DMP XR150, XR550 Installation Manual

Page 1
INSTALLATION GUIDE
XR150/XR550 CANADIAN SERIES CONTROL PANEL
Page 2
MODEL XR150CAN/XR550CAN Series
CANADIAN INSTALLATION GUIDE
INDUSTRY CANADA NOTICE
This Class A digital apparatus complies with Canadian ICES-003.
© 2021 Digital Monitoring Products, Inc.
This information is subject to change without notice.
Page 3
TABLE OF CONTENTS
Product Specications
1.1 Power Supply .........................................................................1
1.2 Communication ......................................................................1
1.3 Panel Zones ...........................................................................1
1.4 Keypad Bus ............................................................................1
1.5 LX-Bus™ ................................................................................1
1.6 Outputs .................................................................................1
1.7 EnclosureSpecications ..........................................................2
Panel Features
2.1 Description .............................................................................2
2.2 Zone Expansion ......................................................................2
2.3 Output Expansion ...................................................................2
2.4 Central Station Communication ................................................2
2.5 Encrypted Communications (XR550 with Encryption only) ..........3
2.7 Compliance Instructions ..........................................................3
System Components
3.1 Wiring Diagram ......................................................................4
3.2 Lightning Protection ................................................................4
3.3 Accessory Devices ..................................................................5
3.3 Accessory Devices (continued) .................................................6
Installation
4.1 Mounting the Enclosure ...........................................................7
4.2 Mounting Keypads and Zone Expansion Modules .......................8
4.3 Connecting LX-Bus and Keypad Bus Devices .............................9
4.4 Wireless Keypad Association ....................................................9
Primary Power Supply
5.1 AC Terminals 1 and 2 ..............................................................9
5.2 Transformer Types ..................................................................9
5.3 J12 3-Pin Header for Transformer Types ...................................9
Secondary Power Supply
6.1 Battery Terminals 3 and 4 .....................................................10
6.2 Earth Ground (GND) .............................................................10
6.3 Battery Only Restart .............................................................10
6.4 Battery Replacement Period...................................................10
6.5 Discharge/Recharge ..............................................................10
6.6 Battery Supervision ...............................................................10
6.7 BatteryCuto .......................................................................10
6.8 XR150/XR550 Series Canadian Power Requirements ................11
6.9 Standby Battery Selection .....................................................13
Bell Output
7.1 Terminals 5 and 6 ................................................................. 14
Keypad Bus
8.1 Description ...........................................................................14
8.2 Terminal 7 - RED ..................................................................14
8.3 Terminal 8 - YELLOW ............................................................14
8.4 Terminal 9 - GREEN ..............................................................14
8.5 Terminal 10 - BLACK .............................................................14
8.6 J8 Programming Connection ..................................................14
8.7 Keypad Bus LEDs ..................................................................14
8.8 OVC LED(s) ..........................................................................14
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
i
Page 4
TABLE OF CONTENTS
Smoke and Glassbreak Detector Output
9.1 Terminals 11 and 12 .............................................................15
9.2 Current Rating ......................................................................15
Protection Zones
10.1 Terminals 13–24 ................................................................... 15
10.2 Dual EOL .............................................................................15
10.3 Zone Response Time .............................................................15
10.4 Keyswitch Arming Zone .........................................................15
Powered Zones for 2-Wire Smoke Detectors
11.1 Terminals 25–26 and 27–28 ..................................................16
Dry Contact Relay Outputs
12.1 Description ...........................................................................16
12.2 Contact Rating .....................................................................16
12.3 Model 431 Output Harness Wiring ..........................................16
Annunciator Outputs
13.1 Description ...........................................................................17
13.2 Model 300 Harness Wiring .....................................................17
13.3 Model 860 Relay Module .......................................................17
Wireless Bus Expansion
14.1 Description ...........................................................................17
14.2 Wireless Bus LEDs ................................................................17
LX-Bus Expansion
15.1 LX-Bus Headers ....................................................................17
15.2 LX-Bus LEDs .........................................................................17
15.3 OVC LEDs ............................................................................18
16.1 Description ...........................................................................18
16.2 Ethernet LEDs ......................................................................18
16.3 Network Transient Suppression .............................................. 18
J3 Telephone RJ Connector
17.1 Description ...........................................................................18
17.2 J10 893A or 277 Trouble Sounder Connector ..........................18
17.3 Notication ..........................................................................18
17.4 Phone Line Monitor ...............................................................18
Reset and Tamper Headers
18.1 J16 Reset Header .................................................................19
18.2 J4 Tamper Header ...............................................................19
Cellular Modules
19.1 J24 Header ..........................................................................19
19.2 Module Installation ...............................................................19
19.3 Connecting the Antenna ........................................................19
20.1 LX-Bus™ Module Connection .................................................20
20.2 Model 860 Relay Module Connection ......................................21
20.3 Dual Zone Protection ............................................................21
Certications
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
ii
Page 5
INTRODUCTION
Product Specications

1.1 Power Supply

Transformer Input: Model 327-CAN, plug-in — Primary input: 120 Vac, 60 Hz, Secondary output: 16.5 Vac 50 VA Model FTA7516 ATC Frost from Standex Electronics — Primary input: 120 Vac, 60 Hz, Secondary output: 16 Vac 75 VA
Standby Battery: 12 VDC, 1.0 Amps Max. charging current Models 365, 366, 368, or 369 Replace every 3 to 5 years
Auxiliary: 12 VDC output at 1.0 Amp Max using Model 327CAN Bell Output: 12 VDC at 1.0 Amp Max using Model 327CAN
Auxiliary: 12 VDC output at 1.5 Amp Max using Model FTA7516 Bell Output: 12 VDC at 1.5 Amp Max using Model FTA7516
All circuits are inherent Power Limited except the red battery wire and AC terminal.

1.2 Communication

• Built-in network communication to DMP Model SCS-1R or SCS-VR Receivers
• Built-in 128-bit or 256-bit encrypted communication to DMP Model SCS-1R or SCS-VR Receivers (XR550E only)
• Built-in Contact ID communication to DMP Model SCS-1R Receivers
• Optional 893A Dual Phone Line Module with phone line supervision
• Can operate as a local panel
Note: 256-bit encrypted messages to SCS-1R receiver only communicate when using SCS-104 Receiver Line
Cards with Version 102 or higher software.

1.3 Panel Zones

Eight 1k Ohm EOL burglary zones (zones 1 to 8)
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10)

1.4 Keypad Bus

You can connect up to a total of 16 of the following supervised keypads and expansion modules to the keypad bus:
• Alphanumeric keypads
• Single-zone detectors
• Access control modules
• Wireless Keypads (maximum of 7)
• Four- and/or single-zone expansion modules

1.5 LX-Bus™

You can connect the following devices to the LX-Bus™ connections provided on the panel. See Accessory Devices section 3.3.
• Four, eight, sixteen- and/or single-zone expansion modules
• Single-zone detectors
• Relay output expansion modules
• Graphic annunciator modules

1.6 Outputs

The XR150/XR550 Series provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A Model 431 Output Harness is required to use these outputs.
The panels also provide four open collector outputs rated for 50mA each. The open collector outputs provide ground connection for a positive voltage source. A Model 300 Output Harness is required to use these outputs.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
1
Page 6
INTRODUCTION
1.7 Enclosure Specications
The panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s guide, and programming sheets.
Enclosure
Model
350 17.5”W x 13.5”H x 3.5”D Gray (G) or Red (R) 18-Gauge
350A 17.5”W x 13.5”H x 3.75”D Gray (G) 18-Gauge with 16-Gauge door
341 13.22”W x 7.0”H x 3.5”D Gray (G) 20-Gauge
349 12.5”W x 11.5”H x 3.5”D Gray (G) 20-Gauge
352X 14.5”W x 32.0”H x 4.0”D Gray (G) 16-Gauge
Size Color(s) Construction (Cold Rolled
Steel)

Panel Features

2.1 Description

The DMP XR150/XR550 Series Canadian panel is a versatile 12VDC, combined access control, burglary, and re
communicator panel with battery backup. The panels provide eight on-board burglary zones and two on-board 12VDC Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices. You can use up to sixteen supervised 32-character LCD keypads; network communications and expansion interface cards; zone and output expansion modules; and initiating and indicating circuit modules. You can also connect auxiliary devices to the panel’s output relays to expand the basic system control capability. Combined current requirements of additional modules may require an auxiliary power supply. Refer to the XR150/XR550 Series Power Requirements section in this guide when calculating power requirements. The XR150/XR550 Series can communicate to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID communication.

