dixell XR420C Installing And Operating Instructions

dIXEL
Installing and Operating Instructions
1598026100
1598026100 XR420C GB r1.0 22.02.2007.doc XR420C 1/4
XR420C
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell
S.p.A.” (see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough
from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR420C, 32x74 mm format, is a microcontroller based device, able to control 2 temperatures in an independent way. Both sections are suitable for applications on normal or medium temperature refrigerating units or cooking applications. It is provided with 3 relay outputs to control two compressors and one light. Defrost process is performed through simple stop of compressors. It is also provided with 2 NTC or PTC probe inputs, one for section 1 and the other one for section 2. There is one digital input (free voltage contact) completely configurable by parameter. The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS-RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
3. REGULATION
Two kinds of actions are available for both sections: cooling action and heating action. The type is selected through cH1/cH2 section parameter.
3.1 HOW TO SET THE TYPE OF ACTION
By means of CH1/2 parameters the kind of action can be set for each section: cH1/cH2 = CL: refrigerating action (1/2); cH1/cH2 = Ht: heating action (1/2)
3.2 CH1/CH2 = CL FOR COOLING ACTION
For each section, the regulation is performed according to the temperature measured by its own thermostat probe with a positive differential from the set point. If the temperature increases and reaches set point1 (2) plus differential1 (2) the compressor is started and then turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “COn1(2)” and “COF1(2)”.
3.3 CH1/CH2 = HT FOR HEATING ACTION
For each section, the regulation is performed according to the temperature measured by its own thermostat probe with a negative differential from the set point. If temperature decreases and reaches set point 1/2 minus differential 1/2 the output is activated and then turned off when the temperature reaches the set point value again and then turned off when the temperature reaches the set point value again.
NOTE: For turn-off defrost you can set MdF1/MdF2 = 0.
4. DEFROST
4.1 SECTION 1 (2)
Defrost is performed through a simple stop of the compressor for both sections. Different kinds of defrosts are available for each section.
4.2 RELATION BETWEEN DEFROSTS
The relation between defrosts is set by the dFS parameter: relation between defrosts. 4 relation between the 2 sections of the controller are available, to manage different kinds for applications:
- in = independent defrosts;
- StS = same defrost start, synchronised defrost end;
- St = same defrost start, independent defrost end;
- SE = sequential defrost;
4.2.1 dFS= in - independent defrosts
The defrosts of the 2 sections of controller are completely independent.
First section: defrost interval is set by idF1 parameter. Second section: defrost interval is set by idF2 parameter. The defrost interval is control by means of parameter “EdF1(2)”:
- in the defrost is made every “IdF1(2)” time
- Sd the interval “IdF1(2)” is calculate through Smart Defrost algorithm (only when the
compressor is ON)
Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2).
By pushing the Down key or Up key for 3s, a defrost request is generated for section 1 or 2 respectively. The defrost interval is re-loaded.
4.2.2 dFS = StS – Same defrost start, end defrost synchronised or dFS = St
- Same defrost start, end defrost independent.
The defrost of the 2 sections of controller starts at the same time. idF1 parameter sets the defrost interval for both the sections. The defrosts are performed at regular interval if EdF1 = in or according to the Smartdefrost algorithm if EdF1 = Sd.
With dFS = StS regulation restarts only when defrost is finished for both the sections. The section that finishes the defrost before the other starts dripping time until also the other section has not finished its defrost.
Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2).
By pushing the Down key or Up key for 3s, a defrost request is generated for both the sections 1 and 2.The defrost interval is re-loaded. With dFS = St each section restarts regulation as soon as its defrost is finished.
4.2.3 dFS = SE – sequential defrost
The defrost of 2 sections is synchronised. idF1 parameter sets the defrost interval for both the sections. Defrosts are performed at regular interval if EdF1 = in or according to the Smartdefrost algorithm if EdF1 = Sd. Section 1 does its defrost first, at the end of the defrost of section 1, section 2 starts its defrost..
Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2).
By pushing the Down key or Up key for 3s, a defrost request is generated for both the sections 1 and 2.The defrost interval is re-loaded.
5. THE DISPLAY
X----C
XR400
The display is divided in 2 parts:
Upper left part: to see the temperature2 (upper display) Lower left part: to see the temperature1(lower display)
SET To display and modify target set point 1 and set point 2, in programming mode it
selects a parameter or confirm an operation. light activation/deactivation.
o/
(UP/DEFROST 2) in programming mode it browses the parameter codes or increases the displayed value. By holding it pressed for 3s the defrost for section 2 is started
.
n/
(DOWN/DEFROST 1) in programming mode it browses the parameter codes or decreases the displayed value. By holding it pressed for 3s the defrost for section 1 is started.
o + n
To lock and unlock the keyboard.
SET +
n To enter the programming mode.
