The XR150/XR550 Series provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation
of two Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A Model 431 Output
Harness is required to use these outputs.
The panels also provide four open collector outputs rated for 50mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model 300 Output Harness is required to use these outputs.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
1
Page 6
INTRODUCTION
1.7 Enclosure Specications
The panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s guide, and
programming sheets.
Enclosure
Model
35017.5”W x 13.5”H x 3.5”DGray (G) or Red (R)18-Gauge
350A17.5”W x 13.5”H x 3.75”DGray (G)18-Gauge with 16-Gauge door
34113.22”W x 7.0”H x 3.5”DGray (G)20-Gauge
34912.5”W x 11.5”H x 3.5”D Gray (G)20-Gauge
352X14.5”W x 32.0”H x 4.0”DGray (G)16-Gauge
SizeColor(s)Construction (Cold Rolled
Steel)
Panel Features
2.1 Description
The DMP XR150/XR550 Series Canadian panel is a versatile 12VDC, combined access control, burglary, and re
communicator panel with battery backup. The panels provide eight on-board burglary zones and two on-board 12VDC
Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or
other latching devices. You can use up to sixteen supervised 32-character LCD keypads; network communications and
expansion interface cards; zone and output expansion modules; and initiating and indicating circuit modules. You can
also connect auxiliary devices to the panel’s output relays to expand the basic system control capability. Combined
current requirements of additional modules may require an auxiliary power supply. Refer to the XR150/XR550
Series Power Requirements section in this guide when calculating power requirements. The XR150/XR550 Series can
communicate to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID communication.
2.2 Zone Expansion
Each panel provides multiple options for zone expansion.
• 10 on-board zones
• Up to 64 programmable keypad zones
• Up to 500 LX-Bus zones
Using DMP LCD keypad remote zone capability and zone expansion modules, additional zones are available on each
panel:
• XR550 provides up to 574 additional zones
• XR150 provides up to 142 additional zones
The panel keypad data bus supports up to 16 supervised device addresses with each address supporting up to four
programmable expansion zones (64 total).
Using the on board LX-Bus™ (LX500-LX900) connections, and any combination of single, four, eight, or sixteen-zone
expansion modules and single-zone LX-Bus™ detectors, additional zones are available on each panel:
• XR550 provides up to 500 additional zones (LX500-LX900)
• XR150 provides up to 100 additional zones (LX500)
Note: Do not use shielded or twisted pair wiring for LX-Bus or Keypad Bus circuits.
2.3 Output Expansion
In addition to the two SPDT relays and four programmable open collector outputs on the XR150/XR550 Series, you
can also connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules can
provide an additional 500, 300, or 100 programmable SPDT relays.
The panels provide Output Schedules for programming the 716 to perform a variety of annunciation and control
functions. Also assign the 716 outputs to any panel Output Options such as Fire Alarm, Communication Fail, or Phone
Trouble Outputs. Refer to the 716 Installation Guide (LT-0183).
The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground
outputs that follow the state of their assigned zones.
Note: The 717 supports the rst eight Keypad Bus addresses. To follow Keypad Bus addresses nine through 16, install
multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).
2.4 Central Station Communication
You can program the panel for reporting to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID
communication. You can program the panel for reporting to DMP SCS-VR Virtual Receivers using cellular or network
communication. The panel connects at the premises to a standard RJ31X or RJ38X telephone jack. Use the DMP 893A
Dual Phone Line Module when connecting the XR150/XR550 Series panel to two separate phone lines.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
2
Page 7
INTRODUCTION
2.5 Encrypted Communications (XR550 with Encryption only)
An XR550 panel with encryption communicates using 128-bit or 256-bit AES encryption. If you currently have an
XR550 panel installed, you may contact DMP Customer Service with the panel serial number. The serial number(s)
should be sent in writing via e-mail or fax. A separate feature key is sent for each panel to activate encrypted
communications using the Feature Upgrade process. Encrypted communication cannot be enabled on a standard
XR550 panel. For more information on the Feature Upgrade process see the XR150/XR550 Series Canadian
Programming Guide (LT-1232CAN).
Note: 256-bit encrypted messages to SCS-1R receiver only communicate when using SCS-104 Receiver Line Cards
with Version 102 or higher software.
2.6 Caution Notes
Throughout this guide you will see caution notes containing information you need to know when installing the panel.
These cautions are indicated with a yield sign. Whenever you see a caution note, make sure you completely read
and understand its information. Failing to follow the caution note can cause damage to the equipment or improper
operation of one or more components in the system. See the example shown below.
Always ground the panel before applying power to any devices: The panel must be properly grounded
before connecting any devices or applying power to the panel. Proper grounding protects against
Electrostatic Discharge (ESD) that can damage system components.
2.7 Compliance Instructions
For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratory certicated system, please see the Compliance Listing Guide (LT-1330) for instructions.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
3
Page 8
INTRODUCTION
The plug-in
transformer shall plug
into a 120 VAC 60 Hz
outlet not controlled
by a switch.
tamper protection
System Components
3.1 Wiring Diagram
The XR550 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.3.
AC Wiring must be in conduit and exit out
the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Bell
12 VDC
Minimum cuto time 15
min.
1.5 Amp Max using
FTA7516
J12
75VA
50VA
¼"
s
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
Bell cuto time
range is 5 to 99
minutes, non-coded.
s
s
s
s
DISARM
1k Ohm
Phone Line
XR550 Series
Canadian Panel
OVC
s
s
s
s
1k
Ohm
Bell
Keyswitch Arming
can be connected
to any zone.