2.2 Zone Expansion

Each panel provides multiple options for zone expansion.
• 10 on-board zones
• Up to 64 programmable keypad zones
• Up to 500 LX-Bus zones
Using DMP LCD keypad remote zone capability and zone expansion modules, additional zones are available on each panel:
• XR550 provides up to 574 additional zones
• XR150 provides up to 142 additional zones
The panel keypad data bus supports up to 16 supervised device addresses with each address supporting up to four programmable expansion zones (64 total).
Using the on board LX-Bus™ (LX500-LX900) connections, and any combination of single, four, eight, or sixteen-zone expansion modules and single-zone LX-Bus™ detectors, additional zones are available on each panel:
• XR550 provides up to 500 additional zones (LX500-LX900)
• XR150 provides up to 100 additional zones (LX500)
Note: Do not use shielded or twisted pair wiring for LX-Bus or Keypad Bus circuits.

2.3 Output Expansion

In addition to the two SPDT relays and four programmable open collector outputs on the XR150/XR550 Series, you can also connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules can provide an additional 500, 300, or 100 programmable SPDT relays. The panels provide Output Schedules for programming the 716 to perform a variety of annunciation and control functions. Also assign the 716 outputs to any panel Output Options such as Fire Alarm, Communication Fail, or Phone Trouble Outputs. Refer to the 716 Installation Guide (LT-0183). The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground outputs that follow the state of their assigned zones.
Note: The 717 supports the rst eight Keypad Bus addresses. To follow Keypad Bus addresses nine through 16, install
multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).

2.4 Central Station Communication

You can program the panel for reporting to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID communication. You can program the panel for reporting to DMP SCS-VR Virtual Receivers using cellular or network communication. The panel connects at the premises to a standard RJ31X or RJ38X telephone jack. Use the DMP 893A Dual Phone Line Module when connecting the XR150/XR550 Series panel to two separate phone lines.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
2
Page 7
INTRODUCTION

2.5 Encrypted Communications (XR550 with Encryption only)

An XR550 panel with encryption communicates using 128-bit or 256-bit AES encryption. If you currently have an XR550 panel installed, you may contact DMP Customer Service with the panel serial number. The serial number(s) should be sent in writing via e-mail or fax. A separate feature key is sent for each panel to activate encrypted communications using the Feature Upgrade process. Encrypted communication cannot be enabled on a standard XR550 panel. For more information on the Feature Upgrade process see the XR150/XR550 Series Canadian Programming Guide (LT-1232CAN). Note: 256-bit encrypted messages to SCS-1R receiver only communicate when using SCS-104 Receiver Line Cards
with Version 102 or higher software.
2.6 Caution Notes
Throughout this guide you will see caution notes containing information you need to know when installing the panel. These cautions are indicated with a yield sign. Whenever you see a caution note, make sure you completely read and understand its information. Failing to follow the caution note can cause damage to the equipment or improper operation of one or more components in the system. See the example shown below.
Always ground the panel before applying power to any devices: The panel must be properly grounded
before connecting any devices or applying power to the panel. Proper grounding protects against Electrostatic Discharge (ESD) that can damage system components.

2.7 Compliance Instructions

For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratory certicated system, please see the Compliance Listing Guide (LT-1330) for instructions.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
3
Page 8
INTRODUCTION
The plug-in transformer shall plug into a 120 VAC 60 Hz outlet not controlled by a switch.
tamper protection

System Components

3.1 Wiring Diagram

The XR550 Series diagram below shows some of the accessory modules you can connect for use in various applications. A brief description of each module follows in section 3.3.
AC Wiring must be in conduit and exit out the left side of the enclosure.
Wiring on terminals 5 through 22 must exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Bell
12 VDC Minimum cuto time 15 min.
1.5 Amp Max using FTA7516
J12
75VA
50VA
¼"
s
s
16 to 18 gauge wire
Maximum AC Wire distance with 16 gauge wire: 70 feet with 18 gauge wire: 40 feet
RED BLACK
Earth Ground
s
s
s
s
1k Ohm
1k Ohm
Use Listed Power Supervision
Relay rated at 12 VDC.
Battery Start
AC
+B BELL GND SMK GNDRED YEL GRN BLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+ Z9– Z10+ Z10–AC –B GND GND GNDGND
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 199 20 21 22 23 24 25 26 27 28
Cold Water Pipe Earth Ground
Bell cuto time range is 5 to 99 minutes, non-coded.
s
s
s
s
DISARM
1k Ohm
Phone Line
XR550 Series
Canadian Panel
OVC
s
s
s
s
1k
Ohm
Bell
Keyswitch Arming can be connected to any zone.
ARM
1k Ohm
J3
3 4 5 6
Outputs 3-6
s
22 gauge minimum
22 gauge minimum
s
RED
YELLOW
Smoke
Detector
s
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309 10K Ohm - DMP Model 308
J11
Output 1 Output 2
K6 K7
J4
Tamper
J14
J8
LX500
s
1k
Ohm
22 gauge minimum
22 gauge minimum
s
s
ss
BLACK
GREEN
RED RED
YELLOW GREEN BLACK
Zone Expander
s
s
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
1k Ohm 1k Ohm
s
Listed Resistors
J2
Zone 1
Zone 2
s
s
s
1k
Ohm
Total current combined from
terminals 7, 11, 25, 27, XBUS
Model 714
s
s
J13
XBUS
Out1 Out2
J15 J19J17
J9
LX800
LX700
s
Ohm
1k
Zone 4
s
s s
Ohm
1k
Zone 5
Ohm
s
s
Ohm
1k
Zone 3
s
Auxiliary/Smoke Power
and LX500-LX900
1.5 Amp Max
13.8 VDC to 10.2 VDC
Zone Expander Model 711
7mA @ 12
s s
s
s
s
1k Ohm
1k Ohm
WARNING: Incorrect connections may cause damage to the unit.
Form C Relays (J2)
Output Color Code–Model 431 Harness Output 2 N/O Orange/White Output 2 Com White/Gray Output 2 N/C Violet/White Output 1 N/O Orange Output 1 Com Gray Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code Output 3 Red Output 4 Yellow Output 5 Green Output 6 Black
J16
Reset
J24
10
3.3k Ohm Resistor
DMP Model
309
1k
Zone 6
s
LX900
sss
s
1k
Ohm
Zone 7
Zone 8
1k
Ohm
DMP Model
3.3k Ohm Resistor
Zone 9Zone
s s s s
309
s
= Supervised Circuit
Zone Expander
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Zone
Expander (up
to 8 zones)
Model 712-8
VDC
19mA @ 12
VDC
s
CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
s
1k Ohm
s s s
3.3k Ohm
3.3k Ohm
s
Front and Rear
included with Model 350A Attack Resistant Enclosure.
Front
Tamper
Rear
Tamper
Heat detectors, pull stations, or any other contact devices listed for Fire Protective Signaling can be connected to zones 9 and 10.
Zones 9 and 10 and Model 715 compatibility identifier: A Maximum operating range: 13.8 VDC to
9.7 VDC. Class B (Style A).
Model 715
sss s s
3.3k Ohm
3.3k Ohm
Figure 1: XR550 Canadian Wiring Diagram

