 26
7 21 70 48 13 92 73 73
8 16 65 43 8 87 68 68
9 11 60 38
10 6 55 33 77 58 58
Number of
90° Elbows
Used
1 15
2 10 46 24 95 73 38 11 7 98 98
3
4 36 14 85 63 28 107 88 88
5 31 9 80 58 23 102 83 83
6 26
7 21 70 48 13 92 73 73
8 16 65 43 8 87 68 68
9 11 60 38
10 n/a 55 33 77 58 58
*Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
1-1/2” Pipe 2” Pipe 2-1/2” Pipe 3" Pipe
Capacity Capacity Capacity Capacity
070 090 110 070 090 11 0 070 090 110 070 090 11 0
51 29 9 100 78 43 122 103 103
95 73 38 117 98 98
41 19 90 68 33 112 93 93
n/a n/a
n/a
n/a
Standard Termination at Elevation 4,501 - 10,000 ft
1-1/2” Pipe 2” Pipe 2-1/2” Pipe 3" Pipe
Capacity Capacity Capacity Capacity
070 090 110 070 090 11 0 070 090 110 070 090 11 0
51 29
41 19 90 68 33 112 93 93
n/a n/a
n/a
n/a
n/a
n/a
75 53 18 97 78 78
n/a
100 78 43 122 103 103
75 53 18 97 78 78
n/a
82 63 63
82 63 63
Table 7A.
508405-01Page 18 of 53 Issue 2332
Page 19
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
1
2 38 22
3 33 17 80 64 29 96 89 89
4 28 12 75 59 24 91 84 84
5 23 7 70 54 19 86 79 79
6 18
7 13 60 44 9 76 69 69
8
9 50 34 66 59 59
10 45 29 61 54 54
Number of
90° Elbows
Used
1
2 38 22 85 69 34 101 94 94
3 33 17 80 64 29 96 89 89
4 28 12 75 59 24 91 84 84
5 23 7 70 54 19 86 79 79
6 18
7 13 60 44 9 76 69 69
8 8 55 39
9
10 45 29 61 54 54
*Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
1-1/2” Pipe 2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity Capacity
070 090 110 070 090 11 0 070 090 110 070 090 11 0
43 27 7 90 74 39 106 99 99
85 69 34 101 94 94
n/a n/a n/a
n/a
n/a
Concentric Termination at Elevation 4,501 - 10,000 ft
1-1/2” Pipe 2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity Capacity
070 090 110 070 090 11 0 070 090 110 070 090 11 0
43 27
n/a n/a n/a
n/a
n/a
n/a
n/a
65 49 14 81 74 74
55 39
n/a
90 74 39 106 99 99
65 49 14 81 74 74
50 34 66 59 59
n/a
71 64 64
71 64 64
Table 7B.
508405-01 Page 19 of 53Issue 2332
Page 20
Maximum Allowable Exhaust Vent Length Using Ventilated Attic or Crawl Space for Intake Air in Feet
Standard Termination at Elevation 0 - 10,000 ft
Number of
90° Elbows
Used
1
1-1/2” Pipe 2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity Capacity
070 090 110 070 090 11 0 070 090 110 070 090 11 0
41 24
85 63 28 102 83 83
2 36 19 80 58 23 97 78 78
3 31 14 75 53 18 92 73 73
4 26 9 70 48 13 87 68 68
5 21 4 65 43 8 82 63 63
6 16
7 11 55 33
8 6 50 28 67 48 48
9 1 45 23 62 43 43
n/a n/a n/a
n/a
n/a
60 38 3 77 58 58
72 53 53
n/a
10 n/a 40 18 57 38 38
NOTE: Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Table 7C.
Pipe size determined in table 7.
2”
2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible. NOTE: Exhaust pipe and intake pipe must be the same diameter.
2”
2”
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
2”
3”
TRANSITION
*2”
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
or
NOTE: 1-1/2” Vent Pipe Diameter Allowed Only on 045/070 Units
1-1/2”
TRANSITION
*2”
Figure 23. Typical Exhaust Pipe Connections
INTAKE
EXHAUST
TOP VIEW
508405-01Page 20 of 53 Issue 2332
Page 21
Pipe size determined in table 7.
2”
2”
3”
TRANSITION
*2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible. NOTE: Exhaust pipe and intake pipe must be the same diameter.
2”
or
or
Figure 24. Typical Intake Pipe Connections (Direct Vent Applications)
Intake Piping
This furnace may be installed in either direct vent or non­direct vent applications. In non-direct vent applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered. Guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
2”
NOTE: 1-1/2” Vent Pipe Diameter Allowed Only on 045/070 Units
1-1/2”
TRANSITION
*2”
2”
INTAKE
EXHAUST
*2”
TOP VIEW
TRANSITION
*2”
3”
2. If intake air is drawn from a ventilated crawl space
(Figure 26) or ventilated attic (Figure 25) the exhaust vent length must not exceed those listed in Table 7C.
If 3” diameter pipe is used, reduce to 2” diameter pipe to accommodate the debris screen.
3. Use a sheet metal screw to secure the intake pipe to the connector, if desired.
Use the following steps when installing the unit in Direct Vent applications, where combustion air is taken from
outdoors and ue gases are discharged outdoors. The
provided air intake screen must not be used in direct vent applications (outdoors).
1. Use cement or a sheet metal screw to secure the intake pipe to the inlet air connector.
2. Route piping to outside of structure. Continue with installation following instructions given in general guide lines for piping terminations and intake and
exhaust piping terminations for direct vent sections.
Refer to Table 7A through Table 7C for pipe sizes.
Use the following steps when installing the unit in Non­Direct Vent applications where combustion air is taken
from indoors and ue gases are discharged outdoors.
1. Use eld-provided materials and the factory-provided air intake screen to route the intake piping. Maintain a minimum clearance of 3” (76 mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward, or sideways.
Roof Terminated
Exhaust Pipe
Ventilation Louvers
*Intake Debris
Screen
(Provided)
Furnace
Inlet Air (Minimum 12 in. (305mm) above
Attic Floor)
* See Maximum Vent Lengths table
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.
Figure 25. Equipment in Conned Space
(Inlet Air from Ventilated Attic and Outlet Air to
Outside)
508405-01 Page 21 of 53Issue 2332
Page 22
Roof Terminated
Exhaust Pipe
Inlet Air
Minimum
Ventilation
Louvers
(Crawl Space)
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
Furnace
12 in. (305mm)
above Crawl Space Floor
*Intake Debris Screen Provided
* See Maximum Vent Lengths table
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour of the total input rating of all equipment in the enclosure.
2
Figure 26. Equipment in Conned Space
(Inlet Air from Ventilated Crawl Space and Outlet Air
to Outside)
WARNING
If this unit is being installed in an application with combustion air coming in from a space serviced by an
exhaust fan, power exhaust fan, or other device which
may create a negative pressure in the space, take care when sizing the inlet air opening. The inlet air opening
must be sized to accommodate the maximum volume of exhaust air as well as the maximum volume of
combustion air required for all gas appliances serviced by this space.
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors and the ue gases are discharged to the outdoors. This unit is then classied as a non-direct vent,
Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the ue gases are discharged to the outdoors. This unit is then classied as a direct vent, Category IV gas
furnace.
In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current
CSA-B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in Figure 28 or Figure 29. In addition, position termination so it is free from any obstructions and 12” above the average snow accumulation.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8 m) of a condensing unit because the condensate can damage the painted coating.
NOTE: See Table 8 for maximum allowed exhaust pipe length without insulation in unconditioned space during winter design temperatures below 32° F (0° C). If required, exhaust pipe should be insulated with 1/2” (13 mm), Armaex or equivalent when run through an unconditioned area. In extremely cold climate areas with temperature below 20° F (6.7° C) it is recommended that 3/4” (19 mm) Armaex or equivalent be used. Insulation on outside runs of exhaust pipe should be painted or wrapped to protect insulation from deterioration in accordance with the insulation manufacturers recommendation. Exhaust pipe insulation may not be necessary in some specic applications.
NOTE: During extremely cold temperatures, below approximately 20° F (6° C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze-ups. Heating cable installation kits are available, see unit specication sheets for part numbers.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and may block the terminations.
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches (305 mm).
508405-01Page 22 of 53 Issue 2332
Page 23
Maximum Allowable Exhaust Vent Pipe Length3 (in ft.) without Insulation in Unconditioned Space for Winter Design
Temperatures
Winter Design Temperatures
(ºC)
1
ºF
Vent Pipe
Diameter
070 090 110
PVC
2
PP PVC
Unit Input Size
2
PP PVC
2
PP
1-1/2 in. 20 N/A N/A N/A N/A N/A
32 to 21
(0 to -6)
2 in. 33 30 46 42 30 30
2-1/2 in. 26 N/A 37 N/A 36 N/A
3 in. 21 21 30 30 29 29
1-1/2 in. 20 N/A N/A N/A N/A N/A
20 to 1
(-7 to -17)
2 in. 19 17 28 25 27 24
2-1/2 in. 14 N/A 21 N/A 20 N/A
3 in. 9 9 16 16 14 14
1-1/2 in. 13 N/A N/A N/A N/A N/A
0 to -20
(-18 to -29)
2 in. 12 10 19 16 18 15
2-1/2 in. 7 N/A 13 N/A 12 N/A
3 in. N/A N/A 8 8 7 7
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP) by Duravent and Centrotherm
3
Vent length in table is equivalent length. Each elbow is equivalent to 5ft of straight pipe and should be included when measuring
total length.
NOTE - Concentric terminations are the equivalent of 5’ and should be considered when measuring pipe length.
NOTE- Maximum uninsulated vent lengths listed may include the termination (vent pipe exterior to the structure ) and cannot exceed
5 linear feet or the maximum allowable intake or exhaust vent length listed in Table 6 or Table 7A through Table 7C.
NOTE - If insulation is required an unconditioned space, it must be located on the pipe closed to the furnace.
Conditioned
Space
Table 8.
Conditioned
Space
Pipe Insulation
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Figure 27. Insulating Exhaust Pipe in an Unconditioned Space
508405-01 Page 23 of 53Issue 2332
Page 24
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
C =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
Clearance to permanently
12 inches (305mm) or 12 inches (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
closed window
Vertical clearance to ventilated soffit
D =
located above the terminal within a
* Equal to or greater than soffit depth.
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
E =
F =
G =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
H =
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
*
above the meter / regulator assembly
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
pliance
K =
ply inlet
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
In accordance with the current CSA B149.1, Natural Gas and Propane Installation
2
Code
†
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Avoiding this location is recommended if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)†
*12 inches (305mm)‡
Operable
A
* 12”
H
Fixed
Closed
J
B
I
M
K
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 inches (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
**
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”
NOTE - This figure is intended to illustrate clearance requirements and does not serve as a substitute for locally adopted installation codes.
Figure 28. Vent Termination Clearances
For Non-Direct Vent Installations in the USA and Canada
508405-01Page 24 of 53 Issue 2332
Page 25
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 inches (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
C =
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
D =
located above the terminal within a
horizontal distance of 2 feet (610mm)
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
K =
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
L =
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
M =
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
1
In accordance with the current CSA B149.1, Natural Gas and Propane Installation
2
Code
†
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Avoiding this location is recommended if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
Operable
A
* 12”
*
H
Fixed
Closed
J
B
I
M
K
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 inches (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”
NOTE - This figure is intended to illustrate clearance requirements and does not serve as a substitute for locally adopted installation codes.
Figure 29. Vent Termination Clearances
For Direct Vent installations in the USA and Canada
508405-01 Page 25 of 53Issue 2332
Page 26
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE: In Direct Vent installations, combustion air is taken
from outdoors and ue gases are discharged to outdoors.
NOTE: Flue gas may be slightly acidic and may adversely aect some building materials. If any vent termination is used and the ue gases may impinge on the building material, a corrosion-resistant shield (minimum 24 inches square) must be used to protect the wall surface. If the optional tee is used, the protective shield is required. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the aected area should be sealed using an appropriate sealant. See Figure 38.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figure 30 through Figure 37 show typical terminations.
1. Vent terminations are not required to be in the same
pressure zone. You may exit the intake on one side of the structure and the exhaust on another side (Figure
31). You may exit the exhaust out the roof and the
intake out the side of the structure (Figure 32).
2. Intake and exhaust pipes should be placed as close together as possible at termination end (refer to illustrations). Minimum separation is 3” (76 mm) on roof terminations and 6” (152 mm) on side wall terminations.
3. On roof terminations, the intake piping should terminate straight down using two 90° elbows (see Figure 30).
4. Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake
piping. See Table 9.
Capacity Exhaust Pipe Size
*070
*090
110 3” (76 mm)
*070 and 090 units with the ush-mount termination must use
the 1-1/2” accelerator supplied with the kit.
2” (51 mm),
2-1/2” (64 mm),
3” (76 mm)
Table 9. Exhaust Pipe Termination Size Reduction
5. On eld supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305 mm) for 2” PVC and 20 inches (508 mm) for 3” (76 mm) PVC beyond the outside wall. Intake piping should be as short as possible. See Figure 38.
Termination
Pipe Size
1-1/2” (38 mm)
2” (51 mm)
NOTE: Care must be taken to avoid recirculation of exhaust back into intake pipe.
6. On eld supplied terminations, a minimum distance between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow. See Figure 38.
Inches (MM)
8” (203MM) MIN
12” (305MM) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76MM) OR
2” (51MM) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
3” (76MM) MIN.
SIZE PER EXHAUST PIPE
TERMINATION SIZE REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
1/2” (13MM) FOAM
INSULATION IN
UNCONDITIONED
SPACE
Figure 30. Direct Vent Roof Termination Kit
Inlet Air
Exhaust
Pipe
Furnace
Minimum 12 in.
(305MM) above
grade or snow
accumulation
Figure 31. Exiting Exhaust and Intake Vent
(no common pressure zone)
Roof T
erminated
Exhaust Pipe
Inlet Air
Furnace
Minimum 12 in.
(305MM) above
grade or snow
accumulation
Figure 32. Exiting Exhaust and Intake Vent
(no common pressure zone)
508405-01Page 26 of 53 Issue 2332
Page 27
2” EXTENSION FOR 2” PVC PIPE1” EXTENSION FOR 3” PVC PIPE
FURNACE EXHAUST
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
1-1/2” ACCELERATOR
FURNACE
INTAKE
PIPE
4''
FLAT SIDE
(all -45, -070 and -090 units)
Figure 33. Flush-Mount Side Wall Termination 51W11
7. If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24” (610 mm) as shown in Figure 38.
When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated
with pipe sized per Table 9. The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5 m) to the equivalent length of the pipe.
8. Based on the recommendation of the manufacturer, a multiple furnace installation may use a group of up to four terminations assembled together horizontally, as shown in Figure 36.
1 1/2” (38mm) accelerator
EXHAUST
12” (305mm)
Minimum
Above Average
Snow
Accumulation
VENT
provided on 71M80 & 44W92
kits for -045 and -070 models
INTAKE
AIR
FLASHING
(Not Furnished)
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
CLAMP
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT DIFFERENT VENT
PIPE SIZE TO TERMINATION
Figure 34. Direct Vent Concentric Rooftop
Termination
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT DIFFERENT VENT
PIPE SIZE TO TERMINATION
OUTSIDE
WALL
EXHAUST
VENT
1-1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for -045 and -070 models
INTAKE
AIR
EXHAUST
VENT
EXHAUST
VENT
5”
(127mm)
5-1/2”
(140mm)
12”
(305mm)
INTAKE
AIR
18” MAX. (457mm)
Front View
EXHAUST VENT
12” (305mm) Min.
above grade or
Inches (mm)
INTAKE
cumulation.
AIR
optional intake elbow
Side View
Figure 36. Optional Vent Termination for Multiple Unit
Installation of Direct Vent Wall Termination Kit
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
(203mm - 305mm)
Minimum 12” (305mm)
above chimney top
plate or average snow
accumulation
* SIZE TERMINATION PIPE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE
8” - 12”
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
3” - 8” (76mm ­203mm)
EXHAUST VENT
1/2” (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
ALTERNATE
INTAKE PIPE
3” - 8” (76mm ­203mm)
EXTERIOR
PORTION OF
CHIMNEY
INTAKE
AIR
CLAMP
(Not Furnished)
INTAKE
AIR
12” (305mm) Min.
above grade or
average snow accumulation.
GRADE
Figure 35. Direct Vent Concentric Wall Termination
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
508405-01 Page 27 of 53Issue 2332
NOTE: Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminates as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
Figure 37. Direct Vent Application Using Existing
Chimney
Page 28
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
C1
REDUCER MAY BE
TO TERMINATION
C1
A
E
D
B
Intake Elbow
STRAIGHT
APPPLICATION
D
B
A
EXTENDED
APPLICATION
FIELD FABRICATED WALL TERMINATION
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal
separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
D
B
* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than 24” (610 mm) but less than 48” (1219 mm). NOTE − One wall support must be within 6” (152 mm) from top of each pipe (intake and exhaust) to prevent movement in any direction.
C2
D
B
C2
A
E
A
2” (51mm)
Vent Pipe
12” (305 mm)
12” (305 mm)
3” (76mm)
Vent Pipe
12” (305 mm)
6” (152 mm)6” (152 mm)
8” (203 mm)8” (203 mm)
6” (152 mm)6” (152 mm)
20” (508 mm)
6” (152 mm)6” (152 mm)
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)
2” (51MM)
Vent Pipe
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 16” (405 mm) Max.
6” (152 mm) Max.
Front View of
Intake and Exhaust
Intake
Exhaust
Intake Elbow
B
C
Exhaust
D
3
A
D
E
B
C
1
12”
A− Clearance above
grade or average snow
accumulation
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
D− Exhaust pipe length
E− Wall support distance
from top of each pipe
(intake/exhaust)
2
A
D
B
1
C
2
A
D
E
B
C
1
12”
2
A
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.
Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion-resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
3” (76MM)
Vent Pipe
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 20” (508 mm) Max.
6” (152 mm) Max.
Figure 38. Field Supplied Wall Termination
508405-01Page 28 of 53 Issue 2332
Page 29
Details of Exhaust Piping Terminations for Non-
Direct Vent Applications
Exhaust pipe may be routed either horizontally through
an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figure 39 through Figure 42 show typical terminations.
1. Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed
in Table 9. The specied pipe size ensures proper velocity required to move the exhaust gases away
from the building.
2. On eld supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches
(305 mm) for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond the outside wall. See Figure 40.
3. If exhaust piping must be run up a sidewall to position above snow accumulation or other obstructions, piping must be supported every 24” (610 mm) as shown in
Figure 41. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the nal elbow.
SIZE TERMINATION PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT DIFFERENT
VENT PIPE SIZE TO
TERMINATION
* Use wall support every 24” (610 mm). Use two supports of extension is greater than 24”
(610 mm) but less than 48” (1219 mm).
Figure 41. Non-Direct Vent Field Supplied Wall
Termination - Extended
* SIZE TERMINATION PIPE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
SIZE PER EXHAUST PIPE
12” (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
3” (76MM) OR
2” (51MM) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
TERMINATION SIZE REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
Figure 39. Non-Direct Vent Roof Termination Kit
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT DIFFERENT
VENT PIPE SIZE TO
TERMINATION
SIZE TERMINATION PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE
Minimum 12” (305mm)
above chimney top
plate or average snow
accumulation
INTAKE PIPE
INSULATION (optional)
METAL TOP
INSULATE
TO FORM
SEAL
SHEET
PLATE
EXHAUST VENT
1/2” (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
NOTE: Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing
unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and
terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
Figure 42. Non-Direct Vent Application Using Existing
Chimney
Figure 40. Non-Direct Vent Field Supplied Wall
Termination
508405-01 Page 29 of 53Issue 2332
Page 30
Exhaust through Crawl Space Vent Option
All 33” condensing gas furnaces (92%+) are now approved to be vented down through a crawl space. Ensure a vent
pipe drain kit, 51W18 (USA) or 15Z70 (Canada), is used as directed through the oor joists and into the crawl space. See the following gures.
Consult the vent tables for vent lengths and approved materials.
From
Furnace
2” or 3”
Sanitary Tee
1/2” PVC
Drain Stub
Drain Trap
Assembly
Rubber Boot (51W18) Drain Plug (15Z70)
Clamp
(51W18 Only)
To Vent
Termination
Drain Trap
(assembled)
Exhaust from
Furnace
To Termination
Exhaust from
Furnace
To Termination
* Kit 51W18 is shown.
Figure 44. Crawl Space Vent Pipe Drain Trap
Assembled Incorrectly
Figure 43. Kit 51W18 (USA) / 15Z70 (Canada) Parts
Identication and Assembly
Downflow Furnace
Exhaust
KIT 51W18 (USA) KIT 15Z70 (Canada)
24” max.
* Kit 51W18 is shown.
Basement Floor
To Termination
1/2” PVC to
Code-Approved
Drain
NOTE: Upow furnaces exhaust from the left side. All dimensions shown are typical for upow or downow furnaces. NOTE: All horizontal runs of exhaust pipe must slope back toward the kit a minimum of 1/4” (6mm) for each 12” (305mm) to ensure drainage.
Figure 45. Upow or Downow Furnace with Exhaust through Crawl Space
508405-01Page 30 of 53 Issue 2332
Page 31

