Dometic Qht, Q3 Operation Manual

Page 1
Q3 Control Qht Control (with bezel)
For Direct Expansion Systems
OPERATIONS MANUAL
Dometic Marine Rev. 20170710 Part Number 0880107 L-2516 English
COPYRIGHT © 2007-2017 Dometic Corporation. All Rights Reserved.
No part of this publication may be reproduced, translated, stored in a retrieval system, or transmitted in any form or by any means electronic, mechanical, photocopying, recording or otherwise without prior written consent by Dometic Corporation. Every precaution has been taken in the preparation of this manual to ensure its accuracy. However, Dometic Corporation assumes no responsibility for errors and omission. Neither is any liability assumed for damages resulting from the use of this product and information contained herein.
Page 2
Table of Contents
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
R
EAD THIS MANUAL BEFORE PROCEEDING . . . . . . . . . 1
CONTROLS OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . 1
F
EATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
H
OW IT WORKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Importance of Seawater Temperature . . . . 1
Power Interruptions . . . . . . . . . . . . . . . . . . . . . . 2
D
ESCRIPTION OF THE CONTROLS . . . . . . . . . . . . . . . . 3
I
MPORTANT PROGRAMMING NOTES TO INSTALLER AND
END USER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ORMAL HEATING OR COOLING CYCLE . . . . . . . . . . . . 5
N
R
EVERSING VALVE OPERATION . . . . . . . . . . . . . . . . . 5
INSTALLING THE DISPLAY PANEL . . . . . . . . . . . . . . . 5
M
OUNTING THE DISPLAY . . . . . . . . . . . . . . . . . . . . . . 5
M
OUNTING THE SENSORS . . . . . . . . . . . . . . . . . . . . . . 5
Ambient Temperature Sensor - required . . . . . 5
Seawater Temperature Sensor - optional . . . . . 5
Outside Air Temperature Sensor - optional . . . 6
Humidity Sensor - optional . . . . . . . . . . . . . . . . 6
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
O
PERATOR CONTROLS AND DISPLAY PANEL . . . . . . . . 6
Button Functions . . . . . . . . . . . . . . . . . . . . . . . . 6
M
ODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . 6
Power On and Basic Modes . . . . . . . . . . . . . . . 6
Dehumidification Mode . . . . . . . . . . . . . . . . . . . 7
Adjusting the Set Point . . . . . . . . . . . . . . . . . . . 7
Fan Operation and Control . . . . . . . . . . . . . . . . 7
Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Display Inside Cabin Temperature . . . . . . . . . . 7
Dimming the Display . . . . . . . . . . . . . . . . . . . . . 7
Sleep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Lockout Display Mode . . . . . . . . . . . . . . . . . . . 7
Anti-Ice Routine . . . . . . . . . . . . . . . . . . . . . . . . 8
FAULT AND ERROR MESSAGES . . . . . . . . . . . . . . . . 15
H
IGH-PRESSURE SHUTDOWN (HI / PS) . . . . . . . . . . . 15
In Cool Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 15
In Heat Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 15
L
OW-PRESSURE SHUTDOWN (LO / PS) . . . . . . . . . . . 15
In Cool Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 15
In Heat Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 15
L
OW-VOLTAGE SHUTDOWN (LO / AC) . . . . . . . . . . . . 15
S
UMMARY OF FAULT CODES AND INDICATOR CODES . 16
INITIAL SYSTEM START UP . . . . . . . . . . . . . . . . . . . . 16
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 17
GENERAL SYSTEM TROUBLESHOOTING . . . . . . . . . . . 17
D
IGITAL-CONTROLS TROUBLESHOOTING . . . . . . . . . . 20
MAINTENANCE OF SYSTEM COMPONENTS . . . . . . 21
ONDENSATE DRAINS . . . . . . . . . . . . . . . . . . . . . . . . 21
C
R
ETURN-AIR FILTER . . . . . . . . . . . . . . . . . . . . . . . . . 21
S
EAWATER CONNECTIONS . . . . . . . . . . . . . . . . . . . . 21
SEAWATER PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
S
EAWATER STRAINER . . . . . . . . . . . . . . . . . . . . . . . . 22
R
EFRIGERANT GAS . . . . . . . . . . . . . . . . . . . . . . . . . . 22
REVERSING VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . 22
C
ONDENSER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
W
INTERIZATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
O
PERATIONAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
D
IMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
CABLE LENGTHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
S
YSTEM INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SAMPLE WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . 24
PROGRAMMING THE CONTROL . . . . . . . . . . . . . . . . . 8
P
ROGRAMMING PROCEDURE . . . . . . . . . . . . . . . . . . . . 8
P
ROGRAMMABLE FUNCTIONS . . . . . . . . . . . . . . . . . . . 8
Customizing the Functions . . . . . . . . . . . . . . . . 8
Restoring Factory Default Settings . . . . . . . . . . 8
Description of Functions . . . . . . . . . . . . . . . . . . 8
Summary Table of Programmable Functions . 14
L-2516 ENGLISH
Page 3
Q3 & Qht Controls for Direct Expansion Systems Read This Manual Before Proceeding
INTRODUCTION
The Q3 and Qht are microcontroller-based units designed for use with reverse-cycle direct expansion (DX) air conditioning systems. This manual provides all necessary information for proper installation and operation of the Q3 and Qht controls. Poor installation or misunderstood operating parameters will result in unsatisfactory performance and possible failure.
READ THIS MANUAL BEFORE PROCEEDING
This manual contains essential information concerning the operation of the control system. It is very important that you read and understand the contents of this manual before using the equipment, and it should be kept on the boat for future reference.
Read this manual completely before you proceed with the installation and operation of the controls. If you have questions or require assistance with your Q3 or Qht control, call your Dometic dealer or the Service Department at +1 954-973-2477.
The Q3 and Qht controls are covered under the existing Dometic Owner’s Limited Warranty Policy. Incorrect installation, neglect and system abuse are not covered under the warranty policy.
CONTROLS OVERVIEW
There are two different controls that can operate a Q-Logic or U-Board system:
Q3 - Rectangular in shape with a bezel look and LED indicators, this display was designed as an economical version of the Qht. The Q3 control is only compatible with a Q-Logic or U-Board and is not backward compatible with an SMXII system
Qht - Using the newest high-technology (ht), this European-style control with LCD display fits into a decorative Vimar® Idea bezel and has many new features. The Qht control is only compatible with a Q-Logic or U-Board and it is not backward compatible with an SMXII system. To distinguish between Qht and SMXht, the Qht has a "Compatible With Q-Logic Only" label displayed on the Qht mounting flange.
While the programming procedure of the Q3 and Qht controls is the same, there are differences in the look of the buttons and and the way the information is presented in the displays. Differences are noted in this manual where applicable. Familiarize yourself with the operation and programming sections of this manual.
FEATURES
Standard Features Optional Features
Universal 115/230 volt, 50/60 Hz AC power supply.
User-friendly four- and five-button display panels.
Option to display temperature in degrees Fahrenheit or Celsius.
33 programmable functions.
Nonvolatile memory requires no backup power.
Switch inputs for High/Low Refrigerant pressure.
Humidity Mode control.
Anti-icing cycle prevents evaporator icing.
Programmable fan operation.
Programmable compressor delays.
Programmable display brightness.
Air Filter Cleaning or Replacement Timer.
Low-Voltage Monitor.
HOW IT WORKS
The basic principle behind an air conditioner is the movement of heat. In a marine DX air conditioner, heat is removed from the inside cabin air and transferred to the seawater. In reverse-cycle heating, the refrigerant flow is reversed and heat is extracted from the seawater and discharged into the living space. The efficiency of the system operation depends on both seawater and cabin temperatures.
Outside temperature sensor.
Seawater inlet temperature sensor.
Auxiliary heating control capabilities.
Humidity sensor for advanced humidity control.
THE IMPORTANCE OF SEAWATER TEMPERATURE
In Cool Mode, the air conditioner will operate most efficiently in seawater temperatures below 90°F (32°C). At higher seawater temperatures the unit will operate, but at a reduced capacity. A high-pressure shutdown may occur at higher seawater temperatures.
L-2516 ENGLISH 1
Page 4
How It Works Q3 & Qht Controls for Direct Expansion Systems Operations Manual
In Heat Mode, the opposite is true. As the seawater gets colder, there is less heat available, and the heating efficiency is reduced. Full heating capacity is obtained at approximately 55°F (13°C) seawater temperature. Performance drops to about 50% of rated capacity in 40°F (4.4°C) water. Below this, the system pressure can be so low that the unit will shut down on low­pressure fault. This problem is compounded when the cabin is also cold. See “FAULT AND ERROR MESSAGES” on page 15.
WARNING
Do not operate your air conditioning unit in water that is colder than 38°F (3.3°C). Doing so could lead to water freezing in the condenser coil which can cause damage to the unit.
POWER INTERRUPTIONS
The control board has built-in protection against sudden power interruptions. The system automatically stores the current operating configuration in permanent memory every time any changes are made. When AC power is lost, the control board retains these settings and resumes using them when AC power is restored.
2 L-2516 ENGLISH
Page 5
Q3 & Qht Controls for Direct Expansion Systems Description of the Controls
4
1
2
3
765
8
9
11
12
13,14 15,16
10
DESCRIPTION OF THE CONTROLS
Figure 1: Q3 Diagram - Control Display Panel and Indicators
Table 1: Q3 Diagram Description of Control Display Panel and Indicators
1
Data Display - Large LED readout displays current
temperature, set point, programmed values and error messages.
9
AUTO Mode Indicator - Lights when Auto Mode is selected.
