WARNING: This manual contains information on limitations regarding product use and function and information on
the limitations as to liability the manufacturer. The entire manual should be read carefully.
Guidelines for Locating Smoke Detectors and CO Detectors
The following information is for general guidance only and it is recommended that local fire codes and regulations be consulted when locating
and installing smoke and carbon monoxide alarms.
Smoke Detectors
Research indicates that all hostile fires in homes generate smoke to a greater or lesser extent. Detectable quantities of smoke precede detectable
levels of heat in most cases. Smoke alarms should be installed outside of each sleeping area and on each level of the home.
DSC recommends that additional smoke alarms beyond those required for minimum protection be installed. Additional areas that should be
protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace and utility rooms; and any hallways not
protected by the required units.
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air
movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other appropriate national standards for installation recommendations.
• Do not locate smoke detectors at the top of peaked or gabled ceilings; dead air space in these locations may prevent smoke detection.
• Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from
entering the unit.
• Do not locate detectors in areas of high humidity.
• Do not locate detectors in areas where the temperature rises above 38
• Smoke detectors should always be installed in USA in accordance with Chapter 11 of NFPA 72, the National Fire Alarm Code: 11.5.1.1. :
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single- and multiple-station smoke alarms
shall be installed as follows:
(1) In all sleeping rooms and guest rooms.
2) Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room, the distance measured along a path of travel.
(
(3) On every level of a dwelling unit, including basements.
(4) On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics.
(5) In the living area(s) of a guest suite.
(6) In the living area(s) of a residential board and care occupancy (small facility).
oC
(100oF) or falls below 5oC (41oF).
Figure 1
CO Detectors
Carbon monoxide gas moves freely in the air. The human body is most vulnerable to the effects of CO gas
during sleeping hours. For maximum protection, a CO alarm should be located outside primary sleeping
areas or on each level of your home. Figure 5 indicates the suggested locations in the home. The electronic sensor detects carbon monoxide, measures the concentration and sounds a loud alarm before a
potentially harmful level is reached.
Do NOT place the CO alarm in the following areas:
• Where the temperature may drop below -10ºC or exceed 40 ºC.
• Near paint thinner fumes.
• Within 5 feet (1.5 meters) of open flame appliances such as furnaces, stoves and fireplaces.
• In exhaust streams from gas engines, vents, flues or chimneys.
• In close proximity to an automobile exhaust pipe; this will damage the detector.
BEDR OOM
BEDROOM
GROUND
FLOOR
CARBON M ONOXIDE DETEC TOR
BEDROOM
KITCHE N
BASEM ENT
Figure 5
GARAGE
ii
Chapter 1 Installation & Wiring
Chapter 1 Installation & Wiring
This Installation Guide provides the basic installation, wiring and programming information required to program the PowerSeries PC1616,
PC1832, and PC1864 control panels.
All necessary information required to meet UL Listing requirements is included in this document.
Classified in Accordance with ANSI/SIA CP-01-2000 (SIA-FAR)
INSTALLATION
Begin the installation by mounting additional modules in the cabinet using the stand-offs provided, then mount the cabinet in a dry, protected
area with access to unswitched AC power. Install hardware in the sequence indicated in the following pages. Do NOT apply power until installation is complete.
All wiring entry points are designated by arrows. All circuits are classified UL power limited except for the battery leads. Minimum 1/4”
(6.4mm) separation must be maintained at all points between power limited and non-power limited wiring and connections.
1
PowerSeries - PC1616/PC1832/PC1864
PC Boar d
Cabinet
Stand Of f
Pr imar y:120V A C/60Hz. Secondar y: 16.5VAC 40VA
DSCPTD 1640U
Class II Tr ansf or mer
NO TE: Do not connect
transf or mer to receptacle
controlled by as witch
Incorrect connections may result in PTC failure or improper operation.
Inspect wiring and ensure connections are correct be fo re appl ying po we r.
W ARNING:
Incorrect connection of batteries ma y result in batter y rupture or Fire Hazar d.
Do NO T allo w metal objects to connect the Positive and Negative Terminals.
Ensure that batteries are connected with correct polarity [Red to (+), Blac k to (-)].
F ailure to compl y with this ma y result in batte ry rupture and/or Fire Hazar d.
All cir cuits are c lassified fo r UL Installations as Po wer Limited/Class II Power Limited
e xcept fo r battery leads which are not po wer limited.
Do NO T r oute an y wiring o ver cir cuit boar ds .M aintain at least 1"(25.4mm) separation.
A minim um of 1/4" (6.4mm) separation mu st be maintained at all points between
po wer limited wiring and all other non-po wer limited wiring.
1. Inser t Stand off into cabinet
mounting hole in the
desired location. Snap-inplace .
2. P osition circuit board
mounting holes ov er standoffs . Press fir mly
on board to snap-in-place .
IMPOR T ANT :
a)This equipment, Alar m Controller PC1616/1832/1864 shal l
be installed and used within an en vironment that pr ov ides th e
pollution degree max 2 and ov er vo ltages categor y II
NON-HAZARDOUS LOCA TIONS , indoor onl y. The equipment is
FIXED and PERMANENTL Y connected and is designed to be
installed by ser vice persons only; [ser vice person is defined asa
person ha ving the appropr iate technical training and e xper ience
necessar y to be aw are of hazards to which that person ma y be
e xposed in per fo rm ing a task and of measures to minimi ze the ri sks
to that person or other persons .]
b)The connection to the mains supply must be made as per the local
author ities ru les and regulations. An appropr iate disconnect de vice must be pr ov ided as par t of th e
bu ilding installation. Where it is not possi bl e to rely on identification of
the neutral in the AC Mainssupply the disconnecting device must
disconnect both polessimultaneously (line and neutral). The device
shall disconnect the supply during servicing.
c)The equipment enclosure must be secured to the bu ilding str uctur e
bef ore operation.
e)Inter nal wi ri ng must be routed in a manner that pr ev ents:
- Excessi ve strain on wire and on te rm inal connections;
- Loosening of te rm inal; connections;
- Damage of conductor insulatio n
f) Disposal of the used batte ri es
shall be made according to the w ast e
reco ve ry and recycling regulationsapplicab le to the intended mar k et.
CON1
BA T+BA T-
FUSE
ACAC
16.5V /40V A
AC
To EGND
Te r m inal
230 V /50 Hz International
AC
CON1
BA T+BA T-
PO WER LIMITED
NON-PO WER LIMITED
DSC Model BD7-12
or equiv alent
Batter y
Standb yTime:
24H rs min.
BLA CK
RE D
TB-2
AC ACRED BL KY EL GRN Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
AUX+ BELL +
AU X- BELL-
PGM1 PGM3
EGND
TI PT -1
PGM2 PGM4
RING R- 1
DSC
220 220
UA 50 3
Cab le Tie (not supplied) recommended
PC1864
On ly
PC1864
PC1832
On ly
PC1616/1832/1864
High V oltage .D isconnect AC Po wer
and telephone lines bef ore servicing
W ARNING:
High V oltage . Disconnect AC Po wer
and telephone lines bef ore servicing
W ARNING:
TB-2
DSC
REV XX
220 220
U A503
CON1
BA T+BA T-
PC-LIN K
Internally Connected
AUX+ and Keybus (Red) are Internally Connected
To ta l current draw from Keyp ads, PG MO utput s and
Aux circuit sm ust not exceed 700m A
PC1864
On ly
PC1864
PC1832
Onl y
PC1616/1832/1864
10
12V / 7 AHr 12V / 7 AHr
Nor th America Onl y
See ground wiring
diagram in the Installation
section of this manual
DG009606
Keybus
PGMs
Zones
Telephone
AC AC + AUX - + BELL -
RED BLK YEL GRN
Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
EGND
RING TIP R-1 T-1
1 PGM 2 3 PGM 4
PC1616/1832/1864 Wiring Diagram
2
Chapter 1 Installation & Wiring
CONTROL
PANEL
150’ (46m)
150’ (46m)
500’ (152m)
500’ (152m)
Burglary Zone Wiring Chart
Wire
Gauge
Maximum Wire Length to
End-of-Line Resistor (ft/meters)
223000 / 914
204900 / 1493
196200 / 1889
187800 / 2377
Figures are based on maximum wiring resistance of 100
Normally Closed Loops - Do NOT use for UL Installations
Single End-of-Line Resistor Wiring
Double End-of-Line Resistor Wiring
1.1 Keybus Wiring
The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules. The 4 KEYBUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.
The following rules must be followed when wiring the Keybus:
• Modules can be home run, connected in series or T-tapped, provided that
the maximum wire distance from the control panel to any module does not
exceed 1,000 feet (305m)
• No more than 3,000 feet (915m) of wire can be used in total
1.2 Zone Wiring
Zones can be wired for Normally Open or Normally Closed contacts, with
Single-End-of-Line (SEOL) or Double End-of-Line (DEOL) resistors.
Observe the following guidelines:
• For UL Listed Installations use SEOL or DEOL only.
• Minimum 22 AWG wire, maximum 18 AWG
•Do not use shielded wire
Wire run resistance shall not exceed 100Refer to the chart below:
•
• [001]-[004] Selects Zone Definition
• [013] Opt [1] Selects Normally Closed or EOL resistors
• [013] Opt [2] Selects SEOL or DEOL resistors
• [101]-[108] Opt [14], [15], [16] Selects Normally Closed SEOL or DEOL
for on-board zones (PC1832/1864, Zone 1-8; PC1616, Zones 1-6)
Zone Status - Loop Resistance/Loop Status
• Fault - 0 (shorted wire/loop)
• Secure - 5600 (contact closed)
1.3 Zone Expanders
Zone expanders add zones in groups
of eight to the Alarm system. Module
jumpers J1, J2, J3 are required to
assign zones to these modules.
Jumper settings for PC5108 v2 are
shown here.
• PC5108 v1.0 supports first 32
zones only.
• PC5700 enrolls as two modules
• Do NOT use PC5108 v1 and
PC5108 v2 on the same panel.
Module Zones
JumpersAssigned
J1J2J3
ONONONZones Disabled
OFF ONONZones 09-16
ONOFF ONZones 17-24
OFF OFF ONZones 25-32
ONONOFF Zones 33-40
OFF ONOFF Zones 41-48
ONOFF OFF Zones 49-56
OFF OFF OFF Zones 57-64
1.4 Bell Wiring
These terminals supply 700mA of current at 12VDC for commercial installations and 11.1-12.6VDC for
residential installations (e.g. DSC SD-15 WULF). To comply with NFPA 72 Temporal Three Pattern
requirements: Program [013] Opt [8] ON. Note that Steady, Pulsed alarms are also supported.
The Bell output is supervised and power limited by 2A PTC. If unused, connect a 1000 resistor across
Bell+ and Bell- to prevent the panel from displaying a trouble. See [][2].
• Tamper - infinite (broken wire, open)
• Violated - 11,200 (contact open)
Refer to the associated installation sheet for Jumper locations
for the PC5108 v1 and PC5700.
3
PowerSeries - PC1616/PC1832/PC1864
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
EOLR-2
END-OF-LINE
RESISTOR
5600 Ohm, 0.5W
2200 Ohm
END-OF-LINE
RESISTOR
EOLR-3
ALARM
INITIATING
LOOP
RESISTANCE
100 Ohm
12V
DC
CO DETECTOR
RM-1/RM-2
POWER LOOP
SUPERVISORY
RELAY
(12V
DC, 35mA)
ALARM
INITIATING
LOOP
RESISTANCE
100 ohm
SEOL
RESISTOR
(5600 ohm)
PC1616/1832/1864
ANY
COM
ZONE
INPUT
POWERALARMTROUBLE
NCCNONCCNO
ANY
Z
(SEOL TYPE 41)
AUX
+
+
-
-
+
-
DG009477
The following hardwired CO Detector models can be used
with PC1616/PC1832/PC1864 v4.5 (and higher) control
panels:
• Potter Model CO-12/24, UL File E321434
• Quantum Model 12-24SIR, UL File E186246
• NAPCO Model FW-CO12 or FW-CO1224, UL File E306780
• System Sensor Model CO1224, UL File E307195
NOTE: For multiple unit connections, the leads between CO detectors need to be broken. The power supervision relay has to be powered from the last detector in the loop.
Wireless CO detectors are also available. When installing
wireless CO detectors, use only DSC model WS4913. A DSC
wireless receiver model RF5132-433 v5.1 (and higher) or DSC
keypad receiver models RFK55XX-433 (xx= 00/01/08/16/64)
v1.2 (and higher) are required when installing wireless CO
detectors. For more details on either the WS4913 CO detector
or the receivers, please refer to their respective installation
manuals.
1.5 AUX Power Wiring
The control panel can provide a maximum of 700mA of current for modules, powered detectors, relays, LEDs, etc. If the total current required
exceeds 700mA an additional power supply is required (e.g., PC5200, PC5204). See list below.
Min/max operating voltages for devices, sensors and modules is 9.5V
DC - 14VDC.
1.6 PGM Wiring
PGMs switch to ground when activated from the control panel. Connect the
positive side of the device to be activated to the AUX+ Terminal. Connect the
negative terminal to the PGM.
For current levels greater than 300mA, a relay is required.
PGM2 can also be used for 2-wire smoke detectors.
NOTE: Use SEOL resistors on fire zones only.
LED output with current limiting resistor and optional relay
driver output
UL Compatibility ID For FSA-210B Series is: FS200
NOTE: For ULC Listed installations use FSA-210A and FSA-410A series.
1.7 Carbon Monoxide Detector Wiring
4-Wire Smoke Detectors
4
1.8 Telephone Line Wiring
T-1
R-1
TIP
RING
RJ-31X
RED
GRN
BRN
GRA
Tighten nut to break paint and make
good connection to the cabinet
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x
Connector as indicated. For connection of multiple devices to the telephone
line, wire in the sequence indicated. Use 26 AWG wire minimum for wiring.
Telephone format is programmed in option [350].
Telephone Call Directions are programmed in options [351]-[376].
NOTE: Battery capacity will deteriorate with age and the number of
charge/discharge cycles. Replace
every 3-5 years.
A sealed, rechargeable, lead acid battery or gel type battery is required to
meet UL requirements for power standby times.
NOTE: UL Residential/Commercial Burglary installations require 4Hrs
of standby battery time.
NOTE: UL/ULC Residential Fire & Health Care installations require 24
Hrs of standby battery time. ULC Commercial Burglary and Fire monitoring installations require 24Hrs of standby battery time plus 5 minutes
of alarm condition.
For UL Listed installations, do NOT connect transformer to a receptacle controlled by a switch.
1.12 RFK5500 and RFK5564 Easy Wireless Enrollment Procedure
1.Enter [ ✱ ][8][Installer Code][898]. The LCD displays the following: “Wireless Enrollment Mode.”
2.Place the wireless device in the desired location.
3.Activate the device as described in the associated installation sheet. The electronic serial number (ESN) is displayed.
4.Press [
5.Enter a zone number (01-64) then press [
6.After successful entry of the zone number, the system prompts for the zone type. (The recommended zone type is displayed). Press [
✱ ] to confirm the ESN. If the serial number is incorrect, press [#] to discard it, and repeat this step. After successful confirmation of
the serial number, the system prompts for the zone number. The next available zone is displayed.
NOTE: Only one device may be enrolled in each zone. If a zone already has a device enrolled, press [*] to overwrite the zone or [#] to enter
another zone number.
accept the zone type or enter:
Device TypeZone Definition
2 Door/Window Contact[01] Delay 1
3 PIR or Glassbreak[05] Interior, Stay-Away
4 Smoke Detector[88] Standard 24 Hr Fire (Wireless)
5 Pendant[16] 24 Hour Panic
8 CO Detector[81] 24 Hour CO Detection
✱ ] to accept. The next available zone is preloaded.
✱ ] to
5
PowerSeries - PC1616/PC1832/PC1864
Chapter 2 User Commands
Any system keypad can be used to program or perform any keypad command. LED keypads use status and zone indicator lights to represent
alarm functions and status. The LCD keypad displays the description and status indicator lights represent alarm functions and status. This section
describes basic keypad commands.
Press the [#] key to reset the keypad if an error has been made entering user codes or keypad commands.
2.1 Away Arming
The Ready light must be ON to arm the system. If the Ready light is OFF, ensure that all protected doors and windows are secure or
bypassed. To arm the system in the Away mode, either press and hold the Away function button for 2 seconds or enter a valid user code and
leave the premises through a door programmed as Delay. Upon arming, the Armed light will turn ON. If a user code was used to arm the system and Stay/Away zones are programmed, the Bypass light will turn ON and will turn OFF when a door programmed as Delay is violated.
If the Audible Exit Delay option is enabled, the keypad will beep once every second during the exit delay (and three times a second during
the last 10 seconds) to prompt the user to leave.
2.2 Stay Arming
The Ready light must be ON to arm the system. If the Ready light is OFF, ensure that all protected doors and windows are secure or
bypassed. To arm the system in the Stay mode, either press and hold the Stay function button for 2 seconds or enter a valid user code and stay
within the premises (do NOT violate a door programmed as Delay). Upon arming, the Armed light and Bypass light will turn ON. If the Stay
function button is used, the keypad will not beep during the exit delay. If a user code was used, the keypad will beep if the Audible Exit
Delay option is enabled.
2.3 Disarming
The user must enter through a door programmed as Delay. Upon entering, the keypad will emit a steady tone (and emit a pulsing tone during
the last 10 seconds of entry delay) to prompt the user to disarm the system. Enter a valid user code to disarm the system. If an alarm occurred
while the panel was armed, the Memory light and the zones that went into alarm will be flashing (LED keypad) or the keypad will display
‘Alarm in Memory’ (LCD keypad). Press the [#] key to return the keypad to the Ready state.
2.4 [] Commands
The following is a list of the [] commands available and a description of each:
Press [][1] to enter the bypass mode. If the Code Required for the Bypass option is enabled, enter a valid user code. The Bypass light will
flash. The keypad will turn ON the corresponding zone light to indicate a zone is bypassed. To bypass or unbypass a zone, enter the 2-digit
zone number. Once the correct zones are bypassed, press [#] to exit. The Bypass light will be ON if any zones are manually bypassed.
LCD Keypad
Press [][1] to enter the bypass mode. If the Code Required for the Bypass option is enabled, enter a valid user code. The keypad will display ‘Scroll to View Zones’. The keypad will display the programmed zone labels for the zones and include the letter ‘O’ in the bottom right
corner if the zone is violated, or the letter ‘B’ if the zone is bypassed. Scroll to the appropriate zone and press the [] key to change the
bypass status (or enter the 2-digit zone number). Once the correct zones are bypassed, press [#] to exit.
Additional Bypass Commands:
Bypass Recall:Press [99]. The keypad will recall the last group of zones that were bypassed
Clear Bypass:Press [00]. The keypad will clear the bypass on all zones.
Save Bypass:Press [95]. The keypad will save which zones are manually bypassed.
Recall Save:Press [91]. The keypad will recall the bypassed zones that were saved.
Hold-up Zones cannot be assigned to bypass groups.
Re-activate Stay/Away Zones: Press [][1] when the system is armed in the Stay mode to change the armed status to Away mode. The
system will add the Stay/Away zones back into the system after the exit delay time expires.
6
Chapter 2 User Commands
[][2] Trouble Display
Refer to Appendix D – Troubleshooting Guide, for troubleshooting assistance and a detailed description of all trouble conditions.
When powering up the system for the first time, or in the event of a loss of power (including battery removal), a Loss of Clock trouble will
appear on the display. Press [8] on any keypad or [
] on any PK series keypad to access the time and date programming menu.
[][3] Alarm Memory Display
The Memory light will be ON if an alarm occurred during the last armed period. Press [][3]. The Memory light will flash and the keypad
will display the zones that went into alarm.
To clear the Memory light, arm then disarm the system.
[][4] Door Chime Enable/Disable
Press [][4]. The keypad will emit 3 rapid beeps if the door chime feature is now enabled and a steady 2-second tone if it is now disabled.
The same function can be performed by pressing and holding the Chime function button for 2 seconds.
[][5] Program User Codes
The following table identifies available user codes:
CodeTypeFunction
[01]-[39], [41]-[95]General User CodesArm, disarm
[40]Master CodeAll functions
Programming User Codes:
LED Keypad:
Press [][5] followed by the Master Code. The Program light will flash. The keypad will turn ON the corresponding zone lights to indicate if
any user codes are programmed. To add or change a user code, enter the 2-digit user code to be programmed. The zone light will flash. Enter
a new 4 or 6-digit user code or press [
the user code will stop flashing. To add or change another user code, enter the 2-digit user code to be programmed or press [#] to exit.
LCD Keypad:
Press [][5] followed by the Master Code. The keypad will display the first user (user 01) and include the letter ‘P’ in the bottom, right corner if the user code is programmed. Scroll to the appropriate user and press the [] key to program the user (or enter the 2-digit user num-
ber). Enter a new 4 or 6-digit user code or press [] to delete the user code. After the user code is programmed or deleted, scroll to another
user or press [#] to exit.
] to delete the user code. After the user code is programmed or deleted, the zone light corresponding to
Programming Partition Assignment:
Press [][5] followed by the Master Code or Supervisor Code. Press [98] followed by the 2-digit user to change to the partition assignment.
The keypad will turn ON the corresponding zone light to indicate which partition(s) the user is assigned to. For example, if zone light 1 is
ON, the user is assigned to partition 1. To change the partition assignment, press the number corresponding to the partition. Once the correct
partitions are assigned to the user, press [#] to exit. To change the partition assignment for another user, press [98] followed by the 2-digit
user number. When finished, press [#] to exit.
Programming User Attributes:
Press [][5] followed by the Master Code or Supervisor Code. Press [99] followed by the 2-digit user to change to the user attributes. The
keypad will turn ON the corresponding zone light to indicate which attributes are assigned to the user.
Light [1]User can enter User Code Programming section with this code
Light [2]Duress Reporting Code is sent whenever this code is entered
Light [3]User can manually bypass zones
Light [4]User can access the Escort5580 module remotely
Light [5]For Future Use
Light [6]For Future Use
Light [7]The panel will squawk when the user arms/disarms
Light [8]One-time use code – Can disarm the system once per day and is reset at midnight.
To change the user attributes, press the number corresponding to the attribute. Once the correct attributes are assigned to the user, press [
exit. To change the user attributes for another user, press [99] followed by the 2-digit user number. When finished, press [
#] to exit.
#] to
7
PowerSeries - PC1616/PC1832/PC1864
[][6] User Functions
Press [][6] followed by the Master Code, then press the number corresponding to the following functions:
[1]
[2]
[3]
[4]
[5]
[6]
[7] -[8]
Program Time and Date:
twenty-four-hour system (e.g., 8:00 PM = 2000 hours).
Auto-arm/Auto-disarm Enable/Disable:
steady 2-second tone if it is now disabled.
Auto-arm Time/Day:
time (HH:MM). Program the time using the twenty-four-hour system (e.g., 8:00 PM = 2000 hours).
System Test:
test the backup battery and transmit a reporting code to the central station (if programmed).
Enable DLS: The panel will temporarily enable DLS for 1 or 6 hours depending on programming (see Sect [702] opt.[7]).
User Initiated DLS:
For Future Use
The panel will perform the following: activate the bell output, keypad buzzer and all keypad status lights for 2 seconds,
If using LCD keypads, scroll to the desired option then press [].
Enter the time and date using the following format [HH:MM] [MM/DD/YY]. Program the time using the
The keypad will emit 3 rapid beeps if the Auto-arm/Auto-disarm feature is now enabled and a
Press the number corresponding to the day of the week (1=Sunday, 2=Monday etc.) followed by the auto- arm
The panel will attempt to call the DLS computer.
Additional Alphanumeric Keypad Functions:
When scrolling through the list of available functions, the following additional functions are available:
Event Buffer:Used to view the 500-event panel log
Brightness Control:Used to adjust the display backlighting level for optimal viewing
Contrast Control:Used to adjust the display contrast level for optimal viewing
Buzzer Control:Used to adjust the keypad buzzer tone for optimal sound
[][7][x] Command Output (1-4)
Press [][7][x]. If the Command Output Code Required option is enabled, enter a valid user code. The panel will activate any PGM output
assigned to the command output.
[][8] Installer Programming
Press [][8] followed by the Installer Code to enter Installer Programming. Refer to the ‘How to Program’ section for more information.
[][9][User Code] No-Entry Arming
Press [][9] followed by a valid user code. The system will arm in the Stay mode, and after the exit delay expires, it will remove entry delay.
All zones programmed as Delay will function like Instant zones. The system will flash the Armed light to indicate that the system is armed
with no entry delay.
[][0] Quick Arm/Quick Exit
Quick Arm: When disarmed, press [][0] to arm the system. The system will arm as if a valid user code was entered.
Quick Exit: When armed, press [][0] to activate Quick Exit. The system will allow a single zone programmed as Delay to be violated a
single time during the following 2-minute time period without changing the status of the system.
2.5 Function Keys
Keypads have 5 programmable one-touch function buttons located in a column down the right side of the keypad. These buttons can also be
activated by pressing and holding numbers [1] through [5] respectively for 2 seconds. The default for these function buttons on the PK series
keypads are as follows:
[1] Stay Arm
[2] Away Arm
[3] Chime Enable/Disable
[4] Fire Reset – Command Output 2
[5] Quick Exit
8
Chapter 3 Programming
Chapter 3 Programming
This chapter provides the information necessary to program all the features required for a basic system, as well as common applications.
3.1 Template Programming
Selecting [][8] [Installer Code] [899] displays the current 5-digit template programming code. Refer to Appendix E - Template Programming for
a detailed description of available templates and corresponding 5-digit codes. After entering a valid 5-digit template programming code, you will
be prompted to enter the following in the sequence indicated below:
This feature requires a PK55xx or RFK55xx series keypad, v.1.1 or higher.
1.Central Station Telephone Number, enter 32-Character Telephone number
Program the required Central Station phone number. Press [#] to complete your entry if less than 32 digits. This phone number will be
entered into the programming option [301].
2.Central Station Account Code, enter 6-digit code
Program the required Central Station Account Code. Press [#] to complete your entry if less than 6 digits. This account code will be entered
into the programming option [310].
3.Partition Account Code, enter 4-digit code
This programming section will only be prompted if Contact ID has been selected as a communications format. Program the required Partition Account Code. This Partition account code will be entered into the programming option [311].
4.DLS Access Code, enter 6-digit code
Program the required DLS Access Code. Press [#] to complete your entry if less than 6 digits. This access code will be entered into the programming option [403].
5.Partition 1 Entry Delay 1, Partition 1 Exit Delay, enter each 3-digit delay time
Program the desired 3-digit Partition 1 Entry Delay (in seconds) followed by the desired 3-digit Partition 1 Exit Delay (in seconds). These
values will be entered in [005] > [01], entries 1 and 3, respectively.
6.Installer Code
Enter the required 4- or 6-digit access code installer access code (dependent on [701], entry 5). This Installer Access Code will be entered in
[006]. After the installer code has been programmed the keypad will return to the base installer programming menu.
All template programming information must be re-entered after performing a hardware or software panel default.
3.2 DLS Programming
3.2.1 Local Programming:
Follow the steps below in the sequence indicated to set up local programming using DLS:
1.Initiate downloading using the DLS software.
2.Connect an RS-232 to PC-Link Cable between the Computer with DLS Software installed and the alarm panel to be programmed.
Connecting the DLS PC to the panel will automatically initiate the connection.
3.2.2 Remote Programming (via telephone line):
Refer to Section [401] on page 22 for details.
The panel battery voltage can be monitored with DLS software. After the panel information has uploaded,
battery voltage can be viewed in the DLS session window.
3.3 Advanced Keypad Programming
DSC recommends filling in the Programming Worksheet with the required information before programming the system. This will reduce the
time required to program and will help eliminate errors.
To enter Installer Programming press [][8][Installer Code]. The Program light will flash (programmable LCD keypad displays will change
to ‘Enter Section’). An error tone indicates the installer code entered is incorrect. Press [#] to clear any key presses and try again.
The default Installer Code is [5555].
The Armed and Ready lights indicate programming status:
Armed Light OnPanel waiting for 3-digit section number
If in module programming, waiting for section # to be entered
Ready Light OnPanel waiting for data to be entered
Ready Light FlashingPanel waiting for HEX data to be entered
You cannot enter Installer Programming while the system or any partition is armed or in alarm.
9
PowerSeries - PC1616/PC1832/PC1864
3.3.1 Programming Toggle Options:
Enter the 3-digit programming section number:
• The Armed light will turn OFF and
• The Ready light will turn ON.
• The keypad will display which toggle options are ON or OFF
according to the chart.
• To toggle an option ON or OFF , press the corresponding num-
ber on the keypad. The display will change accordingly.
Keypad TypeOption ONOption OFF
LED Zone Light ONZone Light OFF
Fixed-Message LCD Indicator # ONIndicator # OFF
Programmable-Message LCD # DisplayedDash [-]
Displayed
• When all the toggle options are configured correctly, press the [#] key to exit the program section.
• The Ready light will turn OFF and the Armed light will turn ON.
3.3.2 Programming Decimal and Hexadecimal (HEX) Data:
• Enter the 3-digit programming section number.
• The Armed light will turn OFF and the Ready light will turn ON.
• Enter the data written in the boxes.
For sections that require multiple 2- or 3-digit numbers, the keypad will beep twice after each 2- or 3-digit entry and move to the next item in
the list. After the last digit in the section is entered, the keypad will beep rapidly 5 time s and exit the program section. The Ready light will
turn OFF and the Armed light will turn ON.
For sections that do not require data for every box (such as phone numbers), press the [#] key to exit the program section after entering all the
required data. The Ready light will turn OFF and the Armed light will turn ON.
At any time the [#] key can be pressed to exit any program section. All changes made up to that point will be saved.
HEX (or hexadecimal) digits are sometimes required. To enter a HEX digit, press the
,] key to begin HEX programming. The Ready light will flash.
[
Refer to the following chart and press the number corresponding to the HEX digit
required. The Ready light will continue to flash. Press [
,] again to return to normal
decimal programming. The Ready light will turn ON.
Not Supported
Simulated [,] key
Simulated [#] key
Dial tone search
Two second pause
End of Number
In addition to the standard digits 0-9, HEX digits and special dialer functions can also be programmed.
3.3.3 How to Exit Installer Programming:
To exit installer programming, press the [#] key when the panel is waiting for a 3-digit section number (the Armed light is ON).
3.3.4 Viewing Programming
LED and LCD5501Z Keypads
Any programming section can be viewed from an LED or LCD5501Z
keypad. When a programming section is entered, the keypad will immediately display the first digit of information programmed in that section.
The keypad displays the information using a binary format, according to
the following chart:
Press any of the Emergency keys (Fire, Auxiliary or Panic) to advance to
the next digit.
When all the digits in a section have been viewed, the panel will exit the section. The Ready light will turn OFF, and the Armed light
will turn ON. The system is now waiting for the next 3-digit programming section number to be entered. Press the [#] key to exit the
section.
LCD Keypad
The keypad will immediately display all the information programmed when a programming section is entered. Use the arrow keys (< >) to
scroll through the data being displayed. Scroll past the end of the data displayed or press the [#] key to exit the section.
10
Chapter 4 Programming Descriptions
Chapter 4 Programming Descriptions
The following is a brief description of the features and options available in the Power PC1616/1832/1864 control panel. Please refer to the keypad
installation sheet for function key programming.