ARM
1k Ohm
J3
3
4
5
6
Outputs 3-6
s
22 gauge minimum
22 gauge minimum
s
RED
YELLOW
Smoke
Detector
s
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
J11
Output 1Output 2
K6K7
J4
Tamper
J14
J8
LX500
s
1k
Ohm
22 gauge minimum
22 gauge minimum
s
s
ss
BLACK
GREEN
RED
RED
YELLOW
GREEN
BLACK
Zone Expander
s
s
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
1k Ohm 1k Ohm
s
Listed Resistors
J2
Zone 1
Zone 2
s
s
s
1k
Ohm
Total current combined from
terminals 7, 11, 25, 27, XBUS
Model 714
s
s
J13
XBUS
Out1 Out2
J15J19J17
J9
LX800
LX700
s
Ohm
1k
Zone 4
s
s s
Ohm
1k
Zone 5
Ohm
s
s
Ohm
1k
Zone 3
s
Auxiliary/Smoke Power
and LX500-LX900
1.5 Amp Max
13.8 VDC to 10.2 VDC
Zone
Expander
Model 711
7mA @ 12
ss
s
s
s
1k Ohm
1k Ohm
WARNING: Incorrect
connections may cause
damage to the unit.
Form C Relays (J2)
Output Color Code–Model 431
Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6 Black
J16
Reset
J24
10
3.3k Ohm
Resistor
DMP Model
309
1k
Zone 6
s
LX900
sss
s
1k
Ohm
Zone 7
Zone 8
1k
Ohm
DMP Model
3.3k Ohm
Resistor
Zone 9Zone
ss ss
309
s
= Supervised Circuit
Zone Expander
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Zone
Expander (up
to 8 zones)
Model 712-8
VDC
19mA @ 12
VDC
s
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN
TO PROVIDE SUPERVISION OF
CONNECTIONS.
s
1k Ohm
ss s
3.3k Ohm
3.3k Ohm
s
Front and Rear
included with
Model 350A
Attack Resistant
Enclosure.
Front
Tamper
Rear
Tamper
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715
compatibility
identifier: A
Maximum operating
range: 13.8 VDC to
9.7 VDC.
Class B (Style A).
Model 715
sss ss
3.3k Ohm
3.3k Ohm
Figure 1: XR550 Canadian Wiring Diagram
3.2 Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR150/XR550 Series
input and output circuits. Additional surge protection is available by installing the DMP 370, 370RJ Lightning
Suppressors or Model 270 Network Transient Suppression Module.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
4
Page 9
INTRODUCTION
3.3 Accessory Devices
Cellular Communicators
263LTE-A Cellular CommunicatorAllows you to connect the XR150/XR550 Series to to the AT&T LTE network.
Accessory Modules
270 Network Transient Suppression
Module
277CAN Trouble SounderProvides local sounder for monitoring of panel operations and loss of Keypad Bus.
370/370RJ Lightning Suppressor
893A Dual Phone Line ModuleAllows you to supervise two standard phone lines connected to an XR150/XR550 Series panel.
Expansion Modules
710 Bus Splitter/RepeaterAllows you to increase keypad or LX-Bus™ wiring distance to 2500 feet.
711 Zone Expansion ModuleIncreases available reporting zones. Provides one Type A Class B zone.
711S Zone Expansion ModuleProvides one Class B zone for connecting burglary devices.
712-8 Zone ExpanderProvides Class B zones for connecting burglary devices.
714, 714-8, 714-16 Zone ExpandersProvides Class B zones for connecting burglary and non-powered re devices.
714N-POE Network Zone ExpanderAllows you to add four zones to the XR150/XR550 Series panels using IP network capability.
715, 715-8, 715-16 Zone ExpandersProvides 12VDC Class B powered zones for connecting smoke detectors, glassbreak detectors,
716 Output ExpanderProvides four Form C relays (SPDT) and four switched grounds (open collector) for use in a
717 Graphic Annunciator ModuleProvides 20 zone following annunciator outputs (open collector) for use in a variety of
734, 734N, 734N-POE Wiegand
Interface Modules
DMP Two-Way Wireless Devices
1100X Series/1100XH Series Wireless
Receiver
1100R RepeaterProvides additional range for wireless devices.
1100T Wireless TranslatorAllows non-DMP wireless devices to integrate with DMP XR150CAN/XR550CAN Series panels.
1101 Series Universal TransmitterProvides both internal and external contacts that may be used at the same time to yield two
1102 Universal TransmitterProvides an external contact.
1103 Series Universal TransmitterProvides both internal and external contacts that may be used at the same time to yield two
1106 Series Universal TransmitterProvides both internal and external contacts that may be used at the same time to yield two
1107 Micro Window TransmitterProvides a wireless window transmitter.
1108 Doorbell ModuleMonitors doorbell presses.
1114 Four-Zone ExpanderProvides four wireless zones.
1116 Relay OutputProvides one Form C relay.
1117 LED AnnunciatorProvides a visual system status indicator.
1118 Remote Indicator LightProvides a visual indication of a Panic situation.
1119 Door SounderProvides a battery powered sounder.
1126R Motion DetectorCeiling mount motion detector with panel programmable sensitivity and Disarm/Disable
1127C/1127W PIR Motion DetectorWall mount motion detector with panel programmable sensitivity and Disarm/Disable
1131 Recessed ContactProvides a recessed contact option for door or window applications.
1135 Wireless SirenProvides a wireless siren.
1136 Remote SounderMulti-function sounder that plugs directly into a standard 110VAC wall outlet.
1139 Bill TrapProvides a silent alarm option for retail and banking cash drawers.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
Provides transient surge protection for the J1 Ethernet Connector.
Provides protection against voltage surges on panel input and output circuits
The 893A module monitors the main and backup phone lines for a sustained voltage drop and
alerts users when the phone line is bad.
and other 2- or 4-wire devices.
variety of remote annunciation and control applications for use on the LX-Bus only.
remote annunciation and control applications for use on the LX-Bus only.
Provides system codeless entry, and arming and disarming using access control readers.
Supports up to 500 devices in residential or commercial wireless operation.
individual reporting zones from one wireless transmitter.
individual reporting zones from one wireless transmitter. Requires EOL resistor for external
contact. Provides Disarm/Disable functionality.
individual reporting zones from one wireless transmitter.
1144 Series Wireless Key FobsKey Fob transmitters designed to clip onto a key ring or lanyard.
1154 Wireless Four-Zone Input
Module
1158 Wireless 8-Zone Input
Module
1164 Wireless Synchronized
Smoke Detector
1166 Wireless Smoke RingInstalls on any traditional AC-powered, three wire, interconnected smoke alarm system.
1183-135F Heat DetectorFixed temperature heat detector.