Flashes if optional Aux Heater is enabled (see Programmable Function “23: Aux Heat Enabled/Disabled” on page 12).
2
AUTO Fan Mode Indicator - Lights when fan is running in
Automatic Fan Mode.
3
Fan Speed Indicators - Column of three LEDs that indicate
the current fan speed of high, medium, or low (refer to fan speed operation).
4
FAN Button - Press to select Automatic or Manual Fan Mode,
indicated by the AUTO Fan LED indicator being on or off. In Manual Fan Mode, additional presses of the Fan button will adjust fan speed higher, then lower, then back to AUTO. In AUTO Fan, fan speed is controlled by the control board as a function of the difference between set point and inside temperature. See Programmable Function “4: Fan Response
Differential” on page 9.
5
UP Button - Press to adjust set point up. In programming mode
press to scroll through program modes and adjust values.
6
DOWN Button - Press to adjust set point down. In
programming mode press to scroll through program modes and adjust values.
7
MODE Button - Press to cycle through the modes of operation
(refer to indicators). Mode sequence selections are OFF, COOL, HEAT, AUX HEAT (optional), AUTO, and DEHUMIDIFY.
10
HEAT/AUX HEAT Mode Indicator - Lights when Heat Mode
is selected or indicates compressor is on when heating in AUTO mode. Flashes when you press the MODE button a second time in Heat Mode to select the optional Aux Heat Mode (refer to Aux Heat Operation).
11
COOL Mode Indicator - Lights when Cool Mode is selected
or indicates compressor is on when cooling in AUTO mode.
12
OFF Mode Indicator - Lights when system is off. Note that
the Data Display remains on. You can continue to adjust set point, display temperature readings and activate the manual fan to circulate air while the system is in the Off Mode.
13
Cooling Indicator - A dot in the upper left corner of the data
display lights to indicate the compressor is running in COOL mode. In AUTO mode, the COOL LED indicator lights to indicate the compressor is running.
14
Heating Indicator - A dot in the upper left corner of the data
display lights to indicate the compressor is running in HEAT mode. In AUTO mode, the HEAT LED indicator lights to indicate the compressor is running.
15
Set Point Indicator - A dot in the upper center of the display
lights to indicate the set point is being adjusted. Normally display defaults to inside temperature.
8
DEHUMIDIFY Mode Indicator - Lights when the Dehumidify
Mode is selected. Flashes if optional humidity sensor is connected and operating in Cooling Mode.
16
Manual Fan Mode Indicator - AUTO Fan indicator turns off
when fan is running in Manual Fan Mode.
L-2516 ENGLISH 3
Page 6
Description of the Controls Q3 and Qht Controls for Direct Expansion Systems
1
28769
10
12131416
11
15
435
Figure 2: Qht Diagram - Control Display Panel and Indicators
Table 2: Qht Diagram Description of Control Display Panel and Indicators
1 Data Display - Large LCD readout displays current temperature,
set point, programmed values and error messages.
9 Fan Speed Indicator - A row of five bars indicate the current fan
speed, with more bars indicating a higher fan speed and fewer bars indicating a lower fan speed.
2 Set Point Indicator - Display shows SET when set point is being
adjusted. Normally display defaults to inside temperature.
3 Aux Heating Indicator and Aux Heat Mode Indicator (optional) -
A solid dot displays next to the words AUX HEAT when the electric heater is on and running in Aux Heat mode. The words AUX HEAT display when you are in Aux Heat mode. (Press the MODE button to select the optional Aux Heat Mode.) See Programmable Function
“23: Aux Heat Enabled/Disabled” on page 12.
4 Heating Indicator - A solid dot displays next to the word HEAT
when the compressor is on and running in Heat mode.
5 Cooling Indicator - A solid dot displays next to the word COOL
when the compressor is on and running in Cool mode.
6 Cool Mode Indicator - The word COOL displays when you are in
Cool mode. (Press the MODE button to select Cool Mode.)
7 Heat Mode Indicator - The word HEAT displays when you are in
Heat mode. (Press the MODE button to select Heat Mode.)
8 AUTO Mode Indicator - A bracket and the word AUTO display to
the right of the words COOL and HEAT when you are in Auto Mode. If optional Aux Heat is enabled (see Programmable Function “23: Aux Heat Enabled/Disabled” on page 12), a bracket and the word AUTO display to the right of the words COOL and AUX HEAT. (Press the MODE button to select Auto Mode.)
10 Fan Mode Indicator - The word MANUAL displays when the fan is
running in Manual Fan Mode. The word MANUAL does not display when the fan is running in Automatic Fan Mode.
11 Dehumidify Mode Indicator - The word DEHUMIDIFY displays
when you are in Dehumidification Mode. It flashes if optional humidity sensor is connected and operating in the Cooling Mode. (Press the MODE button to select Dehumidification Mode.)
12 FAN Button - Press to select Manual or Automatic Fan Mode,
indicated by the word MANUAL displaying or not displaying. In Manual Fan Mode, additional presses of the FAN button will adjust fan speed higher, then lower, then back to Automatic. In Automatic Fan Mode, fan speed is controlled by the control board as a function of the difference between set point and inside temperature. See Programmable Function “4: Fan Response Differential” on page 9.
13 UP Button - Press to adjust set point up. In programming mode
press to scroll through program modes and adjust values.
14 DOWN Button - Press to adjust set point down. In programming
mode press to scroll through program modes and adjust values.
15 MODE Button - Press to cycle through the modes of operation
(refer to indicators). Mode sequence selections are COOL, HEAT, AUTO, AUX HEAT (optional), and DEHUMIDIFY.
16 POWER Button - Press to turn the system on and off. Note that
the Data Display remains on in the Off mode. You can continue to adjust set point, display temperature readings and activate the manual fan to circulate air while the system is in the Off Mode.
4 L-2516 ENGLISH
Page 7
Q3 & Qht Controls for Direct Expansion Systems Important Programming Notes To Installer and End User
IMPORTANT PROGRAMMING NOTES TO INSTALLER AND END USER
If your air conditioning unit is Cool Only (does not have a reversing valve), then you MUST set Programmable Function 19 to “CL” for Cool Only. Once this parameter is set, the only allowable operational modes that can be selected are OFF, COOL, and DEHUMIDIFICATION. (See Programmable Function “19: Cool-Only Mode” on page 12 for more information.)
NORMAL HEATING OR COOLING CYCLE
In Automatic Mode, heating and cooling are supplied as required. If Cooling is required, the system will start a cooling cycle when the cabin temperature exceeds the set point by the Compressor Differential setting in Programmable Function 3 (1.5°F/
0.8°C by default) and will continue to cool until the temperature equals the set point. Similarly, if Heating is required, the system will start a heating cycle when the cabin temperature is below the set point by the Compressor Differential setting and will continue to heat until the temperature equals the set point.
If you select Cool Mode, only cooling is supplied. If you select Heat or (optional) Aux Heat Mode, only heating is supplied. The cabin temperature in either mode is maintained within the Compressor Differential setting.
During a Cooling or Heating cycle, the fan will operate at a fan speed depending on the fan’s operational mode. If a Manual fan speed is selected, the fan will operate at this speed at all times, even if the set point has been satisfied and the cooling or heating cycle has ended. If the fan is in Auto mode, the fan speed will be determined by Programmable Function 4, the Fan Response Differential, and Programmable Function 22, Fan-Speed Divisions. Please refer to these parameters for further details on the fan speeds during Auto fan operation. When in Auto fan mode, the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended.
REVERSING VALVE OPERATION
The position of the reversing valve determines if the system is in Cool Mode or Heat Mode. When the reversing valve is not energized, the system will operate in Cool Mode. When energized, the system will operate in reverse-cycle heating. In addition, the reversing valve will toggle (switch back and forth) to relieve the system’s internal refrigerant pressures in these situations:
Just before the system starts the compressor if the compressor has not run for less than 2 minutes.
When a cycle is interrupted from the display panel by pressing the POWER button or changing the set point.
INSTALLING THE DISPLAY PANEL
MOUNTING THE DISPLAY
1. For the Qht display, make a rectangular cut-out in the panel where it will be mounted. The Qht cut-out size is 3-7/16” (88mm) wide by 2-1/8” (54mm) high. For the Q3 display, only a 1” (26mm) round hole is required in the panel for mounting.
2. Use the installation instructions included with your display to complete the mounting, securing the display with the appropriate size and number of screws.
3. Plug one end of the display cable (6-pin connector) to the back of the display and the other end to socket labeled “Display” located on the edge of the circuit board.
MOUNTING THE SENSORS
NOTE
Do not staple any sensor cables when mounting.
AMBIENT TEMPERATURE SENSOR - REQUIRED
Install the ambient temperature sensor in a proper location to accurately sense the room air temperature. Ideally, the sensor should be located in a reliable return-air stream moving from the room to be controlled to the air conditioner it is plugged into.
Locating the sensor on the back of the air conditioner coil is not ideal and can result in false readings for several reasons. It is best to locate the sensor just inside of a return-air grille or passage. The standard cable length for the remote air sensor is 7 feet (2.1m). Plug in the sensor’s 6-pin connector to the “Inside Temp” socket located on the edge of the circuit board.
SEAWATER TEMPERATURE SENSOR - OPTIONAL
Install the optional seawater temperature sensor to monitor the temperature of the seawater feeding the air conditioner. Ensure that the sensor is in direct contact with the copper pipe and use thermal mastic to ensure good heat transfer. Strap the sensor wire in place for strain relief and to prevent the sensor from being accidentally removed. Plug the sensor’s 2-pin connector into the “Loop Water Out” (blue) socket located in the corner of the circuit board.
