1592008200 XR110C GB XR110C with built in RS485 2/4
1. Press SET key until “rST” label starts blinking.
4.5 HOW TO SEE THE SET POINT
1. Push and immediately release the SET key: the display will show the Set
point value;
2. Push and immediately release the SET key or wait for 5 seconds to
display the probe value again.
4.6 HOW TO CHANGE THE SETPOINT
1. Push the SET key for 3 seconds to change the Set point value;
2. The value of the set point will be displayed; led
and LED 1 start
blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
4.7 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as
follows:
1. Enter the Programming mode by pressing the Set and UP key for few
seconds (LED 1 and led
start blinking).
2. The instrument will show the first parameter present in “Pr1”
4.8 TO ENTER IN PARAMETERS LIST “PR2”
To enter in the parameter list “Pr2” (installer level) operate as follows:
To access parameters in “Pr2” a security code is required.
1. To enter in “Pr1” level.
2. Select “Pr2” parameter and press the “SET” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing
zero.
4. Use o or n to input the security code in the flashing digit; confirm the figure by
pressing “SET”. The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the
last digit.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing
“SET” + n. When a parameter is present in “Pr1” LED
is on.
4.9 HOW TO CHANGE THE PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode.
2. Select the required parameter with n or o.
3. Press the “SET” key to display its value (
and LED 1 starts blinking).
4. Use o or n to change its value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the
time-out.
4.10 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored.
4.10.1 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and n keys.
4.11 STAND BY FUNCTION
If the stand-by function is enabled (Onf = 1), by holding pressed the SET key for 5s., the
instrument shows “OFF”. The stand-by function switches OFF all the relays and stops the
regulation. During the stand by if a XJ500 is connected, it does not record the instrument
data and alarms.
N.B. When the instrument is under Stand-by, all the relays are under power supply.
Don’t connect any loads to the normal closed contact of the relays.
5. LIST OF PARAMETERS
REGULATION
Hy Differential: (0,2°C ÷ 30,0°C/ 1°F÷54°F): Intervention differential for set point,
always positive. Compressor Cut IN is Set Point Plus Differential (Hy). Compressor
Cut OUT is when the temperature reaches the set point.
LS Minimum set point limit: (- 50.0°C÷SET/ -58°F÷SET) Sets the minimum acceptable
value for the set point.
US Maximum set point limit: (SET÷ 150°C / SET ÷302°F) Set the maximum
acceptable value for set point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the
initial start up of the instrument and inhibits any output activation for the period of time
set in the parameter. (AUX and Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the
following restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous
cycle. Can be used, for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the
compressor is active in case of faulty thermostat probe. With COn=0 compressor is
always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the
compressor is off in case of faulty thermostat probe. With COF=0 compressor is
always active.
CH Type of regulation: cL = cooling; Ht = heating.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the
measurement unit is changed the SET point and the values of the regulation
parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
de = 0,1°C
in = 1 °C
ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
ALC= rE, 0
÷ 50°C or 90°F
ALC= Ab, ALL
÷ 110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is
enabled.
ALL Low temperature alarm setting:
ALC = rE , 0
÷ 50 °C or 90°F
ALC = Ab , - 50°C or -58°F
÷ ALU
when this temperature is reached and after the ALd delay time, the LA alarm is
enabled,.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention
differential for temperature alarm set point and fan regulation set point, always
positive.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an
alarm condition and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between
the detection of the temperature alarm condition after the instrument power on and
the alarm signalling.
dot Delay of temperature alarm after closing the door : (0
÷255 min) Time delay to
signal the temperature alarm condition after closing the door.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door
condition and its alarm signalling: the flashing message “dA” is displayed.
nPS Pressure switch number: (0
÷15) Number of activation of the pressure switch,
during the “did” interval, before signalling the alarm event (I2F= PAL).
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible
offset of the thermostat probe.
HES Temperature increase during the Energy Saving cycle : (-30,0°C
÷ 30,0°C / -
22÷86°F) sets the increasing value of the set point during the Energy Saving cycle.
DIGITAL INPUTS
odc Compressor and fan status when open door: