dixell XR30C Installing And Operating Insructions

Page 1

Alarm duration
Safe food zone
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
Digital controller with off cycle defrost
XR30C
CONTENTS
1. GENERAL WARNING___________________________________________ 1
2. GENERAL DESCRIPTION _______________________________________ 1
4. FRONT PANEL COMMANDS_____________________________________ 1
5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP)___ 1
6. MAIN FUNCTIONS _____________________________________________ 1
8. DIGITAL INPUT________________________________________________ 2
9. INSTALLATION AND MOUNTING _________________________________ 3
10. ELECTRICAL CONNECTIONS ___________________________________ 3
11. HOW TO USE THE HOT KEY ____________________________________ 3
12. ALARM SIGNALS ______________________________________________ 3
13. TECHNICAL DATA _____________________________________________ 3
14. CONNECTIONS _______________________________________________ 4
15. DEFAULT SETTING VALUES ____________________________________ 4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must
In case of failure or faulty operation send the instrument back to the distributor
Consider the maximum current which can be applied to each relay (see
Ensure that the wires for probes, loads and the power supply are separated
In case of applications in industrial environments, the use of mains filters (our
2. GENERAL DESCRIPTION
Model designed for refrigeration applications at normal temperature. It provides two relay outputs, one for the compressor, the other one can be used for alarm signalling or as auxiliary output. The probe input can be selected between PTC or NTC. The instrument has a digital input, for alarm signalling, for switching the auxiliary output or for start a defrost cycle.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “
3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter “ controls the interval between defrost cycles, while its length is controlled by parameter “
SAFETY PRECAUTIONS
limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation
not be opened. or to “Dixell s.r.l.” (see address) with a detailed description of the fault. Technical Data). and far enough from each other, without crossing or intertwining. mod. FT1) in parallel with inductive loads could be useful.
, format 32 x 74 mm, is a digital termostat with off cycle defrost
XR30C
MdF
” and “
COn
”.
COF
”.
IdF

4. FRONT PANEL COMMANDS
: To display target set point; in programming mode it selects a parameter or
SET
confirm an operation.
To start a manual defrost
(DEF)
'
(UP): To see the last temperature alarm happened; in programming mode it
'
browses the parameter codes or increases the displayed value.
&
(DOWN) To see the last temperature alarm happened; hold pressed it switches
&
the auxiliary output; in programming mode it browses the parameter codes or decreases the displayed value.
KEY COMBINATIONS:
'
+
&
'
SET + SET +
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE FUNCTION
$8;
5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP)
XR30C signals and records temperature alarms, together with their duration and max value reached. See drawing:
Ex. High temperature alarm
5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min) reached temperature and alarm duration do as follows:
1. Push the Up or Down key.
2. On the display the following message is shown::
3. Then the instrument displays the temperature once again.
NOTE1: NOTE2:
5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL OCCURRING
1. Hold the SET key pressed for more than 3s, while the recorded alarm is
2. To confirm the operation, the “rSt” message starts blinking and the normal
6. MAIN FUNCTIONS
To lock & unlock the keyboard.
&
&
To enter in programming mode.
& '
To return to the room temperature display.
'
ON Compressor enabled Flashing
-Programming Phase (flashing with
- Anti-short cycle delay enabled
ON Defrost enabled Flashing
- Programming Phase (flashing with
ON Second relay ON ON An temperature alarm happened
Tem pe ratu re
Max
Temperature
ALu
High temp. alarm
Set
ALL
Low temp. alarm
” for high temperature alarm (“
HAL
the
Maximum (minimum) temperature.
Then the “ h.mm.
if an alarm is still occurring the “
the alarm is recorded when the temperature come back to normal values
displayed. (the rSt message will be displayed) temperature will be displayed.
tiM
” (
tiM
;
LAL
e) message is displayed, followed by the
” shows the partial duration.
tim
)
)
;
;
Time
” fot the minimum allarm), foll owed by
“Duration”
in
6.1 HOW TO SEE THE SET POINT
1. Push and immedi ately release the show the Set point value;
2. Push and im mediately release the probe value again.
SET
key: the display will
SET
key or wait for 5 seconds to display the
Page 2