L-2516 ENGLISH 5
Page 8
Operator Controls and Display Panel Q3 and Qht Controls for Direct Expansion Systems
OUTSIDE AIR TEMPERATURE SENSOR - OPTIONAL
Install the optional outside air temperature sensor to monitor temperature outside the cabin. Outside air sensor cables are available in various lengths. Mount the sensor outside but not in direct sunlight. Plug in the sensor’s 6-pin connector to the socket labeled “Outside Temp” (white) located on the edge of the circuit board.
HUMIDITY SENSOR - OPTIONAL
Install the optional humidity/temperature combo sensor to monitor the relative humidity of the cabin. Locate the sensor in the same location as the ambient air temperature sensor. Plug in the combo sensor’s 6-pin connector to the “Inside Temp” socket located on the edge of the circuit board. The control board automatically detects the presence of this combo sensor and immediately starts measuring humidity.
OPERATION
OPERATOR CONTROLS AND DISPLAY PANEL
For the button locations and display functions, refer to Figure 1, Table 1 on page 3 for the Q3 control and to Figure 2, Table 2 on page 4 for the Qht control.
BUTTON FUNCTIONS
POWER button (Qht only) - Press and release to toggle between the On and Off Modes.
MODE button - Press and release to toggle between the Off (Q3 only) and all other modes of operation.
UP button - Press and release to display the set point. Press and hold the UP button to increase the set point. Set point increases one degree each time the button is pressed.
DOWN button - Press and release to display the set point. Press and hold the DOWN button to decrease the set point. Set point decreases one degree each time the button is pressed.
FAN button - Press to select the Automatic Fan Mode, the Manual Fan Mode, or to advance through the manual fan speeds.
Display Seawater Temperature (optional) - Press the FAN and UP buttons simultaneously to display the seawater temperature (optional). If the seawater temperature is not available, open or shorted (closed), the display flashes “- -” instead of a temperature reading.
Q3 - The display flashes “SE” for one second then the seawater temperature displays in two segments: The
display flashes the first digit of the seawater temperature for one second, then the next two digits of the seawater temperature for one second. The cycle repeats until the buttons are released.
Qht - The word WATER displays, “SE” flashes for one second, then the seawater temperature displays in two
segments: The display flashes the first digit of the seawater temperature for one second, then the next two digits of the seawater temperature for one second. The cycle repeats until the buttons are released.
Display Outside Temperature (optional) - Press the FAN and DOWN buttons simultaneously to display the outside temperature (optional). If outside temperature is not available, open or shorted (closed), the display flashes “- -” instead of a temperature reading.
Q3 - The display flashes “OU” for one second then the outside temperature displays in two segments: The display
flashes the first digit of outside temperature for one second, then the next two digits of outside temperature for one second. The cycle repeats until the buttons are released.
Qht - The word OUTSIDE displays, “OU” flashes for one second, then the outside temperature displays in two
segments: The display flashes the first digit of outside temperature for one second, then the next two digits of outside temperature for one second. The cycle repeats until the buttons are released.
Display Relative Humidity (optional) - Press the MODE and UP and DOWN buttons simultaneously to display the relative humidity (optional). “HS” displays for one second then the two digits of relative humidity display for one second. The cycle repeats until the buttons are released. If HS is not available, open or shorted (closed), the display flashes “- -” instead of the humidity reading.
MODES OF OPERATION
POWER ON AND BASIC MODES
Press the MODE (Q3) or POWER (Qht) button to turn the system on. In three seconds, the system will start operating in whichever mode it was running prior to the last shut down. For the initial startup, the control will be in Cool Mode.To change mode before the system starts, press the MODE button before the three-second startup completes (while the display is flashing). Or, while the system is on, press the MODE button at any time to change the mode.
6 L-2516 ENGLISH
Page 9
Q3 & Qht Controls for Direct Expansion Systems Modes of Operation
The modes available are: Off, Cool, Heat, Auto (automatically switches between Cool and Heat Modes, depending on set point requirement), Aux Heat (optional) and Dehumidification Mode.
DEHUMIDIFICATION MODE
Press the MODE button until the DEHUMIDIFY LED indicator lights (Q3) or the word DEHUMIDIFY appears in the display (Qht). The display flashes “HU” during this mode of operation. When Dehumidification Mode is activated, the Humidity Control Program automatically turns the air conditioning system on at timed intervals to remove moisture from the air. The system is programmed at the factory for average values. To change the factory settings, see Programmable Function “10: Dehumidification Pre-Circulation Time” on page 10, Programmable Function “11: Dehumidification Time” on page 10, and Programmable Function “12: Dehumidification Overall Time Period” on page 10.
NOTE
When the system is in Dehumidification Mode, all system safeguard controls remain active. For example, if the line voltage falls below preset limits, the system will automatically shut down. Or, if AC power is interrupted, the system will automatically resume operation in Dehumidification Mode when power is restored.
ADJUSTING THE SET POINT
To view the set point, momentarily press and release the UP or DOWN button. To adjust the set point, press the UP or DOWN buttons to set the desired room temperature (press and hold either button to scroll). The set point range is 55-99°F (12.8-
37.2°C). After selecting the desired set point temperature, if no buttons are pressed for three seconds the display automatically reverts to showing the inside cabin temperature. Inside cabin temperature is continuously displayed.
Q3 - The upper center dot in the display lights when set point is being adjusted.
Qht - The word SET appears in the display while set point is being adjusted.
FAN OPERATION AND CONTROL
Press the FAN button to adjust the fan speed while in Manual Fan Speed Mode or to switch between Manual and Automatic Fan Speed Modes. The fan may be run manually whether the system is on or off. Automatic Fan Speed Mode can only operate when the system is on. Fan behavior also depends on how the Fan Mode function is programmed: “C” for continuous or “I” for intermittent running with the compressor. See Programmable Function “7: Fan Mode” on page 9.
Q3 - When in Manual Fan mode, the AUTO Fan LED is off.
Qht - The word MANUAL appears in the display when in Manual Fan mode.
MEMORY
The control has nonvolatile memory requiring no batteries or backup power. When power is lost, the operating parameters are retained indefinitely. When power is restored, the control resumes operating as last programmed.
DISPLAY INSIDE CABIN TEMPERATURE
The control continuously displays inside cabin temperature. If Mode or Set Point is changed, after three seconds the display automatically reverts to showing inside temperature. If inside temperature is greater than 99°F (37°C) or less then 0°F (-17°C), the display shows either 99°F (37°C) or 0°F (-17°C) respectively as the maximum or minimum inside temperature.
DIMMING THE DISPLAY
Press the MODE and UP buttons simultaneously and repeatedly to select the brightness setting for the display.
SLEEP MODE
Sleep Mode dims all LEDs (Q3) or turns off the backlight (Qht). When in Sleep Mode, press any button to brighten the display, and then operate as usual. See Programmable Function “18: Sleep Mode” on page 11.
LOCKOUT DISPLAY MODE
Press the MODE and UP and FAN buttons simultaneously to select the Lockout Display Mode setting. This mode locks the display in the current mode selected. If a button is pressed, the display flashes “LC” for 2 seconds then goes back to displaying the inside temperature. In Lockout Mode, the display shows inside temperature and the indicators operate as normal, but all button presses are ignored until MODE and UP and FAN buttons are pressed simultaneously, then “UL” displays momentarily and the buttons are unlocked for normal operation. In Lockout Mode all sensors operate as normal and any fault and error codes will be displayed.
L-2516 ENGLISH 7
Page 10
Programming procedure Q3 and Qht Controls for Direct Expansion Systems
ANTI-ICE ROUTINE
The control occasionally shuts down the compressor when in Cool Mode to allow any ice to melt that may have formed on the evaporator coil. The Anti-Ice Routine shutdown occurs when the inside cabin temperature falls below 70°F (21°C). The default setting of 70°F (21°C) can be adjusted. See Programmable Function “21: Anti-Icing Routine Adjustment” on page 12.
During a ten-minute cycle period, the compressor shuts off for 15 seconds for each degree below 70°F (21°C) (default). For example, if the inside temperature is 67°F (19°C), the compressor will shut off for 45 seconds, and then run for nine minutes and 15 seconds, repeating this cycle in ten-minute intervals.
PROGRAMMING THE CONTROL
PROGRAMMING PROCEDURE
The Q3 and Qht must be in Off Mode prior to entering Programming Mode.
Q3 - Press the MODE button and select the Off Mode.
Qht - Press the POWER button to turn the control off or on.
Once in the Off Mode, then:
1. Simultaneously press and hold the MODE and DOWN buttons for three seconds.
Q3 - “PO” flashes in the display while the buttons are being held. When “PO stops flashing and the OFF LED
flashes, you have successfully entered Program Mode.
Qht - “PROG” flashes in the display while the buttons are being held. When “PROG” stops flashing and a flashing
“01” appears in the display, you have successfully entered Program Mode.
2. Press the UP or DOWN buttons to scroll until the desired Programmable Function Number (1-29) is displayed. See Table 4 on page 14.
3. Press the MODE button to access the programmable value of the displayed Function Number. That function’s current value and a flashing OFF LED (Q3) or the word “PROG” (Qht) will also be displayed.
4. Press the UP or DOWN buttons to change the value of that function.
5. Press the FAN button to save the new setting and return to Program Mode. Scroll to another function number and continue programming, or press FAN again to exit Programming Mode and return to Off Mode.
NOTE
Whether your control is set to display temperatures in °F or °C, all temperature-related programming values must be adjusted in °F only.