Global Stay Arming
If enabled by the installer, when this function key is pressed the panel will prompt the user for an access code. The panel will arm all partitions
assigned to that access code in Stay Mode when exit delay expires. If a partition was armed in Away mode when the Global Stay Arming key is
pressed, that partition will switch armed status to Stay when the delay expires. The Force arm attribute must be enabled on Entry/Exit points for
this feature.
Global Away Arming
If enabled by the installer, when this function key is pressed the panel will prompt the user for an access code. The panel will arm all partitions
assigned to that access code in Away Mode when exit delay expires. If a partition was armed in Stay mode when the Global Away Arming key is
pressed, that partition will switch armed status to Away when the delay expires. The Force arm attribute must be enabled on Entry/Exit points for this
feature.
Global Disarming
If enabled by the installer, when this function key is pressed the panel will prompt the user for an access code. The panel will then disarm all partitions assigned to that access code.
[001] to [004] Zone Definitions
Option Description
[00]
Null Zone: Zone not used
[01]
Delay 1: When armed, provides entry delay when violated (follows Entry Delay 1)
[02]
Delay 2: When armed, provides entry delay when violated (follows Entry Delay 2)
[03]
Instant: When armed, instant alarm when violated
[04]
Interior
[05]
Interior Stay/Away: Similar to ‘Interior’ except that panel will auto-bypass the zone if Armed in the Stay mode
[06]
Delay Stay/Away: Similar to ‘Delay 1’ except that panel will auto-bypass the zone if Armed in the Stay mode
[07]
Delayed 24-Hour Fire (Hardwire): Instant audible alarm when violated, communication is delayed 30 seconds. If alarm is acknowl-
edged during this time (by pressing a key), the alarm will be silenced 90 seconds and will repeat the cycle. If not, alarm will latch and
communicate after a 30-second delay
[08]
Standard 24-Hour Fire (Hardwire): Instant alarm and communication when violated
[09]
24-Hr Supervision (Hardwire): Instant alarm and communication when violated. Will not sound the bell or keypad buzzer
[10]
24-Hr Supervisory Buzzer: Instant alarm, panel will activate keypad buzzer instead of bell output
[11]
24-Hr Burglary: Instant alarm when violated, audible alarm at default. Reporting code BA, BH
[12]
24-Hr Hold-up: Instant alarm when violated, silent alarm at default. Reporting code HA, HH
[13]
24-Hr Gas: Instant alarm when violated, audible alarm at default. Reporting code GA, GH
[14]
24-Hr Heat: Instant alarm when violated, audible alarm at default (also known as high-temp). Reporting code KA, KH
[15]
24-Hr Auxiliary (Medical): Instant alarm when violated, silent alarm at default. Reporting code MA, MH
[16]
24-Hr Panic: Instant alarm when violated, audible alarm at default. Reporting code PA, PH
[17]
24-Hr Emergency: Instant alarm when violated, audible alarm at default. Reporting code QA, QH
[18]
24-Hr Sprinkler: Instant alarm when violated, audible alarm at default. Reporting code SA, SH
[19]
24-hr Water: Instant alarm when violated, audible alarm at default (also known as high water level). Reporting code WA, WH
[20]
24-Hour Freeze: Instant alarm when violated, audible alarm at default (also known as low-temp). Reporting code ZA, ZH
[21]
24-Hr Latching Tamper: Instant alarm when violated, panel cannot be armed until Installer Programming is entered
[22]
Momentary Keyswitch Arm: Arm or disarm the system when violated
[23]
Maintained Keyswitch Arm: Arm system when violated, disarm system when restored
[24]For Future Use
[25]
Interior/Delay: Zone will function as an Interior zone when armed in Away mode, and as a Delay zone when armed in Stay mode
[26]
24-Hr Non-Alarm: Zone will NOT create an alarm. Can be used with zone follower function for automation applications
[29]
Auto-Verified Fire: When violated, system will reset all smoke detectors for 20 seconds, then wait 10 seconds for detectors to settle.
If another fire alarm is detected within 60 seconds, the zone will go into alarm immediately
: When armed, instant alarm will sound first if the zone is violated; instant alarm will follow the entry delay if entry delay is active
11
PowerSeries - PC1616/PC1832/PC1864
[30]
Fire Supervisory: Instant alarm, system will activate keypad buzzer. A valid user code is required to silence keypad buzzer
[31]
Day Zone: Instant alarm when system is armed, keypad buzzer (no alarm) when system is disarmed
[32]
Instant Stay/Away: Similar to ‘Instant’ except panel will auto-bypass the zone if Armed in the Stay mode
[35]
24-Hr Bell/Buzzer: Instant alarm when violated, system will activate bell output if armed, keypad buzzer if disarmed
[36]
24-Hr Non-Latching Tamper Zone: Instant tamper condition when violated. Active in both the armed and disarmed state
[37]
Night Zone: Functions like Interior Stay/Away but will remain bypassed if the user presses [][1] to re-activate Stay/Away zones
when armed in the Stay mode
[41]
24 Hr. Carbon Monoxide: This zone type is used with a hardwired CO detector. This zone definition has a distinct bell cadence in the
event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then repeated.
After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is entered or the
bell times out (see your Carbon Monoxide instruction sheet for more details).
[81]
24 Hr. Carbon Monoxide (Wireless): This zone type is used with a wireless CO detector. This zone definition has a distinct bell
cadence in the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then
repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is
entered or the bell times out.
[87]
Delayed 24-Hour Fire (Wireless/Addressable): Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless or address-
able smoke detectors
[88]
Standard 24-Hour Fire (Wireless/Addressable): Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless or
addressable smoke detectors
[005] System Times
After entering Section [005], enter the 2-digit subsection number for the desired partition and program the Entry Delay 1, Entry Delay 2 and Exit
Delay for each active partition on the system. Valid entries are from [001] to [255] or [045] to [255] for SIA CP-01 panels (in seconds). Enter
subsection [09] to program the Bell Cut-Off Time. Valid entries are from [001] to [255] (in minutes).
[006] Installer Code
The default Installer Code is [5555] or [555555] if 6-Digit Access Codes is enabled.
[007] Master Code
The default Master Code is [1234] or [123456] if 6-digit Access Codes is enabled.
[008] Maintenance Code
The default Maintenance Code is [AAAA] (not programmed). This code can arm any partition, but cannot disarm unless the partition is in alarm.
[009] to [011] PGM Outputs
The PC1616 and PC1832 have two on-board PGM outputs (PGM1 and PGM2). The PC1864 has four on-board PGM outputs (PGM1 to
PGM4). The panel has the capacity for up to 14 PGM outputs (8 additional low-current PGM outputs with PC5208 module, 4 additional
high-current PGM outputs with a PC5204 module).
PGM Output Options:
Option Description
[00]
For Future Use
[01]
Fire and Burglary: Output will activate (steady for burglary, pulsing for fire) if an alarm occurs on the selected partition
[02]
For Future Use
[03]
Sensor Reset: Output will normally be active and deactivate for 5 seconds when a [][7][2] fire reset command is entered or when
Armed Status: Output will activate when all of the selected partitions are armed
[06]
Ready Status: Output will activate when all the selected partitions are in the Ready state (Ready light ON)
[07]
Keypad Buzzer Follow: Output will activate and follow the keypad buzzer for the selected partition when the following events
occur: entry delay, door chime, audible exit delay, automatic arming pre-alert, 24-hr Supervisory Buzzer zone alarm
[08]
Courtesy Pulse: Output will activate during entry/exit delay if the selected partition is armed, and will remain active for an addi-
tional 2 minutes after the entry or exit delay expires
[09]
System Trouble: Output will activate when any selected trouble condition is present
[10]
Latched System Event (Strobe): Output will activate when a selected condition occurs on any selected partition. Note output can
be programmed to follow timer
12
Chapter 4 Programming Descriptions
[11]
System Tamper: Output will activate when any tamper condition is present
[12]
TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13]
Kissoff: Output will activate for 2 seconds when a valid kissoff is received from the central station
[14]
Ground Start: Output will activate for 2 seconds when the panel attempts to seize the phone line (additional dial tone search must
be programmed in the central station phone number – HEX [D])
[15]
Remote Operation: Output can be activated/deactivated via the DLS software
[16]
For Future Use
[17]
Away Armed Status: Activates when all of the selected partitions are armed in Away mode
[18]
Stay Armed Status: Activates when all of the selected partitions are armed in Stay mode
[19]
Command Output 1: Activates when a [,][7][1] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[20]
Command Output 2: Activates when a [,][7][2] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[21]
Command Output 3: Activates when a [,][7][3] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[22]
Command Output 4: Activates when a [,][7][4] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[23]
Silent 24-Hour Input: Changes PGM to a 24-hr Silent zone (PGM2 only)
[24]
Audible 24-Hour Input: Changes PGM to a 24-hr Audible zone (PGM2 only)
[25]
Delayed Fire and Burglary: Functions as a Fire and Burglary output but does not activate until the TX Delay time expires
[26]
Battery Test Output: Output activates for 10 seconds at midnight each day.
[27]
For Future Use
[28]
Holdup Output: Activates when a Holdup Alarm occurs on any assigned partition. Remains active until all assigned partitions have
been armed or disarmed. Will not activate if a Holdup Zone goes into a fault or tamper condition.
[29]
Zone Follower (Zones 1-8):
[30]
Partition Status Alarm Memory: Activates if the selected partition is armed. Output will pulse “one second ON / one second OFF
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
if an alarm occurs
[31]
Alternate Communicator: Activates when selected system event occurs. If active in the armed state, it remains active until the sys-
tem is disarmed. If activated in the disarmed state, it remains active until a valid access code is entered within the bell cut-off time, or
when the system is armed after the bell cut-off time has expired.
[32]
For Future Use
[33]
For Future Use
[34]
Away Armed with no Zone Bypassed Status: Activates when armed with stay/away zones active and no zones bypassed.
[35]
Zone Follower (Zones 9-16): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[36]
Zone Follower (Zones 17-24): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[37]
Zone Follower (Zones 25-32): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[38]
Zone Follower (Zones 33-40): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[39]
Zone Follower (Zones 41-48): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[40]
Zone Follower (Zones 49-56): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[41]
Zone Follower (Zones 57-64): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
* See Section [501]-[514] Programmable Output Attributes, PGM Output Option [29] and [35]-[41] Option 8 on 24.
[012] Keypad Lockout
The system can be programmed to ‘lockout’ keypads if a series of incorrect user or installer codes are entered. When lockout is active, all
keypads emit a steady 2-second error tone when a key is pressed. Program the Number of Invalid Codes Before Lockout with the desired
number. Valid entries are from [000] to [255]. Program data [000] to disable the feature. Keypads will remain locked out for the number of
minutes programmed for the Lockout Duration. Valid entries are from [000] to [255].
13
PowerSeries - PC1616/PC1832/PC1864
[013] First System Option Code
OptionDescription
[1]ON: zones require normally-closed loops. OFF: zones require End-Of-Line resistors, as determined by option [2].
[2]ON: zones require double End-Of-Line resistors. OFF: zones require single End-Of-Line resistors.
[3]ON: keypads will display all trouble conditions while armed. OFF: keypads will only display fire trouble when armed. This option
must be OFF if LCD5500 v2.x (or older) keypads are used on the system.
[4]ON: only a trouble will be displayed. OFF: keypads will display a trouble and a zone violation if a tamper or fault is detected.
[5]ON: auto-arming schedules (Program Sections [181]-[188]) will be available to the user in the [][6] menu.
OFF: auto-arming schedules will not be available to the user in the [][6] menu.
[6]ON: the Audible Exit Fault feature will be enabled. If a delay zone is not secured correctly and not force-armed at the end of the exit
delay, the system will go into entry delay and turn ON the bell output. The bell will also sound if the delay zone is opened within 10
seconds of the exit delay timeout.
OFF: the keypad will sound the entry delay through the keypad as per usual.
[7]ON: the system will NOT log additional alarms for a zone that has reached the swinger shutdown threshold.
OFF: all zone alarms will be logged.
[8]ON: Temporal Three Fire Signal is used to sound fire alarms (½ second ON, ½ second OFF, ½ second ON, ½ second OFF ½ second
ON, 1 ½ seconds OFF).
OFF: the system will pulse the bell output (½ second ON, ½ second OFF).
[014] Second System Option Code
OptionDescription
[1]ON: the system squawks the bell output once when a partition is armed, twice when disarmed.
OFF: the bell output does not activate. Refer to section [017] option 8.
[2]ON: the system squawks the bell output every 10 seconds during the auto-arm pre-alert.
OFF: the bell output does not activate.
[3]ON: the system will squawk the bell output once every second during Exit Delay, 3 squawks per second for the last 10s.
OFF: the bell output will not activate.
[4]ON: the system will squawk the bell output once every second during Entry Delay, 3 squawks per second for the last 10s.
OFF: the bell output will not activate.
[5]ON: the system squawks the bell output once every 10 seconds when a trouble condition is present.
OFF: the bell output does not activate.
[6]ON: the system will beep the keypads once every second, and 3 times a second over the last 10 seconds, during an exit delay when
the system is armed with a user code or armed in the Away mode.
OFF: the keypads will not beep.
[7]ON: the exit delay will be terminated (reduced to 5 seconds) when a Delay 1 zone is violated and restored after the system is armed.
OFF: the exit delay will count down as normal.
[8]ON: the bell output will not timeout if a fire alarm occurs. The user must turn OFF the bell by entering a valid user code.
OFF: the bell output will timeout normally.
[015] Third System Option Code
OptionDescription
[1]ON: the keypad fire emergency key will be enabled. OFF: the keypad fire emergency key will be disabled.
[2]ON: the keypad Panic emergency will be audible (bell output). OFF: the Panic emergency key will be silent.
[3]ON: the Quick Exit feature will be enabled. OFF: the Quick Exit feature will be disabled.
[4]
ON: the Quick Arming [
If this feature is disabled, a valid user code must be entered after the Stay or Away function buttons are pressed.
[5]
ON: a valid user code must be entered after pressing [
[6]ON: the Master Code (user code 40) can only be changed in Installer Programming.
OFF: the Master Code can be changed using the User Programming [
[7]ON: the system supervises the telephone line and displays a trouble if disconnected.
OFF: the telephone line is not supervised.
[8]ON: the system activates the bell output if a telephone line trouble is detected while the system is armed.
OFF: the system activates the keypad buzzer trouble tone.
][0] feature will be enabled. OFF: Quick Arming [][0] feature will be disabled.
][1] to access the Bypass feature. OFF: user code is not required.
][5] command.
14
Chapter 4 Programming Descriptions
[016] Fourth System Option Code
Option Description
[1]ON: the system supervises the AC input and displays a trouble if a failure is detected. OFF: AC Input is not supervised.
[2]ON: the trouble light will flash when an AC trouble is detected. OFF: the trouble light turns on, does not flash.
[3]ON: the keypad blanks (no indicator lights) if a key is not pressed for 30 seconds. OFF: the keypad does not blank.
ON: a valid user code must be entered to restore normal keypad operation after the blanking.
[4]
OFF: pressing any key will return the keypad to normal operation.
ON: the system temporarily enables the Keypad Blanking feature if an AC failure is detected (to preserve the back-up battery).
[6]
OFF: the system will operate as normal.
ON: the keypad turns ON the Bypass light if zones are bypassed while the system is armed.
[7]
OFF: the Bypass light turns OFF when the system is armed.
[8]ON: the system supervises keypad tampers. OFF: the system does not supervise keypad tampers.
[017] Fifth System Option Code
Option Description
[1]ON: the system does NOT associate wireless keys to user codes.
OFF: the system will assign user code 17 to wireless key #01, user code 18 to wireless key #02 etc. If the wireless key is used to arm
or disarm, the system will report the Opening or Closing for the associated User Code.
