Ducane (HVAC) 2HP13-14 User Manual

Page 1
2HP13/14 & 4HP13 SPLIT SYSTEM HEAT PUMP
INSTALLATION / START-UP INSTRUCTIONS
/HOMEOWNERS INFORMATION MANUAL
These instructions must be read and understood completely before attempting installation.
TABLE OF CONTENTS
Safety Precautions ..................................... 2
Unit Location & Installation ............................... 2
Rooftop Installation & Recommendations . . . . . . . . . . . . . . . . . . . . 3
Indoor Coil Piston Selection .............................. 3
Refrigeration Line Sets .................................. 3
Installation of Line Sets .................................. 4
Leak Check ........................................... 4
Evacuating & Charging .................................. 4
Opening Service Valve .................................. 5
Electrical Connections................................... 5
Control Wiring ......................................... 5
Start-Up Procedure ..................................... 6
Adjusting charge ....................................... 6
Defrost System ........................................ 7
Single Phase Wiring Diagram ............................. 9
3 Phase Wiring Diagram ................................. 10
Homeowner's Information ................................ 11
These units are designed for use in residential and light commercial type buildings. Heat Pumps may only be installed with indoor combinations listed in the Air-Conditioning and Refrigeration Institute (ARI) Directory of Certified Products.
Inspect the unit for any damage before installation. If damage is found, notify the transportation company immediately and file a concealed damage claim.
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes and with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part 1 CSA C22.1.
Improper installation, adjustment, alteration, service or maintenance will void the warranty. The qualified installer or agency must use factory-authorized kits or accessories when added to this products. Refer to the individual instructions included with the specific accessory kit.
NOTE
These instructions are intended as a general guide and do not supersede national, state or local codes in any way.
These instructions must be left with the property owner.
506162-02 Issue 0847 Page 1 of 14
Page 2
NOTE TO INSTALLING DEALER
These instructions and warranty are to be given to the owner or prominently displayed near the indoor air handler unit.
UNIT LOCATION & INSTALLATION
NOTE: In some cases noise in the living area has been
traced to gas pulsations from improper installation of equipment.
1. Locate unit away form windows, patios, decks, etc. where unit operation sounds may disturb customer.
This product and/or the indoor unit that is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further inform ation, consult material safety data sheets available from your distributor.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other silicon-based caulk.
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, walls, and any structure.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
When outdoor unit is connected to factory-approved
indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft. of field-supplied tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover.
IMPORTANT: Maximum liquid-line size is 3/8 in. O.D. for
all residential applications including long
Safety Precautions
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions attached to the unit.
1. Always wear proper personal protection equipment.
2. Always disconnect electrical power before removing
panel or servicing equipment.
3. Keep hands and clothing away from moving parts.
4. Handle refrigerant with caution, refer to proper MSDS
from refrigerant supplier.
5. Use care when lifting, avoid contact with sharp edges.
506162-02 Issue 0847 Page 2 of 14
Outdoor Section
Zoning ordinances may govern the minimum distance
the condensing unit can be installed from the property line.
Install on a Solid, Level Mounting Pad
The outdoor section is to be installed on a solid foundation. This foundation should extend a minimum of 2" (inches) beyond the sides of the outdoor section. To reduce the possibility of noise transmission, the foundation slab should NOT be in contact with or be an integral part of the building foundation.
lines.
Page 3
Elevate Unit
Accumulation of water and ice in base pan may cause equipment damage.
DO LOCATE THE UNIT:
! W ith proper clearances on sides and top of unit
! On a solid, level foundation or pad
! To minimize refrigerant line lengths
Elevate unit per local climate and code requirem ents to provide clearance above estim ated snowfall level and ensure adequate drainage of unit. Use snow stand in areas where prolonged freezing temperatures are encountered.
If conditions or local codes require the unit be attached to pad or mounting frame, tie down bolts should be used and fastened through knockouts provided in unit base pan.
Roof Top Installations
Mount on level platform or frame 6 inches above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and m inimize transmission of vibration to building. Ensure roof structure and anchoring method is adequate for location. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. A sheet metal baffle should be spaced 6-1/2" from the fall of the coil. The height should cover the face of the coil and the length should be 6" from the access panel.
