Domus Ventilation DX6WW, DX9WW, DX12WW Installation Instructions

Page 1
1.0 Safety Informaon
Front view
269mm
134 mm*
269mm
137mm*
272mm
DX6GL (6 in ch)
Front view
DX9GL (9 in ch) DX12GL (12 inch)
Side view
Cable entry
Aperture required
184mm dia.
*To centre of 'duct'
337 mm
171 mm*
342mm
175mm*
342mm
Cable entry
*To centre of 'duct'
413mm
206mm*
420mm
214 mm*
420mm
Cable entry
*To centre of 'duct'
Aperture required
260mm dia.
Aperture required
337mm dia.
269mm
272mm
DX6GL (6 in ch)
Front view
DX9GL (9 in ch) DX12GL (12 inch)
Side view
342mm
342mm
420mm
420mm
V E N T I L A T I O N
DX Window Fan Kit 50Hz/60Hz
Supply / Extract Units – Installaon and Maintenance
IMPORTANT: Installaon or replacement of units or spare parts must be carried out by a qualified or Domus approved service engineer/ electrician and in accordance with IEE or local naonal wiring regulaons.
2.0 Introducon
The Domus DX Window Fan Kit is available in 6, 9 and 12 inch impeller sizes suitable for supply or extract and can be the heart of a room’s automac venlaon system.
Ensure adequate air replacement for the fan and any fuel burning appliance in the room.
Figure 1. Main components of Window installaon assembly.
Outer grille
Clamping plate
2.1 Switching
variable speed and automatic or manual switching of several fans if desired.
Spacer
Fan plate assembly
Inside grille
2.2 Sensors
Sensors are available as remote units or integral ‘plug in’ units. They are able to control mulple fans, depending on sensor and fan types. Integral sensors are quick and easy to install and are aesthecally pleasing, whilst remote sensors give the benefit of locaon close to the pollutant source. Remote sensors can be fied with an oponal security strap to prevent unwanted tampering.
2.3 General
The removable interior grille provides easy access while the external rotor motor makes for simple removal of the push-on impeller for cleaning. Upward angled interior grille vanes shield workings from view and downward sloping external vanes throw off rain. The fan is IP24 splash proof approved with the motor rated at IP44.
All external components are made in so grey colours from ultra violet stable ABS material so they will blend with most decors and will not fade in sunlight.
2.3.1 Coding For Window Fan Kits
Descripon Code*
6 inch Window Fan Kit Complete DX6WW
9 inch Window Fan Kit Complete DX9WW
12 inch Window Fan Kit Complete DX12WW
Window Fan Kits are supplied as a complete package with all window installaon parts included and are suitable for glazing thickness of up to 32mm and wall/panels of 360mm.
3.0 Dimensions
DX6WW (6 inch)
269mm
LAB1350R May
272mm
2018 Page 1
Figure 2.
DX9WW (9 inch) DX12WW
342mm
Rear view
342mm
( 12 inch)
420mm
128mm
420mm
Aperture required
184mm dia.
Cable entry
134 mm*
269 mm
130mm
137 mm*
*To centre of 'duct'
Aperture required
260mm dia.
Cable entry
171 mm*
337 mm
169 mm
175mm*
*To centre of 'duct'
Aperture required
337mm dia.
Cable entry
206 mm*
413mm
214 mm*
*To centre
of 'duct'
Page 2
Clean the window glass and affix the outer grille assembly over window aperture.
2
4
6
8
Feed supply cable into the case.
Remove fan plate.
Fix outer grille to spigot plate. Check plate orientaon is vercal. N ote grille locates over top lugs on spigot plate.
Installation and Maintenance
DX Window Fan Kit 50Hz/60Hz
4.0 Installaon
4.1 Installaon of Window Fan Kits
1
Remove front grille. Release 2 screws. Lift grille upwards.
3
Required Glass Aperture
DX6WW DX9WW XDX12WW
184 dia 260 dia 337 dia
V E N T I L A T I O N
2
Remove fan plate.
4
Prepare the window.
5
Remove adhesive pad covers.
7
Fix outer grille to spigot plate. Check plate orientaon is vercal. Note grille locates over top lugs on spigot plate.
6
Clean the window glass and affix the outer grille assembly over window aperture.
8
Ensure rubber seal is located into case spigot.
LAB1350R May 2018
Feed supply cable into the case.
Page 2
Page 3
Installation and Maintenance
10
12
Release the electrical cover from the fan plate.
Assemble the fan plate to the case.
IMPORTANT
(Shuer Operaon XS fans)
There will be a short delay on start-up and shutdown of
approximately 40 seconds, this is normal.
4.2.2 WeatherTerminal
The oponal Weather Terminal is offered for use in exposed site
condions.
The illustraon shows the Weather Terminal installed replacing the Outside Grille assembly.Terminal is held in posion using the same fixings as the Outside Grille assembly. The base of the Terminal
incorporates a foam strip which is designed to adhere to the glass surface assisng fing and also as a seal for the joint when assembled together with the fan unit.
Glass
Main Window fan kit
Weather Terminal
DX Window Fan Kit 50Hz/60Hz
9
Screw the case/ grille assembly together.
11
10
Release the electrical cover from the fan plate.
12
V E N T I L A T I O N
For various wiring opons see page 5.
13
Fit the inside grille, locang it over the top lip before engaging screws.
4.2 Fing Ancillaries (Also see page 8)
4.2.1 Thin Wall Installaon
The diagram shows the unit installed in a mber wall.
A Wall Fixing Plate is used to support the fan assembly and the installaon is similar to that for a window.
Outside Grille
Spacer
Wall Fixing Plate
Interior Grille
Assemble the fan plate to the case.
IMPORTANT
There will be a short delay on start-up and shutdown of
(Shuer Operaon XS fans)
approximately 40 seconds, this is normal.
4.2.2 Weather Terminal
The oponal Weather Terminal is offered for use in exposed site
condions.
The illustraon shows the Weather Terminal installed replacing the Outside Grille assembly. Terminal is held in posion using the same fixings as the Outside Grille assembly. The base of the Terminal
incorporates a foam strip which is designed to adhere to the glass surface assisng fing and also as a seal for the joint when assembled together with the fan unit.
Glass
Weather Terminal
Main Window fan kit
LAB1350R May 2018
Page 3
Page 4
Installation and Maintenance
accordance with the wiring regulaons.
2
4
Remove the terminal cover.
Refit terminal cover before replacing the electrical panel.
5.1.3 Basic Fan Operated By Remote Sensor
Double pole isolator
max.
Fuse
3 amp
Remote sensor
L5
L4
L3
L2
L1
N
or
L
N
DX Fan unit
L1 L2 N
Connect link wire between L2 & L4 for extract OR connect link wire between L2 & L3 for supply.
IMPORTANT
Isolaon - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
DX Window Fan Kit 50Hz/60Hz
5.0 Electrical Installaon
5.0 Electrical Installaon
Electrical work should be undertaken by a qualified electrician in
Electrical work should be undertaken by a qualified electrician in accordance with the wiring regulaons.
1
Release the electrical panel from the fan plate.
3
2
Remove the terminal cover.
4
V E N T I L A T I O N
Clamp the cable and complete the connecons.
5.1 Wiring
5.1.1 Fan Operated By On / Off Switch
or
Double pole isolator
L
N
Fuse max. 3 amp
DX Fan unit
Connect link wire between L2 & L4 for extract OR connect link wire between L2 & L3 for supply.
5.1.2 Fan Operated By Integral Sensor
SL
(Switched Live)
Double pole isolator
L
N
Fuse max. 3 amp
Connect link wire between L2 & L4 for extract OR connect link wire between L2 & L3 for supply. Connect switched live signal to L5 for integral mer module.
or
DX Fan unit with integral sensor
Refit terminal cover before replacing the electrical panel.
5.1.3 Basic Fan Operated By Remote Sensor
L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
N
Connect link wire between L2 & L4 for extract OR connect link wire between L2 & L3 for supply.
Double pole isolator
L
N
IMPORTANT
Isolaon - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
Fuse max. 3 amp
Remote sensor
L1 L2 N
or
L5
L4
L3
L2
L1
N
DX Fan unit
LAB1350R May 2018
Page 4
Page 5
Installation and Maintenance
IMPORTANT
(Shuer Operaon DX fans)
There will be a short delay on startup and shutdown of
approximately 40 seconds. This is normal.
Model
Input Power
(W)
Weight
(kg)
Max. Economy
DX6WW supply & extract 38 20 4.1
DX9WW supply & extract 50 37 5.7
DX12WW supply & extract 100 70 8.6
5.2 Unit Consumpon & Weight
5.3 Electrical Specificaon
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from a 5A lighng circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same operang mode in the same room they should all be controlled from the same CON speed control. This avoids the possibility of one fan (if speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide venlaon in accordance with building regulaons is required in all rooms. This should be checked during commissioning with all fans in the same room running together in all possible configuraons.
The automac shuers, motor bearings should be frequently inspected and maintained to ensure they open fully/operate sasfactorily. Use of an RCD and fused spur with 1A, BussmannTDC180, BS1362, fuse (Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362 fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direcon before commissioning.
Note figures are for extract only at 50hz.
DX Window Fan Kit 50Hz/60Hz
5.1.4 Supply / Extract Fan Operated via remote DX-CON Control
Double
Fuse
pole
max.
isolator
L
N
mains supply
3 amp
Remote switch may be set: On/Off, Supply/ Extract, Economy/Std. (variable
speed), Auto/Manual.
5.1.5 Supply / Extract Fan Operated via remote DX-CON Control
Double
Fuse
pole
max.
isolator
L
N
mains supply
3 amp
Remote switch may be set: On/Off, Supply/ Extract, Economy/Std.
(variable speed), Auto/Manual.
One or more Remote Sensors may be wired in parallel to one DX-CON Control.
Humidity Sensor: DX-RH
5.1.6 Supply / Extract Fan Operated via remote DX-CON Control
Double
Fuse
pole
max.
isolator
3 amp
mains supply
L
N
L4
L3
L2
L1
L1
N
N
DX-CON controller
L4
L3
L2
L1
NL1N
DX-CON controller
L4
L3
L2
L1
NL1N
DX-CON controller
Remote sensor
L2 L1 N
Required if using integral Timer
DX Fan unit
DX Fan unit
DX Fan unit with integral sensor
V E N T I L A T I O N
5.2 Unit Consumpon & Weight
L5
L4
L3
L2
L1
N
DX6WW supply & extract 38 20 4.1
DX9WW supply & extract 50 37 5.7
DX12WW supply & extract 100 70 8.6
Note figures are for extract only at 50hz.
Model
L5
L4
L3
L2
L1
N
5.3 Electrical Specificaon
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from a 5A lighng circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 5 x 6 or 9 inch fans are used in the same
operang mode in the same room they should all be controlled from the same CON speed control. This avoids the possibility of one fan (if speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide venlaon in accordance with building regulaons is required in all rooms. This should be checked during commissioning with all fans in the same room running together in all possible configuraons.
The automac shuers, motor bearings should be frequently inspected and maintained to ensure they open fully/operate sasfactorily. Use of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse (Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362 fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direcon before commissioning.
L5
L4
L3
L2
L1
N
IMPORTANT
(Shuer Operaon DX fans)
There will be a short delay on startup and shutdown of
approximately 40 seconds. This is normal.
Input Power
(W)
Max. Economy
Weight
(kg)
Remote
switch may be set: On/Off, Supply/ Extract, Economy/Std.
(variable speed), Auto/Manual.
Maximum one Integral Sensor per fan, 6/9/12 denotes unit size identy. Humidity Sensor: DX-H6/9/12
Passive I
nfra Red Sensor: DX-PIR6/9/12
Run on Timer: DX-T6/9/12.
A single sensor will switch all fans if mo re than one fan is being operated by a single DX-CON controller.
NOTE: M
ul-fan opons:
Up to 5 fans (size 6"/9") can be controlled by one DX-CON. Up to 2 fans (size 12") can be controlled by one DX-CON. Do not mix different fan sizes on the same controller.
LAB1350R May 2018
Page 5
Page 6
Installation and Maintenance
Screw the sensor module into posion.
1
3
5
7
Push the repacement cover into the grille front.
Lift out the sensormodule wiring connector.