SET +
o To exit the programming mode.
5.1 MEANING OF THE ICONS
Icon FUNCTION Meaning
ON Celsius degree ON Fahrenheit degree ON Compressor 1 on
FLASHING Anti-short cycle delay enabled for compressor 1
ON Compressor 2 on
FLASHING Anti-short cycle delay enabled for compressor 2
ON Defrost 1 in progress
ON Defrost 2 in progress
ON ALARM signal
Temperature2
Temperatature1
dIXEL
Installing and Operating Instructions
1598026100
1598026100 XR420C GB r1.0 22.02.2007.doc XR420C 2/4
5.2 HOW TO SEE AND MODIFY THE SET-POINT
1. Push and release the SET key:
2. the bottom display shows the St1 label
3. the upper display shows the Set point value flashing
4. To change the Set value push the o or n;
5. To memorise the new set point value push the SET key again,
6. To change the SET2 repeat this procedure.
5.3 HOW TO START MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2
To start a defrost for the section 1: push the DOWN key( ) for 3s. To start a defrost for the section 2: push the UP key(
) for 3s.
5.4 HOW TO ENTER THE “PR1” PARAMETER LIST
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the Set1 and DOWN key for 3s
2. The controller will show the first parameter present in the Pr1 menu:
- Bottom menu: label
- Upper menu: value
To exit: Press SET + UP or wait 15s without pressing a key.
5.5 HOW TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” – “PAS” parameter and press the “SET” key.
3. The flashing value “0 - - ” is displayed. use o or n to input the security code and confirm the figure by pressing “SET” key.
The security code is “321”.
4. If the security code is correct the access to “Pr2” is enabled by pressing “SET1” on the last digit.
NOTE: Each parameter present in “Pr2” MENU can be removed or put into “Pr1”, user level, by pressing “SET1 + n. In “Pr2” when a parameter is present in “Pr1” the decimal point LE of the bottom display is on.
5.6 HOW TO CHANGE A PARAMETER
To change a parameter value operates as follows:
1. Enter the Programming mode
2. Select the required parameter.
3. Press the “SET” key and the value starts blinking.
4. Use “UP” or “DOWN” to change its value.
5. Press “SET” to store the new value and move to the following parameter.
TO EXIT: Press SET + o or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
5.7 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set points.
3. If a key is pressed more than 3s the “POF” message will be displayed.
5.8 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and n keys, till the “Pon” message will be displayed.
5.9 ON/OFF FUNCTION – HOW TO SWITCH ON AND OFF THE CONTROLLER
If the function is enabled (par. onF=yES), by pressing the SET key for more than 5s the controller is switched OFF. The stand-by function switches OFF all the relays and stops the regulation. During the stand by if a monitored unit is connected, it does not record the instrument data and alarms
To switch the instrument on again press the SET1 key for 5s.
NOTE1: When the instrument is under Stand-by, all the relays are under power supply. Don’t connect any loads to the normal closed contact of the relays. NOTE2: With the instrument in stand-by, it’s possible to see and modify the set points and enter the programming mode.
6. PARAMETER LIST
DIFFERENTIALS
Hy1 Differential1: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point1, always positive.
Compressor1 Cut IN is Set Point Plus Differential1 (Hy1). Compressor1 Cut OUT is when the temperature reaches the set point1.
Hy2 Differential2: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point2, always positive.
Compressor2 Cut IN is Set Point2 Plus Differential2 (Hy2). Compressor2 Cut OUT is when the temperature reaches the set point2.
REGULATION – SECTION 1
LS1 Minimum set point1 limit: (-50,0°C÷SET1; -58°F÷SET1) Sets the minimum acceptable
value for the set point1.
US1 Maximum set point1 limit: (SET1
÷110°C; SET1÷230°F) Set the maximum acceptable
value for set point1.
OdS1 Outputs activation delay of section 1 at start up: (0÷255 min) This function is enabled at
the initial start up of the instrument and inhibits any output activation of the section 1 for the period of time set in the parameter. (Light can work)
AC1 Anti-short cycle delay for compressor1: (0÷30 min) interval between the compressor1
stop and the following restart.
Con1 Compressor1 ON time with faulty probe1: (0÷255 min) time during which the
compressor1 is active in case of faulty thermostat probe. With COn=0 compressor1 is always OFF.
COF1 Compressor1 OFF time with faulty probe1: (0÷255 min) time during which the
compressor is off in case of faulty thermostat probe. With COF=0 compressor is always active.
CH1 Kind of action for section 1: CL = cooling; Ht = heating
REGULATION – SECTION 2
LS2 Minimum set point2 limit: (-50,0°C÷SET2; -58°F÷SET2) Sets the minimum acceptable
value for the set point2.
US2 Maximum set point2 limit: (SET2
÷110°C; SET2÷230°F) Set the maximum acceptable
value for set point2.