NOTE: Unit must be level to within ± 2/ (± 3/8 in./ft) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. For proper airflow, quiet operation and maxim um efficiency. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
DO NOT LOCATE THE UNIT:
! On brick, concrete blocks or unstable surfaces ! Near clothes dryer exhaust vents ! Near sleeping area or near windows ! Under eaves where water, snow or ice can fall
directly on the unit
! w ith clearance less than 2 ft. from a second unit ! w ith clearance less than 4 ft. on top of unit
Operating Ambient
The minimum outdoor operating ambient in cooling
mode is 55/F, and the maximum outdoor operating ambient in cooling mode is 125/F. The maximum outdoor operating ambient in heating mode is 66/F.
Indoor Coil Piston Selection
The outdoor heat pump section must be matched to a factory approved indoor section. It is mandatory that the installer ensure that the correct piston is installed in the indoor section. If necessary remove the existing piston and replace it with the correct piston See indoor unit instructions for details of changing the piston. Contact your distributor for accessory piston kits.
Indoor (Cooling) Piston Size
13 SEER Heat Pump Indoor Piston Sizes
Unit Size 2HP13 4HP13
18 .055 .051 24 .063 .055 30 .068 .059 36 .076 .070 42 .076 .070 48 .082 .082 60 .098 .082
The evaporator coil may use an expansion valve (TXV) in place of piston.
NOTE: If a TXV is installed a hard start kit is required on all models with reciprocating compressors. See spec sheet for proper kit selection.
14 SEER Heat Pum p Models
All 14 SEER heat pump models are only rated with TXV on the indoor side.
14 SEER Heat Pump Indoor TXV
Unit Size TX V Kit 18 thru 36 TXV3 42 thru 48 TXV5
Refrigeration Line Sets
Use only refrigerant grade copper tubes. Split systems may be installed with up to 50 feet of line set (no more than 20 feet vertical) without special consideration (see long line set guidelines).
506162-02 Issue 0847 Page 3 of 14
Page 4
Recommended Liquid & Vapor Tube Diameters (In.)
Unit Size
Connection Dia. Tube Dia. Connection Dia. Tube Dia. 018 3/8" 3 /8" 3/4 3/4 024 3/8" 3 /8" 3/4 3/4 030 3/8" 3 /8" 3/4 3/4 036 3/8" 3 /8" 3 /4 3/4 042 3/8" 3 /8" 7/8 7/8 048 3/8" 3 /8" 7/8 7/8 060 3/8" 3 /8" 7/8 *1-1/8
*FIELD SUPPLIED 7/8 X 1-1/8 CONNECTOR REQUIRED ON BOTH ENDS OF VAPOR TUBING.
LIQUID VAPOR
It is important that no tubing be cut or seals broken until you are ready to actually make connections to the evaporator and to the condenser section. DO NOT remove rubber plugs or copper caps from the tube ends until ready to make connections at evaporator and condenser. Under no circumstances leave the lines open to the atmosphere for any period of time, if so unit requires additional evacuation to remove moisture.
Be extra careful with sharp bends. Tubing can "kink" very easily, and if this occurs, the entire tube length will have to be replaced. Extra care at this time will eliminate future service problems.
It is recommended that vertical suction risers not be up-sized. Proper oil return to the compressor should be maintained with suction gas velocity.
The following is the recommended method for making
braze connections at the refrigerant line connections:
1. Debur and clean refrigerant tube end with emery cloth or steel brush.
2. Insert tubing into swage fitting connection.
3. W rap wet rags over valves to protect from heat.
4. Allow dry nitrogen to flow through refrigerant lines.
5. Braze joint, using a suitable brazing alloy for copper to copper joints.
6. Quench the joint and tubing with water using a wet rag. Leave rag on fitting body and re-wet with water to help cool area.
Leak Check
Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation. The recommended procedure is to apply a trace amount of vapor refrigerant (approximately two ounces or 3 psig) into the line set and indoor coil, then pressurize with 150 psig of dry nitrogen. Use a refrigerant leak detector to check all joints. The system may also be checked for leaks using a halide torch or pressure and soapy solution. After completion of leak check, relieve all pressure from system before evacuation.