Condensate Piping

This unit is designed for either right or left side exit of condensate piping in downow applications. Refer to
Figure 46 for condensate trap locations.
NOTE: If necessary the condensate trap may be installed up to 5 feet away using PVC pipe from the furnace. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.
1. Determine which side condensate piping will exit the
unit, location of trap, eld-provided ttings and length
of PVC pipe required to reach available drain.
2. Use a large at head screw driver or a 1/2” drive
socket extension and remove plug (Figure 46) from the cold end header box at the appropriate location
on the side of the unit. Install provided 3/4 NPT street
elbow tting into cold end header box. Use Teon tape
or appropriate pipe dope.
3. Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See Figure 51.
4. Install drain trap using appropriate PVC ttings, glue
all joints. Glue the provided drain trap as shown in Figure 51. Route the condensate line to an open drain. Condensate line must maintain a 1/4” downward slope from the furnace to the drain.
NOTE: Vinyl tubing may be used for condensate drain. Tubing must be 1-1/4” OD x 1” ID and should be attached to the drain on the trap using a hose clamp.
5. Figure 48 shows the furnace and evaporator coil using a separate drain. If necessary, the condensate line from the furnace and evaporator coil can drain
together. See Figure 49. The eld provided vent must be a minimum 1” to a maximum 2” length above the
condensate drain outlet connection.
CAUTION
Do Not use copper tubing or existing copper condensate
lines for drain line.
Trap
(same on
right side)
1-1/2 in.
Plug (same on left side)
Figure 47. Condensate Trap Location
(shown with right side exit of condensation)
6. If unit will be started immediately upon completion of installation, prime trap per procedure outlined in Unit Start-Up section.
Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available in various lengths; 6 ft. (1.8 m) - kit no. 26K68; 24 ft. (7.3 m) ­kit no. 26K69; and 50 ft. (15.2 m) - kit no. 26K70.
Figure 46. Condensate Trap and Plug Locations
508405-01 Page 31 of 53Issue 2332
Page 32
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate
Drain Connection
Evaporator Drain Line
(vent required)
Drain
From Evaporator Coil
Optional
Overflow Switch
Field-Provided Vent
(Upflow Furnace 1” Min. to 2” Max.
Horizontal Furnace 4” Min. to 5” Max.
above condensate drain connection)
Furnace Condensate
Drain Connection
Figure 48. Evaporator Coil Using a Separate Drain
CAUTION
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in order for the furnace pressure switch to operate properly.
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate
Drain Connection
Evaporator Drain Line
(vent required)
Figure 50. Condensate Trap with Optional Overow
Switch
Figure 49. Evaporator Coil Using a Common Drain
508405-01Page 32 of 53 Issue 2332
Page 33
Optional Condensate Drain Connection
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow 3/4 inch PVC (not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow 3/4 inch PVC ( furnished)
To
Trap
Optional Drain Piping From Tr ap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
1(25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Elbow 3/4 inch PVC
90°
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
V
ent
5 Feet
Maximum
3/4 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
(Not Furnished)
Drain Trap
Assembly
(Furnished)
Condensate Drain
Connection In Unit
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
DrainTr ap Assembly
(Furnished)
7
(178)
Drain Trap Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
o
T
Coupling 3/4 inch slip X slip
Drain
DrainTr ap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain
Connection In Unit
To
Drain
DrainTr ap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain
Connection In Unit
To
Drain
Figure 51. Trap Drain Assembly Using 1/2” PVC or 3/4” PVC
508405-01 Page 33 of 53Issue 2332
Page 34