3.2 Lightning Protection

Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR150/XR550 Series input and output circuits. Additional surge protection is available by installing the DMP 370, 370RJ Lightning Suppressors or Model 270 Network Transient Suppression Module.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
4
Page 9
INTRODUCTION

3.3 Accessory Devices

Cellular Communicators
263LTE-A Cellular Communicator Allows you to connect the XR150/XR550 Series to to the AT&T LTE network.
Accessory Modules
270 Network Transient Suppression Module
277CAN Trouble Sounder Provides local sounder for monitoring of panel operations and loss of Keypad Bus.
370/370RJ Lightning Suppressor
893A Dual Phone Line Module Allows you to supervise two standard phone lines connected to an XR150/XR550 Series panel.
Expansion Modules
710 Bus Splitter/Repeater Allows you to increase keypad or LX-Bus™ wiring distance to 2500 feet. 711 Zone Expansion Module Increases available reporting zones. Provides one Type A Class B zone. 711S Zone Expansion Module Provides one Class B zone for connecting burglary devices. 712-8 Zone Expander Provides Class B zones for connecting burglary devices. 714, 714-8, 714-16 Zone Expanders Provides Class B zones for connecting burglary and non-powered re devices. 714N-POE Network Zone Expander Allows you to add four zones to the XR150/XR550 Series panels using IP network capability. 715, 715-8, 715-16 Zone Expanders Provides 12VDC Class B powered zones for connecting smoke detectors, glassbreak detectors,
716 Output Expander Provides four Form C relays (SPDT) and four switched grounds (open collector) for use in a
717 Graphic Annunciator Module Provides 20 zone following annunciator outputs (open collector) for use in a variety of
734, 734N, 734N-POE Wiegand Interface Modules
DMP Two-Way Wireless Devices
1100X Series/1100XH Series Wireless Receiver
1100R Repeater Provides additional range for wireless devices.
1100T Wireless Translator Allows non-DMP wireless devices to integrate with DMP XR150CAN/XR550CAN Series panels.
1101 Series Universal Transmitter Provides both internal and external contacts that may be used at the same time to yield two
1102 Universal Transmitter Provides an external contact.
1103 Series Universal Transmitter Provides both internal and external contacts that may be used at the same time to yield two
1106 Series Universal Transmitter Provides both internal and external contacts that may be used at the same time to yield two
1107 Micro Window Transmitter Provides a wireless window transmitter.
1108 Doorbell Module Monitors doorbell presses.
1114 Four-Zone Expander Provides four wireless zones.
1116 Relay Output Provides one Form C relay.
1117 LED Annunciator Provides a visual system status indicator.
1118 Remote Indicator Light Provides a visual indication of a Panic situation.
1119 Door Sounder Provides a battery powered sounder.
1126R Motion Detector Ceiling mount motion detector with panel programmable sensitivity and Disarm/Disable
1127C/1127W PIR Motion Detector Wall mount motion detector with panel programmable sensitivity and Disarm/Disable
1131 Recessed Contact Provides a recessed contact option for door or window applications.
1135 Wireless Siren Provides a wireless siren.
1136 Remote Sounder Multi-function sounder that plugs directly into a standard 110VAC wall outlet.
1139 Bill Trap Provides a silent alarm option for retail and banking cash drawers.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
Provides transient surge protection for the J1 Ethernet Connector.
Provides protection against voltage surges on panel input and output circuits
The 893A module monitors the main and backup phone lines for a sustained voltage drop and alerts users when the phone line is bad.
and other 2- or 4-wire devices.
variety of remote annunciation and control applications for use on the LX-Bus only.
remote annunciation and control applications for use on the LX-Bus only. Provides system codeless entry, and arming and disarming using access control readers.
Supports up to 500 devices in residential or commercial wireless operation.
individual reporting zones from one wireless transmitter.
individual reporting zones from one wireless transmitter. Requires EOL resistor for external contact. Provides Disarm/Disable functionality.
individual reporting zones from one wireless transmitter.
functionality.
functionality.
5
Page 10
INTRODUCTION
1141 Wall Button One button wall mounted wireless transmitter.

3.3 Accessory Devices (continued)

DMP Two-Way Wireless Devices (continued)
1142BC Two-button Hold-up Belt Clip Transmitter
1142 Two-button Hold-up Transmitter
1144 Series Wireless Key Fobs Key Fob transmitters designed to clip onto a key ring or lanyard. 1154 Wireless Four-Zone Input
Module 1158 Wireless 8-Zone Input
Module 1164 Wireless Synchronized
Smoke Detector 1166 Wireless Smoke Ring Installs on any traditional AC-powered, three wire, interconnected smoke alarm system. 1183-135F Heat Detector Fixed temperature heat detector. 1183-135R Heat Detector Fixed temperature and rate-of-rise heat detector. 1184 Carbon Monoxide Detector Carbon Monoxide Detector.
Interface Modules
736P Radionics™ Popit Interface Allows a Radionics™ POPIT System to interface with DMP XR150/XR550 Series panels while
738A Ademco Interface Allows Ademco™ 5881 wireless receivers to interface with DMP XR150/XR550 Series panels. 738I ITI Interface Module Allows ITI™ SuperBus™ 2000 Series wireless receivers to interface with DMP XR150/XR550
738Zplus Z-Wave Interface Module
Indicating and Initiating Devices
860 Relay Output Module Provides one relay and three relay sockets for expansion of up to four relays. 865 Supervised Style W or X
Notication Circuit Module
866 Style W Notication Circuit
Module
867 Style W LX-Bus Notication
Circuit Module
869 Dual Class A Style D Initiating Module
Keypads
LCD keypads Allows you to control the panel from various remote locations. Connect up to sixteen
9000 Series Wireless Keypads Allows you to control the panel from various remote locations. Connect up to seven
9800 Series Wireless Touchscreen keypads
Graphic
Addressable Smoke Detectors
2W-BLX, 2WT-BLX Single-zone, addressable conventional smoke, smoke/heat detectors that connect to the
Provides two-button hold-up operation with a belt clip.
Provides permanently mounted under-the-counter two-button hold-up operation.
Converts up to four existing normally closed,hardwired zones into wireless zones.
Allows installers to convert up to 8 existing hardwired zones into wireless zones.
Commercial or residential, battery powered, wireless, low prole, photoelectric smoke
detector, with synchronizing sounder.
maintaining Radionics™ wiring.
Series panels. Provides connection for Z-Wave modules.
Provides supervised alarm current when using the XR150/XR550 Series panel bell output and up to 5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 865 can supervise 2-wire or 4-wire style circuits for opens and shorts with individual LED annunciation.
Provides supervised alarm current using the XR150/XR550 Series panel bell output and up to 5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 866 can supervise 2-wire Style W circuits for opens and shorts.
Provides supervised alarm current using the XR150/XR550 Series panel bell output and up to 5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 867 connects to the
XR150/XR550 Series panel LX-Bus™ and provides one 2-wire Style W notication circuit for
open and short conditions. Individual Bell Relay addresses Bell Ring styles.
Provides two Class A, Style D, 4-wire initiating zones for connecting waterow switches and other non-powered re and burglary devices.
supervised Model 630F Remote Fire Command Center, 7060, 7063, 7070, 7073, 7160, 7163, 7170, 7173 Thinline™ keypads, 7060A, 7063A, 7070A, 7073A Aqualite™ keypads, and 7872 and 7873 Graphic Touchscreen keypads to the keypad bus using terminals 7, 8, 9, and 10.
9060/9063 Wireless Keypads.
Allows you to control the panel from various remote locations. Connect up to seven 9862 Wireless Keypads.
LX-Bus. Includes drift compensation.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
6
Page 11