Installation of Line Sets
DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist. Use an insulated or suspension type of hanger. Keep both lines separate, and always insulate the suction line. Long liquid line runs (30 feet or more) in an attic will require insulation. Route refrigeration line sets to minimize length.
DO NOT let refrigerant lines come in direct contact with foundation. When running refrigerant lines through the foundation or wall, openings should allow for a sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a vibration damping m aterial.
If ANY refrigerant tubing is buried, provide a 6 inch vertical rise at service valve. Refrigerant tubing lengths up to 36 inches may be buried without further special consideration. For lengths above 36 inches, consult your local distributor.
Before making braze connections, be sure all joints are clean. Before heat is applied for brazing, dry nitrogen should be flowing through the tubing to prevent oxidation and scale formation on the inside of the tubing.
Evacuating And Charging Instructions NOTE: Intentional release of CFC or HCFC refrigerant
to the atmosphere violates Federal Law. It may also violate State and Local Codes. Check all Federal, State and Local Codes before proceeding.
These outdoor units are pre-charged at the factory with
adequate refrigerant to handle 15 feet of refrigerant tubing.
NOTE: DO NOT use any portion of the charge for purging
or leak testing. It is mandatory that a thorough evacuation of the refrigeration lines and indoor coil be performed.
The liquid line and suction line service valves have been
closed after final testing at the factory. DO NOT disturb
these valves until the lines have been leak checked and evacuated or the charge in the unit may be lost.
1. Connect the vacuum pump to the center hose of the manifold gauge set, the low-pressure m anifold gauge to the vapor service valve and the high pressure manifold gauge to the liquid service valve.
NOTE: Unnecessary switching of hoses can be avoided
and complete evacuation of all lines can be achieved by also connecting a branch hose from the manifold gauge center port to a cylinder of the proper refrigerant. Provide a separate shut-off valve to vacuum pump to avoid contaminating vacuum pump oil with refrigerant.
506162-02 Issue 0847 Page 4 of 14
Page 5
2. The valves should be kept in the "front seated" (closed) position. This will allow evacuation of the refrigeration lines and the indoor coil, without disturbing the factory charge in the outdoor unit.
3. Follow the vacuum pump manufacturer's instructions. Allow the pump to operate until the system has been evacuated down to 300 microns. Allow the pump to continue running for an additional 15 minutes. Turn OFF the pump and leave the connections secured to the two (2) service valves. After 5 minutes, if the system fails to hold 500 microns or less, check all connections for tight fit and repeat the evacuation procedure.
4. Isolate the vacuum pump from the system by closing the shutoff valves on the gauge-set. Disconnect the vacuum pump.
Opening Service Valves
After evacuation of the connecting lines, remove the service valve cap and fully insert the hex wrench into the stem . A back-up wrench is required on the valve body to open the valve stem. Back-out counterclockwise until the valve stem just touches the coined edge.
Wrench sizes:
3/8 service valve: 3/16" Hex wrench 3/4 service valve: 5/16" Hex wrench 7/8 service valve: 5/16" Hex wrench
Replace service valve cap and torque to 8-11 ft-lb on 3/8" valves; 12-15 ft-lb on 3/4" valves; 15-20 ft-lb on 7/8" valves. Use backup wrench on valve body when torqueing valve cap.
Provide line voltage power supply to unit from a properly sized disconnect switch. Route power and ground wires from disconnect switch to unit. Line voltage connections are made at the line side of the contactor in the control box of the outdoor unit. Follow the appropriate wiring diagram attached to inside of the access panel.
Proper circuit protection recomm endations are indicated on Unit Rating Plate. Time delay fuses are required to prevent blowing due to starting current (the current in rush when equipment starts is referred to as the Locked Rotor Amps or (LRA). A fuse of this kind properly sized will give maximum equipment protection.
Use copper wire only between disconnect switch and unit.
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box. Flexible conduit is required for the swing out control box feature.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor.
Install Electrical Accessories
Refer to the instructions packaged with the accessories.
Electrical Connections
....
ELECTRICAL SHOCK HAZARD!
Turn OFF electric power before connecting unit, performing any maintenance or removing panels or doors. More than one disconnect may be required to turn off all power.