1183-135R Heat DetectorFixed temperature and rate-of-rise heat detector.
1184 Carbon Monoxide DetectorCarbon Monoxide Detector.
Interface Modules
736P Radionics™ Popit InterfaceAllows a Radionics™ POPIT System to interface with DMP XR150/XR550 Series panels while
738A Ademco InterfaceAllows Ademco™ 5881 wireless receivers to interface with DMP XR150/XR550 Series panels.
738I ITI Interface ModuleAllows ITI™ SuperBus™ 2000 Series wireless receivers to interface with DMP XR150/XR550
738Zplus Z-Wave Interface
Module
Indicating and Initiating Devices
860 Relay Output ModuleProvides one relay and three relay sockets for expansion of up to four relays.
865 Supervised Style W or X
Notication Circuit Module
866 Style W Notication Circuit
Module
867 Style W LX-Bus Notication
Circuit Module
869 Dual Class A Style D
Initiating Module
Keypads
LCD keypadsAllows you to control the panel from various remote locations. Connect up to sixteen
9000 Series Wireless KeypadsAllows you to control the panel from various remote locations. Connect up to seven
9800 Series Wireless
Touchscreen keypads
Graphic
Addressable Smoke Detectors
2W-BLX, 2WT-BLXSingle-zone, addressable conventional smoke, smoke/heat detectors that connect to the
Provides two-button hold-up operation with a belt clip.
Converts up to four existing normally closed,hardwired zones into wireless zones.
Allows installers to convert up to 8 existing hardwired zones into wireless zones.
Commercial or residential, battery powered, wireless, low prole, photoelectric smoke
detector, with synchronizing sounder.
maintaining Radionics™ wiring.
Series panels.
Provides connection for Z-Wave modules.
Provides supervised alarm current when using the XR150/XR550 Series panel bell output
and up to 5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 865
can supervise 2-wire or 4-wire style circuits for opens and shorts with individual LED
annunciation.
Provides supervised alarm current using the XR150/XR550 Series panel bell output and up
to 5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 866 can supervise
2-wire Style W circuits for opens and shorts.
Provides supervised alarm current using the XR150/XR550 Series panel bell output and up to
5 Amps at 12 or 24VDC when using a listed auxiliary power supply. The 867 connects to the
XR150/XR550 Series panel LX-Bus™ and provides one 2-wire Style W notication circuit for
open and short conditions. Individual Bell Relay addresses Bell Ring styles.
Provides two Class A, Style D, 4-wire initiating zones for connecting waterow switches and
other non-powered re and burglary devices.
supervised Model 630F Remote Fire Command Center, 7060, 7063, 7070, 7073, 7160, 7163,
7170, 7173 Thinline™ keypads, 7060A, 7063A, 7070A, 7073A Aqualite™ keypads, and 7872 and
7873 Graphic Touchscreen keypads to the keypad bus using terminals 7, 8, 9, and 10.
9060/9063 Wireless Keypads.
Allows you to control the panel from various remote locations. Connect up to seven 9862
Wireless Keypads.
LX-Bus. Includes drift compensation.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
6
Page 11
INSTALLATION
Installation
4.1 Mounting the Enclosure
The metal enclosure for the XR150/XR550 Series must be mounted in a secure, dry place to protect the panel from
damage due to tampering or the elements. It is not necessary to remove the XR150/XR550 Series PCB when installing
the enclosure. Figure 2 shows the mounting hole locations for the Model 350/350A Enclosures. Figure 3 shows the
Model 341 Enclosure. Figure 4 shows the Model 352X panel cabinet and 352S shelf cabinet for multiple batteries.
The 350A Attack Resistant enclosure is factory shipped with one knockout on the top left of the enclosure. As
needed, additional knockouts or antenna exits may be added at the time of installation. See Figure 2 for the
positions on the enclosure that can be added. Each additional knockout must be lled with conduit.
Enclosure Mounting Holes
XR550 Panel
J6
J23
K
*
Dual 1 3/4" and 1 3/8" Conduit Knockouts
* 350A Optional Knockout
Battery Shelf holds up to three 7 Ah Batteries
*
Figure 2: XR550 Series in Model 350 or 350A Enclosure
*
3-Hole
Pattern for
Accessory
Modules
Front and
Rear
Tamper
Switches for
350A
Attack
Resistant
Enclosure
*
*
PEMs for optional battery bracket.
Lid Mounting Holes (4 places)
Lid Mounting Holes
(4 places)
XR550 Panel
See 341 Installation sheet for additional
information.
J23
K
Enclosure Mounting Holes (4 places)
Dual 1/2" and 3/4" Conduit Knockouts
J6
Figure 3: XR550 Series in Model 341 Enclosure
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
7
Page 12
INSTALLATION
56 VA
Transformer
Mounting
Plate
XR550 Panel
XR550 Panel
K
Mounting for one (1)
Zone Expansion Module.
J6
Battery Shelf
Figure 4: XR550 Series in Model 352X Enclosure and Separate 352S Enclosure with Shelves
4.2 Mounting Keypads and Zone Expansion Modules
DMP LCD keypads have removable covers that allow you to easily mount the keypad to a wall or other at surface
using the screw holes on each corner of the base. Before mounting the base, connect the keypad wire harness leads
to the keypad cable from the panel and to any device wiring run to that location. Then attach the harness to the pin
connector on the PC board, mount the base, and install the keypad cover making sure all of the keys extend through
their respective holes.
For mounting keypads on solid walls, or for applications where conduit is required, use the Model 695 1-1/2” deep or
the Model 696 1/2” deep backboxes.