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
6.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the
3. To change the Set value push the
4. To memorise the new set point value push the SET key again or wait 10s.
'
or
&
'
&
arrows within 10s.
LED starts blinking;
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost will start.
6.4 HOW TO SWITCH ON OR OFF THE SECOND RELAY (OAC= LHt)
Hold pressed the turned ON or OFF
&
key for some seconds, till the
&
6.5 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
1. Enter the Programming mode by pressing the Set and DOWN key for 3s (
2. Select the required parameter.
3. Press the “SET” key to display its value (now only the LED is blinking).
4. Use “UP” or “DOWN” to change its value.
and
start blinking).
6.6 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.6.1 HOW TO ENTER THE HIDDEN MENU
3. Select the required parameter.
4. Press the “SET” key to display its value (Now only the
5. Use
''or
6. Press “SET” to store the new value and move to the following parameter. To exit: Press SET + NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.6.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user level) by pressing “SET + In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
1. Enter the Programming mode by pressing the Set +
for 3s (LED 1 and
2. When a param eter is displayed keep pressed the Set+
for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
&& to change its value.
''or wait 15s without pressing a key.
start blinking).
&
”.
&
LED is blinking).
6.7 HOW TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 s the
2.
The “POF” message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored
3.
If a key is pressed more than 3s the “POF” message will be displayed.
''and
&& keys.
6.8 TO UNLOCK THE KEY BOARD
Keep pressed together for more than 3s the will be displayed.
''and
&& keys, till the “Pon” message
6.9 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding the “
''” key pressed for about 3 seconds.
The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle can be terminated before the end of the set time using the same activation key “
''” for 3 seconds.
7. PARAMETERS
NOTE: the parameters preceded by dots are in the Hidden Menu. REGULATION Hy Differential
Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum acceptable value for the set point.
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum
acceptable value for set point.
: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.
$8;
LED is
&
key
&
&
&

Ot Thermostat probe calibration: (-12.0÷12.0°C;
-120÷120°F) allows to adjust possible offset of the thermostat probe.
OdS Outputs activation delay at start up: (0÷255min) This function is
enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor
stop and the following restart.
CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min)
Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products.
COn Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is OFF in case of faulty thermostat probe. With COF=0
compressor is always active.
CH Type of action: CL = cooling; Ht = heating. DISPLAY
CF Temperature measurement unit:
°C=Celsius; °F=Fahrenheit. WARNING: When the measurement unit is
changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. DEFROST IdF Interval between defrost cycles: (0÷120h) Determines the time interval
between the beginning of two defrost cycles.
MdF (Maximum) length for defrost: (0÷255min) W hen P2P = n, (not evaporator
probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost.
dFd Temperature displayed during defrost: (rt = real temperature; it =
temperature at defrost start; SEt = set point; dEF = “dEF” label)
dAd MAX display delay after defr ost: (0÷255min). Sets the maximum time between the end of defrost and the restarting of the real room temperature display.
ALARMS
ALC Temperature alarms configuration: (Ab; rE) Ab= absolute temperature: alarm temperature is given by the ALL or ALU
values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperature alarm
temperature is reached the alarm is enabled, after the “ALd” delay time.
ALL Minimum temperature alarm: (-50.0 ÷ SET°C;
-58÷230°F when this temperature is reached the alarm is enabled, after the “ALd” delay time.
ALd Temperature alarm delay: (0÷255 min) time interval between the
detection of an alarm condition and alarm signalling.
dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling.
SECOND RELAY AND DIGITAL INPUT
tbA Alarm relay silencing (with oAC=ALr): (n= silencing disabled: alarm relay stays on till alarm condition lasts, y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm).
OA1 Second relay configuration: ALr: alarm; LHt: auxiliary; onF: always on; dEF:
do not select it!.; FAn: do not select it!.;
AoPAlarm relay polarity: it set if the alarm relay is open or closed when an alarm
happens. CL= the relay is closed; oP = the relay is open
i1P Digital input polarity: oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
i1F Digital input configuration:
EAL = external alarm: “EA ” message is displayed; bAL = serious alarm “CA”
message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt =switch on the second relay if oA1=LHt; Htr = kind of action inversion (cooling – heating).
did:(0÷255 min)
with i1F= EAL or i1F = bAL digital input alarm delay:
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay with i1F = PAL: time for pressure switch function: time interval to calculate
the number of the pressure switch activation.
nPS Pressure switch number: (0
switch, during the “did” interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
odc Compressor status when open door: no, Fan = normal; CPr, F_C =
Compressor OFF
OTHER PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC
= PBC probe, ntC = NTC probe.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
8. DIGITAL INPUT
The free contact digital input is programmable in five different configurations by the “i1F” parameter.
: (SET÷110°C; SET÷230°F) when this
delay between the
÷
15) Number of activation of the pressure
Page 3