PROGRAMMABLE FUNCTIONS
CUSTOMIZING THE FUNCTIONS
The system’s default settings may be changed by the installing dealer or end user.
A summary of the function settings, permitted values, and original factory default settings of each are listed in Table 4: Programmable Functions - Ranges and Factory Defaults, page 14. Record the data for any function settings you change in the Custom Settings column of that table.
RESTORING FACTORY DEFAULT SETTINGS
You can restore the original factory default settings and overwrite all the customized changes you made. To restore the factory default settings, switch to Off Mode and then press and hold the UP and DOWN buttons simultaneously. Hold the buttons for three seconds while “00” flashes in the display. Successful memory reset is indicated by a “1” flashing back and forth across the display. Release the buttons. System returns to the Off Mode.
DESCRIPTION OF FUNCTIONS
1: Compressor Time Delay
(Factory Default: 0 seconds)
The compressor time delay is for staged installations where more than one system operates from the same power source. Setting different staging delays for each compressor allows them to start at different times when turning on power to the system or when power is interrupted. Stage the units at least five seconds apart. Minimum delay is 0 seconds and maximum is 70 seconds. At initial power up, the display will show the countdown for the compressor time delay setting.
8 L-2516 ENGLISH
Page 11
Q3 & Qht Controls for Direct Expansion Systems Programmable Functions
2: Fahrenheit, Celsius, or Auto Selection
(Factory Default: Fahrenheit)
Select F for Fahrenheit. Select C for Celsius. Select Auto to have the system automatically set the unit based on system voltage frequency: For 60 Hz systems, F will be selected as the degree unit; for 50 Hz systems, C will be selected as the degree unit.
3: Compressor Restart Differential
(Factory Default: 12 = 1.5°F / 0.8°C)
The Compressor Restart Differential is the ambient temperature change needed for the compressor to cycle on and off. The factory setting of 1.5°F should be adequate for most applications. Differential selections are available in increments of 1/8°F. Thus, to change the setting one degree, you should add or subtract 8 (for 8-eighths). All program functions must be adjusted in °F even if the temperature display is changed from Fahrenheit to Celsius (see Programmable Function 2). Be careful not to set
the Compressor Restart Differential too low, since this will cause the compressor to start and stop very often and place an undue load on your electrical system and may shorten the life of the compressor.
4: Fan Response Differential
(Factory Default: 8= 1.0
°F / 0.6°C)
When the fan is in the Automatic Fan Mode, its speed is governed by how much the room temperature differs from the set point. The fan runs faster when the difference is greater. As the room cools or warms, and the temperature approaches set point, the fan slows down automatically. The Fan Response Differential can be adjusted from 1/4°F to 4°F, in 1/8° increments. All program functions must be adjusted in °F even if the temperature display is changed from Fahrenheit to Celsius (see Programmable Function 2).
The fan speed range is divided by the control system into five equal increments. If the Fan Response Differential is set at 1/2°, then the fan speed will change 20% for each 1/2° of temperature deviation from set point. Lowering the fan speed differential will cause the fan to change speed more frequently as temperature changes. Raising the fan speed differential will result in slower fan speed changes for a given temperature change. The factory setting of 1/2° is good for most applications, but you may wish to try a slightly higher setting in your salon and a lower setting in your stateroom.
NOTE
If the Compressor Restart and the Fan Response Differentials are both set to the factory default or a comparable range and the Automatic Fan Mode is on, then the fan will not run at high speed unless the cabin temperature rises 3°F above set point.
5: Low Fan Speed
(Factory Default: 38)
You can adjust the lowest fan speed to suit individual preferences. For instance, you may wish to decrease the low fan speed setting in your stateroom to minimize fan noise.
NOTE
For most efficient operation of your system, you should normally keep the low fan speed at the highest possible setting, consistent with a comfortable noise level. Running the fan speed too low may have an adverse effect on the system and may cause the evaporator coil to freeze.
6: High Fan Speed
(Factory Default: 85)
A blower will often reach its highest speed at a voltage lower than full line voltage. For example, at a line voltage of 120V, the blower might reach its fastest speed at 110V. At higher voltages, the bower speed will not increase significantly.
The High Fan Speed Adjustment allows you to set the maximum high-speed voltage to the threshold of the blower high-speed response. The control system divides the fan speed voltage steps into five equal increments (between the low-speed and high­speed adjustments). Accurately setting the High and Low Fan Speed Adjustments can help ensure that each fan speed increment step results in a noticeable change of fan speed.
While in Program Mode, listen to the fan noise level and use the UP button to raise the displayed value past the point that you can hear an increase in the fan noise level.
Press the DOWN button to lower the voltage until you hear a drop in fan speed, then raise that number by 2 or 3 to ensure that it is set at the highest speed.
7: Fan Mode
(Factory Default: Continuous)
You can select continuous or intermittent fan operation.
L-2516 ENGLISH 9
Page 12
Programmable Functions Q3 and Qht Controls for Direct Expansion Systems
Select C and the fan will run continuously while the system is on. Select I for intermittent operation and the fan will cycle on and off with the compressor.
NOTE
If you select intermittent fan operation, you should relocate the thermistor from the return air grill to a cabin wall where it can best sense the average room temperature. Check with your dealer or call the Dometic Applications Department for more information.
8: AC Line Voltage Calibration
The control board assembly has a built-in voltmeter that senses AC line voltage and this feature displays the voltage being read. The control board automatically responds to sustained low-voltage or high-voltage conditions by shutting down the air conditioning system to prevent compressor damage. At installation, the control board voltmeter should be calibrated to line voltage within +/- 1%. To check or re-calibrate AC line voltage:
Line voltage will be displayed as the last two digits of the voltage. On 115V systems, 95V appears as “95”, 100V as “00”, and 120V as “20”. On 230V systems, 190V will appear as “90”, 200V as “00”, and 230V as “30”.
To check accuracy or to calibrate, turn off all on-board AC loads and measure the line voltage with an accurate voltmeter.
Press the UP or DOWN buttons to recalibrate the value as required.
9: Temperature Calibration
This feature calibrates the ambient sensor within a range of ±1%. The temperature sensor should be within one or two degrees of actual room temperature. Note that setting increments are in °F even when the control is set to display °C. Adjust this parameter to display the correct room-temperature reading.
The sensed temperature is displayed. Place an accurate thermometer beside the sensor and compare the temperatures.
Press the UP or DOWN buttons to recalibrate the value as required.
10: Dehumidification Pre-Circulation Time
(Factory Default: 10 minutes)
The Humidity Control Program (HU) automatically operates the air conditioning system for a programmed time period to help control humidity in the boat. This dehumidification feature works in three stages:
1. The fan comes on at high speed to circulate air for ten minutes.
2. The fan then drops to low speed, and the compressor cycles on in the Cool Mode to dehumidify.
3. After the dehumidification cycle, the system turns off. The process repeats according to the programmed time period.
The Compressor Time Delay (Programmable Function 1) setting governs when the dehumidification cycle starts. Every one­second of compressor delay equals a six-minute advance into the dehumidification cycle.
The factory default settings are:
10: Pre-circulation cycle - 10 minutes
11: Dehumidification cycle - 30 minutes
12: Overall time period - 12 hours
The factory settings are adequate for most moderate climates and boats. For very humid climates, shorten the overall time period and extend the dehumidification time. In dry climates, select a longer overall time period between cycles and a shorter dehumidification time. Programmable Function 10 governs the pre-circulation cycle time and should not be changed.
11: Dehumidification Time
(Factory Default: 30 minutes)
The dehumidification time determines how long the compressor runs in the Dehumidification Mode (see Programmable Function 10). The display shows the dehumidification time period in minutes.You can select 10, 20, 30, 40, 50 or 60 minutes. Select a longer dehumidification time in climates with high humidity and a lower dehumidification time in climates with low humidity.
12: Dehumidification Overall Time Period
(Factory Default: 12 hours)
This setting determines how often the system performs the dehumidification process. The display shows the overall time period in hours. You can select intervals of 2, 4, 6, 8, 10, 12, 14 or 16 hours. Choose a shorter overall time period in climates with high humidity and a longer overall time period in climates with low humidity.
10 L-2516 ENGLISH
Page 13
Q3 & Qht Controls for Direct Expansion Systems Programmable Functions
Table 3: Recommended Humidity Control Settings
Outside Temperature Relative Humidity Time Period Dehumidification Time
Below 80° F (27°C) 75-85% 12 hours 10 minutes
Above 85% 8 hours 20 minutes
80° - 90° F (27°- 32°C) 75-85% 10 hours 30 minutes
Above 85% 6 hours 40 minutes
Above 90° F (32°C) 75-85% 8 hours 40 minutes
Above 85% 6 hours 60 minutes
13: Software Revision Level
This setting displays the software version and revision level of the system. It will display a 2-digit number such as “05” for version 5. Have this information ready prior to calling a dealer or the factory for service assistance.
14: Determining Your Product Type
This setting displays the product type of the system being used. Have this information ready prior to calling a dealer or the factory for service assistance. “dE” displays for marine Direct Expansion Self-Contained and Remote Products; “CH” displays for Chilled Water or Modulating Air Handlers.
15: Low-Pressure Switch Test
The Low-Pressure Switch Test is used to test the low-pressure circuit for a fault or to test for low charge in system. This test can also be used to charge a system. Press the MODE button to enter the Low-Pressure Switch Test. During the test, the unit will operate in Cool Mode at high fan speed, and the display will show “OA” (closed circuit) if the low-pressure switch circuit is OK or “FA” (open circuit) if the low-pressure switch circuit has a fault or system is low on charge. Press the FAN button to exit this test mode.