Gas Piping

CAUTION
If a exible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe shall
be installed at the gas valve and extend outside the furnace cabinet. The exible connector can then be
added between the black iron pipe and the gas supply line.
WARNING
Do Not exceed 600 in. lbs. (50 ft. lbs.) torque when
attaching the gas piping to the gas valve.
1. Gas piping may be routed into the unit through either the left or right hand side. Supply piping enters into the gas valve from the side of the valve as shown in Figure 53.
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
Leak Check
After gas piping is completed, carefully check all eld-
installed piping connections for gas leaks. Use a
commercially available leak detecting solution specically manufactured for leak detection. Never use an open ame
to test for gas leaks.
The furnace must be isolated from the gas supply
system by closing the individual manual shut-o󰀨 valve
during any gas supply system at pressures greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.). This furnace and its components are designed, manufactured
and independently certied to comply with all applicable
ANSI/CSA standards. A leak check of the furnace and its components is not required.
IMPORTANT
A low inlet pressure switch in LP/propane applications is recommended.
2. When connecting gas supply, factors such as length
of run, number of ttings and furnace rating must be considered to avoid excessive pressure drop. Table 10
lists recommended pipe sizes for typical applications.
NOTE: Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.
3. Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See Figure 53.
4. Piping should be sloped 1/4 inch per 15 feet (6 mm per
5.6 m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05 m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.
5. A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection.
6. In some localities, codes may require installation of a
manual main shut o󰀨 valve and union (furnished by installer) external to the unit. Union must be of the
ground joint type.
Figure 52.
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. Gas Valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open ame to test for gas leaks. Check
all connections using a commercially available soap
solution made specically for leak detection. Some
soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
508405-01Page 34 of 53 Issue 2332
Page 35
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Tap Shown)
GROUND
JOINT
UNION
Left Side Piping
(Standard)
AUTOMATIC
GAS VALV E
(with manual
shut-off valve)
AUTOMATIC
GAS VALV E
(with manual
shut-off valve)
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Ta p
Shown)
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 53.
Gas Pipe Capacity - FT³/HR (kL/HR)
Nominal
Iron Pipe
Size -
inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
4
(101.6)
Internal
Diameter
- inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
175
(4.96)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
120
(3.40)97(2.75)82(2.32)73(2.07)66(1.87)61(1.73)57(1.61)53(1.50)50(1.42)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
NOTE: Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specic gravity gas.
Length of Pipe - feet (m)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
9700
(274.67)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
(12.18)
(18.41)
(34.55)
(55.22)
(97.69)
(203.88)
(Alternate)
110
(3.11)
205
(5.80)
430
650
1220
1950
3450
7200
100
(30.480)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Table 10.
508405-01 Page 35 of 53Issue 2332
Page 36

Electrical

ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can a󰀨ect electronic components.
Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions
will help to avoid control exposure to electrostatic
discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
Figure 54. Interior Make-Up Box Installation
Figure 55. Interior Make-Up Box Installation
The unit is equipped with a eld makeup box. The makeup box may be installed on the exterior of the right side of
the furnace to facilitate installation. Seal unused openings on left side with plugs removed from right side. Secure
the excess wire to the existing harness to protect it from
damage.
Refer to Figure 65 for eld wiring and Figure 64 for
schematic wiring diagram and troubleshooting.
1. The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.
NOTE: Unit nameplate states maximum current draw. Maximum over current protection allowed is shown in Table 11.
2. Holes are on both sides of the furnace cabinet to facilitate wiring.
3. Install a separate (properly sized) disconnect switch
near the furnace so that power can be turned o󰀨 for
servicing.
Capacity
070 15
090, 110 20
Maximum Over-Current
Protection (Amps)
Table 11.
4. Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.
5. Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the eld
wiring diagram shown in Figure 64. Use 18 gauge wire or larger that is suitable for Class II rating for thermostat connections.
6. Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70). A green
ground wire is provided in the eld make-up box.
NOTE: This furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
7. One line voltage “ACC” 1/4” spade terminal is provided on the furnace integrated control. Any electronic air cleaner or other accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. This terminal is energized when the indoor blower is operating.
8. One line voltage “HUM” 1/4” spade terminal is provided
on the furnace integrated control. Any humidier rated
up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. This terminal is energized in the heating mode whenever the combustion air inducer is operating.
9. Install the room thermostat according to the instructions provided with the thermostat. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
508405-01Page 36 of 53 Issue 2332
Page 37
Indoor Blower Speeds
1. When the thermostat is set to “FAN ON,” the indoor
blower will run continuously at approximately 50%
of the second stage cooling speed when there is no cooling or heating demand. See Table 19 for allowable continuous circulation speeds.
2. When this unit is running in the heating mode, the indoor blower will run on the heating speed designated by the positions of DIP switches 1 (A,B,C,D) of the
HEAT jumper plug. When the heat demand is satised,
the indoor blower will continue to run at the low stage heat cfm for the duration of the user-selected heat
blower o󰀨 delay. The user can select one of the four preset heat blower o󰀨 delays (60/90/120/180 sec) by
repositioning the movable shunt on the 5-pin header on the ignition control.
Electrical Wiring
WARNING
Risk of electrical shock. Disconnect electrical power at the circuit breaker or service panel before making electrical connections. Failure to disconnect power supplies can result in property damage, personal injury, or death.
The furnace must be grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70 (latest edition) and/or CSA C22.1 Electrical Code (latest edition) if an
external electrical source is utilized.
60
Heat Blower OFF Delay Moveable
90
Shunt
P4
120
180
Figure 56. Heat Blower O󰀨 Delay Moveable Shunt
3. When there is a cooling demand, the indoor blower will run on the cooling speed designated by the positions of DIP switches (A, B, C, D) of the COOL jumper plug. See Figure 58.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
• The furnace requires 120 volts ± 10% (Range: 108 volts to 132 volts).
• The furnace operates at 60 Hz ± 5% (Range: 57 Hz to 63 Hz).
• The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power.
• Generator should have a wave form distortion of less than 5% THD (Total Harmonic Distortion).
In all instances, other than wiring for the thermostat, the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire –63°F (35°C) rise.
Connect a su󰀩ciently sized wire with ground to the
furnace’s line voltage connections and ground wire. Refer to the furnace rating plate for electrical characteristics
to be used in sizing eld supply wiring and overcurrent
protection.
The line voltage supply should be routed through a readily accessible disconnect located within sight of the furnace. A
junction box on the furnace side panel is provided for line
voltage connections. Refer to the furnace wiring diagram
for specic connection information.
Proper polarity of the supply connections (“HOT” and “NEUTRAL”) must be observed to ensure that safety controls provide the protection intended.
A connection to the unit’s ground wire and actual earth ground (typically a ground stake or buried steel pipe) must be maintained for proper operation.
Thermostat
Install a room thermostat according to the instructions furnished with it. Select a location on an inside wall that is not subject to drafts, direct sunshine, or other heat sources. The initial heat anticipator setting should be equal to the total current draw of the control circuit. Low voltage thermostat connections are to be made to the integrated ignition/blower control board as indicated on the wiring diagram.
508405-01 Page 37 of 53Issue 2332
NOTE: The automatic heat staging option allows a single stage thermostat to be used with two stage furnace models. To activate this option, move the jumper pin (see Figure 57) to desired setting (5 minutes or 10 minutes). The furnace will start on 1st stage heat and stay at 1st stage heat for the duration of the selected time before switching to 2nd stage heat. W1 on the control board must be connected to W1 on the thermostat.
Page 38
Figure 57. Automatic Heat Staging Jumper
Humidier
Terminals are provided on the integrated ignition/blower
control board for connection to a 120-volt humidier. The
“HUM” terminal is energized whenever the thermostat
calls for heat. See the furnace wiring diagram for specic
connection information.
Electronic Air Cleaner
Terminals are provided on the integrated ignition/blower control board for connection of a 120-volt electronic air cleaner. The “ACC” terminal is energized whenever the thermostat calls for heat, cooling, or continuous blower. See
furnace wiring diagram for specic connection information.
Active Dehumidication
To achieve additional dehumidication, clip the jumper
wire located below the DEHUM terminal on the integrated ignition/blower control board and connect a humidity control that opens on humidity rise to the DEHUM and R terminals. The DEHUM terminal on the control board must be connected to the normally closed contact of the humidity control so that the board senses an open circuit on high humidity. In this setup, the variable speed motor
will operate at a 30% reduction in the normal cooling airow rate when there is a call for dehumidication.
Both the passive and active dehumidication methods
described above can be utilized on the same furnace.
Circulating Airow Adjustments
Cooling Mode
The units are factory set for the highest airow for each model. Adjustments can be made to the cooling airow
by repositioning the jumper plug marked COOL – A, B, C, D (see Figure 58). To determine what CFM the motor is delivering at any time, count the number of times the amber
LED on the control board ashes. Each ash signies 100 CFM; count the ashes and multiply by 100 to determine the actual CFM delivered (for example: 10 ashes x 100 =
1000 CFM).
Variable Speed Features
This furnace is equipped with a variable speed circulation
air blower motor that will deliver a constant airow within a wide range of external static pressures. Other features of
this variable speed motor include:
Soft Start
The variable speed motor will slowly ramp up to normal operating speed. This minimizes noise and increases comfort by eliminating the initial blasts of air encountered with standard motors.
Soft Stop
At the end of a cooling or heating cycle, the variable speed
motor will slowly ramp down after a short blower “o󰀨” delay.
If continuous blower operation has been selected, the variable speed motor will slowly ramp down until it reaches
the airow for that mode.
Passive and Active Dehumidication
Passive Dehumidication
For situations where humidity control is a problem, a
dehumidication feature has been built into the variable
speed motor. At the start of each cooling cycle, the variable
speed motor will run at 82% of the rated airow for 7.5
minutes. After 7.5 minutes has elapsed, the motor will
increase to 100% of the rated airow.
Heating Mode
These units are factory set to run at the middle of the heating rise range as shown on the unit rating plate. If higher or lower rise is desired, reposition the jumper plug marked HEAT - A, B, C, D (see Figure 58) . To determine what CFM the motor is delivering at any time, count the number of times the amber LED on the control board
ashes. Each ash signies 100 CFM; count the ashes
and multiply by 100 to determine the actual CFM delivered
(for example: 10 ashes x 100= 1000.
Adjust Tap
Airow amounts may be increased or decreased by 10%
by moving the ADJUST jumper plug (see Figure 58) from the NORM position to the (+) or (-) position. Changes to the
ADJUST tap will a󰀨ect both cooling and heating airows.
The TEST position on the ADJUST tap is not used.
Continuous Blower Operation
The comfort level of the living space can be enhanced when using this feature by allowing continuous circulation of air between calls for cooling or heating. The circulation
of air occurs at half the full cooling airow rate.
To engage the continuous blower operation, place the fan switch on the thermostat into the ON position. A call for fan from the thermostat closes R to G on the ignition control board. The control waits for a 1 second thermostat debounce delay before responding to the call for fan by ramping the circulating blower up to 38% of the cooling
508405-01Page 38 of 53 Issue 2332
Page 39
speed. When the call for continuous fan is satised, the
control immediately ramps down the circulating blower.
lockout. Lockout may be manually reset by removing power from the control for more than 1 second or removing the thermostat call for heat for more than 3 seconds.
If during a heating cycle the limit control senses an abnormally high temperature and opens, the control board de-energizes the gas valve and the combustion blower while the circulating blower runs at 1st stage heat speed. The circulating blower remains energized until the limits are closed.
Fan On
When the thermostat is set for continuous fan operation and there is no demand for heating or cooling, a call for fan closes the R to G circuit and the circulating blower motor runs at 38% of the selected cooling CFM until switched
o󰀨. When the call for fan is turned OFF, the control de-
energizes the circulating blower.
Figure 58. ADJUST, HEAT, and COOL Taps on
Integrated Ignition/Blower Control Board
Sequence of Operation
Heating
On a call for heat from the room thermostat, the control
board performs a 1 second self check. Upon conrmation
that the pressure switch contacts are in an open position, the control energizes the combustion blower on high speed. The control then checks for adequate combustion
air by making sure the low-re pressure switch contacts
are closed.
The igniter energizes and is allowed to warm up for 20 seconds before the gas valve energizes on 1st stage
and burners ignite. 45 seconds after the control conrms
ignition has occurred, the control drops the combustion blower to low speed.
The circulating blower operates at full 1st stage heat
speed until either the heat call is satised or the thermostat
initiates a call for 2nd stage heat. On a call for 2nd stage heat, the control energizes the circulating air blower on full CFM 2nd stage heat.
If the automatic heat staging option is being used the furnace does not switch to 2nd stage heat in response to a call from the thermostat but instead operates at 1st stage heat for the duration of the selected time before automatically switching to 2nd stage heat.
When the call for heat is satised, the gas valve and
combustion air blower shut down. The control board shuts
o󰀨 the gas valve and runs the combustion blower for an
additional 15 seconds. The circulating air blower continues
to run for selected blower o󰀨 delay time (60/90/120/180 sec) before ramping down and shutting o󰀨.
In the event the unit loses ignition, the control will attempt
to recycle up to ve times before it goes into a 1 hour
Cooling
The unit is set up at the factory for single stage cooling. For two stage cooling operation, clip the jumper wire located between the Y to Y2 terminals on the integrated ignition/ blower control board.
If the active dehumidication feature is enabled, the
circulating blower runs at 70% of the selected cooling
speed as long as there is a call for dehumidication.
WARNING
The system must not be in either the passive or active
dehumidication mode when charging a cooling system.
Single Stage Cooling
A call for cooling from the thermostat closes the R to Y circuit on the integrated ignition/blower control board. The control waits for a 1-second delay before energizing the circulating blower to 82% of the selected cooling CFM
(passive dehumidication mode). After 7.5 minutes, the
circulating blower automatically ramps up to 100% of
the selected cooling airow. When the call for cooling is satised, the circulating blower ramps down to continuous
fan cfm (38% of high stage cooling) for 45 seconds before completely shutting down the blower.
Two Stage Cooling
A call for 1st stage cooling from the thermostat closes the R to Y circuit on the control board. The control waits for a 1-second delay before energizing the circulating blower.
The blower motor runs at 57% of the selected air ow for the rst 7.5 minutes of the 2nd stage cooling demand (passive dehumidication mode). After 7.5 minutes, the blower motor runs at 70% of the selected cooling air ow until 1st stage cooling demand is satised.
508405-01 Page 39 of 53Issue 2332
Page 40
A call for 2nd stage cooling from the thermostat closes the R to Y2 circuit on the control board. The blower motor
ramps up to 100% of the selected cooling air ow. When
the demand for cooling is met, the blower ramps down
to Y1 until satised, then ramps down to continuous fan
cfm (38% of high stage cooling) for 45 seconds before completely shutting down the blower.
Heat Pump
For heat pump operation, clip the jumper wire located below the O terminal on the integrated ignition/blower control board. In heat pump mode, a call for heat will result in the circulating air blower operating at the selected
cooling airow after a brief ramp-up period.
Control Diagnostics
Troubleshooting
Make the following visual checks before troubleshooting:
1. Check to see that the power to the furnace and the integrated ignition/blower control board is ON.
2. The manual shuto󰀨 valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the Sequence of Operation.
Start the system by setting thermostat above room temperature. Observe system response. Then use the information provided in this section to check the system operation.
CFM LED
On models equipped with a variable speed motor, an amber LED is provided on the control board to display CFM. To determine what CFM the motor is delivering at any time,
count the number of times the amber LED ashes. Each ash signies 100 CFM; count the ashes and multiply by 100 to determine the actual CFM delivered (for example: 10 ashes x 100 = 1000 CFM).
LED Status Fault Description
LED O󰀨
LED On Normal operation
1 Flash Flame present with gas valve o󰀨
2 Flashes Pressure switch closed with inducer o󰀨
3 Flashes
4 Flashes
5 Flashes Not used
6 Flashes Pressure switch cycle lockout
7 Flashes Lockout due to no ignition
8 Flashes
9 Flashes Incorrect polarity and phasing
No power to control or control hardware fault detected
Pressure switch open with inducer energized
Primary Limit, Secondary Limit, or Roll­Out switch open
Lockout due to too many ame
dropouts
Table 12. Failure Codes - Red LED
The furnace has a built-in, self-diagnostic capability. If a system problem occurs, a fault code is shown by a red LED on the control board. The control continuously monitors its own operation and the operation of the system. If a failure
occurs, the LED will indicate the failure code. The ash
codes are presented in Table 12.
Fault Code History Button
The control stores the last ve fault codes in memory. A
push button switch is located on the control. When the push button switch is pressed and released, the control
ashes the stored fault codes. The most recent fault code is ashed rst; the oldest fault code is ashed last. To
clear the fault code history, press and hold the push button switch in for more than 5 seconds before releasing.
High Heat State LED
On models, a green LED is provided on the control board to indicate high heat state (see Table 13).
LED Status Description
LED O󰀨 No demand for high heat
LED On High heat demand, operating normally
LED Flashing
High heat demand, high pressure switch not closed
Table 13. High Heat State - Green LED
508405-01Page 40 of 53 Issue 2332
Page 41
W1/W2
w1 w2
W2
CALL
W1
100%**
100%*
***min
100%*
w1
CALL
*Percentage of Low Fire CFM ** Percentage of High Fire CFM *** User-Selected Heat Blower OFF Delay
Figure 59. Indoor Blower Operation - 1st Stage-2nd Stage (W1/W2) Heat Call
w2
***min
100%*
W2 - High Heat Demand Present
w2 - High Heat Demand Satisfied
*Percentage of Low Fire CFM ** Percentage of High Fire CFM *** User-Selected Heat Blower OFF Delay
OFF
***min
100%*
W1 - Heat Demand Present
w1 - Heat Demand Satisfied
W2 - High Heat Demand Present
w2 - High Heat Demand Satisfied
OFF
y
100%*
45 sec 38%
OFF
CALL
Y
7.5 minutes
82%*
Y - Heat Demand Present
y - Heat Demand Satisfied
*Percentage of High Stage Cooling CFM
Figure 62. Indoor Blower Operation - Single Stage
Cooling
Figure 60. Indoor Blower Operation - High Heat (W2)
Call
gG
38%*
G - Fan Switch ON
g - Fan Switch OFF
CALL
*Percentage of High Stage Cooling CFM
Figure 61. Indoor Blower Operation - Call for Fan
OFF
Y1
Y1/Y2
7.5
Y1 y2
100%*
y1
min.
70%*
CALL
57%*
Y1 - 1st Stage Cool Demand Present
y1 - 1st Stage Cool Demand Satisfied
Y2 - 2nd Stage Cooling Demand Present
y2 - 2nd Stage Cooling Demand Satisfied
*Percentage of High Stage Cooling
45 sec 38%*
y1
Figure 63. Indoor Blower Operation - Two Stage
Cooling
70%*
45 sec 38%*
OFF
508405-01 Page 41 of 53Issue 2332
Page 42
L1 HOT
120/1
NEUTRAL
/60
INTERLOCK
SWITCH
CHOKE (IF USED)
ROLLOUT
SWITCH
ROLLOUT
SWITCH (IF USED)
120V
24V
FP
IGN
IND HIGH
IND LOW
HUM
EAC
CIRCULATION BLOWER
TRANSFORMER
MOTOR
TH
HLO
HPS1
LPS1
HLI
W1
MVH
MVL
IGNITION CONTROL
W2
C
FLAME SENSOR
HOT SURFACE IGNITER
INDUCED DRAFT BLOWER
MOTOR
HUMIDIFIER
AIR CLEANER
TR
2ND STAGE
1ST STAGE
GAS VALVE
G
Y
R
MOTOR
LIMIT
PRESSURE SWITCH (LOW)
WIRING SCHEMATIC
WARNING­ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH.UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
NOTE­IF ANY WIRE IN THIS APPLIANCE IS REPLACED,IT MUST BE REPLACED WITH WIRE OF LIKE SIZE,
RATING, INSULATION THICKNESS, AND TERMINATION
Figure 64. Typical Field Wiring Diagram
PRESSURE
SWITCH
(HIGH)
W1W2YR THERMOSTAT CONDENSER
G
LINE VOLTAGE FIELD INSTALLED LINE VOLTAGE - FACTORY CLASS II VOLTAGE FIELD WIRING LOW VOLTAGE - FACTORY
GAS FIRED TWO STAGE FURNACE
HEATING UNITS-GAS
Supersedes
508405-01Page 42 of 53 Issue 2332
Page 43
WHITE
GRN/YLW
442
3
WHITE
RED
BLACK
1
3
1
2
RED
BLACK
5 PIN CONNECTOR
INDUCED DRAFT BLOWER
S1 P1
1
2
3
4
5
PRESSURE SWITCH (HIGH)
LIMIT
PARK 2
HI HEAT
LO HEAT
PINK
PUR
PRESSURE
SWITCH (LOW)
PINK
BLUE
FLAME SENSOR
BLUE
YELLOW
WHT/PINK
BROWN
BLACK
BLACK
LINE
HUM
ROLLOUT
XFMR
CONT
HOT
EAC
BLUE
BROWN
BLACK
BLACK
COOL
PARK 1
EAC
CIRC
LINE
ROLLOUT
XFMR
HUM
NEUTRAL
HOT
NEUTRAL
GROUND
1
/60
120/1
GRN/YLW
INTERLOCK SWITCH
WHITE
WHITE
GAS VALVE
PURPLE
H1 C
BROWN
YELLOW
M
ORANGE
2
2
BLACK
HOT SURFACE IGNITOR
2 PIN
1
CONNECTOR
1
IGNITION
CONTROL
3 AMP
9
12
11
10
3
6
5
8
2
1
4
7
G
W2
W1
W2
W1
THERMOSTAT
YC Y2
R
G
YR
C
0
CONDENSER
DEHUM
WHITE
WHITE
WHITE
CIRCULATION BLOWER
GRN
5 PIN CONNECTOR
2345
1
RED
WHITE
BLACK
INPUT CHOKE (IF USED)
CONNECTION DIAGRAM
1
PROPER POLARITY MUST BE OBSERVED FOR FIELD LINE VOLTAGE SUPPLY. IGNITION CONTROL WILL LOCK OUT IF POLARITY IS REVERSED
NOTES:
1. PRESS AND RELEASE FAULT CODE HISTORY BUTTON TO DISPLAY FAULT CODES. TO ERASE CODES, PRESS AND HOLD BUTTON
IN FOR MORE THAN 5 SECONDS
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING
MATERIAL HAVING A TEMP. RATING OF AT LEAST 90°c.
3. DO NOT CONNECT C (COMMON) CONNECTION BETWEEN INDOOR UNIT AND THERMOSTAT EXCEPT WHEN REQUIRED BY THE
INDOOR THERMOSTAT. REFER TO THE THERMOSTAT INSTALLATION INSTRUCTIONS.
Figure 65. Typical Wiring Diagram
508405-01 Page 43 of 53Issue 2332
Page 44
Testing for Proper Venting and Su󰀩cient Combustion Air for Non-Direct Vent Applications
1. Seal any unused openings in the venting system.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.
After the gas furnace has been started, the following test should be conducted to ensure proper venting and
su󰀩cient combustion air has been provided to the unit as well as to other gas red appliances which are separately
vented.
If this furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace ue products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been
made for su󰀩cient amounts of combustion air, corrections
must be made as outlined in the previous section.
2. Visually inspect the venting system for proper size and horizontal pitch. Determine there is no blockage
or restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3. To the extent that it is practical, close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building.
4. Close replace dampers.
5. Turn on clothes dryers and any appliances not
connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instruction to place the appliance being inspected into operation. Adjust thermostat so appliance will operate continuously.
7. Use the ame of a match or candle to test for spillage
of ue gases at the draft hood relief opening after 5
minutes of main burner operation.
8. If improper venting is observed during any of the above tests, the venting system must be corrected or
su󰀩cient combustion/makeup air must be provided.
The venting system should be resized to approach the minimum size as determined by using the appropriate
tables in appendix G in the current standards of the National Fuel Gas Code ANSI-Z223.1/NPFA 54 in the
U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the current standard of the CSA-B149 Natural Gas and Propane Installation Codes in Canada.
9. After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors,
windows, exhaust fans, replace dampers and any
other gas burning appliance to their previous condition of use.
508405-01Page 44 of 53 Issue 2332
Page 45

Unit Start-Up

FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwater.
A ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in re or explosion. Immediately call a qualied service technician to inspect
the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or
product or property damage. Should the gas
supply fail to shut o󰀨 or if overheating occurs, shut o󰀨 the gas valve to the furnace before shutting o󰀨 the electrical power.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING the unit, smell all around the furnace
area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
The gas valve on the unit is equipped with a gas control switch (lever). Use only your hand to move switch. Never use tools. If the switch will not move by hand, do not try to
repair it. Force or attempted repair may result in a re or explosion.
2. Set the thermostat to initiate a heating demand.
3. Allow the burners to re for approximately 3 minutes.
4. Adjust the thermostat to deactivate the heating demand.
5. Wait for the combustion air inducer to stop. Set the thermostat to initiate a heating demand and again
allow the burners to re for approximately 3 minutes.
6. Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop. At this
point, the trap should be primed with su󰀩cient water to
ensure proper condensate drain operation.
WARNING
If you do not follow these instructions exactly, a re or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation
1. STOP! Read the safety information at the beginning of this section.
2. Set the thermostat to the lowest setting.
3. Turn OFF all electrical power to the unit.
4. This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.
5. Remove the heating compartment access panel.
6. Move gas valve switch to OFF. See Figure 66.
7. Wait ve minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step.
8. Move gas valve switch to ON. See Figure 66.
Gas Valve Shown In “ON’ Position
Placing the Furnace into Operation
This furnace is equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units.
Priming Condensate Trap
The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either
pour 10 . oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1. Follow the lighting instructions to place the unit into operation.
508405-01 Page 45 of 53Issue 2332
Figure 66.
9. Replace the heating compartment access panel.
10. Turn on all electrical power to the unit.
Page 46
11. Set the thermostat to desired setting.
NOTE: When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12. If the appliance will not operate, follow the instructions
“Turning O󰀨 Gas to Unit” and call your service
technician or gas supplier.
Turning O󰀨 Gas to Unit
1. Set the thermostat to the lowest setting.
2. Turn o󰀨 all electrical power to the unit if service is to be performed.
3. Remove the heating compartment access panel.
4. Move gas valve switch to OFF.
5. Replace the heating compartment access panel.
Gas Pressure Adjustment
Gas Flow (Approximate)
Gas Meter Clocking Chart
Seconds for One Revolution
Capacity
070 55 110 136 272
090 41 82 102 204
110 33 66 82 164
Natural - 1000 btu/cu ft LP - 2500 btu/cu ft
Furnace should operate at least 5 minutes before checking
gas ow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in Table
14. If manifold pressure matches Table 16 and rate is
incorrect, check gas orices for proper size and restriction.
Remove temporary gas meter if installed.
NOTE: To obtain accurate reading, shut o all other gas appliances connected to meter.
Natural LP
1 cu ft
Dial
2 cu ft
Dial
Table 14.
1 cu ft
Dial
2 cu ft
Dial
one turn, connect a piece of 5/16” tubing and connect a manometer to measure supply pressure.
NOTE: Shut unit o and remove manometer as soon as an accurate reading has been obtained. Take care to re­tighten the 3/32 Hex screw.
Manifold Pressure Measurement
1. A manifold post located on the gas valve provides access to the manifold pressure. See Figure 66. Back
out the 3/32 Hex screw one turn, connect a piece of
5/16” tubing and connect to a manometer to measure manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady state.
3. While waiting for the unit to stabilize, observe the
ame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in Table 16.
NOTE: Shut unit o and remove manometer as soon as an accurate reading has been obtained. Take care to re­tighten the 3/32 Hex screw.
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas ow rate before checking combustion. Take combustion sample beyond the ue outlet and compare to the tables below. The maximum carbon monoxide reading should not exceed 100 ppm.
CO2% for Nat CO2% for L.P.
Capacity
Low Fire High Fire Low Fire High Fire
070 5.5 - 6.5 7.3 - 8.3 6.5 - 7.5 8.6 - 9.6
090 5.9 - 6.9 7.8 - 8.8 6.9 - 7.9 9.1 - 10.1
110 6.3 - 7.3 8.2 - 9.2 7.3 - 8.3 9.5 - 10.5
The maximum carbon monoxide reading should not exceed
100 ppm.
Supply Pressure Measurement
A pressure post on the inlet side of the gas valve provides
access to the supply pressure. Back out the 3/32 Hex screw
Manifold Pressure in w.g.
Capacity Gas
Natural 1.7 3.5 1.6 3.3 1.5 3.2 1.5 3.1 1.7 3.5 4.5 13.0
All Models
LP/Propane 4.5 10.0 4.2 9.4 4.0 9.1 3.9 8.9 4.5 10.0 11.0 13.0
0 - 4500 ft. 4501 - 5500 ft. 5501 - 6500ft. 6501 - 7500ft. 7501-10000ft.
Low Fire
High
Fire
Low
Fire
High
Fire
Table 16. Manifold and Supply Line Pressure 0 - 10,000 ft.
Low
Fire
High
Fire
Low
Fire
Table 15.
High
Fire
Low
Fire
High
Fire
Supply Line
Pressure in
w.g.
0 - 10000 ft.
Min. Max.
508405-01Page 46 of 53 Issue 2332
Page 47
Capacity
Natural to LP/
Propane
0 - 7500 ft
(0 - 2286m)
High Altitude Natural
Burner Orice Kit
7501 - 10000 ft (2286 - 3048m)
High Altitude LP/
Propane Burner
Orice Kit
7501 - 10000 ft
(2286 - 3048m)
High Altitude Pressure Switch
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft (2286 - 3048m)
070
090 14A54 14A53
110 25B93 14A45
*Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1371 m).
11K48 *51W01 11K47
14A48 14A54
Table 17. Conversion Kit Fan Pressure Switch Requirements at Varying Altitudes
High Altitude Information
NOTE: In Canada, certication for installations at
elevations over 4500 feet (1371 m) is the jurisdiction of
the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
local authorities.
Fan Control
Units may be installed at altitudes up to 4,500 ft. above sea level without manifold adjustment. Units installed at altitude of 4,501 - 10,000 feet (1371 to 3048 m) may require a pressure switch change which can be ordered
The fan ON time of 30 seconds is not adjustable. The fan OFF delay (amount of time that the blower operates after
the heat demand has been satised) is 120 seconds and
is not adjustable.
separately. Table 17 lists conversion kit and pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory-set and requires no adjustment.
NOTE: A natural to LP/propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (with
Other Unit Adjustments
Primary Limit
The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of
the burner box. These limits are factory set and require no
adjustment.
Pressure Switches
The pressure switches are located in the heating
compartment on the cold end header box. These switches
furnace operating). Correct voltage is 120 VAC ± 10%.
3. Check amp–draw on the blower motor with the blower compartment access panel in place.
Motor Nameplate__________Actual__________
Electronic Ignition
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic reset device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the integrated control to begin the ignition sequence.
check for proper combustion air inducer operation before allowing ignition trial. The switches are factory set and must not be adjusted.
Temperature Rise
After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. See Table 18 for allowable heating speeds. Increase the blower speed to decrease
Exhaust and Air Intake Pipe
1. Check exhaust and air intake connections for tightness and to make sure there is no blockage.
2. Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut o󰀨 at pressure switch. Check
termination for blockages.
3. Obstructed pipe or termination may cause rollout
switches to open. Reset manual ame rollout switches on burner box assembly if necessary.
508405-01 Page 47 of 53Issue 2332
Page 48

Blower Performance

Model Temp Rise
97G2DF070BV16
Model Temp Rise
High Fire
35 - 65
Low Fire
20 - 50
Cooling
Stage
2nd Stage
1st Stage
High Fire
35 - 65
Low Fire
25 - 55
Speed
Adjustment
+ 1110 1305 1430 1700
Normal 995 1175 1315 1520
- 880 1055 1170 1365
+ 860 1020 1140 1340
Normal 795 910 1030 1230
- 680 825 910 1085
Speed
Adjustment
+ 1110 1340 1575 1800
Normal 995 1230 1420 1650
- 880 1085 1290 1460
+ 740 915 1055 1255
Normal 660 820 940 1120
- 575 735 850 995
Speed
Adjustment
+ 1395 1555 1695 1825
Normal 1275 1395 1585 1670
- 1145 1265 1405 1525
+ 1130 1230 1365 1475
Normal 1040 1130 1250 1340
- 910 1025 1130 1210
Setting “D” Setting “C” Setting “B” Setting “A”
Setting “D” Setting “C” Setting “B” Setting “A”
Setting “D” Setting “C” Setting “B” Setting “A”
Heating CFM @ 0 - 0.8” w.c.
Cooling CFM @ 0 - 0.8” w.c.
Heating CFM @ 0 - 0.8” w.c.
97G2DF090CV20
Cooling
Stage
2nd Stage
1st Stage
Speed
Adjustment
+ 1335 1600 1750 1980
Normal 1225 1450 1630 1830
- 1120 1270 1450 1660
+ 955 1115 1265 1450
Normal 855 1005 1150 1285
- 750 890 1060 1170
Setting “D” Setting “C” Setting “B” Setting “A”
Cooling CFM @ 0 - 0.8” w.c.
508405-01Page 48 of 53 Issue 2332
Page 49
Model Temp Rise
High Fire
35 - 65
Low Fire
20 - 50
Speed
Adjustment
+ 1595 1795 1955 2140
Normal 1450 1615 1795 1975
- 1290 1460 1610 1795
+ 1165 1305 1465 1625
Normal 1055 1185 1315 1475
- 930 1070 1180 1320
Setting “D” Setting “C” Setting “B” Setting “A”
Heating CFM @ 0 - 0.8” w.c.
97G2DF110CV20
Model Number Speed Adjust Setting "D" Setting "C" Setting "B" Setting "A"
97G2DF070BV16
97G2DF090CV20
Cooling
Stage
2nd Stage
1st Stage
+10% Allowed Allowed Allowed Allowed
Norm Allowed Allowed Factory Setting Allowed
-10% Allowed Allowed Allowed Allowed
+10% Allowed Allowed Allowed Allowed
Norm Allowed Allowed Factory Setting Allowed
Speed
Adjustment
+ 1335 1585 1790 2010
Normal 1220 1440 1630 1865
- 1100 1275 1475 1680
+ 920 1095 1265 1440
Normal 830 965 1130 1290
- 735 860 1035 1155
Allowable Heating Speeds
Setting “D” Setting “C” Setting “B” Setting “A”
Cooling CFM @ 0 - 0.8” w.c.
-10% Allowed Allowed Allowed Allowed
+10% Allowed Allowed Allowed Allowed
97G2DF110CV20
Norm Allowed Allowed Factory Setting Allowed
-10% Allowed Allowed Allowed Allowed
Table 18.
Allowable Circulation Speeds
Model Number 38% of Second Stage Cooling
All Models Factory Setting
Table 19.
508405-01 Page 49 of 53Issue 2332
Page 50

