dixell XR02CX Operating Manual

dIXEL
Operating Manual
DIGITAL CONTROLLE R
XR02CX
1. Contents __________________________________________________________________________ 1
2. General warnings ___________________________________________________________________ 1
3. General description__________________________________________________________________ 1
4. Regulation_________________________________________________________________________ 1
5. Defrost ___________________________________________________________________________ 1
6. Front panel commands_______________________________________________________________1
7. Parameters________________________________________________________________________1
8. Installation and mounting _____________________________________________________________2
9. Electrical connections________________________________________________________________ 2
10. How to use the hot key_______________________________________________________________2
11. Alarm signalling_____________________________________________________________________ 2
12. Technical data______________________________________________________________________ 2
13. Connections ____________________________________ ________________________ ___________ 2
14. Default setting values ________________________________________________________________ 2
2. GENERAL WARNINGS
PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting t he instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all elect rical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see
address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Techni c al Dat a).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertw ining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
3. GENERAL DESCRIPTION
Model XR02CX, format 32 x 74 x 50 mm, is a digital thermostat with off cycle defrost designed for refrigeration applications at normal temperature. It provides a relay output to drive the compressor. It is also provided with 2 NTC probe input. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard or the by HOTKEY.
4. REGULATION
THE REGULATION OUTPUT
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “Cy” and “Cn”.
5. DEFROST
Defrost is performed through a simple stop of the compressor. Parameter “id” controls the interval between defrost cycles, while its length is controlled by parameter “Md”.
6. FRONT PANEL COMMANDS
To display target set point, in programming mode it selects a parameter or confirm an operation
To start a manual defrost In programming mode it browses
the parameter codes or increases the displayed value In programming mode it browses the parameter codes or
AUX
decreases the displayed value
KEYS COMBINATION
+
+ +
LED MODO SIGNIFICATO
On Compressore enabled
Flashing Anti short cycle delay enabled (AC parameter)
To lock or unlock the keyboard To enter in programming mode To return to room temperature display
On Defrost in progress
Flashing Dripping in progress
On Measurement unit
Flashing Programming mode
On Measurement unit
Flashing Programming mode
HOW TO SEE THE SET POINT
1. Push and immediately release the SET key, the set point will be showed;
2. Push and immediately release the SET key or wait about 5s to return to normal visualisation.
HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
HOW TO START A MANUAL DEFROST (ONLY XR02CX) Push the DEF
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the SET+ blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use
4. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET+ NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
key for more than 2 seconds and a manual defrost will start
or to change its value.
or wait 15s without pressing a key.
keys for 3s (“°C” or “°F” LED starts
HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the SET+ blinking).
2. Released the keys, then push again the SET+ displayed immediately followed from the Hy parameter. NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the “SET” key to display its value
or to change its value.
5. Use
6. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET+ NOTE1: if none parameter is present in L1, after 3s the “nP” message is displayed. Keep the keys
pushed till the L2 message is displayed. NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire.
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user level) by pressing SET+ point is on.
TO LOCK THE KEYBOARD
1. Keep pressed for more than 3s the and keys.
2. The “OF” message will be displayed and the keyboard will be locked. If a key is pressed more
than 3s the “OF” message will be displayed.
TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the and keys till the “on” message will be displayed.
or wait 15s without pressing a key.
. In HIDDEN MENU when a parameter is present in First Level the decimal
keys for 3s (“°C” or “°F” LED starts
keys for more than 7s. The L2 label will be
7. PARAMETERS
REGULATION Hy Differential: (0,1°C ÷ 25°C) Intervention differential for set point. Compressor Cut IN is SET
POINT + differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum SET POINT: (-55°C÷SET/-58°F÷SET): Sets the minimum value for the set point.. US Maximum SET POINT: (SET÷99°C/ SET÷99°F). Set the maximum value for set point. ot First probe calibration: (-9.9÷9.9°C) allows to adjust possible offset of the first probe. P2 Evaporator probe presence: n= not present; y= the defrost stops by temperature. oE Second probe calibration: (-9.9÷9.9°C) allows to adjust possible offset of the second probe od Outputs activation delay at start up: (0÷99min) This function is enabled at the initial start up of
the instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the
following restart.
Cy Compressor ON time with faulty probe: (0÷99 min) time during which the compressor is active
in case of faulty thermostat probe. With Cy=0 compressor is always OFF.
Cn Compressor OFF time with faulty probe: (0÷99 min) time during which the compressor is OFF
in case of faulty thermostat probe. With Cn=0 compressor is always active.
DISPLAY CF Measurement unit: (°C÷°F) °C =Celsius; °F =Fahrenheit. WARNING: When the measurement
unit is changed the SET point and the values of the parameters Hy, LS, US, oE, o1, AU, AL have to be checked and modified if necessary).
rE Resolution (only for °C):(dE ÷ in) dE= decimal between -9.9 and 9.9°C; in= integer;
Ld Default display: (P1 ÷ P2) P1= thermostat probe; P2= evaporator probe. SP=Set point
dy Display delay: (0÷15 min.) when the temperature increases, the display is updated of 1 °C/1°F
after this time.
DEFROST dE Defrost termination temperature: (-50÷50°C) if ot=Y it sets the temperature measured by the
evaporator probe, which causes the end of defrost.
1598024510
XR02CX US.doc XR02CX 1/2
dIXEL
p
id Interval between defrost cycles: (0÷99 ore) Determines the time interval between the
beginning of two defrost cycles.