INSTALLATION

Installation

4.1 Mounting the Enclosure

The metal enclosure for the XR150/XR550 Series must be mounted in a secure, dry place to protect the panel from damage due to tampering or the elements. It is not necessary to remove the XR150/XR550 Series PCB when installing the enclosure. Figure 2 shows the mounting hole locations for the Model 350/350A Enclosures. Figure 3 shows the Model 341 Enclosure. Figure 4 shows the Model 352X panel cabinet and 352S shelf cabinet for multiple batteries.
The 350A Attack Resistant enclosure is factory shipped with one knockout on the top left of the enclosure. As needed, additional knockouts or antenna exits may be added at the time of installation. See Figure 2 for the
positions on the enclosure that can be added. Each additional knockout must be lled with conduit.
Enclosure Mounting Holes
XR550 Panel
J6
J23
K
*
Dual 1 3/4" and 1 3/8" Conduit Knockouts
* 350A Optional Knockout
Battery Shelf holds up to three 7 Ah Batteries
*
Figure 2: XR550 Series in Model 350 or 350A Enclosure
*
3-Hole
Pattern for
Accessory
Modules
Front and
Rear
Tamper
Switches for
350A
Attack
Resistant
Enclosure
*
*
PEMs for optional battery bracket.
Lid Mounting Holes (4 places)
Lid Mounting Holes (4 places)
XR550 Panel
See 341 Installation sheet for additional
information.
J23
K
Enclosure Mounting Holes (4 places)
Dual 1/2" and 3/4" Conduit Knockouts
J6
Figure 3: XR550 Series in Model 341 Enclosure
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
7
Page 12
INSTALLATION
56 VA
Transformer
Mounting Plate
XR550 Panel
XR550 Panel
K
Mounting for one (1)
Zone Expansion Module.
J6
Battery Shelf
Figure 4: XR550 Series in Model 352X Enclosure and Separate 352S Enclosure with Shelves

4.2 Mounting Keypads and Zone Expansion Modules

DMP LCD keypads have removable covers that allow you to easily mount the keypad to a wall or other at surface
using the screw holes on each corner of the base. Before mounting the base, connect the keypad wire harness leads to the keypad cable from the panel and to any device wiring run to that location. Then attach the harness to the pin connector on the PC board, mount the base, and install the keypad cover making sure all of the keys extend through their respective holes.
For mounting keypads on solid walls, or for applications where conduit is required, use the Model 695 1-1/2” deep or the Model 696 1/2” deep backboxes.
The DMP 711, 712-8, 714, 715, 716, and 717 modules are each contained in molded plastic housings with removable covers. The base provides you with mounting holes for installing the unit to a wall, switch plate, or other surface.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
8
Page 13
INSTALLATION
PROG
LX500
LX600
LX700
LX800
LX900
RED BLK
RED
BLK
RED
BLK
RED
BLK
RED
J17
BLK
XMIT RCV
RED
BLK
XMIT RCV
J8
J14
J9
XMIT
RCV
XMIT
RCV
XMIT
RCV
XMIT
RCV
PROG
500
600
700

4.3 Connecting LX-Bus and Keypad Bus Devices

Connections for LX-Bus and Keypads are provided through the J8 (PROG), J14 (LX500), J9 (LX600), J15 (LX700), J17 (LX800), J19 (LX900), and J13 (XBUS) 4-pin headers. Several factors determine the DMP LX-Bus™ and keypad bus performance characteristics: the wire length and gauge used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™ and keypad bus installation, keep in mind the following information:
• DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted pair
or shielded wire for LX-Bus and keypad bus data circuits.
• On keypad bus circuits, to maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add devices, install an additional power supply that is listed for Fire Protective Signaling, power limited, and regulated (12VDC nominal) with battery backup.
Note: Each panel allows a specic number of supervised keypads. Add additional keypads in the unsupervised mode. Refer to the Keypad Bus section for the specic number of supervised keypads allowed.
• Maximum distance for any one bus circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases. Maximum number of LX-Bus devices on
the rst 2,500 foot circuit is 40 devices.
• Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly.
For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031).

4.4 Wireless Keypad Association

Enable Wireless Keypad Association operation on both the keypad and panel:
1. Access the Installer Options Menu (3577 (INST)).
2. Select RF Survey). The keypad logo LEDs turn on red until association is successful.
Enable Wireless keypad Association operation in the XR150/XR550 panel:
Reset panel 3 times within 12 seconds. Allow the keypad bus Transmit/Receive
Figure 5: Keypad Bus LEDs
LEDs to turn back on between each reset. For 60 seconds the panel listens for wireless keypads that are in the Installer Options Menu (3577 CMD) and have not been programmed, or associated into another panel. Those keypads are
assigned to the rst open device position automatically based upon the order in
which they are detected. The keypad logo turns Green to indicate it has been associated with the panel.

Primary Power Supply

5.1 AC Terminals 1 and 2

Connect the transformer wires to terminals 1 and 2 on the panel. Use no more than 70 ft. of 16 gauge or 40 ft. of 18 gauge wire between the transformer and the XR150/XR550 Series.
Always ground the panel before applying power to any devices: The XR150/XR550 Series must be
properly grounded before connecting any devices or applying power to the panel. Proper grounding protects against Electrostatic Discharge (ESD) that can damage system components. See the Earth ground
section.

5.2 Transformer Types

Use Model 327CAN (16.5 Vac 50 VA) plug-in or Model FTA7516 from ATC Frost.
The transformer must be connected to an unswitched 120 Vac 60 Hz electrical outlet with at least .87A of
available current. Never share the transformer output with any other equipment.

5.3 J12 3-Pin Header for Transformer Types

Place the jumper on the left two pins for a Maximum 2 Amp (Bell+Aux+Smoke+XBUS+LX500-LX900) when using the Model 327CAN plug-in transformer (default).
Use an ATC Frost FTA7516 transformer and place the jumper on the right two pins for a Maximum, 3 Amps (Bell+Aux+Smoke+XBUS+LX500-LX900).
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
9
Page 14
INSTALLATION

Secondary Power Supply

6.1 Battery Terminals 3 and 4

Connect the black battery lead to the negative battery terminal. The negative terminal connects to the enclosure ground internally through the XR150/XR550 Series circuit board. Connect the red battery lead to the battery positive terminal. Observe polarity when connecting the battery.
You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness. DMP requires each
battery be separated by a PTC in the battery harness wiring to protect each battery from a reversal or short within the circuit. See Figure 6.
Use sealed lead-acid batteries only: Use
the Model 365 (12VDC 9 Ah), Model 366 (12VDC 18 Ah), Model 368 (12VDC 5.0 Ah), or Model 369 (12VDC 7 Ah) sealed lead-acid rechargeable battery. Batteries supplied by DMP have been tested to ensure proper charging with DMP products.
GEL CELL BATTERIES CANNOT BE USED WITH THE XR150/XR550 SERIES PANEL.
Battery
318 Battery Harness
318 Battery
Battery
PTC
Harness
PTC
Red
Black
Red
Battery
Figure 6: Wiring Multiple Batteries
Black
Battery Start
To AC
Panel Red and Black Battery Cables
14 AWG to Earth Ground
XR550
Panel
AC
+BAC –B
1234
To Bell Circuit
BELLGND
56

6.2 Earth Ground (GND)

To provide proper transient suppression, XR150/XR550 Series panel terminal 4 must be connected to earth ground using 14 gauge or larger wire. DMP recommends connecting to a cold water pipe, ground rod, or building ground
only. Do not connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground.

6.3 Battery Only Restart

When powering up the XR150/XR550 Series panel without AC power, briey short across the battery start pads to pull in the battery cuto relay. The leads need a momentary short only. Once the relay has pulled in, the battery voltage holds it in that condition. If the XR150/XR550 Series panel is powered up with an AC transformer, the battery cuto
relay is pulled in automatically. For more information refer to Figure 1.

6.4 Battery Replacement Period

DMP recommends replacing the battery every 3 to 5 years under normal use.

