DR DRY-1-15-AT, DRY-1-25-AT, DRX-1-15-AT, DRX-1-25-AT Mounting And Operating Instructions

Mounting and operating instructions
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 2 - 7
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
OPERATIONAL DIAGRAM 5
WIRING AND CONNECTIONS 5
MOUNTING & OPERATING INSTRUCTIONS IN STEPS 5
VERIFICATION OF THE INSTALLATION INSTRUCTIONS 6
TRANSPORT AND STOCK KEEPING INFORMATION 7
WARRANT Y INFORMATION AND RESTRICTIONS 7
MAINTENANCE 7
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 3 - 7
back to the table of contents
SAFETY AND PRECAUTIONS
Read all information, the datasheet, mounting instructions and wiring scheme before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product.
For safety and licensing (CE) reasons, unauthorised conversion and/ or modifications to the product are not permitted.
e product must not be exposed to abnormal conditions, such as: extreme temperatures, direc t sunlight or vibrations. Chemical vapours wi th high concentrat ion in combination with long exposure times can affect the product performance. Make sure the work environment is as dry as possible; check for condensation spots.
All installations shall comply with the local health and safety regulations and local electrical codes. is product can only be installed by an engineer or a technician who has an expert knowledge of the product and safety precautions.
Avoid contacts with energised electrical parts; always treat the product as if it is life. Always disconnect the power source before connecting the power cables, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use wires with appropriate size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and disposed in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your technical support or consult a professional.
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 4 - 7
back to the table of contents
PRODUCT DESCRIPTION
e DRX/DRY controller controls manually the speed of single phase (230 VAC / 50 ­60 Hz) voltage controllable motors / fans from high to low (DRX) or from low to high output (DRY ). It is suitable for DIN rail mounting (DIN EN 50022). Multiple fans can be connected as long as the current limit is not exceeded.
ARTICLE CODES
Code Regulation Max. rated current Max. load L1 Fuse 5*20mm
DR Y-1-15- AT min. to max. 1,5 A 0,5 A 3,15 A
DR X-1-15 - AT max. to min. 1,5 A 0,5 A 3 ,15 A
DR Y-1-25 - AT min. to max. 2,5 A 0,5 A 5,0 A
DR X-1-25 - AT max. to min. 2,5 A 0,5 A 5,0 A
INTENDED AREA OF USE
Speed control of motors / fans in ventilation systems
For indoor use only
TECHNICAL DATA
Supply: 230 VAC ±10% / 50 - 60 Hz
Unregulated output load (L1): 230 VAC / max. 0,5 A
Regulated output to motor / fan, U:
max. load: 1,5 for DRX / DRY-1-15-AT
max. load: 2,5 for DRX/DRY-1-25-AT
Speed control:
DRX – from maximum to minimum
DRY – from minimum to maximum
Minimum speed adjustment by trimmer: 60—230 VAC
Green operating LED indication: on / off
Enclosure:
DIN rail mounting (DIN EN 50022)
ABS/PC, grey (RAL 7035)
Protection standard: IP30 (according to EN 60529)
Operating ambient conditions:
temperature: 0—40 °C
rel. humidity: < 80 % rH (non-condensing)
Storage temperature: -14—50 °C
STANDARDS
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC: EN 61326
WEE E Di r ective 2012/19/EU
DIN rail EN 60715:2001
RoHs Directive 2011/65/EU
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 5 - 7
back to the table of contents
OPERATIONAL DIAGRAM
Motor
output
[VAC]
Vmax
Vmin
0
on min.
Off
DRY series
DRX series
Motor
output
[VAC]
Vmax
Vmin
0
on min.
Off
WIRING AND CONNECTIONS
L, N Supply voltage, 230 VAC ± 10 % / 50 - 60 Hz
U, N Regulated output
L1, N Unregulated output 230 VAC / 0,5 A
Connections Cable cross section: max. 2,5 mm
2
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the DR speed controller, read carefully “Safety and Precautions”. Then proceed with the following mounting steps:
1. Switch off the power supply.
2. Mount the controller on a standard 35 mm DIN rail. Pull the locking clip before
you place the unit onto the rail, and then release the locking clip back to its original position to fix the enclosure to the rail. See Fig. 1 DIN rail locking clip, Fig. 2 Mounting
dimensions and Fig. 3 Mounting position.
Fig. 1 DIN rail locking clip Fig. 2 Mounting dimensions Fig. 3 Mounting position
Lock release
Locking clip
86
94
35
Acceptable Not acceptable
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 6 - 7
back to the table of contents
3. Do the wiring according to the wiring diagram (see Fig. 4) using the legend
information from section “Wiring and connections”.
Fig. 4 Wiring
M
L L1 N N U
Speed adjustment
trimmer
Normal operation
LED indication
Output voltage
adjustment
potentiometer
Power supply
Regulated output
M
L L1 N N U
Power supply
Regulated output
Unregulated output
230 VAC / max . 2 A
4. Switch on the power supply.
5. Set the required output voltage with the help of the potentiometer on the front
cover. Adjust the minimum speed with the trimmer (if necessary). e factory preset is 100 VAC. See Fig 1.
VERIFICATION OF THE INSTALLATION INSTRUCTIONS
When you switc h on the power supply the LED f or operating indication shown in Fig. 4 should give out constant green light. If this is not the case, check the connections.
TRANSPORT AND STOCK KEEPING INFORMATION
Avoid shocks and extreme conditions; stock in original packing.
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING
MIW-DRX-EN-000 - 27 / 11 / 2015 7 - 7
back to the table of contents
WARRANTY INFORMATION AND RESTRICTIONS
Two years fr om the delive ry date against defects in manufactur ing. Any modi fications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. e manufacturer bears no responsibility for any misprints or mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dr y or dampish cloth. In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completelydry.
DR
ELECTRONIC FAN SPEED CONTROLLER, DIN RAIL MOUNTING