.
WARNING
During this test, low- and high-pressure faults are ignored. The system must be monitored closely during this test, and the system must be shut down immediately if pressures exceed 425 psi for R-417A or 575 psi for R-410A. The system should only be operated for a brief period of time if pressures fall below 30 psi for R-417A or 60 psi for R-410A.
16: High-Pressure Switch Test
The High-Pressure Switch Test is used to test the high-pressure circuit for a fault or to test for an overcharged system or loss of water flow. Press the MODE button to enter the High-Pressure Switch Test. During the test, the unit will operate in Cool Mode at high fan speed, and the display will show “OA” (closed circuit) if the high-pressure switch circuit is OK or “FA” (open circuit) if the high-pressure switch circuit has a fault or system is overcharged or has loss of water flow. Press the FAN button to exit this test.
.
WARNING
During this test, low- and high-pressure faults are ignored. The system must be monitored closely during this test, and the system must be shut down immediately if pressures exceed 425 psi for R-417A or 575 psi for R-410A. The system should only be operated for a brief period of time if pressures fall below 30 psi for R-417A or 60 psi for R-410A.
17: LED/LCD SegmentTest
Press the MODE button to test the display. All LED segments (Q3) or LCD graphics (Qht) should display. Press the FAN button to exit this test.
18: Sleep Mode
(Factory Default: On)
You can set the Q3’s LED brightness level to dim or you can set the Qht’s backlight to be on or off. Select “SL” for Sleep Mode and the LEDs will remain dim or the backlight will remain off until a key is pressed, which will temporarily brighten the display. Select “On” and the Q3’s LEDs will stay at the current brightness setting or the Qht’s backlight will stay on.
L-2516 ENGLISH 11
Page 14
Programmable Functions Q3 and Qht Controls for Direct Expansion Systems
19: Cool-Only Mode
(Factory Default: HP)
You can select Heat Pump or Cool-Only operation. Select “HP” and the unit will operate in the default Heat Pump Mode, which allows for cooling, reverse cycle heating and (optional) electric heat modes. Select “CL” for cool-only operation and the unit will operate in Cooling or (optional) electric heat modes.
.
NOTE
If you select “CL” Cool-Only mode, a 2-minute compressor delay will initiate whenever the compressor shuts down on set point, a fault, or a power outage. The two minute delay will begin immediately after compressor shuts down. The display will show the remaining time delay countdown at two second intervals when compressor is called to operate within the two minute countdown period. If the two minute delay period has passed before the compressor is called to operate, the compressor will come on with no delay.
20: High Pressure Delay
(Factory Default: 3 minutes)
This function is used when the standard 3-minute delay during the high pressure fault routine requires an extended delay. The delay can be increased up to 5 minutes between high-pressure-fault off cycles.
21: Anti-Icing Routine Adjustment
(Factory Default: 70°F)
The anti-icing routine prevents ice build up on the evaporator coil during extended periods of cooling operation. Installation variables such as grille sizes, length of ducting, insulation, and ambient temperatures determine the run time required to achieve set point. Factors that substantially increase run time include operating the system with hatches and doors open, and programming an unrealistic set point (e.g. 65°F/18.3°C). Such situations can cause the evaporator to form ice on warm humid days.
This function is used during cooling operation to allow any ice that may have formed on the evaporator coil to melt when the cabin temperature drops below 70°F (default). This routine works in 10-minute cycles during which time the compressor cycles off for 15 seconds for each degree the ambient-temperature is below 70°F (default) and runs during the rest of the 10-minute cycle. For example, if the inside temperature is 67°F, the compressor will shut off for 45 seconds (3 x 15 seconds), and then run for nine minutes and 15 seconds (10 minutes minus 45 seconds), repeating in 10-minute intervals. You may adjust the cabin temperature at which the Anti-Icing routine is initiated. The range of adjustment is 65°F to 80°F.
22: Fan Speed Division
(Factory Default: 5)
You can select either 5 or 3 fan-speed divisions based on the Fan Response Differential (see Programmable Function “4: Fan Response Differential” on page 9). The default is set at 5 fan-speed divisions.
Q3 - Displays either the individual High, Medium and Low fan-speed LEDs if 3 speeds are selected, or a combination of the High, Medium and Low fan-speed LEDs if 5 speeds are selected, for example:
Low Speed = Low LED
Medium Low Speed= Medium and Low LEDs
Medium Speed = Medium LED
Medium High Speed = Medium and High LEDs
High Speed = High LED
Qht - Displays 5 bars to indicate the five distinct speed changes or groups the bars to show three distinct speed changes.
23: Aux Heat Enabled/Disabled
(Factory Default: “- -” Disabled)
The control allows operation of an optional auxiliary (aux) electric heater. The default for this feature is “- -” indicating disabled. If an aux heater upgrade kit is installed, change this setting to “h1”. Selecting “h1” allows the electric heater to be operated independently of the reverse-cycle heating and never at the same time.
.
NOTE
If you enable the aux heat function (“h1”), the fan will delay turning off for 30 seconds to allow the electric heater to cool down. The delay occurs when the electric heater cycles off after set point is reached or when the mode is changed.
12 L-2516 ENGLISH
Page 15
Q3 & Qht Controls for Direct Expansion Systems Programmable Functions
24: Seawater Low Limit Adjustment
(Optional; Factory Default: 40
If the optional seawater sensor is connected to the control board, this feature allows the system to switch from reverse-cycle heat to electric heat (if an auxiliary electric heater is installed and enabled) if the seawater temperature drops below 40°F (4.4°C) (default) and the reverse-cycle heat has operated more than five minutes. Once the seawater rises 3°F above the Seawater Low Limit temperature, the system returns to reverse-cycle heating. If an aux heater is not installed, the system will shut down and flash “LO” then “SE” when the seawater drops below 40°F (4.4°C) (default). Once the seawater rises 3°F above the Seawater Low Limit temperature, the system goes back into reverse-cycle heating and stops flashing “LO” then “SE”. The range of adjustment is 35°F to 50°F.
25: Humidity Sensor Limit Adjustment
(Optional; Factory Default: 60%)
If the optional humidity sensor is connected to the control board, this feature allows the system to dehumidify with electric heat (if electric heat is installed and enabled) when the cabin humidity rises above 60% (default) relative humidity (RH). When the room temperature has reached the set point, the compressor will turn off. The display will indicate that the system is in "Dehumidify" mode. If the temperature decreases by one degree, the electric heat will turn on to maintain the set point. If the temperature increases back to set point, the electric heat will turn off. If the temperature increases one degree above the set point, the compressor will then turn back on. This operation will continue until the cabin’s relative humidity is less than 60% (default). If an electric heater is not installed, the compressor run time will extend by operating to 1°F lower than set point. This cycle continues until the cabin’s relative humidity is less than 60% (default). The range of adjustment is 50% to 80% RH.
26: Air Filter Timing Setting and Reset
(Factory Default: 0)
Use this feature for a reminder to clean or replace the unit’s air filter. Select the number of operating hours until the filter reminder appears in the display flashing “Ar” then “FL”. The value entered represents that number times 100 hours. Function values are between 1 (100 hours) and 25 (2500 hours). Dometic recommends that you check the air filter at least every 500 hours of operation. The default setting is off, designated with “00”. To reset the timer and stop the flashing filter reminder, press the FAN, UP, and DOWN buttons simultaneously.
27: Select FAMU Operation (future feature)
28: CAN Bus Unit ID
(Factory Default: 59)
This feature allows all units with a CAN Bus adapter installed to be networked together to communicate with each other or the ship’s CAN Bus system (with additional translator equipment in some cases). Enter the unit’s CAN Bus Unit ID number.
29: CAN Bus Group ID
(Factory Default: 58)
This feature allows all units with a CAN Bus adapter installed to be grouped together in a network system and communicate with the ship’s CAN Bus system (with additional translator equipment in some cases). Enter the unit’s CAN Bus Group ID number.
30: Custom Medium Fan Speed (only with U-Board platform)
(Factory Default: 2)
You can set the number of fan speeds that can be modified by selecting either 2 or 5 speeds (if function 22, Fan Speed Division, is set to 5). If function 22 is set to 3, the selection options for function 30 will be 2 or 3, and if 3 is selected, then function 32, Medium Fan Speed, will be enabled. If function 22 is set to 5, you can modify 3 more fan speeds: Medium Low, Medium, and Medium High, as functions 31, 32, and 33 are enabled.
31: Fan Speed Medium Low (only with U-Board platform)
(Factory Default: 50)
You can adjust the Medium Low fan speed to suit individual preferences. For instance, you may wish to decrease the Medium Low fan speed setting in your stateroom to minimize fan noise.
32: Fan Speed Medium (only with U-Board platform)
(Factory Default: 62)
You can adjust the Medium fan speed to suit individual preferences. For instance, you may wish to decrease the Medium fan speed setting in your stateroom to minimize fan noise.
33: Fan Speed Medium High (only with U-Board platform)
(Factory Default: 74)
You can adjust the Medium High fan speed to suit individual preferences. For instance, you may wish to decrease the Medium High fan speed setting in your stateroom to minimize fan noise.