6.5 Discharge/Recharge

The XR150/XR550 Series battery charging circuit oat charges at 13.8VDC at a maximum current of 1.0 Amps. Listed
below are the various battery voltage level conditions:
Battery Trouble: Below 11.9VDC
Battery Cuto: Below 10.2VDC
Battery Restored: Above 12.6VDC

6.6 Battery Supervision

The XR150/XR550 Series tests the battery when AC power is present. The test is done every three minutes and lasts
for ve seconds. During the test, the panel places a load on the battery; if the battery voltage falls below 11.9VDC
a low battery is detected. If AC power is not present, a low battery is detected any time the battery voltage falls below 11.9VDC.
If a low battery is detected with AC power present, the test repeats every two minutes until the battery charges above 12.6VDC indicating the battery has restored voltage. If a weak battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is completed.
6.7 Battery Cuto
The panel disconnects the battery any time the battery voltage drops below 10.2VDC. This prevents battery deep discharge damage.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
10
Page 15
INSTALLATION

6.8 XR150/XR550 Series Canadian Power Requirements

During AC power failure, the XR150/XR550 Series panel and all connected auxiliary devices draw their power from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The following table lists the XR150/XR550 Series panel power requirements. You must add the additional current draw of keypads, zone expansion modules, smoke detector output, and any other auxiliary devices used in the system for the total current required. The total is then multiplied by the number of standby hours required to calculate the total ampere-hours required.
Standby Battery Power Calculations Standby Current Alarm Current
XR150/XR550 Series Control Panel
Relay Outputs 1-2 (ON) Switch Grounds 3-6 (ON) Active Zones 1-8 Active Zones 9-10 2-Wire Smoke Detectors Panel Bell Output
893A Dual Phone Line Module Qty _______ x 12mA ______ Qty _______ x 50mA ______
263LTE-A Cellular Communicator Qty _______ x 20mA ______ Qty _______ x 20mA ______
277CAN Trouble Sounder Module Qty _______ x 5mA ______ Qty _______ x 5mA ______
1100X Series Wireless Receiver Qty _______ x 25mA ______ Qty _______ x 35mA ______
1100XH Series Wireless High Power Receiver Qty _______ x 75mA ______ Qty _______ x 102mA ______
860 Relay Output Module (one relay active)
All four relays active
865 Style Y or Z Notication Module Qty _______ x 26mA ______ Qty _______ x 85mA ______
866 Style W Notication Module Qty _______ x 45mA ______ Qty _______ x 76mA ______
867 LX-Bus Style W Notication Module Qty _______ x 30mA ______ Qty _______ x 86mA ______
869 Dual Style D Initiating Module Qty _______ x 25mA ______ Qty _______ x 75mA ______
7060/7160 Thinline/7060A Aqualite Keypad Qty _______ x 72mA ______ Qty _______ x 87mA ______
7063/7163 Thinline/7063A Aqualite Keypad Qty _______ x 85mA ______ Qty _______ x 100mA ______
7070/7170 Thinline/7070A Aqualite Keypad
Active Zones (EOL Installed)
7073/7173 Thinline/7073A Aqualite Keypad
Active Zones (EOL Installed)
7872 Graphic Touchscreen Keypad
Active Zones (EOL Installed)
7873 Graphic Touchscreen Keypad
Active Zones (EOL Installed)
734 Wiegand Interface Module
Active Zones (EOL Installed) Annunciator (ON)
Copy Sub-Totals to next page Sub-Total Standby *Based on 10% of active zones in alarm.
Qty 1 _ Qty _______ Qty _______ Qty _______ Qty _______ Qty _______
Qty _______ x 34mA
Qty _______ x 72mA
Qty _______ x 85mA
Qty _______ x 145mA
Qty _______ x 143mA
Qty _______ Qty _______xx
x 174mA
30mA
5mA
1.6mA 4mA
0.1mA
138mA
1.6mA
1.6mA
1.6mA
1.6mA
40mA
1.6mA
174 mA ______ ______ ______ ______ ______
______ ______
______ ______
______ ______
______ ______
______ ______
______ ______
______mA Sub-Total Alarm ______mA
Qty 1 _ Qty _______ Qty _______ Qty _______ Qty _______ Qty _______
Qty _______ x 34mA
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______ Qty _______
x 217mA
30mA
5mA
2mA*
30mA
0.1mA
1500mA
138mA
87mA
2mA*
100mA
2mA*
215mA
2mA*
243mA
2mA*
x
60mA
x
2mA*
x
20mA
217 mA ______ ______ ______ ______ ______ ______mA
______ ______
______ ______
______ ______
______ ______
______ ______
______ ______ ______
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
11
Page 16
INSTALLATION
Standby Battery Power Calculations Standby Current Alarm Current
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
738A Ademco Wireless Interface Module Qty _______ x 75mA ______ Qty _______ x 75mA ______
738Zplus Z-Wave Interface Module Qty _______ x 40mA ______ Qty _______ x 40mA ______
710 Bus Splitter/Repeater Module Qty _______ x 32mA ______ Qty _______ x 32mA ______
711 Zone Expansion Module Active Zone
(EOL Installed)
711S Zone Expansion Module Active Zone Qty _______ 4.2mA ______ Qty _______ 11mA ______
Qty _______ Qty _______xx
Qty _______ Qty _______xx
25mA
___mA
11mA
1.6mA
______ ______
______ ______
Qty _______ Qty _______xx
Qty _______ Qty _______xx
25mA
___mA
4.7mA 2mA*
______ ______
______ ______
714 Zone Expansion Module
Active Zones (EOL Installed)
712-8 Zone Expansion Module
Active Zones (EOL Installed)
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
715 Zone Expansion Module
Active Zones (EOL Installed) 2-Wire Smokes
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed) 2-Wire Smokes
716 Output Expansion Module
Active Form C Relays
717 Graphic Annunciator Module
Annunciator Outputs
2W-BLX, 2WT-BLX Smoke Detectors Qty _______ x 15mA ______ Qty _______ x 35mA* ______
572 Indicator LED Qty _______ x 20mA ______ Qty _______ x 20mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and LX-Bus Modules
This page only Sub-Total Standby
Sub-Totals from previous page Sub-Total Standby
*Based on 10% of active zones in alarm Total Standby ______mA Total Alarm ______mA
Total Standby______mA x number of Standby Hours needed
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______ Qty _______
Qty _______ Qty _______ Qty _______
Qty _______ x 13mA ______ Qty _______
Qty _______ x 10mA ______ Qty _______
7mA
1.6mA
17mA
1.6mA
20mA
1.6mA
x
7mA
x
4mA
x
.1mA
x
20mA
x
4mA
x
.1mA
Total Alarm
______ ______
______ ______
______ ______
______ ______ ______
______ ______ ______
______mA ______mA
______mA Sub-Total Alarm ______mA
______mA Sub-Total Alarm ______mA
______ = ______mA
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______xx
Qty _______ Qty _______ Qty _______
Qty _______ Qty _______ Qty _______
Qty _______xx
Qty _______xx
_______mA-hours +_______mA-hours
Total
_______mA-hours X .001 = _______Amp-hrs Required
7mA
______
2mA*
______
17mA
______
2mA*
______
20mA
______
2mA*
______
x
7mA
30mA*
.1mA
20mA
30mA*
.1mA
13mA 12mA
10mA
1mA
______ ______ ______
______ ______ ______
______ ______
______ ______
x x
x x x
Refer to section 6.9 for standby battery selection.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
12
Page 17
INSTALLATION