FAILURE TO DO SO COULD RESULT IN BODILY INJURY OR DEATH.
Be sure to check all local codes to determine that the unit is installed accordance with local requirements. Consult the National Electric Code for wire size requirements. Use 60/ C wire or higher. Always provide ground connections to the outdoor unit. Power supply m ust agree with rating on unit nameplate.
High voltage power connections to 3-phase m odels is made to "Pig Tail" leads with field supplied splice connectors.
Control Wiring
The control voltage is 24 Vac. NEC Class I insulated 18 AWG is required for control wiring. For lengths longer than 150 feet, contact your local distributor for technical service.
Ensure the room thermostat is properly installed per instructions shipped with room thermostat. Generally the thermostat should not be exposed to sunlight, drafts or vibration and should not be mounted on exterior walls.
Low voltage control wire connections should be made to the screw connection terminal board mounted on the defrost control as shown. All low voltage control wiring must be separated from incoming power leads.
506162-02 Issue 0847 Page 5 of 14
Page 6
Heat Pump Application with Electric Heat
Emergency Heat (heating heat pump)
If selector switch on thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat ( if applicable). A jumper should be placed between W and E on the thermostat so that the electric heat control will transfer to the first stage heat on the therm ostat. This will allow the indoor blower to cycle on and off w ith the electric heat when the fan switch is in the AUTO position.
* Add Jumper on Subbase (O ptional)
Adjusting Charge
Factory charge is shown on the rating label located on the access panel.
All split system heat pumps are factory charged for 15 feet of connecting line set and matched indoor fan coil. Nameplate refrigerant charge should initially be
adjusted for line set lengths other than 15 feet. For line sets shorter than 15 feet in length, remove charge. For line sets longer than 15 feet, add charge. Oil charge is sufficient for all line lengths.
Refrigeration Charge Adjustment
Liquid Line Diameter Oz. Per Linear Foot *
3/8" .6
* Factory charge for series is for 15' (ft.) line sets and matched fan
coil.
Before final adjustment is made to the refrigerant charge, it is imperative that proper indoor airflow be established. Airflow will be higher across a dry coil versus a wet coil. Blower charts are calculated with a dry or wet coil basis. Recomm ended airflow is 350-450 CFM per ton (12,000 Btuh) through a wet coil. Refer to indoor unit instructions for methods of determining air flow and blower performance.
Cooling Cycle Charge Adjustment The optimum method for checking the charge is by weight. However the following methods may be used to confirm the proper charge:
Units with Indoor Pistons
Units installed with indoor pistons require charging with the superheat method.
Start-Up Procedure
1. Check to ensure: ! Service valve and gage port caps are installed and
tightened.
! Voltage supply at unit agrees with nameplate
rating.
! Field wiring connections are tight and factory
wiring has not been disturbed and are tight.
! Indoor fan motor is on correct speed tap.
2. Set thermostat selector switch to OFF and fan control switch to "Auto" is so equipped.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5. Set the system switch of the thermostat on COOL (or HEAT if applicable) and fan switch for continuous operation (ON) or AUTO, as desired. There will be a 5 minute short cycle compressor delay on startup. Operate unit for 15-20 minutes, then check the system refrigerant charge.
6. Adjust refrigerant charge per "Adjusting Charge" section.
The following procedure is valid when indoor airflow is
within ± 20% of its rated CFM.
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure suction pressure by attaching a gage to suction valve service port. Do not use compressor suction port. Determine saturation temp from T/P chart.
3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service valve.
4. Calculate superheat (measured temp. — saturation temp.).
5. Measure outdoor air dry-bulb temperature with thermom eter.
6. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling psychrometer.
7. Compare superheat reading at service valve with the chart located on control box cover.
8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
9. If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
506162-02 Issue 0847 Page 6 of 14
Page 7
10. Remove charge if superheat is low and add charge if superheat is high.
Required Subcooling
Model
18 14 10 12
24 9 3 14
30 13 8 17
36 9 14 10
42 11 3 16
48 8 9 7
60 12 - 13
2HP13 2HP14 4HP13
(± I/F)
NOTE: If a TX V is installed on indoor unit, a hard start kit
is required on all models with reciprocating compressors. Refer to the specification sheet for details. Hard start kits are also recommended for areas with utility power lower than 208 Vac.