[2]ON: the system logs an RF Jam trouble condition if the condition is present for 5 minutes.
OFF: the system logs the trouble condition after 30 seconds.
[3]ON: the keypads beep if an RF Jam trouble is detected.
OFF: the trouble is not announced via the keypad buzzer.
[4]ON: the Double Hit feature will be enabled. Two violations from the same zone within the Cross Zone Timer will be considered a
valid Police Code or Cross Zone event. The system will report the event and log it to the event buffer.
OFF: two alarms from the same zone is not a valid Police Code or Cross Zone event.
[5]ON: the system logs and communicates a Late-To-Close event when the auto-arm time comes, but the function has been disabled
(not if auto-arming was caused by the No-Activity Arming feature).
OFF: the system does not transmit or log a Late-To-Close event.
[6]ON: enables the Daylight Savings automatic clock adjustment feature.
OFF: the system does not automatically adjust the clock for Daylight Savings.
[7]For Future Use
[8]ON: the system only squawks the bell output when the system is armed in the Away mode.
OFF: the system squawks the siren when the system is armed in any mode. (See Section [14], Option [1]).
[018] Sixth System Option Code
Option Description
[1]ON: the system only transmits a Test Transmission reporting code if no other event was transmitted to the central station during t
programmed time.
OFF: the system always transmits a Test Transmission reporting code as programmed.
[2]-[4]For Future Use
[5]ON: the keypad buzzer follows the bell output for all alarms.
OFF: the system only activates the bell output for all alarms.
[6]ON: When an alarm is detected on a zone (with the Cross Zone attribute enabled), a timer is started. The alarm is not transmitted and
the bell output is not activated unless a second cross zone enabled zone is violated before the Cross Zone timer times out.
OFF: the system reports all alarms normally and logs and transmits a Police Code reporting code if a second zone alarm is detected
during the armed period.
[7]ON: The system restarts the Exit Delay (one time) if a Delay zone is violated and restored during the exit delay time.
OFF: The Exit Delay does not restart.
[8]ON: The system activates the trouble beeps when an AC trouble is detected.
OFF: the system does not announce AC troubles using the keypad buzzer.
15
he
PowerSeries - PC1616/PC1832/PC1864
[019] Seventh System Option Code
Option Description
[1]For Future Use
[2]For Future Use
[3]ON: When disarming, the keypad will display only the first alarm to occur during the last arming period.
OFF: When disarming, the keypad will display all zones that were in alarm during the last arming period
[4]-[5]For Future Use
[6]ON: the green LED indicator on the keypads indicate the status of AC on the system
OFF: the green LED indicator on the keypads indicate the partition ready status
[7]ON: All user access codes can enter the User Functions menu.
OFF: Only the Master Code can enter the User Functions menu.
[8]For Future Use
[020] Keypad Zone Assignment
Enter the two-digit zone number to be assigned to each keypad assigned to a specific slot. Only one keypad can be assigned to a specific slot.
See Keypad Assignment. Valid entries are from [00] to [64].
[021] Eighth System Option Code
Option Description
[1]ON: Access codes will not be accepted by the system during entry delay.
OFF: An access code can be used to disarm the system during entry delay
[2]-[5]For Future Use
[6]ON: Key-switches and wireless keys can only disarm the system during an entry delay
OFF: Key-switches and wireless keys can disarm the system regardless if entry delay is active or not.
[7]-[8]For Future Use
[022] Ninth System Option Code
OptionDescription
[1]
ON: An access code is required for access to the [][1], [][2], [][3] menus.
OFF: No access code is required for [][1], [][2], [][3] menu access.
[2]-[3]
For Future Use
[4]
ON: Only the Master code can be used to bypass a hold up zone.
OFF: Any valid access code can bypass a hold up zone.
[5]
For Future Use
[6]
ON: RF Delinquency Enabled, if any wireless zone supervisory transmission is not received by the PC5132 during a 15-minute period,
the PC5132 will place the panel into Not Ready To Arm mode. In the armed state, the Zone faults will generate tamper alarms. The panel
will generate a silent trouble (NO trouble beeps but the Trouble LED is turned ON) called “RF Device Delinquency”, which is only
viewable in [][2] (Trouble Menu). The user can override the condition and arm the panel by using the feature.
OFF: RF Delinquency Disabled, the system will not indicate an RF Delinquency when a zone supervisory transmission is not
received during a 15 minute period.
[7]
Future Use
[8]
ON: When the system is armed in Stay mode, during the Exit delay, the system will sound one beep every 3 seconds.
OFF: When the system is armed in Stay mode, the system will be silent during the Exit delay.
[023] Tenth System Option Code
OptionDescription
[1]
ON: the keypad [F] emergency key will only beep three times to acknowledge that the button has been pressed. The system will not activate the bell output. OFF: the system will activate the bell output and beep the keypad.
[2]
For Future Use
[3]
ON: the system will only transmit the Test Transmission reporting code if the system is armed at the time the system is programmed to report the event. OFF: the system will always report the Test Transmission reporting code at the programmed time.
[4]
ON: the system changes the Test Transmission Reporting Cycle Time from Days to Hours.
OFF: the Test Transmission Reporting Cycle Time is in Days.
16
Chapter 4 Programming Descriptions
[5]
ON: the user cannot switch from Away Arm mode to Stay Arm mode using the function keys.
OFF: the user can switch arming modes.
[6]
ON: the system disconnects a listen in/two-way session if a new event occurs.
OFF: the system does NOT disconnect. New events are transmitted only after the session is terminated.
[7]
ON: the system does NOT activate the keypad buzzer for any trouble condition (excluding Fire Troubles).
OFF: the system announces troubles via the keypad buzzer (two beeps every 10 seconds).
[8]
ON: Keyswitches will always arm in Away mode.
OFF: Keyswitches will arm in Away mode if an entry/exit zone is violated during exit delay.
[030] Fast Loop Response
This section is used to determine the Loop Response Time for the main panel zones.
ON: the loop response time will be 36 ms. OFF: the loop response time will be 400 ms.
[101] to [164] Zone Attributes
These sections are used to customize the operation of the zones. There are 9 toggle options in each section:
OptionDescription
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]-[13]
[14]
[15]
[16]
Options [14], [15], [16] apply to first 8 zones only. If more than one of these options are enabled then lowest numbered option is enabled. E.g.,
If Option [14] and option [15] are enabled then the zones are configured as normally closed loops.
ON: alarms are audible (bell output).
OFF: alarms are silent.
ON: the bell output is steady (burglary).
OFF: the alarm output pulses (fire).
ON: a zone violation or restoral will activate Chime.
OFF: Chime is not activated.
ON: the user can manually bypass the zone using the [][1] command.
OFF: the zone cannot be manually bypassed.
ON: the partition can be armed even if the zone is violated (the zone will not affect the Ready status).
OFF: the zone must be secure before arming.
ON: the system shuts down alarm reporting after the programmed number of alarms have occurred.
OFF: the panel will always report the event if an alarm occurs.
ON: the system delays reporting the event for the time programmed for the Transmission Delay time.
OFF: the panel immediately transmits the reporting event when an alarm is detected.
ON: the zone is a wireless or addressable device.
OFF: the zone is a hardwire zone (main panel, zone expander or keypad zone).
ON: the zone has the Cross Zone feature enabled.
OFF: the zone functions normally.
For Future Use
ON: the zone requires a normally-closed loop
OFF: the zone will follow the EOL configuration in [013]
ON: the zone requires a single End-of-Line resistor
OFF: the zone will follow the EOL configuration in [013]
ON: the zone requires double End-of-Line resistors
OFF: the zone will follow the EOL configuration in [013]
Keypad zones and zone expanders will always follow [013].
When Zone Types ([001] to [004]) are programmed, the system will change the Zone Attributes to those found in the chart included in the
Programming Worksheets. The Zone Attributes will default if a new Zone Type is programmed for a specific zone. After programming the Zone
Types, enter
[101] to [164] and ensure that all options are programmed correctly.