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter:
no, Fan = normal (any change); CPr, F_C = Compressor OFF;
Since the door is opened, after the delay time set through parameter “ did”, the door alarm is enabled, the display shows the message “dA” and the regulation restarts. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The compressor and the regulation are stopped. W hen the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
8.5 SWITCHING SECOND RELAY ON (i1F = LHt)
With oA1= LHt it switches on and off the second relay.
8.6 START DEFROST (i 1F = dFr)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time is expired.
8.7 INVERSION OF THE KI ND OF ACTION: HEATING­COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.8 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” parameter. i1P=CL: the input is activated by closing the contact. i1P=OP: the input is activated by opening the contact
9. INSTALLATION AND MOUNTING
Instrument XR30C shal l be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-C) as shown in figure.
The temperature range allowed for correct operation is 0÷60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
10. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 mm complies with the instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
2
. Before connecting cables make sure the power supply

formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
11. HOW TO USE THE HOT KEY
11.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. W hen the controller is ON, insert the “ message appears followed a by flashing
3. Push
4. Turn OFF the instrument remove the
: the “
NOTE
again
'
'
the operation.
key and the
SET”
” message is displayed for failed programming. In this case push
Err
key if you want to restart the upload again or remove the “
will stop flashing.
End
“Hot Key”,
11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a
3. Automatically the parameter list of the
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the
NOTE
unit off and then on if you want to restart the download again or remove the “
” to abort the operation.
key
programmed “Hot Key” into the 5 PIN receptacle
the Controller ON. Controller memory, the “
“End”.
“Hot Key”.
the message “
” is displayed for failed programming. In this case turn the
Err
” message is blinking followed a by flashing
doL
.
12. ALARM SIGNALS
Message Cause Outputs
“P1” Room probe failure Compressor output according “HA” Maximum temperature alarm Outputs unchanged.
“LA” Minimum temperature alarm Outputs unchanged. “dA” Door open Regulation restarts “EA” External alarm Output unchanged. “CA” Serious external alarm (i1F=bAL) All outputs OFF. “CA” Pressure switch alarm (i1F=PAL) All outputs OFF
12.1 ALARM RECOVERY
Probe alarm “P1” starts some seconds after the fault in the related probe; it automatically stops some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values and when defrost starts. Alarms disabled. Alarm “
and
“EA”
(with i1F=PAL) recovers only by
CA”
(with i1F=bAL) recover as soon as the digital input is
“CA”
13. TECHNICAL DATA
Housing: Case: XR30C Mounting: XR30C Protection: Frontal protection: Connections: Power supply:
±10%, 50/60Hz, 110Vac ±10%, 50/60Hz
Power absorption: Display Inputs Digital input Relay outputs
Data storing Kind of action: Operating temperature: Storage temperature: Relative humidity: Measuring and regulation range:
Resolution: Accuracy (ambient temp. 25°C)
self extinguishing ABS.
frontal 32x74 mm; depth 60mm;
panel mounting in a 71x29mm panel cut-out
IP20.
IP65 with frontal gasket RG-C (optional).
Screw terminal block 2,5 mm
according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
: 3 digits, red LED, 14,2 mm high.
: 1 NTC or PTC probe.
compressor:
second relay:
3VA max
: free contact
SPST relay 8(3) A, 250Vac or
SPST relay 20(8)A; 250Vac
SPDT relay 8(3) A, 250Vac or
: on the non-volatile memory (EEPROM).
1B;
Pollution grade:
0÷60 °C.
-30÷85 °C.
20÷85% (no condensing)
NTC probe: PTC probe:
0,1 °C or 1°C or 1 °F (selectable).
-40÷110°C (-40÷230°F)
-50÷150°C (-58÷302°F)
normal;
: ±0,7 °C ±1 digit
” and push
Hot key
“End”
then turn it ON again.
“Hot Key”
switching off and on
2
wiring.
Software class:
is downloaded into the
to par. “Con” and “COF”
A.
'
key; the
'
” to abort
Hot key
and then turn
the instrument.
"uPL"
Hot
10.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent dam ages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost
termination probe among the evaporator fins in the coldest place, where most ice is
Page 4