Units with Indoor TXV
Units installed with TXV on indoor side, require charging
with the subcooling method.
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure liquid service valve pressure by attaching an accurate gage to service port. Determine saturation temp. from T/P chart.
3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil.
4. Calculate subcooling (saturation temp.— measured temp.).
5. Find the point where required subcooling temperature intersects measured liquid service valve pressure.
6. Add refrigerant if subcooling is lower than table below. Recover refrigerant if subcooling is high.
SYSTEM OPERATION
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
Filter Drier
The outdoor unit is equipped with a bi-flow filter drier. If replacement is necessary, order new dryer according to the service parts m anual.
Emergency Heat Function (Room Thermostat)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the em ergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Em ergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage. If power has been off for over an hour and the outdoor temperature is below 50/F (10/C). System should be left in the em ergency heat mode at least six hours to allow the crankcase heater sufficient tim e to prevent com pressor slugging. This applies only to systems with crank case heaters.
Defrost System
The defrost system includes two (2) components: a defrost thermostat and a defrost control.
Defrost Thermostat
Heating Check Chart Procedure
To check system operation during heating cycle, refer to the Heating Check Chart located on back of control box cover. This chart indicates wheth er a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust
The defrost thermostat is located on the outdoor coil of most models and on the liquid line between the check/expansion valve and the distributor on R-4110A TXV equipped models. When defrost thermostat senses 29/F (42/ on R-410A TXV’s) or cooler, the therm ostat contacts close and send a signal to the defrost control board to start the defrost tim ing. It also terminates defrost when the liquid line warms up to 60/F.
refrigerant charge.
Charge must be rechecked again during the cooling
season.
Defrost Control
The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring
Cold Weather Application
connections.
A cold weather accessory kit may be required for heat
pumps operating at ambient conditions below 25/ F. Supplemental heat should be provided for these conditions due to the expected performance degeneration.
The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle, the control accumulates compressor run times at 30-, 60-, or 90-minute field-adjustable
506162-02 Issue 0847 Page 7 of 14
Page 8
intervals. If the defrost thermostat is closed when the selected compressor run tim e interval ends (call for defrost), the defrost relay is energized and defrost begins. The factory setting is 60 minutes. However, if frost
accumulation is easily cleared, the optimum efficiency setting is 90 minutes.
Outdoor Unit Defrost Control Board
Defrost Control Timing Pins
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (/T1), 60 (T2), or 90 (T3) minutes. The defrost tim ing jumper is factory-installed to provided a 90-minute defrost interval. If the timing selector jumper is not in place the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
defrost mode when the com pressor delay jumper is removed.
NOTE: The 30 second "off" cycle is not functional when
jumpering the TEST pins.
Time Delay
The timed-off delay is 5 minutes long. The delay help to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Pressure Sw itch Circuit
The defrost control incorporates 2 pressure switch circuits. The optional high pressure switch connects to the boards HI PS terminals. The low pressure switch is factory installed.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch. The unit will rem ain locked out until power to the board is interrupted, then re-established or until the jum per is applied to the TEST pins for 0.5 seconds.
NOTE: The defrost control board ignores input from the
low-pressure switch terminals as follows:
! During the TEST mode,
! During the defrost cycle,
! During the 90 second start-up period,
! and for the first 90 seconds each time the reversing
valve switches heat/cool modes. If the TEST pins are jumpered and the 5 minute delay is being by­passed, the LO PS terminal signal is not ignored during the 90 second start-up period.
A TEST option is provided for troubleshooting. The
TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power-
Diagnostic LEDS
The defrost board uses 2 LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5 second period has elapsed ( 7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not rem oved until after the additional 5 second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied.