°F)
L-2516 ENGLISH 13
Page 16
Programmable Functions Q3 and Qht Controls for Direct Expansion Systems
SUMMARY TABLE OF PROGRAMMABLE FUNCTIONS
Table 4: Programmable Functions - Ranges and Factory Defaults
Function Number Description Factory Default
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23 Aux Heat Enable/Disable “- -” “- -” = Aux Heat Disabled
24 Seawater Low Limit Temp 40 (°F) 35 to 50 °F
25 Humidity Sensor Limit 60 (%RH) 50 - 80 %RH
26 Air Filter Timing Setting
27 Select FAMU (Fresh Air Make-
28 CAN Bus Unit ID 59 0 - 99
29 CAN Bus Group ID 58 0 - 99
30 Custom Medium Fan Speeds 2 (only with U-Board) 2 or 5, or 2 or 3
31 Medium Low Fan Speed 50 (only with U-Board) 2 - 99
32 Medium Fan Speed 62 (only with U-Board) 2 - 99
33 Medium High Fan Speed 74 (only with U-Board) 2 - 99
Compressor Time Delay 0 0 - 70 seconds
Display Fahrenheit, Celsius, or Auto
Compressor Differential 12 (12/8 = 1.5°F [0.8°C]) 2 - 31
Fan Response Differential 8 (8/8 = 1°F [0.6°C]) 2 - 31
Low Fan Speed 38 2 - 57
High Fan Speed 85 41 - 99
Fan Mode C (Continuous) C (Continuous)
AC Line Voltage Calibration -- Plus or minus 1%
Temperature Calibration -- Plus or minus 1%
HU (Humidity) Pre-circulation 10 (minutes) 0 - 30 minutes
HU Dehumidification 30 (minutes) 10 - 60 minutes
HU Time Period 12 (hours) 2 - 16 hours
Software Revision (current version) n/a
Product Software dE = Direct Expansion
Low-Pressure Switch Test OA = OK
High-Pressure Switch Text OA = OK
LCD or LED Segment Test Displays all LCD graphics or
Sleep Mode LCD backlight off or LEDs dim
Cool-Only Mode HP HP = Heatpump
High-Pressure Delay 3 (minutes) 1 - 5 minutes
Anti-Icing Routine Adjustment 70 (°F) 65 - 80 °F
Fan-Speed Divisions 5 3 = 3 speeds
(x100 hours)
Up) Operation (future feature)
F F, C, or A (only with U-Board)
CH = Chilled Water or Modulating Air Handler
FA = Fault
FA = Fault
LED segments
On On = Continuous display
0 0 = Disabled
“- -” “- -” = Normal
Custom
Settings Function Range
I (Intermittent)
n/a
n/a
n/a
n/a
SL = Sleep Mode
CL = Cool Only
5 = 5 speeds
“h1” = Aux Heat Enabled (Reverse-cycle heat and aux heat operate independently)
1 - 25 (100 - 2500 hours)
FA = FAMU
14 L-2516 ENGLISH
Page 17
Q3 & Qht Controls for Direct Expansion Systems High-Pressure Shutdown (HI / PS)
FAULT AND ERROR MESSAGES
To protect the equipment, certain fault conditions trigger a shutdown, and the system will not restart until the fault is repaired.
If an operational failure occurs, the display will flash one of the following fault or error code messages. Fault code displays are canceled by pressing the MODE button (Q3) or POWER button (Qht)..
NOTE
Your system must be equipped with the optional high-pressure switch and low-pressure switch for the high- and low­pressure shutdown to operate. Check with your dealer to make sure these important protective devices are installed properly.
HIGH-PRESSURE SHUTDOWN (HI / PS)
The high-pressure switch is monitored by the control board. The high-pressure switch opens when the discharge pressure rises above a preset maximum limit. The high-pressure fault routine operates differently in the Cool and Heat Modes.
IN COOL MODE
In Cool Mode, if the high-pressure switch opens, the control board will attempt three restarts and display a three-minute countdown between restarts before it shuts down the entire system. The display will alternately flash “HI” and “PS”. This is a sustained shutdown, and even when the pressure lowers after shutdown, the system will remain off until reset by pressing the MODE button (Q3) or POWER button (Qht).
IN HEAT MODE
In Heat Mode, if the high-pressure switch opens, the control board will shut down the compressor for three minutes. The display will alternately flash “HI” and “PS” while the fan continues to run, allowing the heat in the coil to dissipate. This prepares the system for recycling in the Heat Mode. The compressor will then continue to cycle, based on input from the high-pressure switch, until the cabin temperature reaches set point, after which compressor cycling is automatically restored to normal operation.
LOW-PRESSURE SHUTDOWN (LO / PS)
When the optional low-pressure switch is installed, it is monitored by the control board. The low-pressure switch opens when the suction pressure drops below a preset minimum limit. The low-pressure fault routine operates differently in the Cool and Heat Modes.
IN COOL MODE
In Cool Mode, if the low-pressure switch opens, the unit will first run for two minutes then shut down for 50 seconds. It will do this four times. If the switch has not closed, the unit will shut down for 15 minutes, and the display will alternately flash “LO” and “PS”. After 15 minutes of shut down, the cycle starts again, in which the unit runs for two minutes and then shuts down for 50 seconds.
If, after 8 attempted compressor starts, the low-pressure switch does not stay closed, the unit will go into a sustained shutdown and the display will alternately flash “LO” and “PS”.
If the low-pressure switch closes at any time before the sustained shutdown, the unit will then operate normally.
IN HEAT MODE
In Heat Mode, if the low-pressure switch opens, the fan will automatically change to low speed to try and raise system pressure. It will run for 11 minutes in this mode. Note that the fan speed can not be adjusted during this time. Any attempt to raise fan speed will result the display alternately flashing “LO” and “PS” while the unit continues to run.
After 11 minutes, the unit will run for two minutes, then shut down for 50 seconds. It will do this four times. If the switch has not closed, the unit will shut down for 15 minutes, and display will alternately flash “LO” and “PS”. After 15 minutes of shut down, the cycle starts again, in which the unit runs for two minutes and then shuts down for 50 seconds.
If, after 8 attempted compressor starts, the low-pressure switch does not stay closed, the unit will go into a sustained shutdown and the display will alternately flash “LO” and “PS”.
If the low-pressure switch closes at any time before the sustained shutdown, the unit will then operate normally.
LOW-VOLTAGE SHUTDOWN (LO / AC)
The low-voltage protection feature is always active. If AC line voltage drops and remains below the limit (90 volts for a 100V system, 100 volts for a 115V system, or 200 volts for a 230V system) for more than three minutes, the control shuts down the entire system. The display will alternately flash “LO” and “AC”. This is a sustained shutdown, and the system will not resume operation even if the line voltage returns to normal levels. To reset, press the MODE button (Q3) or POWER button (Qht).
For the low-voltage shutdown function to work properly, the control board internal voltmeter should be calibrated. This should be done when the system is installed. To check or recalibrate line voltage, see “8: AC Line Voltage Calibration” on page 10.
L-2516 ENGLISH 15
Page 18
Summary of Fault Codes and Indicator Codes Q3 and Qht Controls for Direct Expansion Systems
SUMMARY OF FAULT CODES AND INDICATOR CODES
Table 5: Fault-Code and Indicator-Code Descriptions and Results
Code Description Result
LO / AC Operating voltage remained below acceptable limit for 3 minutes or more (100V for a
115V system or 200V for a 230V system).
HI / PS Head pressure above maximum preset limit. Indicates pump failure or loss of water
flow.
HP / - - High-pressure switch failed open or circuit wires open. Shutdown
LO / PS Suction pressure below minimum preset limit. Indicates loss of gas, or water too cold
for heating during Heat Mode.
LP / - - Suction pressure below minimum preset limit, failed low-pressure switch or circuit wires
open.
- - (flashing) Display connected to SMXII unit. The two components are not compatible. No Operation
IS / - - or - - Inside temperature sensor failure flashes IS / - - for 3 seconds if MODE button is
pressed. After 3 seconds, display shows constant - -. Cool or Heat Mode may be selected for emergency operation and display will show a constant - -.
Ar / FL Display flashes Ar / FL for 15 seconds every 30 minutes indicating return air filter needs
to be cleaned or replaced. Reset and stop flashing by pressing the FAN, UP, and DOWN buttons simultaneously.
LC LC flashes momentarily if a button is pressed indicating the display is locked in current
mode of operation. Enter or exit lock mode by pressing the MODE, UP, and FAN buttons simultaneously. UL flashes for 3 seconds when exiting lock mode.
OU or Outside / 1st digit / 2nd 2 digits or OU or Outside / - -
Displays the optional outside temperature as OU (Q3) or Outside (Qht) then the first digit followed by second two digits. Displays OU or Outside / - - if optional outside temperature sensor is not installed or failed open or shorted. See “Button Functions” on page 6 for instructions.
Shutdown
Shutdown
Shutdown
Shutdown
Emergency Operation
Continue Operation
Continue Operation
Continue Operation
LO / SE After 5 minutes of compressor reverse-cycle heat operation, compressor shuts down if
optional seawater sensor is installed and temperature drops below 40°F (4.4°C). If an optional electric heater is installed, operation switches from compressor reverse-cycle heat to electric heater until seawater temperature rises above 43°C (6.1°C). Refer to “24: Seawater Low Limit Adjustment” on page 13.
SE or Water / 1st 2 digits or SE / - -
HS / 1st 2 digits or HS / - -
Displays the optional seawater temperature as SE (Q3) or Water (Qht) then the first digit followed by second two digits. Displays SE or Water / - - if optional seawater temperature sensor is not installed or failed open or shorted. See “Button Functions” on page 6 for instructions.