The DMP 711, 712-8, 714, 715, 716, and 717 modules are each contained in molded plastic housings with removable
covers. The base provides you with mounting holes for installing the unit to a wall, switch plate, or other surface.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
8
Page 13
INSTALLATION
PROG
LX500
LX600
LX700
LX800
LX900
RED BLK
RED
BLK
RED
BLK
RED
BLK
RED
J17
BLK
XMITRCV
RED
BLK
XMITRCV
J8
J14
J9
XMIT
RCV
XMIT
RCV
XMIT
RCV
XMIT
RCV
PROG
500
600
700
4.3 Connecting LX-Bus and Keypad Bus Devices
Connections for LX-Bus and Keypads are provided through the J8 (PROG), J14 (LX500), J9 (LX600), J15 (LX700), J17
(LX800), J19 (LX900), and J13 (XBUS) 4-pin headers. Several factors determine the DMP LX-Bus™ and keypad bus
performance characteristics: the wire length and gauge used, the number of devices connected, and the voltage at
each device. When planning an LX-Bus™ and keypad bus installation, keep in mind the following information:
• DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted pair
or shielded wire for LX-Bus and keypad bus data circuits.
• On keypad bus circuits, to maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet.
When using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add devices, install an
additional power supply that is listed for Fire Protective Signaling, power limited, and regulated (12VDC nominal)
with battery backup.
Note: Each panel allows a specic number of supervised keypads. Add additional keypads in the unsupervised mode.
Refer to the Keypad Bus section for the specic number of supervised keypads allowed.
• Maximum distance for any one bus circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance
can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As
wire distance from the panel increases, DC voltage on the wire decreases. Maximum number of LX-Bus devices on
the rst 2,500 foot circuit is 40 devices.
• Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2VDC. If the voltage at any
device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too
low, the devices cannot operate properly.
For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031).
4.4 Wireless Keypad Association
Enable Wireless Keypad Association operation on both the keypad and panel:
1. Access the Installer Options Menu (3577 (INST)).
2. Select RF Survey). The keypad logo LEDs turn on red until association is
successful.
Enable Wireless keypad Association operation in the XR150/XR550 panel:
Reset panel 3 times within 12 seconds. Allow the keypad bus Transmit/Receive
Figure 5: Keypad Bus LEDs
LEDs to turn back on between each reset. For 60 seconds the panel listens for
wireless keypads that are in the Installer Options Menu (3577 CMD) and have
not been programmed, or associated into another panel. Those keypads are
assigned to the rst open device position automatically based upon the order in
which they are detected. The keypad logo turns Green to indicate it has been
associated with the panel.
Primary Power Supply
5.1 AC Terminals 1 and 2
Connect the transformer wires to terminals 1 and 2 on the panel. Use no more than 70 ft. of 16 gauge or 40 ft. of 18
gauge wire between the transformer and the XR150/XR550 Series.
Always ground the panel before applying power to any devices: The XR150/XR550 Series must be
properly grounded before connecting any devices or applying power to the panel. Proper grounding
protects against Electrostatic Discharge (ESD) that can damage system components. See the Earth ground
section.
5.2 Transformer Types
Use Model 327CAN (16.5 Vac 50 VA) plug-in or Model FTA7516 from ATC Frost.
The transformer must be connected to an unswitched 120 Vac 60 Hz electrical outlet with at least .87A of
available current. Never share the transformer output with any other equipment.
5.3 J12 3-Pin Header for Transformer Types
Place the jumper on the left two pins for a Maximum 2 Amp (Bell+Aux+Smoke+XBUS+LX500-LX900) when using the
Model 327CAN plug-in transformer (default).
Use an ATC Frost FTA7516 transformer and place the jumper on the right two pins for a Maximum, 3 Amps
(Bell+Aux+Smoke+XBUS+LX500-LX900).
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
9
Page 14
INSTALLATION
Secondary Power Supply
6.1 Battery Terminals 3 and 4
Connect the black battery lead to the negative battery terminal. The negative terminal connects to the enclosure
ground internally through the XR150/XR550 Series circuit board. Connect the red battery lead to the battery positive
terminal. Observe polarity when connecting the battery.
You can add a second battery in parallel using the DMP
Model 318 Dual Battery Harness. DMP requires each
battery be separated by a PTC in the battery harness
wiring to protect each battery from a reversal or
short within the circuit. See Figure 6.
Use sealed lead-acid batteries only: Use
the Model 365 (12VDC 9 Ah), Model 366
(12VDC 18 Ah), Model 368 (12VDC 5.0 Ah),
or Model 369 (12VDC 7 Ah) sealed lead-acid
rechargeable battery. Batteries supplied by
DMP have been tested to ensure proper
charging with DMP products.
GEL CELL BATTERIES CANNOT BE USED WITH THE
XR150/XR550 SERIES PANEL.
Battery
318 Battery
Harness
318 Battery
Battery
PTC
Harness
PTC
Red
Black
Red
Battery
Figure 6: Wiring Multiple Batteries
Black
Battery
Start
To AC
Panel Red and
Black Battery Cables
14 AWG to
Earth Ground
XR550
Panel
AC
+BAC–B
1234
To Bell
Circuit
BELLGND
56
6.2 Earth Ground (GND)
To provide proper transient suppression, XR150/XR550 Series panel terminal 4 must be connected to earth ground
using 14 gauge or larger wire. DMP recommends connecting to a cold water pipe, ground rod, or building ground
only. Do not connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground.
6.3 Battery Only Restart
When powering up the XR150/XR550 Series panel without AC power, briey short across the battery start pads to pull
in the battery cuto relay. The leads need a momentary short only. Once the relay has pulled in, the battery voltage
holds it in that condition. If the XR150/XR550 Series panel is powered up with an AC transformer, the battery cuto
relay is pulled in automatically. For more information refer to Figure 1.
6.4 Battery Replacement Period
DMP recommends replacing the battery every 3 to 5 years under normal use.
6.5 Discharge/Recharge
The XR150/XR550 Series battery charging circuit oat charges at 13.8VDC at a maximum current of 1.0 Amps. Listed
below are the various battery voltage level conditions:
Battery Trouble: Below 11.9VDC
Battery Cuto: Below 10.2VDC
Battery Restored: Above 12.6VDC
6.6 Battery Supervision
The XR150/XR550 Series tests the battery when AC power is present. The test is done every three minutes and lasts
for ve seconds. During the test, the panel places a load on the battery; if the battery voltage falls below 11.9VDC
a low battery is detected. If AC power is not present, a low battery is detected any time the battery voltage falls
below 11.9VDC.
