DMP 1184 Installation Guide

1184 WIRELESS CARBON MONOXIDE DETECTOR
Installation Guide
PROGRAM THE TRANSMITTER IN THE PANEL
1
Figure 1: 1184
DESCRIPTION
The 1184 is a 3 V battery powered
wireless carbon monoxide (CO)
detector that provides early
warning when the electrochemical
levels in the air.
The detector has an electrochemical
CO sensor assembly coupled with
an 1100 Series wireless transmitter
and an audible sounder. The
transmitter can send alarm, trouble,
tamper, and low battery condition
messages to the alarm panel.
The detector works well for dicult
wiring locations, for critically
aesthetic applications, or for areas
where hazardous materials exist.
1. In ZONE INFORMATION, enter the wireless ZONE NO: - and press CMD.
2. Enter the ZONE NAME and press CMD.
3. Select CO for ZONE TYPE and press CMD.
4. At NEXT ZN?, select NO.
5. Select YES when WIRELESS? displays.
6. Enter the eight-digit SERIAL#:- and press CMD.
7. Enter the SUPRVSN TIME and press CMD.
Detector Annunciation Notifications
The 1184 provides the following transmitter messages, LED display, and audible annunciations:
TEST/HUSH BUTTON
1
GREEN LED
2
3
4
5
Figure 2: Carbon Monoxide Detector Callouts
1
2
Normal
RED LED
3
Alarm
4
CO ENTRY POINTS
5AUDIBLE SOUNDER
Compatibility
All DMP 1100 Series Receivers and Panels.
What is Included?
1184 Carbon Monoxide Detector with DMP wireless transmitter installed
3V lithium Model CR123-FIRE battery
Hardware pack
MESSAGE
Alarm ALARM
Low
battery
Detector
Head
Removed
Tamper
Detector
End of Life
KEYPAD DISPLAY
LO BAT
TROUBLE
TAMPER
(XR150/XR550)
(XTL/XT30/XT50)
TROUBLE
RED LED
Blinks
once
every
second
Blinks
once
every 45
seconds
Blinks
once
every 5
seconds
OPEN
Table 1: Detector Notifications
O On O
Blinks
once every 10 seconds
GREEN
LED
O Temporal 4
O
O
O
SOUNDER
Chirps after
7 days
One chirp
every
45 seconds
One chirp
every
45 seconds
2
SELECT A LOCATION
Install the transmitter away from large metal objects which impair wireless performance. For the LED Survey Operation complete the following steps before proceeding:
1. Use a separate 1100 Series Transmitter for the LED Survey Operation such as an 1106 since the 1184 transmitter PCB is not visible.
2. Find the survey button on the 1106 transmitter PCB and the survey LED near the survey button location. The transmitter PCB Red Survey LED turns on whenever data is sent to the receiver then immediately turns o when the receiver acknowledgement is received.
3. Press and release the tamper switch to send data to the receiver to confirm operation.
Confirmed: If communication is confirmed, for each press or release of the tamper switch, the LED blinks immediately on and immediately o.
Faulty: If communication is faulty, the LED remains on for about 8 seconds or flashes multiple times in quick succession. Relocate the [generic product] or receiver until the LED confirms clear communication.
4. Test the communication between the control panel and the detector using the panel walk test feature. See Test the Detector Alarm.
General Location Guidelines
In addition to NFPA 720, use the following location guidelines to optimize performance from the CO detector:
Install ceiling-mounted detectors at least 12 inches from any wall
Install wall-mounted detectors at least as high as the light switch and 6 inches below the ceiling.
Mount the detector on a firm permanent surface
Locate the detector in environmentally controlled areas where the temperature does not exceed 104° F (40° C) or drop below 32° F (0° C).
When mounting to suspended ceiling tile, the tile must be secured with the appropriate fastener to prevent tile removal
Install in the vicinity of flame-fueled appliances, but no closer than 10 feet.
Keep detectors away from vents and the reach of children and pets.
3
MOUNT THE DETECTOR
When setting up a wireless system, it is recommended to program zones and connect the wireless receiver before installing batteries in the transmitters.
1. Use the two screws provided to mount the base in the location previously surveyed for proper communication.
2. Use the alignment notch on the lip of the mounting base as a guide to align the detector with the alignment tabs.
3. Insert the detector into the mounting base and turn clockwise approximately 15 degrees to snap into place.
To remove the detector from the mounting base, grasp the detector and turn it counterclockwise approximately 15 degrees. The detector snaps o of the mounting base. See Figure 3.
C
B
Figure 3: Exploded View of CO Detector
A
Mount the base using the screws
A
Align notch and tab
B
A
B
Turn clockwise
C
2 1184 INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS
Loading...
+ 2 hidden pages