DMP 1168 Installation Manual

1168 Wireless Smoke/CO/
Low Temp Detector
INSTALLATION AND PROGRAMMING GUIDE
TABLE OF CONTENTS
About the 1168 ............................................ 1
Indicator LEDs ....................................................... 1
Power Supply ......................................................... 1
Voice Annunciation .............................................. 1
Tamper Magnet ..................................................... 1
Cadence Synchronization ............................... 2
Low Temp Sensor ................................................ 2
1168 Features ...............................................3
Program the Detector ................................4
Fire/Smoke Zone ................................................. 4
Program Start Display .......................................4
Zone Information ................................................. 4
Zone Number ........................................................ 4
Zone Name.............................................................4
Zone Type ............................................................... 4
Fire Bell Out ........................................................... 5
Next Zone ............................................................... 5
Wireless ................................................................... 5
Serial Number ....................................................... 5
Contact Type ......................................................... 5
Supervision Time ................................................. 5
Next Zone ............................................................... 5
Carbon Monoxide Zone ....................................6
Zone Number ........................................................ 6
Zone Name............................................................. 6
Zone Type ............................................................... 6
Fire Bell Out ........................................................... 6
Next Zone ............................................................... 6
Wireless ................................................................... 7
Serial Number ....................................................... 7
Contact Type ......................................................... 7
Supervision Time ................................................. 7
Next Zone ............................................................... 7
Low Temperature Zone ..................................... 8
Zone Number ........................................................ 8
Zone Name............................................................. 8
Zone Type ............................................................... 8
Fire Bell Out ........................................................... 8
Next Zone ............................................................... 8
Wireless ................................................................... 8
Serial Number ....................................................... 9
Contact Type .........................................................9
Supervision Time ................................................. 9
Next Zone ............................................................... 9
Bell Options ........................................................... 9
Fire Bell Action ..................................................... 9
Select a Location ...................................... 10
Install the Detector ...................................11
Mounting Guidelines ................................ 13
Locations to Avoid ............................................. 15
Test the 1168 .............................................. 17
Smoke Test ............................................................ 17
CO Test ................................................................... 17
Additional Information ........................... 20
Reset the Language Selection .....................20
Supervision Message........................................20
Inspection Testing and Maintenance .......... 21
Replace The Batteries .......................................21
NFPA 72 Guidelines ..........................................22
Compliance Specifications......................27
Patents ................................................................... 27
Certifications .............................................28
Compatibility .....................................................28
Certifications .......................................................28

ABOUT THE 1168

The 1168 Wireless Smoke/CO/Low Temp Detector features multi-criteria smoke sensing using a combination of photoelectric, heat, IR flame flicker, and carbon monoxide indicators. When multiple triggers are not present the smoke detector will also report after being exposed to alarm levels of smoke for 5 minutes. The 1168 reports fire, CO, and low temp alarms to the control panel. Use the onboard wireless transmitter to connect the 1168 with DMP1100Series Wireless Receivers.

Indicator LEDs

The 1168 has a multi-color top LED that indicates the state of the device:
GREEN—Supervisory indication; blinks during power on, reset, and during normal operation
AMBER—Signal maintenance and trouble events
RED—Alarm (Smoke/CO)
Indicator lights on the side alarms (initiating detector only):
RED—Smoke
BLUE—CO
Digital Monitoring Products, Inc. | 1168 Installation and Programming Guide 1

Power Supply

The 1168 is powered by four 3.0V lithium batteries. Battery life expectancy for the unit is at least three years under normal conditions.

Voice Annunciation

The 1168 audibly announces alarm and maintenance requirements, enhancing occupant understanding and evacuation. See LED Indication and Sounder table.

Tamper Magnet

The 1168 features a tamper magnet which sends a trouble message to the panel if the detector is removed from the mounting base.

Cadence Synchronization

The 1168 provides cadence synchronization with other 1168 or 1164 units on the system.

Low Temp Sensor

The 1168 includes a low temperature sensor that sends a message to the panel when inside temperature falls below 41°F (5°C).
2 1168 Installation and Programming Guide | Digital Monitoring Products, Inc.

1168 FEATURES

CO Test Button
Indicator
Lights
CO Entry
Port
Figure 1: Product Features
Digital Monitoring Products, Inc. | 1168 Installation and Programming Guide 3
Smoke Test Button
Indicator
LED
IR Flame Detector
Indicator
Lights

PROGRAM THE DETECTOR

When programming an 1168 Wireless Smoke/CO/Low Temp Detector, refer to the appropriate panel programming guide as needed.
PROGRAMMER

ZONE INFORMATION

ZONE NO:
The 1168 takes up to three zone numbers (Smoke, CO, Temp). The zone numbers must be consecutive.

Program Start Display

Enter 6653 (PROG) at the keypad to enter the PROGRAMMER menu.
Zone Information
Press CMD until ZONE INFORMATION displays. Press a select key or area to enter the menu.

Zone Number

Enter the zone number. Press CMD.

Fire/Smoke Zone

* UNUSED *

ZONE TYPE

FI PN EM SV
4 1168 Installation and Programming Guide | Digital Monitoring Products, Inc.

Zone Name

Denote the zone name as a fire zone. Press CMD.
Zone Type
Press any select area. Press CMD to move to the next set of menu options. Select FI (fire) as the ZONE TYPE.
FIRE BELL OUT: 0
NEXT ZONE? NO YES
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: FIRE
SUPVSN TIME: 240
NEXT ZN? YES
Digital Monitoring Products, Inc. | 1168 Installation and Programming Guide 5

Fire Bell Out

Default is 0. Press CMD

Next Zone

At the NEXT ZONE? prompt, select NO.

Wireless

At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.

Serial Number

Enter the eight-digit serial number found on the device and press CMD.

Contact Type

Enter the CONTACT type as FIRE and press CMD.

Supervision Time

Enter the SUPVSN TIME, and press CMD.

Next Zone

At the NEXT ZONE? prompt, select YES.

Carbon Monoxide Zone

ZONE NO:
* UNUSED *
ZONE TYPE CO IN
FIRE BELL OUT: 0
NEXT ZONE? NO YES
6 1168 Installation and Programming Guide | Digital Monitoring Products, Inc.

Zone Number

Enter the zone number. This number must be consecutive with the previous zone. For example, if 500 was entered for Fire,501 should be entered here. Press CMD.

Zone Name

Denote the zone name as a carbon monoxide (CO) zone. Press CMD.

Zone Type

Press any select area. Press CMD to move to the next set of menu options. Select CO (carbon monoxide) as the ZONE
TYPE.

Fire Bell Out

Default is 0. Press CMD

Next Zone

At the NEXT ZONE? prompt, select NO.
WIRELESS? YES
TRANSMITTER SERIAL #: -
CONTACT: CO
SUPVSN TIME: 240
NEXT ZN? YES
Digital Monitoring Products, Inc. | 1168 Installation and Programming Guide 7

Wireless

At the WIRELESS? prompt, select YES.
Note: If you are programming the 1168 onto a zone that
can be either hardwired or wireless, then this prompt appears. If the zone you are programming is wireless-only, then the prompt does not appear.

Serial Number

Enter the eight-digit serial number found on the device and press CMD.

Contact Type

Enter the CONTACT type as CO and press CMD.

Supervision Time

Enter the SUPVSN TIME, and press CMD.

Next Zone

At the NEXT ZONE? prompt, select YES.