Ready light ON:Program attributes [1-8] (press [1]-[8] to turn option ON or OFF)
Ready light and Armed light ON:Program attributes [9-16] (press [1]-[8] to turn option ON or OFF)
Press [9] to switch between attributes [1-8] and attribute [9-16].
[165] Maximum Dialing Attempts
Program the Maximum Dialing Attempts before the panel will generate a Failure to Communicate (FTC) trouble condition.
Valid entries are
[001] to [005]. For UL Listed installations, 5 attempts is required.
17
PowerSeries - PC1616/PC1832/PC1864
[166] Post Dial Wait for Handshake
Program the maximum time the panel will wait, after dialing, for a valid handshake from the central station.
Valid entries are
[001] to [255] seconds.
[167] TL/GS Module Wait for Acknowledgement
Program the maximum time the panel will wait, after sending a data packet, for an acknowledgement from the central station.
Valid entries are
Do not program this section with a value less than 60.
[060] to [255] seconds.
[168] Daylight Saving Time (Move Clock Ahead)
This option is used to program the Date, Time and Increment that the clock will move ahead for Daylight Savings Time each year. Programming can be accomplished by programming the Month, Day, Hour and Increment or Month, Week, Day of Week, Hour and Increment:
Month:
Week:
Increment:
Data [001] to [012] represents January to December.
Data [000] indicates that the day of the month will be programmed in the Day section below . Data [001] to [005] repr esents weeks 1
to 5 of the month. Week 5 always represents the last week in the month, regardless if the number of weeks in the month is 4 or 5.
Day:
Data [001] to [031] represents day of the month if [000] was programmed in the Week section above. If [001] to [005] was
programmed in the Week Section above, then Data [000] to [006] represents Sunday to Saturday
Hour:
Data [000] to [022] represents the hour that Daylight Saving Time will take effect.
Data [001] to [002] represents the number of hours to advance the clock for Daylight Savings Time.
Do not program the Hour outside of the valid range or the time will no t change. Do not program the value of the Increment to be greater
then the number of hours remaining in the current day.
[169] Standard Time (Set Clock Back)
This option is used to program the Date, Time, and Increment that the clock will move back for Standard Time each year. Programming can
be accomplished by programming the Month, Day, Hour, and Increment or Month, Week, Day of Week, Hour, and Increment:
Month:
Week:
Increment:
Data [001] to [012] represents January to December.
Data [000] indicates that the day of the month will be programmed in the Day section below . Data [001] to [005] repr esents weeks 1
to 5 of the month. Week 5 always represents the last week in the month, regardless if the number of weeks in the month is 4 or 5.
Day:
Data [001] to [031] represents day of the month if [000] was programmed in the Week section above. If [001] to [005] was
programmed in the Week section above, then Data [000] to [006] represents Sunday to Saturday.
Hour:
Data [000] or [023] represents the hour that Standard Time will take effect.
Data [001] or [002] represents the number of hours to roll back the clock for Daylight Saving Time.
[170] PGM Output Timer
Program the amount of time, in seconds, that the PGM Output Timer will be active. Valid entries are [001] to [255].
[171] Tamper PGM Output Timer
Program the amount of time, in minutes, that a tamper condition will latch the Tamper PGM output. Valid entries are [000] to [255].
[175] Auto-arm Postpone Timer
Program the amount of time, in minutes, that the system will postpone automatic arming. When the programmed time has expired, the system will
attempt to auto-arm again. If data [000] is programmed, the system will instead abort the auto-arm sequence. Valid entries are [001] to [255].
[176] Cross Zone/Police Code Timer
Program the amount of time in seconds (Cross Zone), or minutes (Police Code), that the panel will use to determine if a Cross Zone or Police
Code event has occurred. If data [000] is programmed when using the Police Code feature, and if any two zones go into alarm during any armedto-armed period, the panel will generate a Police Code event. Valid entries are [001] to [255].
[181] to [188] Auto-arm Schedules
Program the amount of time to auto-arm ([181] for partition 1, [182] for partition 2, etc.) for each day of th e week. Each opti on has seven, 4-digit
entries: two digits for the hour, two digits for the minute, Sunday through Saturday. Program using the twenty-four-hour system (for example, to
auto-arm at 8:00 pm, program data [20][00]). Valid entries are [00][00] to [23][59]. Program [99][99] to disable auto-arming.
[190] No Activity Arming Pre-Alert Duration
Program the amount of time, in minutes, for the No Activity Arming Pre-Alert Duration. The keypads will emit a steady tone, warning the user
that the system is about to arm. The user can either violate a zone or press any key to abort the arming sequence. Valid entries are [000] to [255].
18
Chapter 4 Programming Descriptions
[191] to [198] No Activity Arm Timer
Program the amount of time, in minutes, for the No Activity Arm Timer ([191] for Partition 1, [192] for Partition 2, etc.). If Delay Zones are
restored and no zone activity is detected for the time programmed, the system will start the auto-arm sequence. Valid entries are [000]-[255].
[199] Auto-Arming Pre-alert Timer
Program the amount of time, in minutes, for the Auto-Arming Pre-Alert T ime. This timer is used fo r all p rogrammed auto-arming features (is not
used for No Activity Arming). The keypads will provide a steady tone, warning the user that the system will arm. The user can enter a valid
access code to abort the arming sequence. Valid entries are [001] to [255].
[201] Partition Selection Mask
Turn the corresponding option ON to enable partitions [1] to [8]. ON (bit 1 cannot be turned OFF).
[202] to [265] Partition Zone Assignments
These options are used to assign zones to specific partitions ([202] to [209] for Partition 1, [210] to [217] for Partition 2, etc.). Turn ON the
option corresponding to the partition and zone to enable the zone on the specified partition. Turn the option OFF to disable the zone on the
specified partition. Zones assigned to more than one partition are called ‘common zones’ and will be armed only if all the partitions the zone
is assigned to are armed. Default = Zones 1-8 enabled on Partition 1.
[301] First Telephone Numbers
The information in this section also applies to sections [302] and [303]. Telephone number 3 is dedicated as a back-up to Te lephone number
1. These sections determine which type of communicator is activated in the event of an alarm (telephone, GPRS and Ethernet) and the
sequence that the system follows in the event of an unsuccessful communication.
• Entry of [D] followed by a [Telephone Number] terminated with “F” configures the section for telephone dialing.
E.g.: [D12223334444F]
• Entry of [D] followed by [CAA] terminated with “F” allows the system configuration to be determined by the GPRS/Ethernet module.
E.g.: [DCAAF]
• Enter [DCBBF] to configure the section for Ethernet Receiver 1
• Enter [DCCCF] to configure the section for Ethernet Receiver 2
• Enter [DCDDF] to configure the section for GPRS Receiver 1
• Enter [DCEEF] to configure the section for GPRS Receiver 2
Please refer to Section [350] Communicator Formats, only SIA and Contact ID are valid alternate communicator formats.
Programming any other format will send SIA by default.
Please refer to your associated communicator manual for more details.
Telephone Communications
All telephone number sections are 32 digits in length. Hexadecimal digits may be programmed in the telephone number to perform additional functions as follows:
• Enter [,][2][,] – HEX B to dial “,”
• Enter [,][3][,] – HEX C to dial “#”
• Enter [
• Enter [,][5][,] – HEX E to insert a 2-second pause in the telephone number.
• HEX A is not used.
• HEX F represents the end of the phone number (everything after F is ignored).
• Pressing [#] in these sections will exit and save the entire phone number.
• The panel will not attempt to communicate, if no phone number is programmed. This applies to phone numbers 1 and 2.
,][4][,] – HEX D for an additional dial tone search, as is required for PBX telephone systems
There is an automatic 2-second pause before additional dial tone searches are initiated.
[302] Second Telephone Number
See [301] First Telephone Number for details.
[303] Third Telephone Number
See [301] First Telephone Number for details.
[304] Call Waiting Cancel String
Program the digits required to disable call waiting. If enabled, the system will dial the programmed string on the first dialing attempt.
Program unused digits with data [F].
19
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.