Displays the optional relative humidity as HS / then the first two digits of relative humidty. Displays HS / - - if optional humidity sensor is not installed or failed open or shorted. See “Button Functions” on page 6 for instructions
INITIAL SYSTEM START UP
1. Open the seacock (seawater inlet valve).
2. Turn on the circuit breaker for the air conditioner. If a pump relay is installed, the breaker for the pump must also be turned on.
3. Turn the control on.
4. Use the control to set the system for cooling or heating and adjust the set point temperature so the unit will turn on.
Shutdown or Switch to Optional Electric Heat.
Continue Operation
Continue Operation
16 L-2516 ENGLISH
Page 19
Q3 & Qht Controls for Direct Expansion Systems General System Troubleshooting
5. Check for a steady solid stream of water from the overboard discharge. If more than one unit is installed, then check all such discharges.
6. Verify that there is steady airflow out of the supply-air grille.
7. Allow unit to run for ten minutes at high fan speed. Check the temperature differential between discharge and return air by placing an accurate thermometer in front of the discharge grill and then in front of the return air grill.
In Cool Mode the difference between the discharge and return should be 15 - 20°F (8.3 - 11.1°C), with normal ambient air and water temperatures.
In Heat Mode the differential can be as high as 25°F (13.9°C).
If the unit does not appear to be operating properly, refer to the guidelines in “TROUBLESHOOTING” on page 17.
IMPORTANT
Do not turn the unit off then immediately turn it back on. Allow at least 30 seconds for refrigerant pressure to equalize.
TROUBLESHOOTING
GENERAL SYSTEM TROUBLESHOOTING
Before you call for service, review this list. It may save you time and expense. This list contains common occurrences that are not a result of defective workmanship or materials. If you need service after trying these procedures, call your nearest Dometic dealer.
See additional troubleshooting information in the manual for your specific air conditioning system. See also “Digital-Controls Troubleshooting” on page 20.
Table 6: General System Troubleshooting
PROBLEM POSSIBLE REASON/SOLUTION
System will not start. 1. Air conditioner circuit breaker is off. Turn circuit breaker on at ship’s panel.
2. Digital control is not turned on. Press the Power button.
3. Wrong wiring at terminal strip. Check wiring diagram; correct if necessary.
4. Input-line voltage is insufficient. Check power source (shore/generator) for proper voltage. Check wiring and terminals for proper sizes and connections. Verify with a volt-meter that the power at the unit is the same as the power source.
5. Push-on connectors or butt splices became disconnected during installation. Disconnect power supply and open electric box, check wiring diagram, correct if necessary.
System runs continuously. 1. Set point temperature is improperly set: too low for cooling or too high for
heating. Raise or lower set point.
2. Porthole or hatches open. Close all port holes and hatches.
3. Improper air sensor location. Check your specific control troubleshooting section.
4. Seawater temperature too high for cooling or too low for heating. Seawater temperature will directly affect the air conditioning unit’s efficiency. This air conditioning unit can effectively cool your boat in water temperatures up to 90°F (32.2°C) and heat (if reverse cycle option is installed) in water as low as 40°F (4.4°C).
L-2516 ENGLISH 17
Page 20
General System Troubleshooting Q3 and Qht Controls for Direct Expansion Systems
Table 6: General System Troubleshooting (continued)
PROBLEM POSSIBLE REASON/SOLUTION
Low airflow. 1. Airflow is blocked. Remove any obstructions in return-air stream. Clean return-air
filter and grille. Check for crushed or restricted ducting; ducting must be as straight, smooth and taut as possible.
2. Fan Coil is iced. See below.
3. Fan speed is set to manual low. If the fan speed is set to manual low, press and release the Fan button until the desired fan speed and airflow are reached. If you want automatic fan speed control, press and release the Fan button until the letter “A” displays.
Fan is not running.
Check “Digital-Controls Troubleshooting” on page 20.
No cooling or heating. 1. Temperature set point is satisfied. Lower or raise set point.
2. Obstructed seawater flow. Clean seawater strainer. Check for obstructions at speed scoop thru-hull inlet. Check for a good steady flow from the overboard discharge.
3. Seawater pump may be air-locked. Remove hose from pump discharge to purge air from line.
4. Loss of refrigerant gas. Check air conditioning unit for refrigerant oil leakage, call service technician.
5. Seawater temperature too high for cooling or too low for heating. Seawater temperature will directly affect air conditioning unit’s efficiency. This air conditioning unit can effectively cool your boat in water temperature up to 90°F (32.2°C) and heat (if reverse-cycle option is installed) in water temperatures as low as 40°F (4.4°C).
6. Fan coil is iced (in cooling). Check your specific control troubleshooting section.
7. Fan is not running. Check your specific control troubleshooting section.
8. Control is in fan-only mode. Set system for Cool Mode or Heat Mode.
9. Seawater plumbing is air-locked. Ensure that seawater plumbing is installed per the guidelines in this manual.
10. Digital control is programmed for Cool or Heat only. See “Digital-Controls Troubleshooting” on page 20.
11. High-pressure switch is open (in cooling) due to improper seawater flow. Strainer or intake may be plugged, seacock may be closed, check seawater hose for kinks or collapses. Verify pump operation. Check pump circuit breaker if applicable.
12. High-pressure switch is open (in heating) due to improper airflow. Remove any obstructions in return air stream. Clean return air filter and grille. Check for crushed or restricted ducting, ducting must be as straight, smooth and taut as possible.
13. High-pressure switch is open (in heating) due to high seawater temperature. System may cycle on high pressure if seawater temperature is above 55°F (12.8°C).
14. Compressor’s thermal overload is open due to either of the above reasons. Compressor needs to cool down. Turn system off for a while (it may take up to three hours to reset thermal overload).
No heating. Unit is in cool-only mode, or if reverse cycle, reversing valve may be stuck.
reversing valve lightly with rubber mallet while unit is in heat mode. Call for service if that does not correct the problem.
Tap
18 L-2516 ENGLISH
Page 21
Q3 & Qht Controls for Direct Expansion Systems General System Troubleshooting
Table 6: General System Troubleshooting (continued)
PROBLEM POSSIBLE REASON/SOLUTION
Fan coil is iced. 1. Thermostat set point is too low. Raise set point.
2. Improper airflow. Remove any obstructions in return air stream. Clean return air filter and grille. Check for crushed or restricted ducting, must be as straight, smooth and taut as possible. See “Digital-Controls Troubleshooting” on page 20 for reprogramming options.
3. Supply air is short-cycling. Redirect supply air so that is not blowing into the return air stream. Seal any air leaks on duct.
4. Humidity level too high. Close hatches and doors.
5. When all else fails. Switch air conditioning unit to heat until ice melts or use hair dryer to melt.
Water coil is iced in the Heating Mode.
Seawater temperature is below 40°F (4.4°C).
condenser. Allow coil to defrost.
Shut down system to prevent damage to
L-2516 ENGLISH 19
Page 22
Digital-Controls Troubleshooting Q3 and Qht Controls for Direct Expansion Systems
DIGITAL-CONTROLS TROUBLESHOOTING
See also “General System Troubleshooting” on page 17.
Contact an authorized Dometic servicing dealer if the problem continues or for replacement parts.
WARNING
The control board operates at 115VAC or 230VAC. Make sure the power is off before removing the cover of the control box.
Table 7: Digital-Controls Troubleshooting
PROBLEM POSSIBLE REASON/SOLUTION
Digital display panel is not lit.
1. No power. Turn circuit breaker on.
2. Wrong power board. Control must be connected to a Q-Logic or U-Board. It will not work with an SMXII Power Board. Replace with Q-Logic or U-Board.
3. Check CXP and TSEP cable and connections. Replace CXP or TSEP cables if necessary.
4. Failed equipment. Replace control, or Q-Logic or U-Board.
Erratic temperature display. 1. Shut power to the unit off and back on.
2. Perform Restore Factory Settings.
3. Check sensor cable and connections.
4. Ensure the temperature sensor is installed properly.
5. Calibrate temperature.
6. Replace Q-Logic or U-Board.
Erratic system operation. 1. Shut power to the unit off and back on.
2. Check CXP cable and connections.
3. Checktemperature sensor, cable and connections.
4. Replace control.
5. Replace Q-Logic or U-Board.
Fan is not running or runs continuously.
Fan is not running but the
Digital control is programmed for either fan cycling with compressor or continuous fan operation.
a heat cycle ends the fan will stay on for 30 seconds even if the fan is set to cycled operation.
Failed triac on circuit board. Send for repair or call local service technician.
Change Programmable Function 7. Note: When configured for aux heat, after
compressor is .
Fan runs continuously
Failed triac on circuit board. Send for repair or call local service technician.
although it is set to cycle with compressor.
No cooling or heating. 1. Digital control programmed for heat or cool only. Reprogram function 19.
2. "HI / PS" or "LO / PS" is flashing. See below.
No heat. Digital Control may be set to Cool Only, not Reverse Cycle.
Function 19.
Change Programmable
Fan coil is iced. Improper airflow. See “General System Troubleshooting” on page 17 first, before
reprogramming digital control.
Change Programmable Function 21 to increase duration of Anti-Icing Routine. If anti-icing cycle does not melt ice, switch air conditioning unit to heat until ice melts or use hair dryer to melt ice.
System runs continuously. Improper air sensor location. Verify air sensor location with criteria found in the control
manual. Ensure that sensor is located out of direct sunlight and away from open doors or hatches.
20 L-2516 ENGLISH
Page 23
Q3 & Qht Controls for Direct Expansion Systems Condensate Drains
Table 7: Digital-Controls Troubleshooting (continued)
PROBLEM POSSIBLE REASON/SOLUTION
"Ar / FL" is flashing. (Filter Reminder)
"HI / - -" is flashing. 1. High-pressure switch is open (in cooling) due to improper seawater flow.
