Drolet ALASKA 2000 User Manual

INSTALLATION AND
OPERATING MANUAL
OIL BURNING STOVE
ALASKA 2000
Vérified and tested following
CAN/CSA B140.3 et UL 896 standards by:
Fabricated by:
1700 Léon-Harmel Québec, (Québec)
G1N 4R9

READ THESE INSTRUCTIONS AND SAVE FOR REFERENCE

990830/45004A

TABLE OF CONTENT

TECHNICAL DATA.........................................................................................................................................1
INSTALLATION INSTRUCTIONS.................................................................................................................. 2
Locating the stove........................................................................................................................................2
Chimney informations...................................................................................................................................3
Connecting the stove to the chimney...........................................................................................................4
Leveling the unit...........................................................................................................................................5
Fixation of stove to floor...............................................................................................................................5
Connecting stove to oil tank.........................................................................................................................6
Adjusting the draught...................................................................................................................................7
Draught regulator .........................................................................................................................................7
OPERATION INSTRUCTIONS....................................................................................................................... 8
Combustible .................................................................................................................................................8
Lighting.........................................................................................................................................................8
Changing intensity........................................................................................................................................9
Turning the stove off...................................................................................................................................10
Maintenance...............................................................................................................................................10
Troubleshooting guide................................................................................................................................11
SPARE PARTS.............................................................................................................................................13
W A R R A N T Y...........................................................................................................................................15

TECHNICAL DATA

HIMALAYA OIL BURNING STOVE

COMBUSTIBLE : OIL NO 1 OIL NO 2 HEAT INPUT : kW BTU/h kW BTU/h
Minimum : 4,8 16 600 3,7 12 800 Maximum : 10,7 36 800 10,3 35 550 FLOWRATE : cc/min litres/h cc/min litres/h Minimum : 9,9 0,59 8,5 0,35 maximum : 17,3 1,04 16,1 0,97
MINIMUM DRAUGHT REQUIRED : 0,05 INWC 0,05 INWC EFFICIENCY : % %
with fan : 81,5 76 without fan : 76,5 73
CLEARANCES TO COMBUSTIBLES
Mm in
Back 150 6 Side 150 6 Corners 150 6 Top 915 36
A MINIMUM CLEARANCE OF 9’’ FROM PIPE TO COMBUSTIBLES SHOULD BE ALLOWED.
mm in Height : 800 31 ½ Width : 635 25 Depth : 485 19 1/8 Ø outlet flue pipe : 130 5 Ø burner : 255 10
Glass ( 3 ) : 460 x 280 18 x 11 Weight : 80kg 175 lbs
DIMENSIONS
Page 1 of 15

INSTALLATION INSTRUCTIONS

LOCATING THE STOVE

Install the stove as close to the chimney as possible.
Many configuration are possible, the most frequent are illustrated in figures 1,2 and 3.
Respect clearances indicated on page 1. They have been tested according to approvals.
Always respect clearances of stove pipe manufacturers. Larger clearances always prevail.
Figure 1 : CORNER INSTALLATION
Figure 3 : WALL INSTALLATION
IMPORTANT: It is essential to ensure that the room were the stove is located is sufficiently ventilated to provide an adequate air supply.
It is possible that if your home is well insulated, that you will have to install an outside fresh air intake.
THE BURNING OF ONE LITRE OF FUEL (OIL) REQUIRES APPROXIMATELY 30 M WILL PRODUCE ABOUT 0.8 KG OF WATER OF WATER VAPOR AND 9 M DIOXIDE AND ATMOSPHERIC NITROGEN. A SOURCE OF AIR FROM THE OUTSIDE IS NEEDED TO REPLACE COMBUSTION AIR. Ref : standard B-139 4.1.4
Figure 2 : PARRALLÈL INSTALLATION
Table 1 : CLEARANCES TO COMBUSTIBLES
mm in
Back 150 6 Side 150 6 Corners 150 6 Top 915 36
Flue Pipe 230 9
3
OF AIR AND
3
OF CARBONE
Page 2 of 15

