dixell XH460L Operating Instructions Manual

Dixell
Operating instructions
1592002910
1592002910 XH460L GB R1.0 18.05.04 XH460L 1/5
XH460L
TEMPERATURE AND HUMI DITY CONTROLLER
FOR FREEZING – PROVING CABINETS
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot
be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel
with inductive loads could be useful.
2. GENERAL DESCRIPTION
The XH460L, 38x185 format, is a microprocessor controller, designed for freezing and proving cabinets­units. It controls both humidity and temperature. It has 6 output relays to control compressor, heating elements, defrost, fan de-humidifier and humidifier. It has 2 NTC inputs one for thermostat the other one for defrost. It’s also present a 4÷20mA input for humidity. There is one digital input (free contact) configurable by parameter. An output allows the user to programme the parameter list with the “Hot Key”.
3. TEMPERATURE REGULATION
The temperature regulation is performed through neutral zone using compressor and heater output relays.
Set point
OFF
ON
Heating output: CUT IN is “SET_T-dbt”, CUT OUT is when the temperature reaches the set point.
Compressor output CUT IN is “ SET_T +dbt”, CUT OUT is when the temperature reaches the set point.
3.1 DEFROST
Two defrost modes are available through the “tdF” parameter: defrost with electrical heater or hot gas. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made every “IdF
time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON). To disable the defrost set the MdF parameter to zero
Humidity regulation during a defrost depends on the Hud parameter. With Hud=no humidity regulation is disabled. Con Hud=yES humidity regulation is performed also during a defrost.
4. HUMIDITY REGULATION
The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions.
Humidity control can be disabled setting the SET_RH to “nu” value. In this case only the temperature
control is perform.
4.1 HUMIDIFYING ACTION
The humidifying action is done enabling the humidifier relay when the humidity is lower than the “SET_RH-dbH” value. The relay is switch off when humidity reaches the set values.
4.2 DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY (OA1 DIFFERENT FROM DEH) ­STANDARD
In this case the dehumidifying action is performed by setting the following parameters in this way:
tHu = c-H kind of dehumidifying by means of heating and compressor relays oA1 different from dEH:
The heating and compressor outputs are activated together when humidity is higher than SET_RH+dbH value. Outputs are disabled when humidity comes back to the SET_RH value.
4.2.1 Relation between cooling, heating and dehumidifying
1. If is simultaneously present a request of cooling (temp>SET_T+dbt) and dehumidifying (RH >
SET_RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET_T is reached at this point al so the heating relay is enabled.
2. If is simultaneously present a request of heating (temp< SET_T-dbt) and dehumidifying (RH >
SET_RH+dbH): the dehumidifying action has the priority over the heating action: both the compressor and the heating relays are energised till the humidity set is reached at this point only the heating relay is enabled.
4.3 DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY (OA1 = DEH) The configurable relay is used, (XH460L terminals 3-4) setting the parameter oA1 =dEH.
NOTE: the LIGHT button is not more available;
Two kinds of de-humidifying are available:
4.3.1 Dehumidifying action with ONLY de-humidifier relay
By setting the parameter tHu = db the de-humidifying action is performed by enabling the de-humidifier relay when the humidity is higher than SET_RH + dbH. The relay is switch off when humidity comes back to the SET_RH value.
4.3.2 Dehumidifying action with de-humidifier and compressor relays
By setting the parameter tHu = cHu the de-humidifying action is performed by enabling the de-humidifier and compressor relays together. when the humidity is higher than SET_RH + dbH. The relays are switched off when humidity comes back to the SET_RH value.
If is simultaneously present a request of cooling (temp>SET_T+dbt) and dehumidifying (RH > SET_RH+dbH): the cooling action has the priority over the dehumidifying action: only the compressor relay is energised till the SET_T is reached at this point also the de-humidifier is enabled.
5. FA NS
The fan control mode is selected by means of the “FnC” parameter: FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:; FnC= O-n fans will run continuously, but not during defrost FnC=C-y fans will switch ON and OFF with the compressor and run during defrost; FnC=O-y fans will run continuously also during defrost
6. FREZING –PROVING CYCLE
FREEZING PROVING HOLDING
(optional)
The diagrams displays a typical freezing and proving cycle with the holding phase.
FREEZING PHASE lasts for the T1 time, usually without humidity control PROVING PHASE lasts for the T2 time, both temperature and humidity are controlled.
The end of the proving phase is signalled by the internal buzzer and by the “End” message on the
display. After the PROVING PHASE the behaviour of the controller depends on the parameter trc, according to the following settings:
trc = co controller maintains the set points of the proving phase (HOLDING) trc = in controller stop the regulation at all. trc = cL controller performs the freezing and proving phase till is stopped manually. trc = cLE as (trc = cL) plus at the end of each cycle the End label is displayed and the buzzer
is switched on.
6.1 HOW TO SET THE DURATION OF THE FREEZING AND PROVING CYCLE
1. Push the CLOCK key, the display shows on the bottom display the “tM1” message, while the
“hourglass” start flashing.
2. Push again the CLOCK the duration of the freezing phase is shown, hh:mm.
3. To set the duration push the UP and DOWN keys.
4. Push again the CLOCK to confirm the time and pass to the setting of the proving phase: the “tM2”
message is displayed.
5. Push the CLOCK key to see its duration and use the UP and DOWN keys to set it.
6. Confirm the value by pushing again the CLOCK key and pass to the humidity display.
NOTE: If the phase length is modified during a cycle, the modification is performed also in the next cycle.
6.2 HOW TO SET THE TARGET HUMIDITY OF THE FREEZING AND PROVING CYCLE
1. Push the SET_RH key, the display shows on the bottom display the “SH1” message, while the “set
” icon starts flashing.
2. Push again the SET_RH the humidity set point of the freezing phase is shown. Set it using the UP
and DOWN keys. To disable the humidity control during the freezing phase set it to “nu”.
3. Push again the SET_RH to confirm the value and pass to the setting of the proving phase: the
“SH2” message is displayed.
4. Push the SET_RH key to see its value and use the UP and DOWN keys to set it.
Dixell
Operating instructions
1592002910
1592002910 XH460L GB R1.0 18.05.04 XH460L 2/5
6.3 HOW TO SET THE TARGET TEMPERATURE OF THE FREEZING AND PROVING CYCLE
1. Push the SET_T key, the display shows on the upper display the “St1” message, while the “set ”
icon starts flashing.
2. Push again the SET_T the temperature set point of the freezing phase is shown. Set it using the UP
and DOWN keys.
3. Push again the SET_T to confirm the value and pass to the setting of the proving phase: the “St2”
message is displayed.
4. Push the SET_T key to see its value and use the UP and DOWN keys to set it.
6.4 HOW TO START THE CYCLE
Push and release START key: the led will be turned ON.
The led flashes during the proving phase
6.5 END OF THE CYCLE When the timer has expired, the buzzer starts sounding and the bottom display shows the “End
message. To mute the buzzer push a key: The display come back to show the humidity and the LED of the START key is turned off.
6.6 HOW TO MODIFY THE SETTING OF THE RUNNING CYCLE.
To modify the setting of the running cycle temperature (SET_T), humidity (SET_RH) or remaining time (CLOCK):
1. Push twice the corespondent key: the setting value of the current phase (freezing or proving) will be
displayed.
2. Modify it using the UP and DOWN keys
3. Confirm the value using the corespondent key: temperature (SET_T), humidity (SET_RH) or
remaining time (CLOCK).
7. THE DISPLAY
To display and modify target temperature set point. (SET_T) for the freezing (St1)and the proving (St2) phase.
To display and modify target humidity set point (SET_RH) or the freezing (SH1)and the proving (SH2) phase; in programming mode it selects a parameter or confirm an operation.
In programming mode it browses the parameter codes or increases the displayed value.
To start a manual defrost: hold it pressed for at least 3s. In programming mode it browses the parameter codes or decreases the displayed value.
Switch ON and OFF the light, if present (oA1=lig)
Start: to start the cycle
Clock: to set the duration of the freezing (tM1) and proving (tM2) phase
Switch ON and OFF the instrument.
KEY COMBINATIONS
+
To lock and unlock the keyboard
+
To enter the programming mode.
+
To exit the programming mode.
7.1 ICONS AND SYMBOLS
Each LED function is described in the following table.
LED2 LED3
LED4
Temperature Display
Humidity Display
LED
MODE
FUNCTION
LED
MODE
FUNCTION
Led 4
ON
- Instrument in stand by.
- In “Pr2” indicates that the parameter is also present in “Pr1”.
ON
°C
°F
ON
°C
ON
The compressor is running
FLASHING
- Anti-short cycle delay enabled
LED 3
ON
The defrost is enabled
LED 3
FLASHING
Drip time in progress
LED 2
FLASHING
Programming Phase (flashing with LED3)
ON
Heating enabled
(temp)
FLASHING
Temperature Set programming phase
ON
- ALARM signal
ON
Fan is running
ON
RH%
ON
Dehumidifying enabled
ON
Humidifying enabled
(umid)
FLASHING
Humidity Set programming phase
ON
Freezing phase is in progress
FLASHING
Proving phase is in progress
FLASHING
Setting of the duration of the cycle
7.2 HOW TO SEE AND MODIFY THE SET POINT (TEMPERATURE AND HUMIDITY)
1. Push and immediately release the SET key: the display will show the Set point
valueand the correspondant set icon starts flashing;
2. To change the Set value push the o or n arrows within 10s.
3. To memorise the new set point value push the SET key again or wait 10s.
7.3 TO START A MANUAL DEFROST
1. Push the DEF key for more than 2 seconds and a manual defrost will start.
7.4 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
+
1. Enter the Programming mode by pressing the SET_RH+ n for few
seconds. (LED2&3 start flashing)
2. The instrument will show the first parameter present in “Pr1”
7.5 TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” parameter and press the “ SET_RH ” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
4. Use o or n to input the security code in the flashing digit; confirm the figure by pressing “
SET_RH ”.
The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “ SET_RH ” on the last
digit.
Another possibility is the following: after switching ON the instrument the user can push SET_RH + n keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing SET_RH + n . When a parameter is present in “Pr1” LED 4 is on.
7.6 TO CHANGE PARAMETER VALUES
1. Enter the Programming mode.
2. Select the required parameter with o or n.
3. Press the “ SET_RH ” key to display its value (LED2&3 start blinking).
4. Use o or n to change its value.
5. Press “ SET_RH ” to store the new value and move to the following parameter.
To exit: Press SET_RH + UP or wait 15s without pressing a key. NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
7.7 HOW TO LOCK THE KEYBOARD
1. Keep the o and n keys pressed together for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and to switch ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the o and n keys pressed together for more than 3s.
Dixell
Operating instructions
1592002910
1592002910 XH460L GB R1.0 18.05.04 XH460L 3/5
7.8 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is switched ON. During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the LED4 button is lighted.
8. PARAMETER LIST
REGULATION
dbt half dead band width for temperature: (0,1÷25,5°C; 1÷45°F) this band is place below and above
the temperature set point (SET_T). The compressor is enabled when the temperature increases and reaches the SET_T + dbt value. It is turned off when it comes back to the SET_T. The heating output is enabled when temperature is less than SET_T -dbt value and disabled when the SET_T is reached.
dbH half dead band width for humidity: (0,5÷25,5RH) this band is place below and above the
humidity set point (SET_RH). The dehumidifying action is enabled when the humidity increases and reaches the SET_RH + dbH value. It is stopped when it comes back to the SET_RH. The humidifying output is enabled when humidity is less than SET_RH -dbH value and disabled when the SET_RH is reached.
LS Minimum temperature set point limit: (-50,0°C SET; -58°F÷SET) Sets the minimum acceptable
value for the set point.
US Maximum temperature set point limit: (SET 110°C; SET÷230°F) Set the maximum acceptable
value for set point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of
the instrument and inhibits any output activation for the period of time set in the parameter. (Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. tHu Kind of de-humidifying: db: only with de-humidifier relay (oA1= dEH)
cHu with de-humidifier and compressor relay (oA1= dEH) c-H: without de-humidifier relay, by means of compressor and heating relays (oA1 dEH).
LSH Minimum humidity set point limit: (Lci ÷ Set H) Sets the minimum acceptable value for the
humidity set point.
USH Maximum humidity set point limit: (Set H ÷ uci) Set the maximum acceptable value for
humidity set point.
DISPLAY AND KIND OF REGULATION CF Measurement unit: °C= Celsius; °F= Fahrenheit
rES Resolution (for °C): allows decimal point display. dE = 0,1°C; in = 1 °C rEH Resolution for RH%: in = integer; Hd= half digit. trC Kind of behaviour after the end of the cycle trC=co the controller goes on working, and maintains the temperature and humidity of the proving
phase, till the controller is stopped.
trC=in at the end of the proving phase the controller gives the “End” message, the buzzer is turned
on, and the regulation is stopped.
trC=cL at the end of the proving phase the controller gives the “End” message, the buzzer is turned
on, and the regulation restarts from the freezing phase
trC=cLE at the end of the proving phase the regulation restarts from the freezing phase.
DEFROST tdF Defrost type: rE = electrical heater (Compressor OFF)
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode: in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the
compressor is running (even non consecutively).
SdF Set point for SMARTFROST: (-30 30 °C/ -22 86 °F) evaporator temperature which allows the IdF
counting (interval between defrosts) in SMARTFROST mode.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the
evaporator probe is present) sets the temperature measured by the evaporator probe which causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two
defrost cycles.
MdF Duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost duration,
when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.
dFd Display during defrost: rt = real temperature; it = temperature reading at the defrost start;
Set = set point; dEF = “dEF” label; dEG = “dEG” label;
dAd Defrost display time out: (0 255 min) Sets the maximum time between the end of defrost and the
restarting of the real room temperature display.
Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and
the restoring of the control’s normal operation. This time allows the evaporator to eliminate water
drops that might have formed due to defrost. dPO First defrost after start-up: y = Immediately; n = after the IdF time Hud Humidity control during defrost: no: the humidity control is stopped during the defrost; yES the
humidity control works also during the defrost.
FANS FnC Fan operating mode: C-n = running when a load is on, OFF during the defrost;
C-y = running when a load is on, ON during the defrost;
O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost; TEMPERATURE ALARMS ALC Temperature alarm configuration: rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature. ALL Low temperature alarm setting: ALC = rE , 0 50 °C or 90°F
ALC = Ab , - 50°C or -58°F ALU when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. ALU High temperature alarm setting: ALC= rE, 0 50°C or 90°F ALC= Ab, ALL 110°C or 230°F when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALH Temperature alarm recovery differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for
recovery of temperature alarm.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition
and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of
the temperature alarm condition after the instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0 255 min) Time interval between the detection of the
temperature alarm condition at the end of defrost and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0 255 min) Time delay to signal the
temperature alarm condition after closing the door.
HUMIDITY ALARMS AHC Humidity alarm configuration: rE = High and Low alarms related to humidity Set Point
Ab = High and low alarms related to the “absolute” humidity.
AHL Low humidity alarm setting: (with AHC = rE: 0 ÷ 50. With AHC = Ab: Lci ÷ AHu)
when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,. AHu High humidity alarm setting: (with AHC = rE: 0÷50°C. with AHC = Ab: AHL ÷ uci when this humidity is reached and after the AHd delay time the HHA alarm is enabled. AHH Humidity alarm recovery differential: (0.5÷20.0) Intervention differential for recovery of humidity
alarm.
AHd Humidity alarm delay: (0÷255 min) time interval between the detection of an alarm condition and
the corresponding alarm signalling.
dHo Delay of humidity alarm at start-up: (0min÷23h 50min) time interval between the detection of the
humidity alarm condition after the instrument power on and the alarm signalling.
doH Alarm delay at the end of defrost: (0 255 min) Time interval between the detection of the
humidity alarm condition at the end of defrost and the alarm signalling.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and
its alarm signalling: the flashing message “dA” is displayed.
tbA Alarm relay status after pushing a key: on= the relay remains on; off= the relay is switched off. nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the “did
interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the “did” time is reached, switch off and on the instrument to restart
normal regulation.
PROBE INPUTS Ot Thermostat probe calibration: (-12.0 12.0°C/ -21 21°F) allows to adjust possible offset of the
thermostat probe.
OE Evaporator probe calibration: (-12.0 12.0°C/ -21 21°F) allows to adjust possible offsets of the
evaporator probe.