"LO / - -" is flashing. 1. Low-pressure switch is open due to low seawater and/or low return air
"HI / PS" is flashing. (High Pressure)
"LO / PS" is flashing. (Low Pressure)
"LO / AC" is flashing. (Low AC Voltage)
Filter needs to be cleaned or replaced.
pressing the FAN, UP, and DOWN buttons simultaneously.
Strainer or intake may be plugged, seacock may be closed. Check seawater hose for kinks or collapses. Verify pump operation; check pump circuit breaker if applicable.
2. High-pressure switch open (in heating) due to improper airflow. Remove obstructions in return air stream. Clean air filter and grille. Check for crushed or restricted ducting. Ducting must be as straight, smooth and taut as possible.
If problem persists, reprogram Low Fan Speed Limit for maximum value. Set Programmable Function 5 to 57.
temperatures. Try restarting the air conditioning unit, the optional low pressure switch has a ten minute shutdown time delay that may be in effect.
2. Low pressure switch is open due to loss of refrigerant. Check air conditioning unit for refrigerant oil leakage, call service technician.
1. Head pressure above 425 PSI for R-22 or R-417A systems or above 575 PSI for R-410A systems.
1. Head pressure below 30 PSI for R-22 or R-417A systems or below 60 PSI for R­410A systems.
1. Supply voltage is too low. Verify power to unit with multimeter.
2. Voltage is improperly calibrated. Verify that Programmable Function 8 matches voltage reading to unit with a multimeter. Adjust Programmable Function 8 if necessary.
Clean or replace filter. Reset and stop flashing by
"- -" is flashing. Display connected to SMXII unit instead of a Q-Logic or U-Board.
Logic or
U-Board.
MAINTENANCE OF SYSTEM COMPONENTS
CONDENSATE DRAINS
At least once every three months, check the condensate drains for obstructions by pouring a quart of water rapidly into the condensate pan. If it does not drain completely within 30 seconds, check the drain outlets for clogging. Remember that many air conditioning units have two drains and hoses, one at each end of the drain pan.
RETURN-AIR FILTER
Check the return-air filter about once a month and replace or clean as necessary. To clean the filter, remove it from the unit, rinse with water, air dry and reinstall.
SEAWATER CONNECTIONS
Verify that all seawater connections are tight, and check for water flow from each unit’s overboard discharge.
SEAWATER PUMP
If the seawater pump has a plastic pump head, then the impeller is made of either plastic or rubber and should be inspected after 300 hours of operation. Replace the impeller if it is worn. If the seawater pump head is made of bronze, then the impeller is too, and regular maintenance is not needed as often; inspect the pump if there are signs of reduced seawater flow.
Replace with Q-
L-2516 ENGLISH 21
Page 24
Seawater Strainer Q3 and Qht Controls for Direct Expansion Systems
SEAWATER STRAINER
Ensure your pump receives adequate seawater flow by regularly cleaning the strainer basket. Check it daily. Periodically check the overboard discharge for a steady stream of water. Check seawater intake speed scoop for obstructions. Make sure hoses are not looped, kinked or crushed.
REFRIGERANT GAS
The refrigerant gas used in the air conditioning system is adequate for the life of the system. Routine “seasonal” charging of the system is not typically necessary.
REVERSING VALVE
Reverse-cycle (cooling and heating) units have a reversing valve that must be energized periodically to keep the internal parts moving freely. To do this, switch the air conditioner unit into Heat Mode for a few seconds once a month.
CONDENSER COIL
A marine-growth-fouled coil reduces efficiency, raising total system pressure and decreasing its ability to produce cold air.
1. With the system turned off at the circuit breaker on the ship’s panel, disconnect the inlet and outlet connections of the condenser coil.
2. Use chemical-resistant hoses (white PVC 5/8" I.D., etc.) to connect the inlet of the condenser coil to the outlet of a chemical resistant, submersible pump (P-500 pump, etc.) and let the hose connected to the coil outlet flow freely into the container mentioned below.
3. Place a strainer or piece of screen over the inlet of the pump and submerse the pump into a container filled with a 5% solution of muriatic or hydrochloric acid and fresh water or use a premixed over-the-counter solution. Use as large a container as possible to hold the solution (5-25 gallons [19-95 liters]).
CAUTION
Avoid spilling or splashing the solution. Follow all warnings and recommendations given by the manufacturer of any acids or premixed solutions.
4. Power the pump and circulate the solution through the condenser coil for 15-45 minutes depending upon the size of the coils and the extent of the contamination. Visual inspection of the solution in the container should indicate when the contamination removal has stopped.
5. Circulate fresh water through the coil to flush any residual acid from the system.
6. Restart the system and check operational parameters to ensure thorough cleaning has taken place. Additional cleaning may be necessary with extreme contamination.
NOTE
For the purpose of protecting the environment, dispose of any contaminated acid solutions in accordance with federal, state and/or local regulations.
WINTERIZATION
There are several methods of winterization, some of which work better than others. Any method that causes the antifreeze solution to flow downward is the method of choice. By this means, the antifreeze solution displaces any trapped water and eliminates the possibility of it freezing in hidden areas.
Choose the method that works best for you. In the following four methods, the first two use a 50/50 nonpolluting biodegradable antifreeze/water solution:
Pump antifreeze solution into the overboard thru-hull fitting, and discharge through the intake thru-hull fitting.
Use the seawater pump to pump antifreeze solution through the system and discharge through the overboard thru-hull fitting: Close seacock, remove hose from strainer discharge, raise hose above pump (so pump does not lose its prime) and pour in antifreeze solution. Pump solution through system. The strainer and hose to seacock need to be drained of water.
Use pressurized air injected at the overboard discharge fitting to force system water through the seawater intake fitting, thus expelling any trapped water from the system.
Use pressurized air injected at the seawater intake fitting to force system water through the seawater overboard discharge fitting, thus expelling any trapped water from the system.
22 L-2516 ENGLISH
Page 25
Q3 & Qht Controls for Direct Expansion Systems Operational
In addition, since the seawater pump utilizes a magnetically driven impeller, remove the impeller from the wet-end assembly, wipe with an alcohol solution, and store in a warm, dry area until commissioning takes place.
NOTE
Collect all discharged liquids and recycle or dispose of in a proper manner in accordance with federal, state and/or local regulations.
SPECIFICATIONS
OPERATIONAL
Set Point Operating Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55°F to 99°F (12.8°C to 37.2°C)
Sensor Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .± 2°F @ 77°F (±1.1°C @ 25°C)
Low Voltage Limit 115 Volt Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 VAC
Low Voltage Limit 220 Volt Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 VAC
Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 through 240 VAC
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 or 60 Hz
Fan Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Amps @ 115 VAC/230 VAC
Valve Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Amps @ 115/230 VAC
Aux Heater Output (using off-board relay) . . . . . . . . . . . . . . . . . . . . . 30 Amps @ 115 VAC/230 VAC
Pump Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4 HP at 115 VAC or 1/2 HP at 230 VAC
Compressor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 HP @ 115 VAC/2 HP @ 230 VAC
Minimum Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°F (-17.8°C)
Maximum Ambient Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .180°F (82.2°C)
Maximum RH Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99% Non Condensing
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Less Than 5 Watts
DIMENSIONS
Q3 Display Panel . . . . . . . . . . . . . . . . . . . . . . .3.50” (89mm) W x 2.53" (65mm) H x 0.75” (19mm) D
Qht Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.84” (123mm) W x 3.27" (83mm) H
Qht Panel Cut Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7/16" (88mm) W x 2-1/8" (54mm) H
Q3 Panel Cut Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1" (26mm) round hole
CABLE LENGTHS
Display Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15' (4.6m) Typical
Ambient Air Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . .7' (2.1m) Standard on Self-Contained Systems
Outside Air Sensor (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75' (22.9m) Maximum
All custom display-cable lengths supplied in standard 5' (1.5m) increments . . 75' (22.9m) Maximum
NOTE
Maximum length of display and sensor cables is 75 feet (22.9m).
SYSTEM INPUTS
Ambient or Inside-Air Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
High Refrigerant Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Low Refrigerant Pressure (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Outside Air Temperature Sensor (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Seawater Input Temperature Sensor (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Humidity Sensor (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
L-2516 ENGLISH 23
Page 26
System Inputs Q3 and Qht Controls for Direct Expansion Systems

     








   



 !


"
#$     %$ $$  "
SAMPLE WIRING DIAGRAMS
IMPORTANT
These are sample diagrams. Wire colors may vary. See unit’s specific diagram located in electrical box. Turn power off before opening electrical box.
Figure 3: Sample Digital Control Wiring Diagram (U-Board)
24 L-2516 ENGLISH
Page 27
Q3 & Qht Controls for Direct Expansion Systems System Inputs
Figure 4: Sample Digital Control Wiring Diagram (obsolete board)
L-2516 ENGLISH 25
Page 28
DOMETIC MARINE DIVISION
2000 N. Andrews Ave.
Pompano Beach, FL 33069 USA
Tel +1 954-973-2477
Fax +1 954-979-4414
Email MarineSales@dometic.com
24/7 TECH SUPPORT FOR UNITED STATES AND CANADA
8:00 AM to 5:00 PM Eastern Time: +1 800-542-2477
After hours and weekends: +1 888-440-4494
INTERNATIONAL SALES AND SERVICE
Europe and the Middle East: +44 (0) 870-330-6101
For all other areas visit our website to find your nearest distributor.
dometic.com
L-2516 | July 10, 2017
Loading...