Unscrew the module plate from motor plate assy.
DX Window Fan Kit 50Hz/60Hz
5.4 Fing Integral Sensors (Oponal)
Note: Before following the pictorial sequence shown, first remove the fans front cover grille (2 screws). Release the four main corner screws and li out the motor/fan plate assembly. Remove the electrical cover plate opposite the sensor plate. Follow the pictorial sequence on this page.
2
1
Unscrew the module plate from motor plate assy.
3
V E N T I L A T I O N
Remove the module plate.
4
Plug the connector into the required sensor module.
6
Lift out the sensor module wiring connector.
5
Screw the sensor module into posion.
7
Push out the sensor area cover from the grille.
LAB1350R May 2018
Push the repacement cover into the grille front.
Page 6
Page 7
Installation and Maintenance
Feed approx. 200mm of supply cable into the box
1
3
5
7
Fit the control into the backplate box and secure. Test the installaon.
Lift up panel and remove two screws to dismantle unit.
Spot through backplate box and drill and plug the wall.
200mm
1.5m
DX Window Fan Kit 50Hz/60Hz
5.5 Fing Remote Controller DX-CON or Remote sensors (oponal)
The DX-CON Mul Fan Control provides supply or extract, variable speed and automac or manual switching of several fans if desired, (see
note below). The control is best mounted approx 1.5m above the floor. Remote Sensors are available for Humidity, Air Quality and Passive Infra Red control. Remote Sensors should be posioned at least 1.5m above the floor and away from direct heat sources e.g. radiators.
Note:
Up to 5 fans (size 6 / 9 inch) can be controlled by one DX-CON. Up to 2 fans (size 12 inch) can be controlled by one DX-CON. Do not mix different fan sizes on the same controller.
2
1
Lift up panel and remove two screws to dismantle unit.
3
1.5m
V E N T I L A T I O N
Push out backplate box cable entry using a screwdriver.
4
Fix backplate box to the prepared wall.
6
Spot through backplate box and drill and plug the wall.
5
Feed approx. 200mm of supply cable into the box
7
200mm
Connect the end of the cable into the control block.
LAB1350R May 2018
Fit the control into the backplate box and secure. Test the installaon.
Page 7
Page 8
Installation and Maintenance
DX Window Fan Kit 50Hz/60Hz
6.0 Ancillaries
Glass
Weather Terminal
Weather Terminal
Used for exposed site wall installaons, comprising one weather terminal, manufactured from HIPS.
Order Code DX-WT6 Dimensions: 360 x 360 x 170mm
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy use, remove the dirt and encrustaon from the grille(s) fan impeller and motor casing. Ensure the impeller is not cracked or deformed and is able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
The Weather terminal unit replaces the outside grille and is supplied with installaon details.
Order Code DX-WT9 Dimensions: 425 x 425 x 180mm
V E N T I L A T I O N
Main Window fan kit
Wall Fixing Plate
The Wall Fixing Plate is used for thin wall and above ceiling applicaons, to support the fan assembly.
Order Code DX-WT12 Dimensions: 506 x 506 x 185mm
9.0 Warranty
The 2 year warranty starts from the day of deli very and includes parts and labour for the first year. The remaining period covers replacement
parts only. This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not installed, commissioned and maintained in accordance with the details contained in this manual and general good pracce.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event of a breakdown of this equipment, it should be adequately packaged and returned to Domus.
Please telephone Domus before posng your unit. A returns number will be issued to idenfy your package.
We will endeavour to repair or replace it within five working days of receipt. See our warranty terms.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
The product warranty applies to the UK mainland and in accordance with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details. A unit returned to Domus should be suitably protecvely packaged and clearly marked with the ‘returns number’ obtained from Domus prior to posng.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare parts and replacement components, please contact the Aer Sales
Department.
V E N T I L A T I O N
Domus Ventilation Block C Caerphilly Business Park
V an Road Caerphilly CF83 3ED
T el: +44 (0)3443 715523
Fax: +44 (0)3443 715524
www.domusventilation.co.uk
The EMC Directive 2014/30/EU
The Low Voltage Directive
2014/35/EU
LAB1350R May 2018
Page 8
Loading...