If a low battery is detected with AC power present, the test repeats every two minutes until the battery charges
above 12.6VDC indicating the battery has restored voltage. If a weak battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is completed.
6.7 Battery Cuto
The panel disconnects the battery any time the battery voltage drops below 10.2VDC. This prevents battery deep
discharge damage.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
10
Page 15
INSTALLATION
6.8 XR150/XR550 Series Canadian Power Requirements
During AC power failure, the XR150/XR550 Series panel and all connected auxiliary devices draw their power
from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The
following table lists the XR150/XR550 Series panel power requirements. You must add the additional current draw of
keypads, zone expansion modules, smoke detector output, and any other auxiliary devices used in the system for the
total current required. The total is then multiplied by the number of standby hours required to calculate the total
ampere-hours required.
Standby Battery Power CalculationsStandby CurrentAlarm Current
XR150/XR550 Series Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
893A Dual Phone Line ModuleQty _______x12mA ______Qty _______x50mA ______
*Based on 10% of active zones in alarmTotal Standby ______mATotal Alarm ______mA
Total Standby______mA x number of Standby Hours needed
Qty _______
Qty _______xx
Qty _______
Qty _______xx
Qty _______
Qty _______xx
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______x13mA ______Qty _______
Qty _______x10mA ______Qty _______
7mA
1.6mA
17mA
1.6mA
20mA
1.6mA
x
7mA
x
4mA
x
.1mA
x
20mA
x
4mA
x
.1mA
Total Alarm
______
______
______
______
______
______
______
______
______
______
______
______
______mA______mA
______mASub-Total Alarm ______mA
______mASub-Total Alarm ______mA
______ =
______mA
Qty _______
Qty _______xx
Qty _______
Qty _______xx
Qty _______
Qty _______xx
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______xx
Qty _______xx
_______mA-hours
+_______mA-hours
Total
_______mA-hours
X .001
= _______Amp-hrsRequired
7mA
______
2mA*
______
17mA
______
2mA*
______
20mA
______
2mA*
______
x
7mA
30mA*
.1mA
20mA
30mA*
.1mA
13mA
12mA
10mA
1mA
______
______
______
______
______
______
______
______
______
______
x
x
x
x
x
Refer to section 6.9 for standby battery selection.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
12
Page 17
INSTALLATION
6.9 Standby Battery Selection
To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours
Required calculation from section 6.8 XR150/XR550 Series Power Requirements, perform the following:
1. Select the desired standby hours required from the table below: 24, 60, or 72 hours.
2. Select the desired battery size: Model 368 (12VDC 5.0 Ah), Model 369 (12VDC 7 Ah), Model 365 (12VDC 9 Ah),
Model 366 (12VDC 18 Ah).
3. Select a Max. Ah Available number that is just greater than the number calculated in Amp Hours Required.
4. Install the number of batteries shown in the corresponding No. of Batteries required column.
Example: If the Amp Hours Required calculation equals 22 Ah for 24 hours of standby time and 4.5 Ah
batteries are desired, install six (6) Model 368 (12VDC, 5.0 Ah) batteries.
Note: You can use either a Model 327CAN Plug-in 50 VA or ATC Frost FTA7516 75VA Transformer with any of the
82616181161
123122132162322
164183203243483
205244274324
246315345405
287376416
328437
369Note: 48 hours is the typical battery recharge time for any of the Number of Batteries
4010
132142172171
203223263342
274294344523
335375435694
406446526
477527617Note: 48 hours is the typical battery
548598698
609679
6710
72 hours of standby power
9 Ah Batteries18 Ah Batteries
Max. Ah
Available
162161
253332
334503
425674
506
597Note: 72 hours is the typical battery recharge time required for any of the Number of
678
Note: If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then
add power supply(s) to power some system devices allowing the Amp Hours Required calculation to be reduced. See
the 710 Bus Splitter/Repeater Installation Guide (LT-0310).
No. of
Batteries
No. of
Batteries
Max. Ah
Available
Max. Ah
Available
Batteries shown in this section.
No. of
Batteries
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
recharge time for any of the Number of
Batteries shown in this section.
No. of
Batteries
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
13
Page 18
INSTALLATION
Bell Output
7.1 Terminals 5 and 6
Terminal 5 supplies positive 12VDC to power alarm bells or horns. This output can be steady, pulsed, or temporal
depending upon the Bell Action specied in Bell Options. Terminal 6 is the ground reference for the bell circuit. This
supervised output detects 1k Ohms or less as normal. The indicating appliance can supply this resistance. If using a
horn or siren, a 1k Ohm 1/2 W EOL resistor (provided) should be added across the bell circuit to provide supervision.
See the Notication Appliance section for a list of approved notication appliances and the Wiring Diagrams for
connections.
Keypad Bus
8.1 Description
XR150/XR550 Series panel terminals 7, 8, 9, and 10 are for the keypad bus. You can connect up to sixteen supervised
keypads and multiple unsupervised keypads to the XR150/XR550 Series. In addition to DMP LCD keypads, you can also
connect any combination of zone expansion modules to the data bus up to 16 devices.
Note: Do not use shielded wire for LX-Bus/Keypad Bus circuits.
8.2 Terminal 7 - RED
This terminal supplies positive 12VDC Regulated to power DMP LCD keypads and zone expansion modules. Terminal 7
also supplies power for any auxiliary device. The ground reference for terminal 7 is terminal 10.
The output current is shared with the smoke power output on terminal 11 and Zones 9 and 10. Current draw for all
connected devices must not exceed the panel maximum current rating. See Power Supply in the Compliance section
for maximum current in a re listed application.
8.3 Terminal 8 - YELLOW
Terminal 8 receives data from keypads and zone expansion modules. It cannot be used for any other purpose.