OdS2 Outputs activation delay of section 2 at start up: (0÷255 min) This function is enabled at
the initial start up of the instrument and inhibits any output activation of the section 1 for the period of time set in the parameter.
Ac2 Anti-short cycle delay for compressor2: (0÷30 min) interval between the compressor2
stop and the following restart.
con2 Compressor2 ON time with faulty probe2: (0÷255 min) time during which the
compressor2 is active in case of faulty thermostat probe. With COn=0 compressor2 is always OFF.
coF2 Compressor2 OFF time with faulty probe2: (0÷255 min) time during which the
compressor is off in case of faulty thermostat probe. With COF=0 compressor2 is always active.
cH2 Kind of action for section 2: CL = cooling; Ht = heating
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement
unit is changed the SET point and the values of some parameters have to be modified.
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. dE = 0,1°C; in = 1
°C
Lod1 Bottom display visualization: select which probe is displayed by the instrument in the
bottom display: P1 = Thermostat1 probe; P2 = Evaporator probe; P2 = Thermostat2 probe
Lod2 Upper display visualization: select which probe is displayed by the instrument in the
upper display: P1 = Thermostat1 probe; P2 = Evaporator probe; P2 = Thermostat2 probe
DEFROST
dFS relation between defrosts.4 relation between the 2 sections of the controller are available,
to manage different kinds for applications: in = independent defrosts;
StS = same defrost start, synchronised defrost end; St = same defrost start, independent
defrost end; SE = sequential defrost;
EdF1 Defrost mode, section 1: in = interval mode. The defrost starts when the time “If” is
expired.
IdF1 Interval between defrosts, section 1: (1÷120h) Determines the time interval between the
beginning of two defrost cycles.
MdF1 Maximum duration of defrost, section 1: (0÷255 min) When P2P = no, no evaporator
probe, it sets the defrost duration, when P2P = yES, defrost end based on temperature, it sets the maximum length for defrost.
EdF2 Defrost mode, section 2: in = interval mode. The defrost starts when the time “IdF" is
expired.
IdF2 Interval between defrosts, section 2: (1÷120h) Determines the time interval between the
beginning of two defrost cycles.
MdF2 (Maximum) duration of defrost, section 2: (0÷255 min) it sets the defrost duration. dFd Display during defrost: rt = real temperature; it = temperature reading at the defrost
start; Set = set point; dEF = “dEF” label; dEG = “dEG” label;
dAd Defrost display time out: (0
÷255 min) Sets the maximum time between the end of defrost
and the restarting of the real room temperature display.
ALARMS ALc1 Temperature alarms configuration, section 1: it determines if alarms are relative to set
point 1 or referred to absolute values: rE relative to set point; Ab absolute temperature
ALu1 Maximum alarm, section 1: with ALc1=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the
probe values exceeds the “SET1+ALU” value.
with ALc1=Ab: absolute alarm, (Set1÷Full Sc.) Maximum alarm is enabled when the probe
values exceeds the “ALU” value. ALL1 Minimum alarm, section 1: with ALc1=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point1.
The alarm signal is enabled when the probe values goes below the “SET1-ALL” value. with ALc1=Ab absolute value, minimum alarm is enabled when the probe values goes
below the “ALL1” value. ALd1 Temperature alarm delay, section 1: (0÷255 min) time interval between the detection of
an alarm condition and the corresponding alarm signalling. dAo1 Delay of temperature alarm at start-up, section 1: (0min÷23h 50min) time interval
between the detection of the temperature alarm condition in section after the instrument
power on and the alarm signalling. ALc2 Temperature alarms configuration, section 2: it determines if alarms are relative to set
point 2 or referred to absolute values: rE relative to set point; Ab absolute temperature
ALu2 Maximum alarm, section 2: with ALc2=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the
probe values exceeds the “SET2+ALU” value. with ALc2=Ab: absolute alarm, (Set2÷Full Sc.) Maximum alarm is enabled when the probe
values exceeds the “ALU” value. ALL2 Minimum alarm, section 2: with ALc2=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point2.
The alarm signal is enabled when the probe values goes below the “SET2-ALL” value. with ALc2=Ab absolute value, minimum alarm is enabled when the probe values goes
below the “ALL2” value. ALd2 Temperature alarm delay, section 2: (0÷255 min) time interval between the detection of
an alarm condition and the corresponding alarm signalling. dAo2 Delay of temperature alarm at start-up, section 2: (0min÷23h 50min) time interval
between the detection of the temperature alarm condition in section after the instrument
power on and the alarm signalling. AFH Temperature alarm / defrost differential: (0,1÷25,5°C; 1÷45°F) Intervention differential
for temperature alarm set point and defrost set point.
Loading...
+ 2 hidden pages