Hot Key
8(3)A250V
8(3)A250V
Line
N.C.
Line
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
14. CONNECTIONS
14.1 XR30C: 8A COMPRESSOR

Aux/
N.C.
Alarm
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
Comp
14.2 XR30C: 20A COMPRESSOR
8(3)A250V 20(8)A250V

Aux/
Alarm
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
Comp
Room

Room

Hot Key

15. DEFAULT SETTING VALUES
Label Name Range °C/°F
Set Set point LS÷US 3.0/37
Hy Differential LS Minimum set point
US Maximum set point
Ot Thermostat probe calibration
OdS Outputs delay at start up 0÷255 min 0
AC Anti-short cycle delay
CCt Continuos cycle duration 0.0÷24.0h
COn Compressor ON time with faulty
probe
COF Compressor OFF time with faulty
probe
CH Kind of action CL=cooling; Ht= heating CL
CF Temperature measurement unit
rES Resolution
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dFd Displaying during defrost
dAd MAX display delay after defrost 0 ÷ 255 min 30
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm ALL Minimum temperature alarm ALd Temperature alarm delay dAO Delay of temperature alarm at
start up
tbA Alarm relay silen c ing n=no; y=yes Y oA1 2nd relay configuration ALr= alarm; dEF=no select it;
AoP Second relay polarity (oA1=ALr) oP; cL cL
i1P Digital input polarity oP=opening;CL=closing cL i1F Digital input configuration
did Digital input alarm delay 0÷255min 5
Nps Number of activation of pressure
switch
odc Compressor status with open
door:
PbC Kind of probe
rEL Software release -- 4.0 Ptb Map code -- -
0,1÷25.5°C/ 1÷ 255°F
-50°C÷SET/-58°F÷SET
SET÷110°C/ SET ÷ 230°F
-12÷12°C /-120÷120°F
0 ÷ 50 min
0 ÷ 255 min 0 ÷ 255 min
°C ÷ °F
in=integer; dE= dec.point
1÷ 120 ore
0÷ 255 min
rt, it, SEt, DEF
rE= related to set;
Ab = absolute
Set÷110.0°C; Set÷230°F
-50.0°C÷Set/ -58°F÷Set
0 ÷ 255 min
0 ÷ 23h e 50’
LHt=auxiliary; onF=always on;
Fan= no select it
EAL=extern. alarm; bAL=lock regulation; PAL=press. switch; dor=door switch; dEF=defrost;
LHt=switch on 2
no, Fan = normal;
CPr; F_C = Compr. OFF;
nd
cooling - heating
relay; Htr=
0 ÷15
Ptc; ntc
2.0/4
-50,0/-58 110/230
0.0
1
0.0
15 30
°C/°F
dE/-
8
20
it
Ab
110/230
-50/-58 15
1.3
LHt
LHt
15 no
ntc/Ptc
Hidden parameters
Weiss Instruments, Inc.
905 Waverly Avenue
Dixell s.r.l. Z.I. Via dell’Industria, 27 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
(PDLO GL[HOO#GL[HOOFRP KWWSZZZGL[HOOFRP
Phone: 631 207 1200 - Fax: 631 207 0900
Holtsville, New York 11742
www.weissinstruments.com
Loading...