8.4 Terminal 9 - GREEN
Terminal 9 transmits data to keypads and zone expansion modules. It cannot be used for any other purpose.
8.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for DMP LCD keypads, zone expansion modules, and all auxiliary devices being
powered by terminal 7.
8.6 J8 Programming Connection
A 4-pin header (J8) is provided to connect a keypad when using a DMP Model 330 Programming Cable. This provides a
quick and easy connection for panel programming.
You may also use the Programming Header to connect Keypad Bus devices. This is an alternative to connecting
keypad bus devices to terminals 7, 8, 9, and 10.
8.7 Keypad Bus LEDs
The two LEDs, located above the J8 PROG connector, indicate data transmission and receipt. The left LED ashes
green to indicate the panel is transmitting keypad bus data. The right LED ashes yellow to indicate the panel is
receiving keypad bus data. See Figure 5.
8.8 OVC LED(s)
The Overcurrent LED (OVC) lights red when the devices connected to the Keypad Bus and LX-Bus(es) draw more
current than the panel is rated for. The LED(s) turn a steady red when lit. When the OVC LED(s) light red, the
appropriate LX-Bus(es) and Keypad bus are shut down.
• The OVC LED located to the left of the 893A connector indicates overcurrent for the Keypad Bus (Terminals 7-10
and PROG header), XBUS, and LX500-LX700.
• The OVC LED to the right of the J24 Cell Module connector indicates overcurrent for LX800-LX900.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
14
Page 19
INSTALLATION
1k Ohm Normally
Closed
1k Ohm
Normally Open
1k Ohm Combination
Normally Open and
Normally Closed
Smoke and Glassbreak Detector Output
9.1 Terminals 11 and 12
Terminal 11 supplies positive 12VDC Regulated to power 4-wire smoke detectors and other powered devices. This
output can be turned o by the user for 5 seconds using the Sensor Reset User Menu option to allow latched devices
to reset. Terminal 12 is the ground reference for terminal 11.
9.2 Current Rating
The Output current from terminal 11 is shared with terminals 7, 25, 27, and LX500-LX900.
Caution: The total current draw of all devices powered from the panel must be included with terminal 11
calculations and must not exceed the maximum output rating.
Protection Zones
10.1 Terminals 13–24
Zones 1 to 8 (terminals 13 to 24) on the XR150/XR550 Series panels are all grounded burglary zones. For
programming purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
TerminalFunctionTerminalFunction
13Zone 1 voltage sensing19Zone 5 voltage sensing
14Ground for Zones 1 and 220Ground for Zones 5 and 6
15Zone 2 voltage sensing21Zone 6 voltage sensing
16Zone 3 voltage sensing22Zone 7 voltage sensing
17Ground for Zones 3 and 423Ground for Zones 7 and 8
18Zone 4 voltage sensing24Zone 8 voltage sensing
The voltage sensing terminal measures the voltage across a 1k Ohm End-of-Line
resistor to ground. Use DMP Model 311 1k Ohm resistors. Dry contact sensing
devices can be used in series (normally-closed) or in parallel (normally-open)
with any of the burglary protection zones.
Each protection zone detects three conditions: Open, Normal, and Short. Listed
below are voltage and resistance parameters for each condition:
Condition Resistance on zone Voltage on positive terminal
Open over 1300 Ohms over 2.0VDC
Figure 7: Protection Zone Wiring
Normal 600 to 1300 Ohms 1.2 to 2.0VDC
Short under 600 Ohms under 1.2VDC
10.2 Dual EOL
The XR150/XR550 Series Canadian panels support the use of dual 1K EOL resistors on panel Zones
1-8. Two EOL resistors are used so a wire trouble can be indicated during the disarm period.
When dual end-of-line operation is chosen in panel programming, normal zone processing occurs
with the following exception: When processing an open zone and a trouble or alarm message is
NOT programmed to be sent for the open state, the panel checks to see if the wire is cut. If the
wire is cut, the panel automatically sends an alarm if armed or trouble is disarmed.
ZONE STATUS
Zone Wires OpenZone Wires ShortContact NormalContact Open
DisarmedTroubleTroubleNormalNormal
ArmedAlarmAlarmNormalAlarm
10.3 Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the XR150/XR550 Series panel.
Ensure detection devices used on the protec tion zones are rated for use with this delay. Zones 1-10 can also be
programmed for a fast response delay of 160 milliseconds.
Zone Wires
to Panel
Zones 1-8
TAMP
1K Ohm
1K Ohm
Indicating Device
N/O
C
N/C
Figure 8:Dual EOL
10.4 Keyswitch Arming Zone
A keyswitch on an Arming type zone allows selected areas to arm and disarm without having to enter a user code.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
15
Page 20
INSTALLATION
Powered Zones for 2-Wire Smoke Detectors
11.1 Terminals 25–26 and 27–28
Panel terminals 25 through 28 provide two resettable Class B, Style A, 2-wire powered zones. For programming
purposes the zone numbers are 9 and 10.
Note: The maximum wire length for either zone 9 or zone 10 is 3000 feet using 18 AWG or 1000 feet using 22
AWG. The maximum voltage is 13.8VDC and the maximum normal standby current is 1.25mA DC. The maximum
line impedance is 100 Ohms. The maximum short circuit current is 56mA. Do not mix detectors from dierent
manufacturers on the same zone.
Caution: Performing a Sensor Reset momentarily drops power to the devices on Zones 9 and 10. The panel
views these zones (9 and 10) as “Open” while the power is absent.
Note: Refer to the Compliance Listing Guide (LT-1330 )for list of compatible DMP 2-wire smoke detectors.
Dry Contact Relay Outputs
12.1 Description
The XR150/XR550 Series panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model
305 relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header. Each
relay provides one SPDT set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition: Steady, Pulsing, Momentary, and Follow
2) Activation by 24-hour 7-day schedule: One on and one o time a day for each relay
3) Manual activation from the DMP LCD keypad menu
4) Communication failure 12) Ready
5) Armed area annunciation 13) Armed
6) Fire Alarm, Fire Trouble or Supervisory 14) Disarmed
7) Ambush Alarm 15) Burglary
8) Exit and Entry timers 16) Phone Trouble
9) System Ready 17) Device Fail
10) Late to Close 18) Sensor Reset
11) Panic Alarm 19) Closing Wait
Refer to the XR150/XR550 Canadian Series Programming Guide (LT-1232CAN) for specic information.