O3 Humidity probe calibration: (-10 10 RH) allows to adjust possible offsets of the humidity probe. P2P Evaporator probe presence: n= not present: the defrost stops only by time; y= present: the
defrost stops by temperature and time.
P3P Humidity probe presence: n= not present; y= present. LCI Readout with 4 mA : (-999 ÷ 999). Adjustment of read out corresponding to 4mA signal. UCI Readout with 20 mA : (-999 ÷ 999). Adjustment of read out corresponding to 20mA signal.
DIGITAL INPUTS i1P Digital input polarity: CL : the digital input is activated by closing the contact; OP : the digital input
is activated by opening the contact
i1F Digital input operating mode: configure the digital input function: EAL = generic alarm; bAL =
serious alarm mode; PAL = Pressure switch; Ht = heating relay safety; dor = door switch
odc Outputs status when open door: on = normal; Fan = Fan OFF; oFF = all the loads off rrd Outputs restarting after doA alarm: no = outputs not affected by the doA alarm; yES = outputs
restart with the doA alarm;
did Time interval/delay for digital input alarm:(0 255 min.) Time interval to calculate the number of
the pressure switch activation when I1F=PAL. If I1F=EAL or bAL (external alarms), “did” parameter
defines the time delay between the detection and the successive signalling of alarms.
OTHER oA1 Light relay configuration (XH460L terminals 3-4): ALr = alarm; dEH = dehumidifier; onF = on/off
relay: close with instrument on, open with instrument off; Lig = light, ESt, dEF not select
Adt RS485 serial address for temperature loads (0÷247) identifies the instrument within a control or
supervising system.
AdH RS485 serial address for humidity loads (0÷247) identifies the instrument within a control or
supervising system.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map. rEL Software release: (read only) Software version of the microprocessor. Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2. Pr2 Access to the protected parameter list (read only).
9. DIGITAL INPUT
One digital input is present configurable by user by means of the i1F parameter according to the following descriptions.
9.1 DOOR SWITCH (I2F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter: no = normal (any change); Fan = Fan OFF; oFF = all the loads are switched off.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the display shows the message “dA”. The status of loads depends on the “rrd” parameter:
with rrd=no outputs are not affected by the doA alarm; with rrd=yES = outputs restart with the doA alarm;
The alarm stops as soon as the external digital input is disabled again. During this time and then for the
delay “dot” and “doH” after closing the door, the temperature and humidity alarms are disabled.
9.2 GENERIC ALARM (I1F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-
activated.
9.3 SERIOUS ALARM MODE (I2F = BAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “bAL” alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de­activated.
Dixell
Operating instructions
1592002910
1592002910 XH460L GB R1.0 18.05.04 XH460L 4/5
9.4 PRESSURE SWITCH (I2F = PAL) If during the interval time set by “did” parameter, the pressure switch has reached the number of
activation of the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
9.5 HEATING RELAY SAFETY (i1F=Ht)
With i1F=Ht as soon as the digital input is activated for “did” time heating relay is disabled. The alarm will stop as soon as the digital input is de-activated.
9.6 DIGITAL INPUTS POLARITY The digital input polarity depends on the “i1P” parameters.
CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact
10. INSTALLATION AND MOUNTING
Instruments XW240L shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the cooling holes.
10.1 XH460L: CUT OUT
165
150
31
+0.5
-0
+0.5
-0
+1
-1
Ø3 x2
11. ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm2 for the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant cables have to be used. Before connecting cables make su re the power supply complies
with the instrument’s requirements. Separate the probe cables from the power supply cables, from the
outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
11.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature.
12. HOW TO USE THE HOT KEY
12.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push o key; the "uPL" message appears
followed a by flashing “End”
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.
12.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the
doL” message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the “Hot key” to abort the operation.
13. ALARM SIGNALLING
Message
Cause
Outputs
“P1”
Thermostat probe failure
Compressor and heating outputs off
“P2”
Evaporator probe failure
Defrost and by time
“P3”
Humidity probe failure
Humidity regulation off
“HA”
High temperature alarm
Outputs unchanged
“LA”
Low temperature alarm
Outputs unchanged
“HHA”
High humidity alarm
Outputs unchanged
“HLA”
Low humidity alarm
Outputs unchanged
“dA”
Door switch alarm
Outputs depending on the odC parameter
“EAL”
External alarm
Other outputs unchanged
“BAL”
Serious external alarm
Outputs OFF
“PAL”
Pressure switch alarm
Outputs OFF
The alarm message is displayed until the alarm condition recoveries.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is
displayed for about 3s.