CHIMNEY INFORMATIONS

Before the hook up of the stove, check if the chimney is in good condition and that the quality of the flue will allow a sufficient draught. For a good combustion, refer to the technical data of the stove to know the minimum draught required.
Factory built a type chimney or L type chimney are approved for this unit. The chimney has to be well insulated, a chimney to cold can affect the gas temperature and lower draught effects. Low gases T
5" factory built chimney is required. Using a larger flue tend to expand combustion gas and cools them off witch has for result of lowering the draught effects. Gas expansion reduces the speed of the draught and have the same effects.
o
will tend to condense and freeze or leak in your chimney.
When the unit is installed on a masonry chimney witch is often oversize, it’s required to use a
stainless steel liner of 5" diameter inside the existing chimney. ref : B-139 4.2.2.6 standard The chimney has to reach a minimum of 15' high (including stove pipes). The chimney has to
extend not less than 3' above the point it exits the roof and 2' higher than any roof, building other obstacle within a horizontal distance of 10'. ref.: standard B-139 - 4.2.2.11.
CHEMNEY MINMUM HEIGHT : Height of chemney should inferior than 15’ (4.6 m).
CLEARANCES WITH ROOF SUMMIT AND BUILDING NEARBY :
The chimney flue shall extend at least 2’ (0,6 m) above the highest roof surface or structure within 10’ (3,0 m) horizontally of the chimney. ref.: standard B-139 - 4.2.2.11
Figure 4: CHEMNEY MINMUM HEIGHT
CLEARANCE FROM ROOFING INTERSECTION : The chimney flue shall extend at least 3’ (1,0 m) above the highest point at which it comes in contact with the roof. ref.: standard B-139 - 4.2.2.11.
Figure 5: CHIMNEY CLEARANCES
YOUR APPLIANCE SHALL BE CONNECTED TO CHIMNEY HAVING SUFFICIENT DRAUGHT AT ALL TIMES TO ASSURE SAFE AND PROPER OPERATION OF THE BURNER
Page 3 of 15

CONNECTING THE STOVE TO THE CHIMNEY

The gases are vented from he back of the unit. The female part of the black pipe connector has to be installed toward the flue connector of the stove. Secure all connections with the (3) self taping screws, with 120
The connection between stove pipes and chimney has to be perfectly sealed.
A maximum horizontal lent of 5' is allowed. Make sure to have a 1/4" slope per foot minimum.
Do not use more than two 90
It is strictly forbidden to pass through combustible materials walls, floors and ceilings with stove
pipe connectors. Ref : Standard B-139 4.2.5.5.
DIRECT HORIZONTAL CONNECTION : You may choose to connect your stove to the chimney with an horizontal flue pipe.
o
distance between each of them.
o
Elbows while connecting the stove to the chimney.
CEILING CONNECTION : In the case where your chimney starts from the ceiling, use one 90º elbow and the necessary straight sections.
Figure 6: HORIZONTAL CONNECTION .
DO NOT CONNECT MORE THAN ONE STOVE TO YOUR CHIMNEY.
FIX FLUE PIPES TOGETHER WITH METAL SCREWS.
MAKE SURE YOU RESPECT A ¼’’ SLOPE PER FOOT OF HORIZONTAL PIPE LENGTH.
RESPECT CAREFULLY CLEARANCES TO COMBUSTIBLES PRESCRIBED BY FLUE PIPES MANUFACTURERS.
FLUE PIPES CLEARANCES TO COMBUSTIBLES DEPEND ON FLUE PIPES TYPE AND MANUFACTURERS
Figure 7: CEILING CONNECTION .
VERTICAL CONNECTION : IT is recommended to not use more than two (2) 90º elbows and the necessary straight sections to connect your stove to the chimney.
Figure 8: VERTICAL CONNECTION .
Page 4 of 15
Loading...
+ 11 hidden pages