6.9 Standby Battery Selection

To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours Required calculation from section 6.8 XR150/XR550 Series Power Requirements, perform the following:
1. Select the desired standby hours required from the table below: 24, 60, or 72 hours.
2. Select the desired battery size: Model 368 (12VDC 5.0 Ah), Model 369 (12VDC 7 Ah), Model 365 (12VDC 9 Ah), Model 366 (12VDC 18 Ah).
3. Select a Max. Ah Available number that is just greater than the number calculated in Amp Hours Required.
4. Install the number of batteries shown in the corresponding No. of Batteries required column. Example: If the Amp Hours Required calculation equals 22 Ah for 24 hours of standby time and 4.5 Ah
batteries are desired, install six (6) Model 368 (12VDC, 5.0 Ah) batteries. Note: You can use either a Model 327CAN Plug-in 50 VA or ATC Frost FTA7516 75VA Transformer with any of the
Number of Batteries choices listed below.
24 hours of standby power
5.0 Ah Batteries 7 Ah Batteries 7.7 Ah Batteries 9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
8 2 6 1 6 1 8 1 16 1 12 3 12 2 13 2 16 2 32 2 16 4 18 3 20 3 24 3 48 3 20 5 24 4 27 4 32 4 24 6 31 5 34 5 40 5 28 7 37 6 41 6 32 8 43 7 36 9 Note: 48 hours is the typical battery recharge time for any of the Number of Batteries 40 10
No. of
Batteries
Max. Ah
Available
shown in this section.
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
60 hours of standby power
7 Ah Batteries 7.7 Ah Batteries 9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
13 2 14 2 17 2 17 1 20 3 22 3 26 3 34 2 27 4 29 4 34 4 52 3 33 5 37 5 43 5 69 4 40 6 44 6 52 6 47 7 52 7 61 7 Note: 48 hours is the typical battery 54 8 59 8 69 8 60 9 67 9 67 10
72 hours of standby power
9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
16 2 16 1 25 3 33 2 33 4 50 3 42 5 67 4 50 6 59 7 Note: 72 hours is the typical battery recharge time required for any of the Number of 67 8
Note: If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then add power supply(s) to power some system devices allowing the Amp Hours Required calculation to be reduced. See the 710 Bus Splitter/Repeater Installation Guide (LT-0310).
No. of
Batteries
No. of
Batteries
Max. Ah
Available
Max. Ah
Available
Batteries shown in this section.
No. of
Batteries
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
recharge time for any of the Number of Batteries shown in this section.
No. of
Batteries
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
13
Page 18
INSTALLATION

Bell Output

7.1 Terminals 5 and 6

Terminal 5 supplies positive 12VDC to power alarm bells or horns. This output can be steady, pulsed, or temporal
depending upon the Bell Action specied in Bell Options. Terminal 6 is the ground reference for the bell circuit. This
supervised output detects 1k Ohms or less as normal. The indicating appliance can supply this resistance. If using a horn or siren, a 1k Ohm 1/2 W EOL resistor (provided) should be added across the bell circuit to provide supervision.
See the Notication Appliance section for a list of approved notication appliances and the Wiring Diagrams for
connections.

Keypad Bus

8.1 Description

XR150/XR550 Series panel terminals 7, 8, 9, and 10 are for the keypad bus. You can connect up to sixteen supervised keypads and multiple unsupervised keypads to the XR150/XR550 Series. In addition to DMP LCD keypads, you can also connect any combination of zone expansion modules to the data bus up to 16 devices.
Note: Do not use shielded wire for LX-Bus/Keypad Bus circuits.

8.2 Terminal 7 - RED

This terminal supplies positive 12VDC Regulated to power DMP LCD keypads and zone expansion modules. Terminal 7 also supplies power for any auxiliary device. The ground reference for terminal 7 is terminal 10.
The output current is shared with the smoke power output on terminal 11 and Zones 9 and 10. Current draw for all connected devices must not exceed the panel maximum current rating. See Power Supply in the Compliance section
for maximum current in a re listed application.

8.3 Terminal 8 - YELLOW

Terminal 8 receives data from keypads and zone expansion modules. It cannot be used for any other purpose.

8.4 Terminal 9 - GREEN

Terminal 9 transmits data to keypads and zone expansion modules. It cannot be used for any other purpose.

8.5 Terminal 10 - BLACK

Terminal 10 is the ground reference for DMP LCD keypads, zone expansion modules, and all auxiliary devices being powered by terminal 7.

8.6 J8 Programming Connection

A 4-pin header (J8) is provided to connect a keypad when using a DMP Model 330 Programming Cable. This provides a quick and easy connection for panel programming.
You may also use the Programming Header to connect Keypad Bus devices. This is an alternative to connecting keypad bus devices to terminals 7, 8, 9, and 10.

8.7 Keypad Bus LEDs

The two LEDs, located above the J8 PROG connector, indicate data transmission and receipt. The left LED ashes green to indicate the panel is transmitting keypad bus data. The right LED ashes yellow to indicate the panel is
receiving keypad bus data. See Figure 5.

8.8 OVC LED(s)

The Overcurrent LED (OVC) lights red when the devices connected to the Keypad Bus and LX-Bus(es) draw more current than the panel is rated for. The LED(s) turn a steady red when lit. When the OVC LED(s) light red, the appropriate LX-Bus(es) and Keypad bus are shut down.
• The OVC LED located to the left of the 893A connector indicates overcurrent for the Keypad Bus (Terminals 7-10 and PROG header), XBUS, and LX500-LX700.
• The OVC LED to the right of the J24 Cell Module connector indicates overcurrent for LX800-LX900.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
14
Page 19
INSTALLATION
1k Ohm Normally
Closed
1k Ohm
Normally Open
1k Ohm Combination
Normally Open and
Normally Closed

Smoke and Glassbreak Detector Output

9.1 Terminals 11 and 12

Terminal 11 supplies positive 12VDC Regulated to power 4-wire smoke detectors and other powered devices. This
output can be turned o by the user for 5 seconds using the Sensor Reset User Menu option to allow latched devices
to reset. Terminal 12 is the ground reference for terminal 11.

9.2 Current Rating

The Output current from terminal 11 is shared with terminals 7, 25, 27, and LX500-LX900. Caution: The total current draw of all devices powered from the panel must be included with terminal 11
calculations and must not exceed the maximum output rating.

Protection Zones

10.1 Terminals 13–24

Zones 1 to 8 (terminals 13 to 24) on the XR150/XR550 Series panels are all grounded burglary zones. For programming purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
Terminal Function Terminal Function
13 Zone 1 voltage sensing 19 Zone 5 voltage sensing 14 Ground for Zones 1 and 2 20 Ground for Zones 5 and 6 15 Zone 2 voltage sensing 21 Zone 6 voltage sensing 16 Zone 3 voltage sensing 22 Zone 7 voltage sensing 17 Ground for Zones 3 and 4 23 Ground for Zones 7 and 8 18 Zone 4 voltage sensing 24 Zone 8 voltage sensing
The voltage sensing terminal measures the voltage across a 1k Ohm End-of-Line resistor to ground. Use DMP Model 311 1k Ohm resistors. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-open) with any of the burglary protection zones.
Each protection zone detects three conditions: Open, Normal, and Short. Listed below are voltage and resistance parameters for each condition:
Condition Resistance on zone Voltage on positive terminal
Open over 1300 Ohms over 2.0VDC
Figure 7: Protection Zone Wiring
Normal 600 to 1300 Ohms 1.2 to 2.0VDC Short under 600 Ohms under 1.2VDC

10.2 Dual EOL

The XR150/XR550 Series Canadian panels support the use of dual 1K EOL resistors on panel Zones 1-8. Two EOL resistors are used so a wire trouble can be indicated during the disarm period.
When dual end-of-line operation is chosen in panel programming, normal zone processing occurs with the following exception: When processing an open zone and a trouble or alarm message is NOT programmed to be sent for the open state, the panel checks to see if the wire is cut. If the wire is cut, the panel automatically sends an alarm if armed or trouble is disarmed.
ZONE STATUS
Zone Wires Open Zone Wires Short Contact Normal Contact Open
Disarmed Trouble Trouble Normal Normal
Armed Alarm Alarm Normal Alarm

10.3 Zone Response Time

A condition must be present on a zone for 500 milliseconds before it is detected by the XR150/XR550 Series panel. Ensure detection devices used on the protec tion zones are rated for use with this delay. Zones 1-10 can also be programmed for a fast response delay of 160 milliseconds.
Zone Wires
to Panel
Zones 1-8
TAMP
1K Ohm
1K Ohm
Indicating Device
N/O
C
N/C
Figure 8:Dual EOL