12.2 Contact Rating
The Model 305 relay contacts are rated for 1 Amp at 30VDC (allows .35 power factor). You can connect auxiliary
power to the Relay Output 1 common terminal by installing the gray harness wire to terminal 7. Current draw for all
connected devices must not exceed the panel maximum current rating.
12.3 Model 431 Output Harness Wiring
The relay contacts are accessible by installing the DMP 431 Output Harness on the 6-pin header labeled J2. Output
2 uses the top three prongs, and Output 1 uses the bottom three prongs. The wire harness and contact locations are
shown below:
ContactColor
Output 1 normally closedViolet
Output 1 commonGray
Output 1 normally openOrange
Output 2 normally closedViolet with white stripe
Output 2 commonWhite with gray stripe
Output 2 normally openOrange with white stripe
The relay contacts must be connected to devices located within the same room as the XR150/XR550 Series panel.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
16
Page 21
INSTALLATION
Annunciator Outputs
13.1 Description
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or
conditions occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground a
voltage from another source. The outputs can respond to any of the conditions listed in the Description section for
Dry Contact Relays. Maximum voltage is 30VDC at 50mA.
13.2 Model 300 Harness Wiring
Access the open collector outputs by installing DMP 300 Harness on the 4-pin header labeled J11. The output
locations are shown below. For listed applications, devices connected to the outputs must be located within the
same room as the panel.
Output ColorWireOutputColorWire
3Red15Green3
4Yellow26Black4
13.3 Model 860 Relay Module
Connect a Model 860 Relay Module to the J11 header on the XR150/XR550 Series panel to provide relays for outputs
3-6.
Use these relays for electrical isolation between the alarm panel and other systems or for switching voltage to
control various functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary
power terminal 7. The module includes one relay and provides three additional sockets for expansion of up to four
relays. Mount the 860 inside the panel enclosure using the 3-hole pattern and plastic standos. Refer to the 860
Module Install Sheet (LT-0484) as needed.
Relay Contact Rating: 1 Amp at 30VDC (allows .35 power factor)
Wireless Bus Expansion
14.1 Description
The J13 Wireless Bus (XBUS) header provides connection for the 1100X Series or 1100XH Series Wireless Receiver. The
XBUS provides up to 500 wireless zones numbered 500-999. Refer to the 1100X Series Wireless Receiver Install Guide
(LT-1822) or the 1100XH Series Wireless Receiver Install Guide (LT-1823) for complete information.
• XR550 provides up to 500 zones
• XR150 provides up to 100 zones
14.2 Wireless Bus LEDs
The two LEDs, located above the XBus header, indicate data transmission and receipt. The left LED ashes green to
indicate the panel is transmitting data. The right LED ashes yellow to indicate the panel is receiving data.
LX-Bus Expansion
15.1 LX-Bus Headers
There are ve LX-Bus headers near the bottom of the XR150/XR550
panels:
• LX500 (J14), provides zones 500-599 (all panels).
• LX600 (J9), provides zones 600-699 (XR550 only).
PROG
• LX700 (J15 ), provides zones 700-799 (XR550 only).
• LX800 (J17 ), provides zones 800-899 (XR550 only).
• LX900 (J19 ), provides zones 900-999 (XR550 only).
10
BLK11SMK12GND13Z114GND15Z216Z317GND18Z419Z520GND
15.2 LX-Bus LEDs
The two LEDs, located above each LX-Bus header, indicate data transmission and receipt. The left LED ashes green
to indicate the
panel is transmitting LX-Bus data. The right LED ashes yellow to indicate the panel is receiving LX-Bus data.
RCV
J8
RED BLK
XMIT
PROG
RED
LX500
XMIT
500
J14
BLK
RCV
RED
LX600
RCV
XMIT
XMIT
RCV
600
700
J9
RED
BLK
LX700
BLK
RED
LX800
BLK
J17
Figure 9: LX-Bus Headers and LEDs
RED
LX900
Z6
XMIT RCV
BLK
22Z721
XMIT RCV
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
17
Page 22
INSTALLATION
15.3 OVC LEDs
The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw more
current than the panel is rated for. The LED(s) turn a steady Red when lit. When the OVC LED(s) light red, the
appropriate LX-Bus(es) and Keypad bus are shut down.
• The OVC LED located to the left of the 893A connector indicates overcurrent for the Keypad Bus (Terminals 7-10
and PROG header), XBUS, and LX500-LX700.
• The OVC LED to the right of the J24 Cell Module connector indicates overcurrent for LX800-LX900.
J1 Ethernet Connector (Panels with Network/Encryption only)
16.1 Description
The Ethernet Connector is available on the XR150/XR550 with network or encryption to connect directly to an
Ethernet network using a standard patch cable. The Ethernet Connector supports 100MB/s full duplex operation and
the maximum impedance is 100 Ohms.
Link LED
16.2 Ethernet LEDs
The two LEDs, located on the top edge of the J1 Ethernet Connector, indicate
network connection. The right, Link LED lights up green to indicate a valid receive
connection from the host network. The yellow LED lights when connected to a
100Mb network and is o when connected to a 10Mb network.
Figure 10: J1 Ethernet and LEDs
16.3 Network Transient Suppression
The Model 270 Network Transient Suppression Module to provide transient surge protection for the J1 Ethernet
Connector. Refer to the Model 270 Installation Sheet (LT-1316) for complete information.
Activity LED
J1
ETHERNET
J3 Telephone RJ Connector
17.1 Description
Connect the panel to the public telephone network by installing a DMP 356 RJ Cable between the panel J3 connector
and the RJ31X or RJ38X phone block. The maximum impedance is 100 Ohms. CAUTION - To reduce the risk of re,
use only No. 26 AWG or larger telecommunication line cord, such as DMP Model 356 Series Phone Cords.