Compressor Delay
The defrost board has a field-selectable function to
reduce occasional sounds that m ay occur while the unit is
Mode Green LED (DS2) Red LED (DS1)
No power to control OFF OFF Normal operation/
power to control Anti-short cycle
lockout Low pressure switch fault (Optional) Low pressure switch lockout (Optional) High pressure switch fault (Optional) High pressure Switch lockout (Optional)
Defrost Control board Diagnostic LED
Simultaneous Slow FLASH
Alternating Slow FLASH
OFF Slow FLASH
OFF ON
Slow FLASH OFF
ON OFF
cycling in and out of the defrost mode. The compressor will be cycled "off" for 30 seconds going in and out of the
506162-02 Issue 0847 Page 8 of 14
Page 9
H/P SINGLE PHASE WIRING DIAGRAM
506162-02 Issue 0847 Page 9 of 14
Page 10
H/P 3 PHASE WIRING DIAGRAM
506162-02 Issue 0847 Page 10 of 14
Page 11
Homeowner's Information
ELECTRICAL SHOCK HAZARD!
Turn OFF electric power to unit before performing any maintenance or removing panels or doors.
FAILURE TO DO SO COULD RESULT IN BODILY INJURY OR DEATH.
Heat Pump Operation
Your new heat pump has several characteristics that you
should be aware of:
! Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas-or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
! Do Not be alarmed if you notice frost on the outdoor
coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45/F. An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
! During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating dem and; however., the unit will run to normal operation at the conclusion of the defrost cycle.
In case of extended power outage...
If the outdoor temperature is below 50/F and power to
your outdoor unit has been interrupted for 6 hours or longer, observe the following when restoring power to your heat pump system.
! Set the room thermostat selector to the "Emergency
Heat" setting to obtain temporary heat for a minimum of 6 hours. This will allow system refrigerant pressures and temperatures enough time to return to a stabilized condition.
! In Emergency Heat mode, all heating dem and is
satisfied by auxiliary heat; heat pump operation is locked out. After a 6 hour "warm-up" period, the thermostat can then be switched to the "Heat" setting and normal heat pump operation my resume.
! Heat pumps (in the cooling mode) rem ove humidity
from your home. Depending on the amount of moisture in the air inside your home, water will trickle from the condensate drain of the cooling coil.
Thermostat Operation
The wall-mounted therm ostat controls your air conditioner. The thermostat is available in various configurations from different manufacturers. The
information below is typical for most thermostats. Ask your dealer for specific information regarding the model of thermostat installed.
Temperature Setting Levers
Most heat pum p thermostats have 2 temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature set points for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
On heat pump systems, increasing your thermostat setting by more than 2 degrees may cause supplem ental heaters to turn on, reducing potential energy savings.
Fan Switch
In AUTO or INT (intermittent ) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to autom atically switch from heating mode to cooling m ode to maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room temperature.
Fan Control
For fan control your thermostat may have a Fan Selection Switch that allows you to run the fan continuously or cycle it automatically with the heating or cooling system. Switch the lever to ON for continuous operation and to AUTO for automatic cycling.
For maximum comfort satisfaction and continual air cleaning/filtering, constant fan operation is recommended.
506162-02 Issue 0847 Page 11 of 14
Page 12
On models without a fan Selection Switch, the fan will
cycle with the outdoor unit.
Periodically, debris should be brushed from the condenser coils.
Important System Information
! Your system should never be operated without a
clean air filter properly installed.
! Return air and supply air registers should be free
from restrictions or obstructions to allow full flow of air.
Regular Maintenance Requirements
Your system should be regularly inspected by a qualified service technician. These regular visits may include (among other things) checks for:
! Motor operation
! Ductwork air leaks
! Coil & drainpan cleanliness (indoor & outdoor)
! Electrical component operation & wiring check
! Proper refrigerant level & refrigerant leaks
! Proper airflow
! Drainage of condensate
! Air filter(s) performance
! Blower wheel alignment, balance & cleaning
! Primary & secondary drain line cleanliness
! Proper defrost operation (heat pumps)
There is some routine maintenance procedures you can do to help keep your system operating at peak performance between visits.
Air Filter
Inspect air filters at least monthly and replace or clean as required. Disposable filters should be replaced. W ashable filters may be cleaned by soaking in mild detergent and rinsing with cold water. Replace filters with the arrows pointing in the direction of airflow. Dirty filters are the most common cause of poor heating / cooling performance and compressor failures.
Indoor Coil
If the system has been operated with a clean filter in place, it should require minim al cleaning. Use a vacuum cleaner and soft brush attachment to remove any accumulation of dust from the top and underside of the finned coil surface. However, perform this maintenance only when the coil is com pletely dry.
If the coil cannot be cleaned by this method, call your dealer for service. It may need a detergent solution and rinsing with water for cleaning, which may require coil removal. You should not attempt this yourself.
Condensate Drain
During cooling season check at least monthly for free flow of drainage and clean if necessary.
.....
SHARP OBJECT HAZARD!
Condenser coils have sharp edges. W ear adequate body protection on body extremities (e.g. gloves). FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY.
Use a soft bristle brush with light pressure only. DO NOT damage or bend condenser coil fins. Damaged or bent fins may affect unit operation.
Painted Surfaces
For maximum protection of the unit's finish, a good grade of automobile wax should be applied every year. In geographical areas where water has a high concentration of minerals (calcium , iron, sulfur, etc.). It is recommended that lawn sprinklers not be allowed to spray the unit. In such applications, the sprinklers should be directed away from the unit. Failure to follow this precaution m ay result in premature deterioration of the unit finish and metal components.
In sea coast areas, special maintenance is required due to the corrosive atmosphere provided by the high salt concentration in ocean mists and the air. Periodic washing of all exposed surfaces and coil will add additional life to your unit. Please consult your installing dealer for proper procedures in your geographic area.
IF YOUR SYSTEM DOES NOT WORK,
BEFORE REQUESTING A SERVICE CALL:
1. Ensure thermostat is set below (cooling) or above
(heating) room temperature and that the system lever is in the "COOL", "HEAT" or "AUTO" position.
2. Inspect your return air filter: If it is dirty your air
conditioner may not function properly.
3. Check indoor and outdoor disconnect switches.
Confirm circuit breakers are ON or that fuses have not blown. Reset breakers/replace fuses as necessary.
4. Inspect the outdoor unit for clogged condenser coils,
(grass cuttings, leaves, dirt, dust or lint). Ensure that branches, twigs or other debris are not obstructing the condenser fan.
IF YOUR SYSTEM STILL DOES NOT OPERATE, CONTACT YOU SERVICING DEALER.
Be sure to describe the problem, and have the model and serial numbers of the equipment available.
Condenser Coils
Grass cuttings, leaves, dirt, dust, lint from clothes dryers, and fall off from trees can be drawn into coils by movement of the air. Clogged condenser coils will lower the efficiency of your unit and could cause dam age to the condenser.
506162-02 Issue 0847 Page 12 of 14
If warranted replacements parts are required, the warranty must be processed through a qualified distribution location.
Page 13
ALLIED AIR ENTERPRISES
EQUIPMENT LIMITED WARRANTY
APPLIES IN U.S.A. AND CANADA ONLY
FAILURE TO MAINTAIN YOUR EQUIPMENT WILL VOID THIS WARRANTY
COVERED EQUIPMENT
The following Allied Air Enterprises heating and cooling equipment is covered by the Limited Warranty:
Condensing Units: 2SCU13, 4SCU13, 4SCU14, 4SCU16, 4SCU18, 2AC13, 2AC14,4AC13 Heat Pumps: 2SHP13, 4SHP13, 2SHP14, 4SHP14, 4SHP16, 4SHP18, 2HP13, 2HP14, 4HP13 Gas Furnaces: G1N80, G1D80, G2D80, G1D91,G1D93, G2D93, G2D95, FPBB, CG80, CG90, CG93, CG90UA Oil Furnaces: LBR80, LBF80, LHF80, LUF80, RULF, RLBR, RLBU, RLHF, RLHR Electric Furnaces: EFC, EFV Evaporator Coils: EC, EU, EH, EM Air Handlers: BCS2, RBCS2 Package Equipment:: 2PCE13, 4PCE13, 4PCE15, 2PGE13, 4PGE13, 4PGE15, 2PHP13, 4PHP13, 4PHP15, 2SG13, 2SH13, 2SA13
PARTS and COMPRESSOR COVERAGE
The covered equipment and covered parts and compressor are warranted by Allied Air for a period of five (5) years from the date of the original installation, when installed in a residential application (which includes homes, duplexes, apartments and condominiums). The covered equipment and covered parts and compressor are warranted by Allied Air for a period of one (1) year from the date of the original installation, when installed in non-residential applications. If during this period, a covered component fails because of a manufacturing defect, Allied Air will provide a free replacement part to the owner through a licensed service contractor utilizing an Allied Air distributor. You must pay shipping charges and all other costs of warranty service. Allied Air will not pay labor involved in diagnostic calls or in removing, repairing, servicing or replacing parts. Such cost may be covered by a separate warranty provided by the installer.
HEAT EXCHANGER EXTENDED COVERAGE
All covered heat exchangers are warranted by Allied Air for a period of twenty (20) years from the date of original installation. Heat Exchanger Availability: If a replacement heat exchanger is no longer available for a unit covered by this warranty, Allied Air will allow a credit toward the purchase of an equivalent Allied Air furnace (at the current suggested distributor’s cost).
NOTE: If the date of original installation cannot be verified, the warranty period will be deemed to begin ninety (90) days after the date of manufacture.
EXCLUD ED COMPO NENTS
The following components are not covered by this warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles, unit accessories and any parts not affecting unit operation.
CARE OF EQUIPMENT
Your new Allied Air unit must be properly installed, operated and maintained in accordance with the unit installation, operation and maintenance instructions provided with each Allied Air unit. Failure to provide maintenance per Allied Air instr uctions will void this warranty.
WARRANTY PROCEDURE
When service or warranty parts are required:
1. Call your local licensed service dealer or contractor
2. If the in stalli ng deal er is un able to provide warrant y service, check onlin e at www.al liedai r.com.
3. Be prepared to furnish the following information: a. complete model and serial number b. proof of required periodic maintenance, installation date and location c. an accurate description of the problem
WARRANTY LIMITATIONS
1. This warranty is void if the covered equipment is removed from the original installation site.
2. This warranty do es not co ver damag e or defe ct resul ting fr om: a. flood, wind, fire, lightning, mold, or installation and operation in a corrosive atmosphere, or otherwise in contact with corrosive material (chlorine, fluorine, salt, recycled waste water, urine,
fertilizers, or other damaging substances or chemicals); accident, or neglect or unreasonable use or operation of the equipment including operation of electrical equipment at voltages
other than the range specified on the unit nameplate (i ncludes damages caused by brownouts) b. modification, change or alteration of the equipment, except as directed in writing by Allied Air c. operation with system components (indoor unit. outdoor unit and refrigerant control devices) which are not an ARI match or meet the specifications recommended by Allied Air d. operation of furnaces with return air temperatures of less than 60/ F (16/ C) or operation of a furnace field installed downstream from a cooling coil e. use of contaminated or refrigerant not compatible with the unit
The installation of replacement parts under the terms of this warranty does not extend the original warranty period.
Allied Air makes no express warranties other than the warranty specified above. All implied warranties, including the implied warranties of merchantability and fitness for a particular purpose, are excluded to the extent to a period legally permissible. Should such exclusion or limitation of the warranty be unenforceable, such implied warranties are in any event limited to a period of one (1) year. Liabilit y for incidental and conseq uential damages is excl uded. Some states do not allow limitat ion of incidental damages, so the limitations or exclusions may not apply to you. Allied Air will not pay electricity or fuel costs, or increases in electricity or fuel costs, for any reason whatsoever, including additional or unusual use of supplemental electric heat. This warranty does not cover lodging expenses or labor charges.
Allied Air shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
NOTE TO CUSTOMER Please complete information below and retain this warranty for your records and future reference.
Outside Unit Model Number: __________________________________________ Serial Number: ___________________________ Installed Date: ______________
Furnace / Air Handler: _______________________________________________ Serial Number: ___________________________ Installed Date: ______________
Indoor Coil Model N umber: ___________________________________________ Serial Number: ___________________________ Installed Date: ______________
Installing Company Name: _________________________________________________________________________ Phone: ______________________________
Installing Company Address: ___________________________________________ State / Province: ________________________ Zip / Postal Code: ___________
215 Metropolitan Drive, West Columbia, SC 29170
506162-02 Issue 0847 Page 13 of 14
Page 14
NOTES
506162-02 Issue 0847 Page 14 of 14
Loading...