Md Maximum length for defrost: (0÷99 min. with 0 no defrost) when ot=n, (not evaporator probe:
timed defrost) it sets the defrost duration, when ot = y (defrost end based on temperature) it sets the maximum length for defrost.
dF Display during defrost: (rt / it / St / dF) rt= real temperature; it= start defrost temperature; St=
SET-POINT; dF= label dF.
ALARMS
AU Maximum temperature alarm: (AL÷99°C) when this temperature is reached the alarm is
enabled, after the “Ad” delay time.
AL Minimum temperature alarm: (-55÷AU°C) when this temperature is reached the alarm is
enabled, after the “Ad” delay time.
Ad Temperature alarm delay: (0÷99 min) time interval between the detection of an alarm conditi on
and alarm signalling.
dA Exclusion of temperature alarm at startup: (0÷99 min) time interval between the detection of
the temperature alarm condition after instrument power on and alarm signalling.
OTHER
d2 Evaporator probe display (read only) Pt Parameter code table rL Software release
Operating Manual
8. INSTALLATION AND MOUNTING
Instrument XR02CX shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 0÷60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
9. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5
2
. Before connecting cables make sure the power supply complies with the instrument’s
mm requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
9.1 PROBES
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
10. HOW TO USE THE HOT KEY
10.1 HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push followed a by flashing “En”
3. Push “SET” key and the “En” will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.
10.2 HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “do” message is blinking followed a by flashing “En”.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.
key; the "uP" message appears
11. ALARM SIGNALLING
Mess. Cause Outputs
"P1" Room probe failure Compressor output according to “Cy” e “Cn” "P2" Evaporator probe failure Defrost end is timed "HA" Maximum temperature alarm Outputs unchanged "LA" Minimum temperature alarm Outputs unchanged “EA” External alarm Outputs unchanged “CA” Serious external alarm All outputs OFF. “dA” Door Open Compressor and fans restarts
11.1 ALARM RECOVERY
Probe alarms P1” and “P2” start some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to normal values. Alarms “EA” and “CA” (with iF=bL) recover as soon as the digital input is disabled.
12. TECHNICAL DATA
Housing: self extinguishing ABS. Case: frontal 32x74 mm; depth 60mm; Mounting: panel mounting in a 71x29mm panel cut-out Protection: IP20; Frontal prote ction: IP65
1598024510
2
Connections: disconnectable terminal block 2,5 mm Power supply: according to the model ±10%; 230Vac ±10%, 50/60Hz, 110Vac ±10%, 50/60Hz Power absorption: 3.5 VA max Display: 2 digits, red LED, 14,2 mm high; Inputs: 2 NTC. Relay outputs: compressor SPST 8(3) A, 250Vac; 20(8)A 250Vac Data storing: on the non-volatile memory (EEPROM). Kind of action: 1B; Pollution grade: 2; Software class: A.; Rated impulsive voltage: 2500V; Overvoltage Category: II Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C. Relative humidity: 20÷85% (no condensing) Measuring and regulation range: NTC -40÷110°C (-40÷230°F); Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
13. CONNECTIONS
NOTE: Fast-on maximum current 16A
wiring and 6.3mm fast-on
14. DEFAULT SETTING VALUES
LBL
REGULATION
Hy Differential 0.1 ÷ 25°C/1 ÷ 45°F 36 °F L1 LS Minimum Set Point -55°C÷SET/-67°F÷SET -40 °F L2 US Maximum Set Point SET÷99°C/ SET÷210°F 99°F L2
ot First probe calibration -9.9÷9.9°C/-18÷18°F 0.0 L2 P2 Second probe presence n – Y y L2 oE Second probe calibration -9.9÷9.9°C/-18÷18°F 0.0 L2 od Outputs activation delay at start up 0 ÷ 99 min 0 L2 AC Anti-short cycle delay 0 ÷ 50 min 0 L1 Cy Compressor ON time faulty probe 0 ÷ 99 min 15 L2 Cn Compressor OFF time faulty probe 0 ÷ 9 9 min 30 L2
DISPLAY
CF Measurement units °C - °F °F L2 rE Resolution (only for °C) dE – in in L1 Ld Default Display P1 - P2 - SP P1 L2 dy Display delay 0 ÷ 15 min 0 L2
DEFROST
dE Defrost termination temperature -50÷50°C/-58÷122°F 46 °F L1
id Interval between defrost cycles 0 ÷ 99 hours 6 L1 Md Maximum length for defrost 0 ÷ 99 min. 20 L1 dF Display during defrost rt – in – dE it L2
ALARMS
AU Maximum temperature alarm ALL÷99°C / ALL÷210°F 99 °F L2 AL Minimum temperature alarm -55°C÷ALU/-67°F÷ALU -50 °F L2 Ad Temperature alarm delay 0 ÷ 99 min 15 L2
Exclusion of temperature alarm at
dA
startup
OTHER
d2 Evaporator probe display Read Only - - - L1
Pt Parameter code table Read Only - - - L2
rL Firmware release Read Only - - - L2
DESCRIPTION RANGE DEFAULT LEVEL
0 ÷ 99 min 99 L2
dIXEL S.p.a.
Z.I. Via dell’Industria, 27 - 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
htt
://www.dixell.com E-mail: dixell@dixell.com
XR02CX US.doc XR02CX 2/2