17.2 J10 893A or 277 Trouble Sounder Connector
Connect an 893A Dual Phone Line Module or Model 277CAN Trouble Sounder to J10 on the XR150/XR550 Series. Refer
to the 893A Installation Sheet (LT-0135) or 277CAN Installation Sheet (LT-1304CAN) for complete information.
17.3 Notication
The user must not repair registered terminal equipment. In case of trouble, immediately unplug the device from the
telephone jack. The factory warranty provides for repairs. Registered terminal equipment may not be used on party
lines or in connection with coin telephones. No tify the telephone company with the following information:
• The particular line(s) where the service is connected
• This Class A digital apparatus complies with Canadian ICES-003.
• The ringer equivalence number (REN) of 0.0
• The device make, model, and serial number
17.4 Phone Line Monitor
The XR150/XR550 Series panel has a built-in telephone monitor that monitors the phone line voltage to verify the
connection to the central oce. Figure 11 and the table below identify the phone block pin layout, wire numbers,
The wires on the RJ31 that feed pins 4 and 5 should be the ONLY wires on the D-marc. All other house phone wiring
should be tied to pins 1 and 8 coming back from the RJ31.
Dial tone must come into RJ31X on pins 4 and 5 and go back to house phones from pins 1 and 8. Follow these steps
to determine if panel is seizing the line:
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
18
To Telephone
Line
To Premise
Phone
Ring
5
8
Ring 1
6
7
Tip 1
Tip
4
3
2
1
Figure 11: Phone Jack Wiring
RJ31X or RJ38X
Phone Block
Page 23
INSTALLATION
1. Unplug phone cord from RJ31X
2. Place butt-set on pins 4 and 5
3. Listen for dial tone. With dial tone present, lift either wire from pins 1 or 8
4. Listen for dial tone again. If the dial tone is present, RJ31X wiring is correct. If no dial tone is present, the
RJ31X wiring is backwards. Rewire so dial tone is coming IN on 4 and 5.
If you still have trouble with the phone line, you may need to replace the RJ cord. If the dial tone is still not
present, swap out the RJ31X phone block.
Reset and Tamper Headers
18.1 J16 Reset Header
The reset header is located just above the terminal strip on the right side of
the circuit board and is used to reset the XR150/XR550 Series microprocessor.
To reset the panel when rst installing the system, install the reset jumper
before applying power to the panel. After connecting the AC and battery,
remove the reset jumper.
LX
LX900
RESET
LOAD
J6
CELL MODULE
To reset the panel while the system is operational, for example, prior to
reprogramming, install the reset jumper without powering down the system.
Remove the reset jumper after one or two seconds.
After resetting the panel, begin programming within 30 minutes. If you wait
longer than 30 minutes, you must reset the panel again.
18.2 J4 Tamper Header
The TAMPER header is for use with the optional DMP 306 Tamper Harness. The
harness connects to one or more tamper switches mounted inside the panel
enclosure to supervise against unauthorized enclosure opening or removal.
Refer to the wiring diagram on the enclosure door for correct tamper switch
wiring.
Momentarily place the Reset
jumper over both of the J16
pins to reset the panel.
J23
L
LX800
How the Tamper Works
If the enclosure is opened or removed while one or more of the system areas
are armed, a panel tamper alarm is indicated. If all areas are disarmed, a
panel tamper trouble is indicated.
Figure 12: XR550 Series
Canadian Panel Showing the
Reset Jumper
Cellular Modules
19.1 J24 Header
The J24 header is located to the right of the J7 Expansion Module on the right side of the circuit board and is used
to connect the DMP Model 263LTE-A Cellular Communicator. This provides a fully supervised alarm communication
path for the XR150/XR550 Canadian panel. Refer to the 263LTE Series (LT-1592) Installation Sheet for complete
information.
19.2 Module Installation
1. Insert the PCB stando end with anges into the stando hole in the panel PCB.
2. Align the PCB stando with the stando hole in the module PCB.
3. Press the module PCB card 12 pin connector onto the Cell Module (J24) connector on the panel while applying
even pressure to both sides of the board to fully seat the module. See Figure 13.
Note: If needed, the PCB can be removed from the enclosure to allow placement of the cell module.
19.3 Connecting the Antenna
1. Attach a 381 cable to the SMA connector on the cell module.
2. Position one of the supplied washers onto the other end of the 381 SMA connector and push the threaded end
through an enclosure knockout.
3. Position the second washer onto the threaded end extending through the knockout and secure the nut.
4. Attach the included 383 Antenna to the SMA connector. See Figure 13. Note: As an alternative, an antenna coax
can be connected directly to the cell module SMA connector when the coax enters the enclosure via conduit.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
19
Page 24
COMPLIANCE
Wiring Diagrams
20.1 LX-Bus™ Module Connection
LX-Bus Expansion
13
2
5
1
3
AC
AC
B+
7
4
6
BELL
RED
B-
GND
11
9
10
8
SMK
GRN
BLK
YEL
15
14
12
Z1
Z2
GND
GND
S
S
S
S
19
17
16
Z3
GND18Z4
20
22
GND21Z6
23
Z7
GND
Z5
Each LX-Bus Module must have
its own independent address
ranging from 00 to 99. A
Supervisory zone must be
programmed into the panel to
24
26
26
Z8
Z9-
Z9+
Z10+
properly supervise each
28
27
Z10-
module.
= Supervised Circuit
S
S
S
S
S
S
S
S
S
Open Collector
Annunciator Outputs
LX-Bus™ Wiring
Optional LED wiring
50mA at 50 VDC resistive
Red
Yellow
Green
To additional
Black
LX-Bus Modules
Form C
Relay 2
Relay 1
Relay 3
Relay 4
Contacts Typical
Normally Closed
Common
Normally Open
Model 716 Output
Expander Module
13m at 12 VDC
Optional LED wiring
50mA at 50 VDC resistive
Model 717 Graphic
Annunciator
Module
10m at 12 VDC
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide