The XR150/XR550 Series provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation
of two Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A Model 431 Output
Harness is required to use these outputs.
The panels also provide four open collector outputs rated for 50mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model 300 Output Harness is required to use these outputs.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
1
INTRODUCTION
1.7 Enclosure Specications
The panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s guide, and
programming sheets.
Enclosure
Model
35017.5”W x 13.5”H x 3.5”DGray (G) or Red (R)18-Gauge
350A17.5”W x 13.5”H x 3.75”DGray (G)18-Gauge with 16-Gauge door
34113.22”W x 7.0”H x 3.5”DGray (G)20-Gauge
34912.5”W x 11.5”H x 3.5”D Gray (G)20-Gauge
352X14.5”W x 32.0”H x 4.0”DGray (G)16-Gauge
SizeColor(s)Construction (Cold Rolled
Steel)
Panel Features
2.1 Description
The DMP XR150/XR550 Series Canadian panel is a versatile 12VDC, combined access control, burglary, and re
communicator panel with battery backup. The panels provide eight on-board burglary zones and two on-board 12VDC
Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or
other latching devices. You can use up to sixteen supervised 32-character LCD keypads; network communications and
expansion interface cards; zone and output expansion modules; and initiating and indicating circuit modules. You can
also connect auxiliary devices to the panel’s output relays to expand the basic system control capability. Combined
current requirements of additional modules may require an auxiliary power supply. Refer to the XR150/XR550
Series Power Requirements section in this guide when calculating power requirements. The XR150/XR550 Series can
communicate to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID communication.
2.2 Zone Expansion
Each panel provides multiple options for zone expansion.
• 10 on-board zones
• Up to 64 programmable keypad zones
• Up to 500 LX-Bus zones
Using DMP LCD keypad remote zone capability and zone expansion modules, additional zones are available on each
panel:
• XR550 provides up to 574 additional zones
• XR150 provides up to 142 additional zones
The panel keypad data bus supports up to 16 supervised device addresses with each address supporting up to four
programmable expansion zones (64 total).
Using the on board LX-Bus™ (LX500-LX900) connections, and any combination of single, four, eight, or sixteen-zone
expansion modules and single-zone LX-Bus™ detectors, additional zones are available on each panel:
• XR550 provides up to 500 additional zones (LX500-LX900)
• XR150 provides up to 100 additional zones (LX500)
Note: Do not use shielded or twisted pair wiring for LX-Bus or Keypad Bus circuits.
2.3 Output Expansion
In addition to the two SPDT relays and four programmable open collector outputs on the XR150/XR550 Series, you
can also connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules can
provide an additional 500, 300, or 100 programmable SPDT relays.
The panels provide Output Schedules for programming the 716 to perform a variety of annunciation and control
functions. Also assign the 716 outputs to any panel Output Options such as Fire Alarm, Communication Fail, or Phone
Trouble Outputs. Refer to the 716 Installation Guide (LT-0183).
The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground
outputs that follow the state of their assigned zones.
Note: The 717 supports the rst eight Keypad Bus addresses. To follow Keypad Bus addresses nine through 16, install
multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).
2.4 Central Station Communication
You can program the panel for reporting to DMP SCS-1R Receivers using digital dialer, cellular, network, or Contact ID
communication. You can program the panel for reporting to DMP SCS-VR Virtual Receivers using cellular or network
communication. The panel connects at the premises to a standard RJ31X or RJ38X telephone jack. Use the DMP 893A
Dual Phone Line Module when connecting the XR150/XR550 Series panel to two separate phone lines.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
2
INTRODUCTION
2.5 Encrypted Communications (XR550 with Encryption only)
An XR550 panel with encryption communicates using 128-bit or 256-bit AES encryption. If you currently have an
XR550 panel installed, you may contact DMP Customer Service with the panel serial number. The serial number(s)
should be sent in writing via e-mail or fax. A separate feature key is sent for each panel to activate encrypted
communications using the Feature Upgrade process. Encrypted communication cannot be enabled on a standard
XR550 panel. For more information on the Feature Upgrade process see the XR150/XR550 Series Canadian
Programming Guide (LT-1232CAN).
Note: 256-bit encrypted messages to SCS-1R receiver only communicate when using SCS-104 Receiver Line Cards
with Version 102 or higher software.
2.6 Caution Notes
Throughout this guide you will see caution notes containing information you need to know when installing the panel.
These cautions are indicated with a yield sign. Whenever you see a caution note, make sure you completely read
and understand its information. Failing to follow the caution note can cause damage to the equipment or improper
operation of one or more components in the system. See the example shown below.
Always ground the panel before applying power to any devices: The panel must be properly grounded
before connecting any devices or applying power to the panel. Proper grounding protects against
Electrostatic Discharge (ESD) that can damage system components.
2.7 Compliance Instructions
For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratory certicated system, please see the Compliance Listing Guide (LT-1330) for instructions.
XR150/XR550 Series Canadian Installation Guide Digital Monitoring Products
3
INTRODUCTION
The plug-in
transformer shall plug
into a 120 VAC 60 Hz
outlet not controlled
by a switch.
tamper protection
System Components
3.1 Wiring Diagram
The XR550 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.3.
AC Wiring must be in conduit and exit out
the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Bell
12 VDC
Minimum cuto time 15
min.
1.5 Amp Max using
FTA7516
J12
75VA
50VA
¼"
s
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
Bell cuto time
range is 5 to 99
minutes, non-coded.
s
s
s
s
DISARM
1k Ohm
Phone Line
XR550 Series
Canadian Panel
OVC
s
s
s
s
1k
Ohm
Bell
Keyswitch Arming
can be connected
to any zone.
ARM
1k Ohm
J3
3
4
5
6
Outputs 3-6
s
22 gauge minimum
22 gauge minimum
s
RED
YELLOW
Smoke
Detector
s
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
J11
Output 1Output 2
K6K7
J4
Tamper
J14
J8
LX500
s
1k
Ohm
22 gauge minimum
22 gauge minimum
s
s
ss
BLACK
GREEN
RED
RED
YELLOW
GREEN
BLACK
Zone Expander
s
s
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
1k Ohm 1k Ohm
s
Listed Resistors
J2
Zone 1
Zone 2
s
s
s
1k
Ohm
Total current combined from
terminals 7, 11, 25, 27, XBUS
Model 714
s
s
J13
XBUS
Out1 Out2
J15J19J17
J9
LX800
LX700
s
Ohm
1k
Zone 4
s
s s
Ohm
1k
Zone 5
Ohm
s
s
Ohm
1k
Zone 3
s
Auxiliary/Smoke Power
and LX500-LX900
1.5 Amp Max
13.8 VDC to 10.2 VDC
Zone
Expander
Model 711
7mA @ 12
ss
s
s
s
1k Ohm
1k Ohm
WARNING: Incorrect
connections may cause
damage to the unit.
Form C Relays (J2)
Output Color Code–Model 431
Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6 Black
J16
Reset
J24
10
3.3k Ohm
Resistor
DMP Model
309
1k
Zone 6
s
LX900
sss
s
1k
Ohm
Zone 7
Zone 8
1k
Ohm
DMP Model
3.3k Ohm
Resistor
Zone 9Zone
ss ss
309
s
= Supervised Circuit
Zone Expander
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Zone
Expander (up
to 8 zones)
Model 712-8
VDC
19mA @ 12
VDC
s
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN
TO PROVIDE SUPERVISION OF
CONNECTIONS.
s
1k Ohm
ss s
3.3k Ohm
3.3k Ohm
s
Front and Rear
included with
Model 350A
Attack Resistant
Enclosure.
Front
Tamper
Rear
Tamper
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715
compatibility
identifier: A
Maximum operating
range: 13.8 VDC to
9.7 VDC.
Class B (Style A).
Model 715
sss ss
3.3k Ohm
3.3k Ohm
Figure 1: XR550 Canadian Wiring Diagram
3.2 Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR150/XR550 Series
input and output circuits. Additional surge protection is available by installing the DMP 370, 370RJ Lightning
Suppressors or Model 270 Network Transient Suppression Module.
Digital Monitoring Products XR150/XR550 Series Canadian Installation Guide
4
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.