10.4 Keyswitch Arming Zone

A keyswitch on an Arming type zone allows selected areas to arm and disarm without having to enter a user code.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
15
Page 20
INSTALLATION

Powered Zones for 2-Wire Smoke Detectors

11.1 Terminals 25–26 and 27–28

Panel terminals 25 through 28 provide two resettable Class B, Style A, 2-wire powered zones. For programming purposes the zone numbers are 9 and 10.
Note: The maximum wire length for either zone 9 or zone 10 is 3000 feet using 18 AWG or 1000 feet using 22 AWG. The maximum voltage is 13.8VDC and the maximum normal standby current is 1.25mA DC. The maximum
line impedance is 100 Ohms. The maximum short circuit current is 56mA. Do not mix detectors from dierent
manufacturers on the same zone.
Caution: Performing a Sensor Reset momentarily drops power to the devices on Zones 9 and 10. The panel
views these zones (9 and 10) as “Open” while the power is absent.
Note: Refer to the Compliance Listing Guide (LT-1330 )for list of compatible DMP 2-wire smoke detectors.

Dry Contact Relay Outputs

12.1 Description

The XR150/XR550 Series panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model 305 relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header. Each relay provides one SPDT set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition: Steady, Pulsing, Momentary, and Follow
2) Activation by 24-hour 7-day schedule: One on and one o time a day for each relay
3) Manual activation from the DMP LCD keypad menu
4) Communication failure 12) Ready
5) Armed area annunciation 13) Armed
6) Fire Alarm, Fire Trouble or Supervisory 14) Disarmed
7) Ambush Alarm 15) Burglary
8) Exit and Entry timers 16) Phone Trouble
9) System Ready 17) Device Fail
10) Late to Close 18) Sensor Reset
11) Panic Alarm 19) Closing Wait
Refer to the XR150/XR550 Canadian Series Programming Guide (LT-1232CAN) for specic information.

12.2 Contact Rating

The Model 305 relay contacts are rated for 1 Amp at 30VDC (allows .35 power factor). You can connect auxiliary power to the Relay Output 1 common terminal by installing the gray harness wire to terminal 7. Current draw for all
connected devices must not exceed the panel maximum current rating.

12.3 Model 431 Output Harness Wiring

The relay contacts are accessible by installing the DMP 431 Output Harness on the 6-pin header labeled J2. Output 2 uses the top three prongs, and Output 1 uses the bottom three prongs. The wire harness and contact locations are shown below:
Contact Color
Output 1 normally closed Violet Output 1 common Gray Output 1 normally open Orange Output 2 normally closed Violet with white stripe Output 2 common White with gray stripe Output 2 normally open Orange with white stripe
The relay contacts must be connected to devices located within the same room as the XR150/XR550 Series panel.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
16
Page 21
INSTALLATION

Annunciator Outputs

13.1 Description

The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or conditions occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground a voltage from another source. The outputs can respond to any of the conditions listed in the Description section for
Dry Contact Relays. Maximum voltage is 30VDC at 50mA.

13.2 Model 300 Harness Wiring

Access the open collector outputs by installing DMP 300 Harness on the 4-pin header labeled J11. The output locations are shown below. For listed applications, devices connected to the outputs must be located within the same room as the panel.
Output Color Wire Output Color Wire
3 Red 1 5 Green 3 4 Yellow 2 6 Black 4

13.3 Model 860 Relay Module

Connect a Model 860 Relay Module to the J11 header on the XR150/XR550 Series panel to provide relays for outputs 3-6. Use these relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power terminal 7. The module includes one relay and provides three additional sockets for expansion of up to four
relays. Mount the 860 inside the panel enclosure using the 3-hole pattern and plastic standos. Refer to the 860
Module Install Sheet (LT-0484) as needed.
Relay Contact Rating: 1 Amp at 30VDC (allows .35 power factor)

Wireless Bus Expansion

14.1 Description

The J13 Wireless Bus (XBUS) header provides connection for the 1100X Series or 1100XH Series Wireless Receiver. The XBUS provides up to 500 wireless zones numbered 500-999. Refer to the 1100X Series Wireless Receiver Install Guide (LT-1822) or the 1100XH Series Wireless Receiver Install Guide (LT-1823) for complete information.
• XR550 provides up to 500 zones
• XR150 provides up to 100 zones

14.2 Wireless Bus LEDs

The two LEDs, located above the XBus header, indicate data transmission and receipt. The left LED ashes green to
indicate the panel is transmitting data. The right LED ashes yellow to indicate the panel is receiving data.

LX-Bus Expansion

15.1 LX-Bus Headers

There are ve LX-Bus headers near the bottom of the XR150/XR550
panels:
• LX500 (J14), provides zones 500-599 (all panels).
• LX600 (J9), provides zones 600-699 (XR550 only).
PROG
• LX700 (J15 ), provides zones 700-799 (XR550 only).
• LX800 (J17 ), provides zones 800-899 (XR550 only).
• LX900 (J19 ), provides zones 900-999 (XR550 only).
10
BLK11SMK12GND13Z114GND15Z216Z317GND18Z419Z520GND

15.2 LX-Bus LEDs

The two LEDs, located above each LX-Bus header, indicate data transmission and receipt. The left LED ashes green
to indicate the
panel is transmitting LX-Bus data. The right LED ashes yellow to indicate the panel is receiving LX-Bus data.
RCV
J8
RED BLK
XMIT
PROG
RED
LX500
XMIT
500
J14
BLK
RCV
RED
LX600
RCV
XMIT
XMIT
RCV
600
700
J9
RED
BLK
LX700
BLK
RED
LX800
BLK
J17
Figure 9: LX-Bus Headers and LEDs
RED
LX900
Z6
XMIT RCV
BLK
22Z721
XMIT RCV
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
17
Page 22
INSTALLATION

15.3 OVC LEDs

The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw more current than the panel is rated for. The LED(s) turn a steady Red when lit. When the OVC LED(s) light red, the appropriate LX-Bus(es) and Keypad bus are shut down.
• The OVC LED located to the left of the 893A connector indicates overcurrent for the Keypad Bus (Terminals 7-10 and PROG header), XBUS, and LX500-LX700.
• The OVC LED to the right of the J24 Cell Module connector indicates overcurrent for LX800-LX900.
J1 Ethernet Connector (Panels with Network/Encryption only)

16.1 Description

The Ethernet Connector is available on the XR150/XR550 with network or encryption to connect directly to an Ethernet network using a standard patch cable. The Ethernet Connector supports 100MB/s full duplex operation and
the maximum impedance is 100 Ohms.
Link LED

16.2 Ethernet LEDs

The two LEDs, located on the top edge of the J1 Ethernet Connector, indicate network connection. The right, Link LED lights up green to indicate a valid receive connection from the host network. The yellow LED lights when connected to a
100Mb network and is o when connected to a 10Mb network.
Figure 10: J1 Ethernet and LEDs

16.3 Network Transient Suppression

The Model 270 Network Transient Suppression Module to provide transient surge protection for the J1 Ethernet Connector. Refer to the Model 270 Installation Sheet (LT-1316) for complete information.
Activity LED
J1
ETHERNET

J3 Telephone RJ Connector

17.1 Description

Connect the panel to the public telephone network by installing a DMP 356 RJ Cable between the panel J3 connector and the RJ31X or RJ38X phone block. The maximum impedance is 100 Ohms. CAUTION - To reduce the risk of re, use only No. 26 AWG or larger telecommunication line cord, such as DMP Model 356 Series Phone Cords.

17.2 J10 893A or 277 Trouble Sounder Connector

Connect an 893A Dual Phone Line Module or Model 277CAN Trouble Sounder to J10 on the XR150/XR550 Series. Refer to the 893A Installation Sheet (LT-0135) or 277CAN Installation Sheet (LT-1304CAN) for complete information.
17.3 Notication
The user must not repair registered terminal equipment. In case of trouble, immediately unplug the device from the telephone jack. The factory warranty provides for repairs. Registered terminal equipment may not be used on party lines or in connection with coin telephones. No tify the telephone company with the following information:
• The particular line(s) where the service is connected
• This Class A digital apparatus complies with Canadian ICES-003.
• The ringer equivalence number (REN) of 0.0
• The device make, model, and serial number

17.4 Phone Line Monitor

The XR150/XR550 Series panel has a built-in telephone monitor that monitors the phone line voltage to verify the
connection to the central oce. Figure 11 and the table below identify the phone block pin layout, wire numbers,
and colors.
Wire Number Wire Color
1 Gray 2 Orange 3 Black 4 Red 5 Green 6 Yellow 7 Blue 8 Brown
The wires on the RJ31 that feed pins 4 and 5 should be the ONLY wires on the D-marc. All other house phone wiring should be tied to pins 1 and 8 coming back from the RJ31.
Dial tone must come into RJ31X on pins 4 and 5 and go back to house phones from pins 1 and 8. Follow these steps to determine if panel is seizing the line:
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
18
To Telephone
Line
To Premise
Phone
Ring
5
8
Ring 1
6
7
Tip 1
Tip
4
3
2
1
Figure 11: Phone Jack Wiring
RJ31X or RJ38X Phone Block
Page 23
INSTALLATION
1. Unplug phone cord from RJ31X
2. Place butt-set on pins 4 and 5
3. Listen for dial tone. With dial tone present, lift either wire from pins 1 or 8
4. Listen for dial tone again. If the dial tone is present, RJ31X wiring is correct. If no dial tone is present, the
RJ31X wiring is backwards. Rewire so dial tone is coming IN on 4 and 5. If you still have trouble with the phone line, you may need to replace the RJ cord. If the dial tone is still not present, swap out the RJ31X phone block.

Reset and Tamper Headers

18.1 J16 Reset Header

The reset header is located just above the terminal strip on the right side of the circuit board and is used to reset the XR150/XR550 Series microprocessor.
To reset the panel when rst installing the system, install the reset jumper
before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
LX
LX900
RESET
LOAD
J6
CELL MODULE
To reset the panel while the system is operational, for example, prior to reprogramming, install the reset jumper without powering down the system. Remove the reset jumper after one or two seconds.
After resetting the panel, begin programming within 30 minutes. If you wait longer than 30 minutes, you must reset the panel again.

18.2 J4 Tamper Header

The TAMPER header is for use with the optional DMP 306 Tamper Harness. The harness connects to one or more tamper switches mounted inside the panel enclosure to supervise against unauthorized enclosure opening or removal. Refer to the wiring diagram on the enclosure door for correct tamper switch wiring.
Momentarily place the Reset jumper over both of the J16 pins to reset the panel.
J23
L
LX800
How the Tamper Works
If the enclosure is opened or removed while one or more of the system areas are armed, a panel tamper alarm is indicated. If all areas are disarmed, a panel tamper trouble is indicated.
Figure 12: XR550 Series
Canadian Panel Showing the
Reset Jumper

Cellular Modules

19.1 J24 Header

The J24 header is located to the right of the J7 Expansion Module on the right side of the circuit board and is used to connect the DMP Model 263LTE-A Cellular Communicator. This provides a fully supervised alarm communication path for the XR150/XR550 Canadian panel. Refer to the 263LTE Series (LT-1592) Installation Sheet for complete
information.

19.2 Module Installation

1. Insert the PCB stando end with anges into the stando hole in the panel PCB.
2. Align the PCB stando with the stando hole in the module PCB.
3. Press the module PCB card 12 pin connector onto the Cell Module (J24) connector on the panel while applying even pressure to both sides of the board to fully seat the module. See Figure 13. Note: If needed, the PCB can be removed from the enclosure to allow placement of the cell module.

19.3 Connecting the Antenna

1. Attach a 381 cable to the SMA connector on the cell module.
2. Position one of the supplied washers onto the other end of the 381 SMA connector and push the threaded end
through an enclosure knockout.
3. Position the second washer onto the threaded end extending through the knockout and secure the nut.
4. Attach the included 383 Antenna to the SMA connector. See Figure 13. Note: As an alternative, an antenna coax
can be connected directly to the cell module SMA connector when the coax enters the enclosure via conduit.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
19
Page 24
COMPLIANCE
Wiring Diagrams

20.1 LX-Bus™ Module Connection

LX-Bus Expansion
13
2
5
1
3
AC
AC
B+
7
4
6
BELL
RED
B-
GND
11
9
10
8
SMK
GRN
BLK
YEL
15
14
12
Z1
Z2
GND
GND
S
S
S
S
19
17
16 Z3
GND18Z4
20
22
GND21Z6
23
Z7
GND
Z5
Each LX-Bus Module must have its own independent address ranging from 00 to 99. A Supervisory zone must be programmed into the panel to
24
26
26
Z8
Z9-
Z9+
Z10+
properly supervise each
28
27
Z10-
module.
= Supervised Circuit
S
S
S
S
S
S
S
S
S
Open Collector
Annunciator Outputs
LX-Bus™ Wiring
Optional LED wiring 50mA at 50 VDC resistive
Red
Yellow
Green
To additional
Black
LX-Bus Modules
Form C
Relay 2
Relay 1
Relay 3
Relay 4
Contacts Typical
Normally Closed Common Normally Open
Model 716 Output
Expander Module
13m at 12 VDC
Optional LED wiring 50mA at 50 VDC resistive
Model 717 Graphic
Annunciator
Module
10m at 12 VDC
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
20
Page 25

20.2 Model 860 Relay Module Connection

WIRING DIAGRAMS
RED YEL
Model 860
GRN BLK
Relay Module
1 2 3 4
J2
J6
K
4-wire
Harness
Assembly
Programmable Relay contact rating: 1 Amp @ 30VDC, Resistive, Power Limited
Relay 3
Relay 4
Relay 1
Relay 2
+12 VDC
N/C
Common
{
N/O
{ { {

20.3 Dual Zone Protection

Tens Ones
KYPD LX
J2
TXD
RED
To LX-Bus or Keypad Bus
YEL
GRN
BLK
J5
Protected Area such as a Vault Door
Tamper Contact
Magnet
714-8 and 714-16: Use 1k EOL
Z1+
Z1-
Z2+
Z2-
Z3+
Z3-
Z4+
Z4-
J7
Z5+
Z5-
Z6+
Z6-
Z7+
Z7-
Z8+
Z8-
J10
Z9+
Z9-
Z10+
Z10-
Z11+
Z11-
Z12+
Z12-
J12
Z13+
Z13-
Z14+
Z14-
Z15+
Z15-
Z16+
Z16-
J14
4-Conductor Jacketed Cable
Zone 2 Programming
Night Type Zone (NT) Disarmed Open (DO) T Disarmed Short (DS) T
Zone 2 1k EOL
Armed Open (AO) A Armed Short (AS) A
Zone 1 Programming
Night Type Zone (NT)
Zone 1
1k EOL
Disarmed Open (DO) — Disarmed Short (DS) T Armed Open (AO) A Armed Short (AS) A Note: Zone Names must be same or equivalent
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
21
Page 26
Certications
SIA
Meets ANSI/SIA CP-01-2010 False Alarm Reduction. This Class A digital apparatus complies with Canadian ICES-003
Underwriters Laboratory of Canada (ULC) Listed
ULC S545 Household Fire
ULC C1023 Household Burglar
ULC/ORD-C1076 Proprietary Burglar
ULC S304 Central Station Burglar
ULC S559 Fire Signal Receiving Centres and Systems
21131
800-641-4282
www.dmp.com
Designed, Engineered and
Assembled in the USA
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
LT-1233CAN © 2021 Digital Monitoring Products, Inc.
Loading...