13.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.
13.2 ALARM RECOVERY Probe alarms : “P1” (probe1 faulty), “P2”, “P3”; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe. Temperature alarms HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts.
Humidity alarms HHA” and “LHA” automatically stop as soon as the humidity returns to normal values. Door switch alarm dA” stop as soon as the door is closed. External alarms EAL”, “BAL” stop as soon as the external digital input is disabled Pressure switch alarm PAL” alarm is recovered by switching OFF the instrument.
14. TECHNICAL DATA
Housing: self extinguishing ABS. Case: XH460L: facia 38x185 mm; depth 76mm; Mounting: XH460L: panel mounting in a 150x31 mm panel cut-out with two screws. 3 x 2mm.
Distance between the holes 165mm
Protection: IP20. Frontal protection: IP65 with optional frontal gasket mod. RG-L (XH460L); Connections: Screw terminal block 2,5 mm2 heat-resistant wiring and 6,3mm Faston Power supply: 230Vac or 110Vac 10%; Power absorption: 7VA max. Display: double display + icons. Inputs: 1 NTC probe + 4÷20mA probe Digital input: 1 free voltage Relay outputs: compressor: relay SPST 20(8) A, 250Vac;
heather: relay SPST 8(3) A, 250Vac; defrost: relay SPST 8(3) A, 250Vac fans: relay SPST 8(3) A, 250Vac; humidifier: relay SPST 8(3) A, 250Vac
de-humidifier: relay SPST 8(3) A, 250Vac Other output : alarm buzzer (optional) Data storing: on the non-volatile memory (EEPROM). Kind of action: 1B.; Pollution grade: normal; Software class: A. Operating temperature: 0÷60 °C.; Storage temperature: -25÷60 °C. Relative humidity: 20 85% (no condensing) Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F) Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
15. WIRING CONNECTIONS
15.1 XH460L
Room
119 10 12 13 1716 18 19 21 22 2314 15
LN
Comp
20(8)A 250V~
62 73 84 51
Fan
8(3)A
250V~
8(3)A
250V~
8(3)A
250V~
8(3)A
250V~
Def
20
Heater Hum
8(3)A
250V~
Def
NC
Supply 115Vac: 14-15 terminals
16. DEFAULT SETTING VALUES
Set temperature
Set humidity
Duration
Freezing Phase
5.0 °C
50.0 RH%
5.00 h
Proving Phase
5.0 °C
50.0 RH%
5.00 h
Label
Value
Menu
Description
Range
dbt
2.0
Pr1
Half dead band width for temperature
0.1°C o 1°F ÷ 25°C o 77°F
dbH
5.0
Pr1
Half dead band width for humidity
0.5 ÷ 50
LS
-40.0
Pr2
Minimum temperature set point limit
-50.0°C o –58°F ÷ Set T
uS
110
Pr2
Maximum temperature set point limit
Set T ÷ 110°C o 230°F
odS
1
Pr2
Outputs activation delay at start up
0 ÷ 250 min
Ac
1
Pr1
Anti-short cycle delay
0 ÷ 30 min
tHu
c-H
Pr2
Humidity regulation
db = dehumidifier relay.; cHu
= dehum+ compr.; c-H=
without dehum. relay
LSH
0.0
Pr2
Minimum humidity set point limit
Lci ÷ Set H
uSH
100
Pr2
Maximum humidity set point limit
Set H ÷ uci
cF
°C
Pr2
Measurement unit
°C ÷°F
rES
dE
Pr2
Resolution (for °C):
in = integer / dE = decimal
rEH
Hd
Pr2
Resolution for RH%:
in = integer / Hd = half digit
trC
co
Pr2
Instrument behaviour at the end of the cycle
co=start hoolding, in=stop
regulation, cL=restart the first
phase+End message; cLE =
restart the first phase
tdf
rE
Pr2
Defrost type
rE, rT, in
EdF
in
Pr2
Defrost mode
In, Sd
SdF
0.0
Pr2
Set point for SMART DEFROST
-30 ÷ +30°C / -22÷+86°F
dtE
8.0
Pr2
Defrost termination temperature
-50,0÷110°C/ -58÷230°F
idF
6
Pr1
Interval between defrosts
1 ÷ 120 h
MdF
20
Pr1
Duration of defrost
0 ÷ 250 min
dFd
it
Pr2
Display during defrost
rt / it / SEt / dEF / dEG
dAd
30
Pr2
Defrost display time out
0 ÷ 250 min
Dixell
Operating instructions
1592002910
1592002910 XH460L GB R1.0 18.05.04 XH460L 5/5
Label
Value
Menu
Description
Range
Fdt
0
Pr2
Draining time
0÷60 min.
