Dräger Sensor User Manual

Catalytic Bead DrägerSensor® Sensors for Fixed Gas Detectors
The DrägerSensor® ... DQ detects  ammable gases and vapours such as
hydrogen. Due to the double-detector compensation method, the catalytic
sensor is particularly long-term stable. The wire mesh at the gas inlet
serves as a  ame barrier. So it ensures explosion protection at the same
Reference chamber with reference pellistorMeasuring pellistor
Flameproof stainless steel housing
Flame barrier
D-10088-2018
02 | Catalytic Bead DrägerSensor®
Benets
The catalytic bead principle
The DrägerSensors ... DQ are based on the catalytic bead detection principle. The most important component
are the hot, catalytically active pearls on platinum coils (pellistors). These pellistors burn the gas and additional
heat of reaction is created. The temperature increases depending on the gas concentration and thus also
changes the electrical resistance of the platinum coils. This change is passed on as a measuring signal. There
are ve different catalytic bead sensors from Dräger, which are used in different transmitters and measuring
heads.
DrägerSensor® PR M DQ
PR stands for poison resistant. The pellistors of the DrägerSensor PR M DQ have a longer service life under the inuence of poisonous substances. The sensor has a metric thread (M) on the back.
DrägerSensor® PR NPT DQ
The DrägerSensor PR NPT DQ also withstands poisoning substances for a long time. This sensor is equipped
with a NPT thread on the back.
DrägerSensor® HT M DQ
The DrägerSensor HT M DQ can be used at ambient temperatures of up to 150 ° C and is also approved accordingly (HT = high temperature). This sensor also has a metric thread.
DrägerSensor® LC M
LC stands for >low concentration<. The DrägerSensor LC M detects very low gas concentrations in the
measuring range from 0 to 10% LEL. This is possible by a special arrangement of the PR pellistors, as well as
an amplier electronics. The sensor has a metric thread.
DrägerSensor® LC NPT
The LC NPT sensor also detects gas concentrations in the measuring range of 0 to 10% LEL. It is equipped
with a NPT thread.
System Components
D-13692-2010
Catalytic Bead DrägerSensor® | 03
Dräger Polytron® SE Ex
The Dräger Polytron® SE Ex ... DQ sensing heads are gas detectors for
the continuous monitoring of ammable gases and vapours in the
ambient air. Measurement is based on the heat of reaction principle
where a chemical reaction takes place in a catalytic bead (also known as a pellistor) inside the sensor.
Dräger PEX 3000
D-11158-2011
D-32407-2011
The transmitter Dräger PEX 3000 detects ammable gases and vapours
in concentrations below their lower explosive limit. Its DQ-sensor provides a long-term stable measuring signal and responds to gas
within a few seconds.
Dräger Polytron® 5200 CAT
The Dräger Polytron® 5200 CAT is a cost-effective explosion-proof transmitter for the detection of ammable gases in the lower explosion limit (LEL). It uses a catalytic bead DrägerSensor® Ex … DQ that will detect most ammable gases and vapours. A 3-wire 4 to 20 mA analogue output with relays makes it compatible with most control
systems.
Dräger Polytron® 8200 CAT
The Dräger Polytron® 8200 CAT is an advanced explosion-proof transmitter for the detection of ammable gases in the lower explosion
®
limit (LEL). It uses a catalytic bead DrägerSensor
Ex … DQ that will
detect most ammable gases and vapours. In addition to a 3-wire 4 to
20-mA analogue output with relays it also offers Modbus and Fieldbus
protocols, making it compatible with most control systems.
D-15042-2010
04 | Catalytic Bead DrägerSensor®
System Components
D-11951-2016
Dräger PointGard 2200
The Dräger PointGard 2200 series is a self-contained gas detection
system for the continuous area monitoring of ammable gases and vapours in ambient air. PointGard 2200’s rugged, water-resistant
housing comes complete with a horn and strobes, a built-in power
supply, and reliable DrägerSensor®.
Related Products
ST-8821-2005
DrägerSensor IR
Upgrade from catalytic bead to infrared technology with ease using the
DrägerSensor IR. The Sensor IR can replace catalytic ex-sensors (pellistors) from the majority of manufacturers without replacing controllers, cables, junction boxes or control systems.
Technical Data
DrägerSensor® PR M DQ, PR NPT DQ, HT M DQ
Catalytic Bead DrägerSensor® | 05
Environmental conditions Temperature (PR M/NPT DQ)
Temperature (HT M DQ)
Pressure
Relative humidity
Storage Temperature
Pressure
Relative humidity
Gas or vapour CAS-No. LEL in Vol.-% Typical sensitivity
in mV/% LEL
Relative
sensitivity based
-50 to +85 °C
-50 to +150 °C
800 to 1.200 hPa
5 to 95 % r. h.
-40 to +65 °C
70 to 1.300 hPa
10 to 90 % r. h.
Response time
t50 in s
1
Response time
t90 in s
on propane
Acetone
Acetylene
Ammonia
Petrol 065/095 Benzene
67-64-1 2.5 0.8 1.1 12 24 74-86-2 2.3 0.9 1.3 12 21 7664-41-7 15.0 1.4 2.0 10 17
---
1.1 0.6 0.9 12 24
71-43-2 1.2 0.6 0.9 14 28
1,3-Butadiene 106-99-0 1.4 0.7 1.0 12 22
n-Butane
n-butyl acetate
Diethyl ether
Dimethyl ether
Acetic acid
Ethyl alcohol
Ethyl acetate
Ethylene (Ethene) Ethylene oxide n-hexane
Methane
Methanol
Methyl ethyl
106-97-8 1.4 0.7 1.0 13 26 123-86-4 1.2 0.5 0.7 14 33 60-29-7 1.7 0.7 0.9 15 30 115-10-6 2.7 0.8 1.1 12 23 64-19-7 4.0 0.5 0.7 14 34 64-17-5 3.1 0.8 1.1 13 24 141-78-6 2.0 0.6 0.8 15 30 74-85-1 2.3 0.8 1.1 11 21 75-21-8 2.6 0.7 1.0 11 22 110-54-3 1.0 0.5 0.7 14 29 74-82-8 4.4 1.1 1.6 10 19 67-56-1 6.0 1.0 1.5 11 21 78-93-3 1.5 0.6 0.8 13 27
ketone
Methyl
80-62-6 1.7 0.6 0.9 14
29
methacrylate n-nonane
n-octane
n-pentane
Propane
i-propanol
Propylene
111-84-2 0.7 0.4 0.6 15 46 111-65-9 0.8 0.5 0.7 15 31 109-66-0 1.1 0.6 0.8 14 33 74-98-6 1.7 0.7 1.0 12 23 67-63-0 2.0 0.7 0.9 13 25 115-07-1 2.0 0.8 1.2 11 21
(Propene) Propylene oxide
Toluene
Hydrogene
o-xylene
1
Response times according to DIN EN 60079-29-1, Annex B, B.2.1 (with calibration adapter).
75-56-9 1.9 0.7 0.9 13 25 108-88-3 1.0 0.6 0.8 14 35 1333-74-0 4.0 1.0 1.5 9 16 95-47-6 1.0 0.7 0.9 14 38
1
06 | Catalytic Bead DrägerSensor®
Technical Data
Approvals
DrägerSensor® PR M DQ ATEX
DrägerSensor® PR NPT DQ ATEX
DrägerSensor® HT M DQ ATEX
IECEx
IECEx
UL
IECEx
II 2G Ex db IIC T6...T4 Gb, II 2G Ex tb IIIC T130°C...T195°C Db
IP6x (-50°C ≤ Ta ≤ +40°C/55°C/85°C)
Ex db IIC T6...T4 Gb, Ex tb IIIC T130°C...T195°C Db IP6x (-50°C ≤
Ta ≤ +40°C/55°C/85°C)
II 2G Ex db IIC T6...T4 Gb, II 2G Ex tb IIIC T130°C...T195°C Db
IP6x (-50°C ≤ Ta ≤ +40°C/55°C/85°C)
Ex db IIC T6...T4 Gb, Ex tb IIIC T130°C...195°C Db IP6x (-50°C ≤
Ta ≤ +40°C/55°C/85°C) Class I, Groups A,B,C,D Class II, Groups E,F,G (-50°C ≤ Ta ≤
+85°C) II 2G Ex db IIC T3 Gb, II 2GD Ex tb IIIC T195°C Db IP6x (-50°C ≤
Ta ≤ +155°C) Ex db IIC T3 Gb, Ex tb IIIC T195°C Db IP6x (-50°C ≤ Ta ≤ +155°C)
DrägerSensor® LC M, LC NPT
Environmental conditions Temperature
Pressure
Relative humidity
Storage Temperature
Pressure
Relative humidity
Gas CAS- LEL in Vol.-% Test gas
concentration in
ppm
Methane
Ammonia
Ethene
Propane
Propene
Hydrogene
Approvals
DrägerSensor® LC M ATEX
DrägerSensor® LC NPT ATEX
74-82-8 4.0 2,5 6.0 7.0 6.0
7664-41-7 15.0 6 4.0 9.0 5.0
74-85-1 2.0 1 4.0 5.0 3.0
74-98-6 2.0 1 6.0 4.0 3.0
115-07-1 2.0 700 4.0 5.0 2.0
1333-74-0 4.0 2 5.0 6.0 4.0
IECEx
IECEx
Test gas
concentration in
% LEL
-40 to +85 °C
900 to 1100 hPa
5 bis 95 % r. h.
-40 to +65 °C
70 to 1300 hPa
10 to 90 % r. h.
Sensitivity in mV
/ % LEL
II 2G Ex db eb IIC T6...T4, II 2D Ex tb IIIC
T80...130°C Db IP6x (-40°C ≤ Ta ≤
+40/50/85°C) Ex db eb IIC T6...T4, Ex tb IIIC T80...130°C
Db IP6x (-40°C ≤ Ta ≤ +40/50/85°C) II 2G Ex db IIC T6...T4, II 2D Ex tb IIIC
T80...130°C Db IP6x (-40°C ≤ Ta ≤
+40/50/85°C) Ex db IIC T6...T4, Ex tb IIIC T80...130°C Db
IP6x (-40°C ≤ Ta ≤ +40/50/85°C)
Reading of a
methane-
calibrated
instrument in %
LEL
Ordering Information
Catalytic bead DrägerSensor®
DrägerSensor® PR M DQ
DrägerSensor® HT M DQ
DrägerSensor® PR NPT DQ
DrägerSensor® LC M
DrägerSensor® LC NPT
Catalytic Bead DrägerSensor® | 07
68 14 140
68 14 145
68 14 150
68 10 350
68 10 675
Calibration / adjustment accessories
Test gas cylinder methane apprx. 40 %LEL, 150 bar Pressure reducer on request
Calibration adapter for PR M DQ, HT M DQ and PR NPT DQ
Remote calibration adapter for PR M DQ, HT M DQ and PR NPT DQ
1
1
Process adapter for PR M DQ, HT M DQ and PR NPT DQDQ
Calibration adapter for LC M and LC NPT
1
metrologically tested according to EN 60079-29-1 (in connection with the respective measuring heads or transmitters)
on request
68 06 978
68 12 480
68 12 470
68 06 978
08 | Catalytic Bead DrägerSensor®
Notes
Not all products, features, or services are for sale in all countries. Mentioned Trademarks are only registered in certain countries and not necessarily in the country in which this material is released. Go to www.draeger.com/trademarks to nd the current status.
CORPORATE HEADQUARTERS
Drägerwerk AG & Co. KGaA
Moislinger Allee 53–55 23558 Lübeck, Germany
www.draeger.com
REGION EUROPE
Dräger Safety AG & Co. KGaA Revalstraße 1
23560 Lübeck, Germany Tel +49 451 882 0 Fax +49 451 882 2080 info@draeger.com
REGION ASIA PACIFIC
Draeger Singapore Pte. Ltd. 61 Science Park Road The Galen #04-01 Singapore 117525 Tel +65 6872 9288 F a x + 65 6259 0398 asia.pacific@draeger.com
REGION MIDDLE EAST, AFRICA
Dräger Safety AG & Co. KGaA
Branch Office P.O. Box 505108 Dubai, United Arab Emirates Tel +971 4 4294 600 Fax +971 4 4294 699 contactuae@draeger.com
REGION CENTRAL
AND SOUTH AMERICA
Dräger Indústria e Comércio Ltda. Al. Pucurui - 51 - Tamboré 06460-100 - Barueri - São Paulo Tel. + 55 (11) 4689-4900 relacionamento@draeger.com
Locate your Regional Sales Representative at: www.draeger.com/contact
90 45 523 | 21.02-3 | HQ | PP | Subject to modications | © 2021 Drägerwerk AG & Co. KGaA
Loading...