Service

3. Check amp-draw on the blower motor with the blower compartment access panel in place.
Motor Nameplate__________Actual__________
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION
HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should
be checked as follows by a qualied service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are pre-lubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
Filters
All air lters are installed external to the unit. Filters should be inspected monthly. Clean or replace the lters when
necessary to ensure proper furnace operation. Table 3
lists recommended lter sizes. A lter must be in place
whenever the unit is operating.
Exhaust and Air Intake Pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE: After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120 VAC ± 10%.
Winterizing and Condensate Trap Care
1. Turn o󰀨 power to the furnace.
2. Have a shallow pan ready to empty condensate water.
3. Remove the clean out cap from the condensate trap and empty water. Inspect the trap then reinstall the clean out cap.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary,
follow the below procedures and refer to Figure 1 when disassembling unit. Use papers or protective covering in
front of furnace while removing heat exchanger assembly.
1. Turn o󰀨 electrical and gas supplies to the furnace.
2. Remove the furnace access panels.
3. Disconnect the wires from the gas valve.
4. Remove gas supply line connected to gas valve. Remove gas valve/manifold assembly.
5. Remove sensor wire from sensor. Disconnect 2 pin plug from the ignitor.
6. Disconnect wires from ame rollout switches.
7. Loosen clamps at vent elbow. Disconnect condensate
drain tubing from ue collar and remove the vent
elbow.
8. Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE: If necessary, clean burners at this time. Follow procedures outlined in Burner Cleaning section.
9. Mark and disconnect all combustion air pressure
tubing from cold end header collector box.
10. Mark and remove wires from pressure switches. Remove pressure switches. Keep tubing attached to pressure switches.
11. Disconnect the plug from the combustion air inducer. Remove two screws which secure combustion air
inducer to collector box. Remove combustion air
inducer assembly. Remove ground wire from vest panel.
12. Remove electrical junction box from the side of the furnace.
13. Mark and disconnect any remaining wiring to heating compartment components. Disengage strain relief bushing and pull wiring and bushing through the hole in the blower deck.
14. Remove the primary limit from the vestibule panel.
15. Remove two screws from the front cabinet ange at the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger.
508405-01Page 50 of 53 Issue 2332
Page 51
16. Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger
assembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger ange. Remove heat exchanger from furnace cabinet.
17. Back wash heat exchanger with soapy water solution or steam. If steam is used it must be below 275°F (135°C).
18. Thoroughly rinse and drain the heat exchanger. Soap solutions can be corrosive. Take care to rinse entire assembly.
19. Reinstall heat exchanger into cabinet making sure
that the clamshells of the heat exchanger assembly
are resting on the support located at the rear of the cabinet. Remove the indoor blower to view this area through the blower opening.
20. Resecure the supporting screws along the vestibule sides and bottom to the cabinet. Reinstall blower and mounting screws.
21. Reinstall cabinet screws on front ange at blower deck.
22. Reinstall the primary limit on the vestibule panel.
23. Route heating component wiring through hole in blower deck and reinsert strain relief bushing.
24. Reinstall electrical junction box.
25. Reinstall the combustion air inducer. Reconnect the combustion air inducer to the wire harness.
26. Reinstall pressure switches and reconnect pressure switch wiring.
27. Carefully connect combustion air pressure switch hosing from pressure switches to proper stubs on cold
end header collector box.
28. Reinstall condensate trap.
29. Reconnect exhaust piping and exhaust drain tubing.
30. Reinstall burner box assembly in vestibule area.
31. Reconnect ame rollout switch wires.
32. Reconnect sensor wire and reconnect 2-pin plug from ignitor.
33. Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
34. Reinstall gas valve manifold assembly. Reconnect gas supply line to gas valve.
35. Reconnect wires to gas valve.
36. Replace the blower compartment access panel.
37. Refer to instruction on verifying gas and electrical connections when re-establishing supplies.
38. Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean
and dry and that furnace is operating properly.
39. Replace heating compartment access panel.
Cleaning the Burner Assembly
1. Turn o󰀨 electrical and gas power supplies to furnace. Remove upper and lower furnace access panels.
2. Disconnect from the gas valve.
3. Remove the burner box cover.
4. Disconnect the gas supply line from the gas valve. Remove gas valve/manifold assembly.
5. Mark and disconnect sensor wire from the sensor. Disconnect 2 pin plug from the ignitor at the burner
box.
6. Remove four screws which secure burner box assembly to vest panel. Remove burner box from the
unit.
7. Use the soft brush attachment on a vacuum cleaner to gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage.
8. Reconnect the sensor wire and reconnect the 2 pin plug to the ignitor wiring harness.
9. Reinstall the burner box assembly using the existing four screws. Make sure that the burners line up in the center of the burner ports.
10. Reinstall the gas valve manifold assembly. Reconnect the gas supply line to the gas valve. Reinstall the
burner box cover.
11. Reconnect wires to gas valve.
12. Replace the blower compartment access panel.
13. Refer to instruction on verifying gas and electrical connections when re-establishing supplies.
14. Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean
and dry and that furnace is operating properly.
15. Replace heating compartment access panel.
508405-01 Page 51 of 53Issue 2332
Page 52

Planned Service

A service technician should check the following items during an annual inspection. Power to the unit must be
shut o󰀨 for safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) - Must be open and unobstructed to provide combustion air.
Burners - Must be inspected for rust, dirt, or signs of water.
Vent pipe - Must be inspected for signs of water, cracked,
damaged or sagging pipe, or disconnected joints.
Unit appearance - Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door - Must be properly in place and provide a seal between the return air and the room where the furnace is installed.
Return air duct - Must be properly attached and provide an air seal to the unit.

Repair Parts List

Operating performance - Unit must be observed during
operation to monitor proper performance of the unit and the vent system.
Combustion gases - Flue products must be analyzed and
compared to the unit specications.
Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced.
Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace
inspections that may result in unsafe operation. For
instance, items innocently stored next to the furnace may
obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon
monoxide gas.
The following repair parts are available through Allied Air dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
• Heating Compartment Access Panel
• Blower Compartment Access Panel
• Top Cap
Control Panel Parts
• Transformer
• Integrated Control Board
• Door Interlock Switch
Blower Parts
• Blower Wheel
• Motor
• Motor Mounting Frame
• Motor Choke
• Blower Housing Cuto󰀨 Plate
Heating Parts
• Flame Sensor
• Heat Exchanger Assembly
• Gas Manifold
• Combustion Air Inducer
• Gas Valve
• Main Burner Cluster
• Main Burner Orices
• Pressure Switches
• Ignitor
• Primary Limit Control
• Flame Rollout Switches
508405-01Page 52 of 53 Issue 2332
Page 53
Requirements for Commonwealth of Massachusetts
Modications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following
requirements:
For all side wall, horizontally vented, gas-fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above the nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side
wall, horizontally vented, gas-fueled equipment, the
installing plumber or gas tter shall observe that a hard-wired carbon monoxide detector with an alarm and battery backup is installed on the oor level where
the gas equipment is to be installed. In addition, the
installing plumber or gas tter shall observe that a battery-operated or hard-wired carbon monoxide
detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas-fueled equipment. It shall be the responsibility of the property owner to
secure the services of qualied licensed professionals for the installation of hard-wired carbon monoxide
detectors.
a. In the event that the side wall, horizontally vented,
gas-fueled equipment is installed in a crawl space
or an attic, the hard-wired carbon monoxide
detector with alarm and battery backup may be
installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30)
day period, a battery-operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. SIGNAGE. A metal or plastic identication plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented, gas-fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas-fueled equipment shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required to Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall, horizontally vented, gas­fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components: and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved sidewall, horizontally vented, gas-fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems,” the following requirements shall
be satised by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
508405-01 Page 53 of 53Issue 2332
Loading...