dPo
no
Pr2
First defrost after start up
n ÷ y
Hud
no
Pr2
Humidity control during defrost
no; yES
Fnc
c-n
Pr2
Fan operating mode
c-n / c-Y / o-n / o-Y
ALc
Ab
Pr2
Temperature alarm configuration
rE = relative / Ab = absolute
ALL
-40.0
Pr1
Low temperature alarm setting
0°C ÷ 50.0°C / -50.0°C ÷ ALu
ALu
110
Pr1
High temperature alarm setting
0°C ÷ 50.0°C / ALL ÷ 110°C
ALH
1.0
Pr2
Temperature alarm recovery differential
0.1°C o 1°F ÷ 25°C o 77°F
ALd
15
Pr2
Temperature alarm delay
0 ÷ 250 min
dAo
1.3
Pr2
Delay of temperature alarm at start-up
0.0 ÷ 23.5 h
EdA
20
Pr2
Alarm delay at the end of defrost
0 ÷ 250 min
dot
20
Pr2
Delay of temperature alarm after closing the door
0 ÷ 250 min
AHc
Ab
Pr2
Humidity alarm configuration
rE = relative / Ab = absolute
AHL
0.0
Pr1
Low humidity alarm setting
0 ÷ 50 / Lci ÷ AHu
AHu
100
Pr1
High humidity alarm setting
0 ÷ 50 / AHL ÷ uci
AHH
2.0
Pr2
Humidity alarm recovery differential
0.5 ÷ 25
AHd
15
Pr2
Humidity alarm delay
0 ÷ 250 min
dHo
1.3
Pr2
Delay of humidity alarm at start-up
0.0 ÷ 23.5 h
doH
20
Pr2
Alarm delay at the end of defrost
0 ÷ 250 min
doA
20
Pr2
Open door alarm delay
0 ÷ 250 min ( 250 = nu )
tbA
oFF
Pr2
Relay status after pushing a key
on÷oFF
nPS
15
Pr2
Pressure switch number
0÷15
ot
0.0
Pr1
Thermostat probe calibration
-12.0 ÷ 12.0
oE
0.0
Pr2
Evaporator probe calibration
-12.0 ÷ 12.0
o3
0.0
Pr1
Humidity probe calibration
-10 ÷ 10
P2P
YES
Pr2
Evaporator probe presence
no = absent / YES = present
P3P
YES
Pr2
Humidity probe presence
no = absent / YES = present
Lci
0.0
Pr2
Readout with 4 mA
-999 ÷ 999
uci
100
Pr2
Readout with 20 mA
-999 ÷ 999
i1P
cL
Pr2
Digital input polarity
cL =open / oP = close
i1F
dor
Pr2
Digital input configuration
dor / PAL / EAL / bAL / Ht
odc
FAn
Pr2
Outputs status when open door
on / Fan / oFF
rrd
YES
Pr2
Outputs restarting after doA alarm
no = no / YES = yes
did 0 Pr2
Digital input alarm delay
0÷255 min.
oA1
LiG
Pr2
Light relay configuration (XH460L terminals 3-4,):
ALr = alarm; dEH =
dehumidifier; onF = on/off; Lig
= light, ESt, dEF not select
Adt
1
Pr2
Serial address for temperature
0÷247 num
AdH
1
Pr2
Serial address for humidity
0÷247 num
Ptb
0.0
Pr2
Parameter table
- - -
rEL
100
Pr2
Software release
- - -
Prd
cL
Pr2
Probes display
Pb1÷Pb3
Pr2
321
Pr1
Access to the protected parameter list
- - -